Semantic search

Jump to navigation Jump to search
 Entered dateEvent description
ENS 500937 May 2014 15:19:00A leak containing a low level tritium concentration assumed to be greater than 100 gallons of water, with the potential to reach groundwater, occurred at Oconee Nuclear Station. A water sample indicated that the tritium level was 3150 picocuries per liter; which is less than a quarter of the US Environmental Protection Agency drinking water standard of 20,000 picocuries per liter for tritium. While conducting a transfer from one chemical treatment pond to another, water was observed seeping from the ground at a location near the transfer piping between the ponds. The transfer was terminated and the ground seepage subsided. Actions have been taken to prevent further use of the chemical treatment pond discharge path at this time. Based upon the on-site location and low tritium levels, there is no health or safety impact to the public or employees. Voluntary notification of state and local agencies is being made via the industry groundwater protection initiative; measured tritium levels were below any required notification threshold. Agencies notified: South Carolina Department of Health and Environmental Control, South Carolina Emergency Management, City of Seneca, City of Anderson, Greenville Water System, Oconee County Administration, Pickens County Administration, Anderson County Administration, Oconee County Emergency Management, Pickens County Emergency Management, Greenville County Emergency Management, and Clemson University Utility Services. The licensee notified the NRC Resident Inspector.