ENS 52061 | 1 July 2016 17:00:00 | On 7/1/16, the Houston County Dispatch (911 Center) was conducting a monthly weather siren test. At approximately 1205 CDT, there was an inadvertent actuation of 41 emergency sirens in Houston County. The emergency sirens were deactivated at approximately 1208 CDT. Houston Country EMA issued a press release to notify the public of the inadvertent actuation. This is being reported under 10 CFR 50.72(b)(2)(xi) due to the inadvertent actuation and subsequent press release. There was no impact to the health and safety of the public as a result of this event as the offsite response capabilities remain functional. The site is operating normally with no emergency conditions present. The NRC Resident Inspector has been notified. |
ENS 51918 | 11 May 2016 10:56:00 | At 0653 (CDT) on 5/11/16, Farley Unit 2 reactor was manually tripped from 29 (percent) power. The initiating event was hi-hi Steam Generator level. Steam Generator levels began to rise following the start of a second condensate pump. The hi-hi steam generator level setpoint was reached causing the only running main feedwater pump to trip, a main feedwater isolation, and an automatic turbine trip. Auxiliary feedwater automatically started as expected. The reactor was manually tripped per procedure. All other systems responded properly for the event and there were no complications. The plant is currently stable in Mode 3. The NRC Resident Inspector has been notified. |
ENS 51148 | 11 June 2015 13:15:00 | A licensed employee supervisor had a confirmed positive test for a controlled substance during a random fitness-for-duty test. The employee's plant access has been placed on administrative hold. The NRC Resident Inspector has been notified. |