Semantic search

Jump to navigation Jump to search
 Entered dateEvent description
ENS 5084121 February 2015 21:35:00The Millstone site stack radiation monitor, RM-8169, failed and was declared inoperable at 1950 EST on February 21, 2015. Repairs are in progress. This event is reportable pursuant to 10 CFR 50.72(b)(3)(xiii) as any event that results in a major loss of emergency assessment capability, off-site response capability, or off-site communications capability. The Instrument and Controls Department is conducting troubleshooting and repair. The cause of the radiation monitor failure was sample pump failure. The licensee has notified the NRC Resident Inspector and applicable State and Local authorities.
ENS 5014225 May 2014 07:30:00

At 0702 EDT on 5/25/14, Millstone Units 2 and 3 experienced a loss of offsite power and subsequent trip of both units. An Unusual Event was declared by Millstone Units 2 and 3 at 0715 EDT. Power is currently being supplied to all emergency busses by the emergency diesel generators. Offsite power is not available. At this time, it appears that the loss of offsite power is due to a localized issue in the Millstone switchyard. The surrounding areas were not affected. A decision was made to take the NRC to monitoring mode at 0749 EDT with Region 1 in the lead. Notified DHS SWO, FEMA Ops Center, NICC Watch Officer, DOE Ops Center, USDA Ops Center, HHS Ops Center, and Nuclear SSA via email.

  • * * UPDATE FROM MICHAEL CICCONE TO CHARLES TEAL AT 1330 EDT ON 5/25/14 * * *

All EDGs have been secured and offsite power has been restored. The licensee is reporting the loss of two stack radiation monitors - 8168 and 8169. This is reportable under 10CFR50.72(b)(3)(xiii). Notified R1DO (Gray), R1DRA (Lew), NRR EO (Kokajko), IRD MOC (Grant).

  • * * UPDATE FROM MICHAEL CICCONE TO DANIEL MILLS AT 1548 EDT * * *

At 1414 EDT the licensee terminated the Unusual Event. Notified R1DO (Gray), R1DRA (Lew), NRR EO (Kokajko), IRD MOC (Grant), DHS SWO, FEMA Ops Center, NICC Watch Officer, DOE Ops Center, USDA Ops Center, HHS Ops Center, and Nuclear SSA via email.