 Entered dateEvent description
ENS 4088621 July 2004 11:11:00Both control room ventilation systems were inoperable due to a seal failure on the in service control room ventilation unit. A 24 hour Limiting Condition of Operation (LCO) was entered at 0512 CDT. (V-EAC-14A) "A" CRV tripped and "B" CRV was isolated for planned maintenance. "B" CRV (V-EAC-14B) was unisolated and restored to service at 0545 CDT (33 minutes later) and the 24 hour LCO exited at 0600 CDT. The plant remains in a 30 day LCO for one train of the CRV being inoperable. Control room temperatures increased slightly during CRV inoperability and are within normal operating band at this time (Temp increased 5 degrees F). State and Local were notified of this by the licensee. The NRC Resident Inspector was notified of this event by the licensee.