BVY-99-109, Ro:On 990812,stack Ng Effluent Instrumentation for PAM Was Declared Oos.Caused by Instrument Drift Due to Electronic Components Based on Insps by Instrumentation & Controls Dept.Detector & Preamplifier Will Be Replaced on 99083119 August 1999Ro:On 990812,stack Ng Effluent Instrumentation for PAM Was Declared Oos.Caused by Instrument Drift Due to Electronic Components Based on Insps by Instrumentation & Controls Dept.Detector & Preamplifier Will Be Replaced on 990831
ML20209J00814 July 1999Special Rept:On 990615,diesel Driven Fire Pump Failed to Achieve Rated Flow of 2500 Gallons Per Minute.Pump Was Inoperable for Greater than 7 Days.Corrective Maint Was Performed to Reset Pump Lift Setting
BVY-97-171, Special Rept:On 971105,fire Alarm Panel & Suppression Sys Were Out of Svc Greater than 14 Days.Caused by Hardware Problems W/New Zone Modules Developed During Mods.Sys Placed Back in Svc on 97112112 December 1997Special Rept:On 971105,fire Alarm Panel & Suppression Sys Were Out of Svc Greater than 14 Days.Caused by Hardware Problems W/New Zone Modules Developed During Mods.Sys Placed Back in Svc on 971121Fire Watch
BVY-97-101, Special Rept:On 970717,determined Ongoing or Recent Contamination Event Could Be Source of Detected Environ Radioactivity.Collection,Analysis & Review of Results of Addl Grab Samples from North Storm Drain Outfall8 August 1997Special Rept:On 970717,determined Ongoing or Recent Contamination Event Could Be Source of Detected Environ Radioactivity.Collection,Analysis & Review of Results of Addl Grab Samples from North Storm Drain OutfallGrab sample
ML20148B87022 April 1997Special Rept:On 970123,periodic Source Leakage Test of 150 Uci Cs-137 Source Revealed Presence of Greater than 0.005 Uci of Removable Contamination.Source Removed from Svc & Will Be Disposed of IAW Applicable Regulatory RequirementsTime of Discovery
ML20135E02627 February 1997Special Rept:On 970116,Cable Vault CO2 & Diesel Fire Pump Day Tank Room CO2 Sys Place in Abort.Caused by Installation of New Low Pressure CO2 Sys for Switchgear Rooms.Established Compensatory Measures & Required Manual Initiation for SysFire Watch
ML20112F8007 June 1996Special Rept:On 960424,fire Protection Sys Declared Inoperable as Conservative Precaution for Greater than 14 Days.Calculations for Sys May Not Accurately Reflect Pressure Loss.Mods Being DevelopedFire Watch
Hourly Fire Watch
ML20108C6712 May 1996Special Rept:On 960320,switchgear CO2 Sys Declared Inoperable.Suppression Sys Remains Capable of Automatic Initiation & Compensatory Measure Will Remain in Effect Until Confirmatory Testing CompletedFire Watch
Hourly Fire Watch
ML20064C35023 February 1994Special Rept:On 940127 & 0209,electric Fire Pump Motor Failed to Start Due to Motor Breaker Trip.Redirected Room Heater Discharge to Diesel Fire Pump Engine Area
BVY-92-105, Special Rept:On 920810,electric Fire Pump Portion of Vital Fire Suppression Water Sys Equipment Inoperable for 17 Days. Caused by Need to Perform Preventive maint.Diesel-driven Fire Pump Remained Operable & Contingency Plans Developed11 September 1992Special Rept:On 920810,electric Fire Pump Portion of Vital Fire Suppression Water Sys Equipment Inoperable for 17 Days. Caused by Need to Perform Preventive maint.Diesel-driven Fire Pump Remained Operable & Contingency Plans Developed
ML20248B9852 June 1989Special Rept:On 890421,cable Vault Carbon Dioxide (CO2) Sys & on 890424,diesel Fire Pump Day Tank Room CO2 Sys Declared Inoperable.Fire Protection Sys Out of Svc for More than 14 by 890602.Fire Watches EstablishedContinuous fire watch
Fire Watch
ML20236E27514 March 1989Special Rept:U Slab Source Found to Be Leaking Contamination During Semiannual Radioactive Source Leak Test.Caused by Break Down of Adhesive That Hold Mylar Covering.Source Removed from Svc & Deconned & Resealed W/New Covering
ML20112E1827 October 1983Rev 1 to RO 83-06:accumulative from 840810-23,buildup of Detectable Quantities of plant-related Co-60 in Connecticut River.Caused by Turbine Bldg Roof Vents Failing to Filter Waste.Procedural Changes Implemented
ML20086E22010 March 1975Ro:On 750209 & 10,excessive Level of Heat Rejected to Connecticut River & Filter Paper Sample Whisked from Numbed Technician Hand by Wind,Respectively.Events Caused by Lack of Communication & Wind,Respectively
ML20086E4109 January 1975Ro:On 741126,RHR Svc Water Pump C (P-8-1C) 1,200-amp Circuit Breaker Encountered Significant Damage During Attempted Start.Caused by Migrating Ionized Gases Causing Front Primary Disconnect Device Failure.Breaker Replaced
ML20086E65725 April 1974Ro:On 740414-16,each Operable Control Rod Not Fully Inserted Was Not Exercised One Notch During Surveillance Exercise. Cause Not Stated.Strict Adherence to Surveillance Test Schedule Emphasized
ML20086D8716 March 1973Ro:On 730205,all-purpose Fuel Grapple Became Detached from Jib Crane Hoist Cable When Tension Applied to Cable.Caused by Design Error.Grapple & Cable End Stud Reassembled,End Stud Drilled & Roll Pin Installed & Staked