RS-12-159, 12Q0108.10-R-002, Revision 0, Seismic Walkdown Report in Response to the 50.54(f) Information Request Regarding Fukushima Near-Term Task Force Recommendation 2.3: Seismic for the Braidwood Station, Unit 2. Part 4 of 5

From kanterella
(Redirected from RS-12-159)
Jump to navigation Jump to search
12Q0108.10-R-002, Revision 0, Seismic Walkdown Report in Response to the 50.54(f) Information Request Regarding Fukushima Near-Term Task Force Recommendation 2.3: Seismic for the Braidwood Station, Unit 2. Part 4 of 5
ML12339A227
Person / Time
Site: Braidwood  
Issue date: 11/16/2012
From: Delaney M
Exelon Generation Co, Stevenson & Associates
To:
Office of Nuclear Reactor Regulation
References
RS-12-159 12Q0108.10-R-002, Rev 0
Download: ML12339A227 (112)


Text

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 5 Status:

N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

21P08E Equipment Class:

(16) Battery Chargers and Inverters Equipment

Description:

INSTRUMENT BUS 214 INVERTER - DIV. 22 Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 451.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used, to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Drawing 20E-0-3391BK Revision D Anchor spacing is 10" at 2 locations while drawing specifies 12". NSWP-S-05 allows 2 diameter relocation which would equal 10" for 1" diameter expansion anchors therefore OK.

6.

Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?

C-254

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 5 Status: M N U Seismic Walkdown Checklist (SWC) '

Equipment ID No.:

21P08E Equipment Class:

(16) Battery Chargers and Inverters Equipment

Description:

INSTRUMENT BUS 214 INVERTER - DIV. 22 Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Seismic block walls.

No bulb guards on lights but they would not impact equipment if they fell. S&L Std E-103 -ok

9.

Do attached lines have adequate flexibility to avoid damage?

1.0.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-255

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 5 Status: M.

N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

21P08E Equipment Class:

(16) Bat Equipment

Description:

INSTRU tery Chargers and Inverters IMENT BUS 214 INVERTER - DIV. 22 Photos Zlf-UtSt (NV-bbVb) 1-31-12 U23 21P1::: (NI-5-95) 7-31-12 024 C-256

Braidwood Station Unit 2 12Q0108.1 0-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 5 Status:

N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

21P08E Equipment Class:

(16) Battery Chargers and Inverters Equipment

Description:

INSTRUMENT BUS 214 INVERTER-DIV. 22 21P08E (NP-6695) 7-31-12 025 21POSE 7-31-12 020 C-257

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 5 of 5 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

21P08E Equipment Class:

(16) Battery Chargers and Inverters iipment

Description:

INSTRUMENT BUS 214 INVERTER - DIV. 22 21P08E 7-31-12 021 C-258

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

21Y-0606 Equipment Class:

(18) Instruments on Racks Equipment

Description:

RH HX 2A OUT li/P TRANSDUCER Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 364.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoracqe

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Attached to well-anchored rack 2PL86J Yes C-259

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

21Y-0606 Equipment Class:

(18) Instruments on Racks Equipment

Description:

RH HX 2A OUT I/P TRANSDUCER Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems,.ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead fire protection piping and HVAC is well-supported

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 8/2/12 pm Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-260

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

21Y-0606 Equipment Class:

(18) Instruments on Racks Equipment

Description:

RH HX 2A OUT I/P TRANSDUCER Photos Z IY -bSUb5

-Z-1IZ U4Vd C-261

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

21Y-0607 Equipment Class:

(18) Instruments on Racks Equipment

Description:

RH HX #2B OUT I/P TRANSDUCER Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 364.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

No of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Well-supported rack Yes C-262

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

21Y-0607 Equipment Class:

(18) Instruments on Racks Equipment

Description:

RH HX #2B OUT I/P TRANSDUCER Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Seismic block walls

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 8/2/12 pm Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-263

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

Equipment

Description:

Photos 21Y-0607 (18) Instruments on Racks RH HX #2B OUT I/P TRANSDUCER 21Y-606 8-2-12 049 21Y-606 8-2-12 050 C-264

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS001C Equipment Class:

(7) Fluid-Operated Valves Equipment

Description:

MS ISOL VLV LOOP 2C ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 377.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-265

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M

, N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS001C Equipment Class:

(7) Fluid-Operated Valves Equipment

Description:

MS ISOL VLV LOOP 2C ASMBLY Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Valve is robust Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 pm Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-266

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS001C Equipment Class:

(7) Fluid-Operated Valves Equipment

Description:

MS ISOL VLV LOOP 2C ASMBLY Photos 2MSO301 (AWB - UAMAUEU IULA I ION JOIN I AND WEATHER STRIP) 8-1-12 AM 008 2Mb001U 8-1-12 AM 001 C-267

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

nmant na'qrrinfinn-2MS001C (7) Fluid-Operated Valves MS ISOL VLV LOOP 2C ASMBLY 2MS001C 8-1-12 AM 002 2MS001C 8-1-12 AM 003 C-268

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS018C Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

S/G 2C PORV Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 404.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-269

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS018C Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

S/G 2C PORV Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Valve is robust Comments Seismic walkdown team M. Delaney & P. Gazda 8/1/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-270

Braidwood Station Unit 2 12QO108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS018C Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

S/G 2C PORV 2MS018C 8-1-12 AM 004 2MS018C 8-1-12 AM 005 C-271

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M-j N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS018C Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Pirminmcanf 'aarrinfinn.

5qi/

92. PC)P\\/

C-272

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status:

  • N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS018D Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

S/G 2D PORV ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 401.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of.equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage.

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-273

Braidwood Station Unit 2 12Q0108.10-R-0P2 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS018D Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

S/G 2D PORV ASMBLY Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Valve is robust Comments Seismic walkdown team M. Delaney & P. Gazda 8/1/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-274

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS018D Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

S/G 2D PORV ASMBLY Photos ZM,-iU1lSL (AVVb - UNIN I-ALLU 05-1--1 AM U1 Z C-275

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2MS018D Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

S/G 2D PORV ASMBLY

= L I I

ý r

I 2MS018D 8-1-12 AM 010 2MS018D 8-1-12 AM 011 C-276

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status:

N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PA03J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

PROTECTION SYSTEM CABINET (I&E Prot. Cab. CH 3)

Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 451.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoracie

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes Floor is tiled

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Drawing 20E-0-339 1 C Revision BM Weld exceeds drawing requirement

6.

Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?

C-277

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PA03J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

PROTECTION SYSTEM CABINET (I&E Prot. Cab. CH 3)

Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

No bulb guards but lights wouldn't impact equipment if they fell. S&L Std E-103 -ok

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-278

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PA03J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

PROTECTION SYSTEM CABINET (I&E Prot. Cab. CH 3)

Photos 2PA03J 7-31-12 035 2PA03J 7-31-12 036 C-279

Braidwood Station Unit 2 12Q01 08.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 5 Status:

N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PA09J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

PROTECTION SYSTEM CABINET (SSPS Cab. Train A)

Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 451.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes Floor is tiled

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Drawing 20E-0-339 IC Revision BM Weld exceeds drawing requirements

6.

Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?

C-280

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 5 Status: FT] N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PAO9J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

PROTECTION SYSTEM CABINET (SSPS Cab. Train A)

Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

No bulb guards but lights wouldn't damage equipment if they fell. S&L Std E-103 -ok Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-281

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 5 Status:

N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PA09J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

PROTECTION SYSTEM CABINET (SSPS Cab. Train A)

Photos 2PA 09J (AWB -MSAC TEST PANEL) 7-31-12 039 2PA 09J (AWB -MSAC TEST PANEL) 7-31-12 040 C-282

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 5 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PAO9J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

PROTECTION SYSTEM CABINET (SSPS Cab. Train A)

-MSAC TEST PANEL) 7-31-12 041 2PAO9J 7-31-12 037 C-283

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 5 of 5 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PAO9J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

PROTECTION SYSTEM CABINET (SSPS Cab. Train A) 2PA09J 7-31-12 038 C-284

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status:

N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PA27J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

AUX SAFEGUARD RELAY CABINET (A)

Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 451.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoraqge

1. Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes Floor is tiled

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Drawing 20E-0-3391C Revision BM Weld exceeds drawing requirements

6.

Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?

C-285

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PA27J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

AUX SAFEGUARD RELAY CABINET (A)

Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

No bulb guards on lights but would not damage equipment if they fell. S&L Std E-103 -ok

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?.

Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-286

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PA27J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

AUX SAFEGUARD RELAY CABINET (A),

Photos ZI'APZ(J I-L*1-1Z U4Z 2PA27J 7-31-12 043 C-287

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PA27J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

AUX SAFEGUARD RELAY CABINET (A) 2PA27J 7-31-12 044 C-288

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: r]

N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PI-0633 Equipment Class:

(18) Instruments on Racks Equipment

Description:

SFP PMP SUCTION PRESSURE INDICATOR Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

FH, 401.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoracqe

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

No of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

,5. Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Rack mounted to wall Nut at 7:00 location is loose. Two other screws are tight and are more than adequate to support small weight of pressure indicator. No immediate concern. IR 1394916 was written.

Yes C-289

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PI-0633 Equipment Class:

(18) Instruments on Racks Equipment

Description:

SFP PMP SUCTION PRESSURE INDICATOR Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adverselyaffect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 7/30/12 pm Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-290

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PI-0633 Equipment Class:

(18) Instruments on Racks Equipment

Description:

SFP PMP SUCTION PRESSURE INDICATOR Photos 2PI-0633 7-30-12 PM 001 C-291

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PL07J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

2A DG 1DG01KA CONTROL PANEL Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 401.00 ft, ALL Manufacturer/Model:

-Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Floor is coated

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Yes Yes Yes Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-292

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PLO7J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

2A DG lDG01KA CONTROL PANEL Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead HVAC well-supported

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 pm Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-293

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PL07J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

2A DG lDG01KA CONTROL PANEL Photos 2PL07J 7-31-12 095 2PL07J 7-31-12 096 C-294

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PL08J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

2B DG 2DG01KB Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 401.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchora-ge

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation.?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable

6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-295

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PL08J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

2B DG 2DG01 KB Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely, to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Small hairline crack in wall is not a structural/seismic issue Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 Evaluated by:

Marlene Delaney Date:

10/1/12 Philip Gazda 10/1/12 C-296

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PL08J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

2B DG 2DG01 KB Photos 2PL08J 7-31-12 104 C-297

Braidwood Station Unit 2 12Q01 08.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status:

N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PM05J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 451.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at.the end of this checklist for documenting other comments.

Anchoraae

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Drawing 20E-0-3391AN Revision U. Additional detailed information from Calculation Detail #8276 Revision B pages 2 to 6 which is input into Structural Calculation 7.16.10.2 (2113/85).

Due to configuration of the panels and the control room, it is not possible to verify all the welds (front/back, interior/exterior) for the control room panels.

Welds that are seen are good, matching the drawings and other inputs without cracks, corrosion, etc. Cabinets opened for inspection.

C-298

Braidwood Station Unit 2 12Q01 08.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PM05J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD

6.

Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?

Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and Yes masonry block walls not likely to collapse onto the equipment?

See associated area walk-by

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of Yes potentially adverse seismic interaction effects?

Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

No structural/seismic issues Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 am C-299

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PM05J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 Photos 2PM05J 7-31-12 045 2PM05J 7-31-12 046 C-300

Braidwood Station Unit 2 1200108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PMO5J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD 2PM05J 7-31-12 055 C-301

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status: L N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PM06J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 451.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Drawing 20E-0-3391AN Revision U. Additional detailed information from Calculation Detail #8276 Revision B pages 7 to 9 which is input into Structural Calculation 7.16.10.2 (2113/85).

Due to configuration of the panels and the control room, it is not possible to venfy all the welds (front/back, interior/exterior) for the control room panels.

Welds that are seen are good, matching the drawings and other inputs without cracks, corrosion, etc.

C-302

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PM06J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD

6.

Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?

Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and Yes masonry block walls not likely to collapse onto the equipment?

see associated area walk-by (AWC 13)

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of Yes potentially adverse seismic interaction effects?

Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 am C-303

Braidwood Station Unit 2 1200108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

Equipment

Description:

2PM06J (20) Instrumentation and Control Panels and Cabinets MAIN CONTROL BOARD Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 Photos

10M1 2PM06J 7-31-12 048 2PM06J 7-31-12 049 C-304

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PM06J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD I

2PM06J 7-31-12 052 2PM06J 7-31-12 053 C-305

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status:

j N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PM07J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 451.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Drawing 20E-0-3391AJ Revision F.

Due to configuration of the panels and the control room, it is not possible to verify all the welds (front/back, interior/exterior) for the control room panels.

Welds that are seen are good, matching the drawings and other inputs without cracks, corrosion, etc. Cabinets were opened to perform verification.

6. Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?

C-306

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PM07J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

see associated area walk-by

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 am C-307

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PM07J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 Photos 2PM07J 7-31-12 050 C-308

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:. 2PM11J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 451.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-309

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PM11J Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

MAIN CONTROL BOARD Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

see associated area walk-by

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 7/31/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-310

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

Equipment

Description:

2PM11J (20) Instrumentation and Control Panels and Cabinets MAIN CONTROL BOARD Photos ZFMl ii t-31-1z u1bi C-311

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0514 Equipment Class:

(18) Instruments on Racks Equipment

Description:

STM GEN LOOP 2A STEAM PRESS PR Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 377.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

I Well-mounted on rack that is anchored with large anchors Yes C-312

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0514 Equipment Class:

(18) Instruments on Racks Equipment

Description:

STM GEN LOOP 2A STEAM PRESS PR Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

.11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 8/1/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-313

Braidwood Station Unit 2 12Q01 08.1 O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0514 Equipment Class:

(18) Instruments on Racks Equipment

Description:

STM GEN LOOP 2A STEAM PRESS PR Photos 2PT- 0514 (AWB) 8-1-12 AM 017 2PT-0514 8-1-12 AM 015 C-314

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0514 Equipment Class:

(18) Instruments on Racks Equipment

Description:

STM GEN LOOP 2A STEAM PRESS PR 2PT-0514 8-1-12 AM 016 C-315

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0546 Equipment Class:

(18) Instruments on Racks Equipment

Description:

STM GEN LOOP 2D STEAM PRESS PR Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 377.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

No of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applica.ble

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Well mounted on rack Rack is welded to embed plate Yes C-316

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0546 Equipment Class:

(18) Instruments on Racks Equipment

Description:

STM GEN LOOP 2D STEAM PRESS PR Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 8/1/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-317

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0546 Equipment Class:

(18) Instruments on Racks Equipment

Description:

STM GEN LOOP 2D STEAM PRESS PR Photos C-318

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0935 Equipment Class:

(18) Instruments on Racks Equipment

Description:

CNMT PRESS XMTTR Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 451.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Instrument mounted on rack that is welded to embed plate Yes C-319

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0935 Equipment Class:

(18) Instruments on Racks Equipment

Description:

CNMT PRESS XMTTR Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 8/2/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-320

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0935 Equipment Class:

(18) Instruments on Racks Equipment

Description:

CNMT PRESS XMTTR Photos 21-1 -U9.3b (NF--bb~Jb) US-2-1 Z ~

ZVI

-U!J.S t F-UO t$-Z-I Z UZI C-321

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2PT-0935 Equipment Class:

(18) Instruments on Racks Equipment

Description:

CNMT PRESS XMTTR ZF 1 -0935 U-2-1 2 024 2F1-' 0935 U-2-1 2 025 C-322

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 5 Status:

N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH01PA Equipment Class:

(6) Vertical Pumps Equipment

Description:

PUMP,2A RESIDUAL HEAT REMOVAL ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 346.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoracie

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

2.

Is the anchorage free of bent,, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Drawing M-1219 Sheet 2 Revision Y Equipment is contaminated so anchor diameter not measured but visual verification performed

6.

Based on the above anchorage evaluations, is the anchoragefree of Yes potentially adverse seismic conditions?

C-323

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 5 Status:

Y N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH01PA Equipment Class:

(6) Vertical Pumps Equipment

Description:

PUMP,2A RESIDUAL HEAT REMOVAL ASMBLY Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 7/30/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-324

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 5 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH01PA Equipment Class:

(6) Vertical Pumps Equipment

Description:

PUMP,2A RESIDUAL HEAT REMOVAL ASMBLY Photos 2RHO1PA 7-30-12 AM 032 21RHO1PA 7-30-12 AM 033 C-325

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 5 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH01PA Equipment Class:

(6) Vertical Pumps Equipment

Description:

PUMP,2A RESIDUAL HEAT REMOVAL ASMBLY 2RH01 PA 7-30-12 AM 034 ZKHUI VA (-SU-1 2 AM UJb C-326

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 5 of 5 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH01PA Equipment Class:

(6) Vertical Pumps Equipment

Description:

PUMP,2A RESIDUAL HEAT REMOVAL ASMBLY 2RH01PA 7-30-12 AM 036 C-327

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: MI N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH01PA-A Equipment Class:

(21) Tanks and Heat Exchangers Equipment

Description:

RH PUMP 2A SEAL COOLER Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 346.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

Mounted to skid. Well-anchored.

2.

Is the anchorage free of bent, broken, missing or loose hardware?

No Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-328

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: [M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RHO1 PA-A Equipment Class:

(21) Tanks and Heat Exchangers Equipment

Description:

RH PUMP 2A SEAL COOLER Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 7/30/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-329

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH01PA-A Equipment Class:

(21) Tanks and Heat Exchangers Equipment

Description:

RH PUMP 2A SEAL COOLER Photos 2RHOI PA-A 7-30-12 AM 030 2RH01 PA-A 7-30-12 AM 031 C-330

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH610 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

RHR PUMP 2A MINFLOW VLV ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 357.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-331

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH610 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

RHR PUMP 2A MINFLOW VLV ASMBLY, Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Nearby block walls are seismic.

Nearby scaffolding is laterally supported with stand-offs on 3 walls. Cannot damage equipment if it were to move in the free direction.

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Valve is a MOV and is robust.

Comments Seismic walkdown team M. Delaney & P. Gazda 7/30/12 am Valve class changed from fluid operated valve as indicated on SWEL.

Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-332

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status:

IN U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH610 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

RHR PUMP 2A MINFLOWVLV ASMBLY Photos 2RH610 7-30-12 AM 018 2RH610 7-30-12 AM 019 C-333

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH610 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

RHR PUMP 2A MINFLOW VLV ASMBLY 2RH610 8-2-12 002 C-334

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH8716B Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

RH HX 2B DISCH CROSSTIE VLV ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 364.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchora-ae

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-335

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH8716B Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

RH HX 2B DISCH CROSSTIE VLV ASMBLY Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Weil-supported valve Comments Seismic walkdown team M. Delaney & P. Gazda 7/30/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-336

Braidwood Station Unit 2 12Q01 08.1 0-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH8716B Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

RH HX 2B DISCH CROSSTIE VLV ASMBLY Photos 2RH8716B 7-30-12 AM 043 2RH8716B 7-30-12 AM 044 C-337

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2RH8716B Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves EauiDment

Description:

RH HX 2B DISCH CROSSTIE VLV ASMBLY C-338

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SI8801A Equipment Class:

(7) Fluid-Operated Valves Equipment

Description:

CHG PUMP TO COLD LEG INJ ISOL ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 375.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

No of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-339

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SI8801A Equipment Class:

(7) Fluid-Operated Valves Equipment

Description:

CHG PUMP TO COLD LEG INJ ISOL ASMBLY Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Gallery above is well-supported

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 8/2/12 am Evaluated by:

Marlene Delaney Date:

10/11/2012 62 "Philip Gazda 10/1/2012 C-340

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SI8801A Equipment Class:

(7) Fluid-Operated Valves Equipment

Description:

CHG PUMP TO COLD LEG INJ ISOL ASMBLY ZZ5i6dOIA d5-Z-1Z U15 Z,,.?I$UIA d-Z-1Z U15O C-341

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SI8801A Equipment Class:

(7) Fluid-Operated Valves Equipment

Description:

CHG PUMP TO COLD LEG INJ ISOL ASMBLY ZZAMUIA O-Z-1Z UI I C-342

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SI8801B Equipment Class:

(7) Fluid-Operated Valves Equipment

Description:

CHG PUMP TO COLD LEGS INST ISOL VLV ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 375.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-343

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SI8801B Equipment Class:

(7) Fluid-Operated Valves Equipment

Description:

CHG PUMP TO COLD LEGS INST ISOL VLV ASMBLY Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead gallety is well-supported

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of

. potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 8/2/12 am Evaluated by:

Marlene Delaney Date:

10/1/2012 (7 '

"-Philip Gazda 10/1/2012 C-344

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SI8801B Equipment Class:

(7) Fluid-Operated Valves Equipment

Description:

CHG PUMP TO COLD LEGS INST ISOL VLV ASMBLY Photos 2SI8801B 8-2-12 019 C-345

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status: M N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX004 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

CC HX 2 INLT VLV ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 330.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-346

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX004 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

CC HX 2 INLT VLV ASMBLY Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Robust valve on well-supported pipe Comments Seismic walkdown team M. Delaney & P. Gazda 8/1/12 pm Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-347

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 4 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX004 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

CC HX 2 INLT VLV ASMBLY Photos 26)WU413-1-1Z FM U15 2ZZXUU46~-1-12 HMU1Th C-348

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX004 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

CC HX 2 INLT VLV ASMBLY 2SX004 8-1-12 PM 017 C-349

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX005 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

U-0 CC HX INLET VLV ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 330.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-350

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX005 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

U-0 CC HX INLET VLVASMBLY Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Robust, well-supported valve Comments Seismic walkdown team M. Delaney & P. Gazda 8/1/12 pm Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-351

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status:

N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX005 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

U-0 CC HX INLET VLV ASMBLY Photos 2SX005 8-1-12 PM 021 2SX005 8-1-12 PM 022 C-352

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX01AA Equipment Class:

(21) Tanks and Heat Exchangers Equipment

Description:

2A SX PUMP LUBE OIL COOLER Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 330.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

No of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Equipment is an in-line mounted cooler with no anchorage details.

Yes C-353

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX01AA Equipment Class:

(21) Tanks and Heat Exchangers Equipment

Description:

2A SX PUMP LUBE OIL COOLER Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Well-supported IR written on component (tagged) but no impact to seismic safety functions Comments Seismic walkdown team M. Delaney & P. Gazda 8/1/12 pm Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-354

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

Equipment

Description:

2SX01AA (21) Tanks and Heat Exchangers 2A SX PUMP LUBE OIL COOLER Photos C-355

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX01PA Equipment Class:

(5) Horizontal Pumps Equipment

Description:

PUMP, 2A ESSENTIAL SER WTR ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 330.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchora-ge

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Well-anchored Yes C-356

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX01PA Equipment Class:

(5) Horizontal Pumps Equipment

Description:

PUMP, 2A ESSENTIAL SER WTR ASMBLY Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 8/1/12 pm Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-357

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX01PA Equipment Class:

(5) Horizontal Pumps Equipment

Description:

PUMP, 2A ESSENTIAL SER WTR ASMBLY Photos 2bXU1 PA 8-1-12 PM 011 2SX01PA8-1-12 PM 010 C-358

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX01PA-C Equipment Class:

(5) Horizontal Pumps Equipment

Description:

PUMP, 2A SX AUX LUBE OIL PP Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 330.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoraqe

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

No of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Equipment is mounted to oil reservoir. Well-anchored.

Yes C-359

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 3 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX01PA-C Equipment Class:

(5) Horizontal Pumps Equipment

Description:

PUMP, 2A SX AUX LUBE OIL PP Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic walkdown team M. Delaney & P. Gazda 8/1/12 pm Evaluated by:

Marlene Delaney Date:

10/1/2012

.° Philip Gazda 10/1/2012 C-360

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 3 of 3 Status: M N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SXO1PA-C Equipment Class:

(5) Horizontal Pumps Equipment

Description:

PUMP, 2A SX AUX LUBE OIL PP Photos 2SX01 PA-C 8-1-12 PM 006 C-361

Braidwood Station Unit 2 12Q0108.1O-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 1 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX033 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

ESSENTIAL SERVICE WTR PMP 2A CROSSTIE VLV ASMBLY Project:

Braidwood 2 SWEL Location (Bldg, Elev, Room/Area):

Auxiliary, 330.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-362

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 2 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX033 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

ESSENTIAL SERVICE WTR PMP 2A CROSSTIE VLV ASMBLY Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Robust, well-supported valve Comments Seismic walkdown team M. Delaney & P. Gazda 8/1/12 pm

/~4~LA(

4d4_

Evaluated by:

Marlene Delaney Date:

10/1/2012 Philip Gazda 10/1/2012 C-363

Braidwood Station Unit 2 12Q01 08.1 O-R-002 Rev. 0 Correspondence No.: RS-1 2-159 Sheet 3 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX033 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

ESSENTIAL SERVICE WTR PMP 2A CROSSTIE VLV ASMBLY Photos 2SX033 (NP-6695) 8-1-12 PM 020 2SX033 8-1-12 PM 018 C-364

Braidwood Station Unit 2 12Q0108.10-R-002 Rev. 0 Correspondence No.: RS-12-159 Sheet 4 of 4 Status: M N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2SX033 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Eauioment Descriotion:

ESSENTIAL SERVICE WTR PMP 2A CROSSTIE VLV ASMBLY 2SX033 8-1-12 PM 019 C-365