RC-05-0192, Update to Emergency Response Data System Data Point Library
| ML053220238 | |
| Person / Time | |
|---|---|
| Site: | Summer |
| Issue date: | 11/16/2005 |
| From: | Archie J South Carolina Electric & Gas Co |
| To: | Martin R Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| RC-05-0192 | |
| Download: ML053220238 (5) | |
Text
Jeffrey B. Archie Vice President, Nuclear Operations 803.345.4214 A SCANA COMPANY November 16, 2005 Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTN: Mr. R. E. Martin
Dear Sir / Madam:
Subject:
VIRGIL C. SUMMER NUCLEAR STATION (VCSNS)
DOCKET NO. 50-395 OPERATING LICENSE NO. NPF-12 UPDATE TO EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY South Carolina Electric & Gas Company is submitting an update to the VCSNS Emergency Response Data System (ERDS) Data Point Library. Attached is a summary of the changes accompanied by the updated data sheets.
Should you have any questions, please call Mr. Robert Sweet at (803) 3454080.
JT/JBA/dr Attachment c:
N. 0. Lorick S. A. Byrne N. S. Cams G. S. Champion (w/o attachment)
R. J. White W. D. Travers R. E. Martin NRC Resident Inspector K. M. Sutton D. H. Carroll NSRC RTS (NL Activity 112)
File (811.10)
DMS (RC-05-0192)
_ro 2, G SCE&G I Virgil C. Summer Nuclear Station P. 0. Box 88. Jenkinsville, South (arolina 29065
- T (803) 345.5209. wwwvsano.aom
Document Control Desk Attachment NL Activity 112 Page 1 of 1 Summary of ERDS Data Point Library Entry Changes
- 1)
Page 54 - Changed Wind Speed Point ID
- 2)
Page 55 - Changed Wind Direction Point ID
- 3)
Page 56 - Changed Atmospheric Stability Class Point ID
Emergency Response Data System (ERDS)
Data Point Library -
V. C. SUMMER Page : 53 Report Date : 10/27/05 DATE REACTOR UNIT DATA FEEDER NRC ERDS PARAMETER POINT ID PLANT SPEC POINT DESC.
GENERIC/COND. DESC.
ANALOG/DIGITAL ENGR UNITS/DIG STATES ENGR UNITS CONVERSION MININUM INSTR.
RANGE MAXIMUM INSTR.
RANGE ZERO POINT REFERENCE REFERENCE POINT NOTES PROC OR SENS NUMBER OF SENSORS HOW PROCESSED SENSOR LOCATIONS ALARM/TRIP SET POINTS NI DET.
POWER CUT OFF NI DET.
POWER CUT ON INSTR. FAILURE MODE 10/27/05 VS1
- N/A
- WIND SPEED
- M9201
- 10 METERS WIND SPEED
- WIND SPEED AT THE REACTOR SITE A
- MPH
- LINEAR CONVERSION
- 0.0
- 125.0
- N/A
- N/A
- S
- 2
- N/A
- 10 METERS ON THE PRIMARY MET TOWER
- NONE
- N/A
- N/A
- LOW DP XMITTER TEMP. COMP.: N LEVEL REFERENCE LEG
- N/A UNIQUE SYSTEM DESCRIPTION Measures the wind speed at the primary meteorological monitoring station at the 10 meter level.
Emergency Response Data System (ERDS)
Data Point Library -
V. C. SUMMER Page : 54 Report Date : 10/27/05 DATE REACTOR UNIT DATA FEEDER NRC ERDS PARAMETER POINT ID PLANT SPEC POINT DESC.:
GENERIC/COND. DESC.
ANALOG/DIGITAL ENGR UNITS/DIG STATES :
ENGR UNITS CONVERSION :
MININUM INSTR.
RANGE MAXIMUM INSTR.
RANGE ZERO POINT REFERENCE REFERENCE POINT NOTES :
PROC OR SENS NUMBER OF SENSORS HOW PROCESSED SENSOR LOCATIONS ALARM/TRIP SET POINTS :
NI DET. POWER CUT OFF :
NI DET. POWER CUT ON INSTR. FAILURE MODE DP XMITTER TEMP. COMP.:
LEVEL REFERENCE LEG 10/27/05 VS1 N/A WIND DIR M9200 10 METER WIND DIRECTION WIND DIR AT THE REACTOR SITE A
DEG LINEAR CONVERSION 0.0 360.0 N/A N/A S
2 N/A 10 METERS ON THE PRIMARY MET TOWERS NONE N/A N/A LOW N
N/A UNIQUE SYSTEM DESCRIPTION Measures the wind direction at the primary meteorological monitoring station at the 10 meter level.
Emergency Response Data System (ERDS)
Data Point Library -
V. C. SUMMER Page :
55 Report Date : 10/27/05 DATE REACTOR UNIT DATA FEEDER NRC ERDS PARAMETER POINT ID PLANT SPEC POINT DESC.
GENERIC/COND. DESC.
ANALOG/DIGITAL ENGR UNITS/DIG STATES ENGR UNITS CONVERSION MININUM INSTR. RANGE MAXIMUM INSTR. RANGE ZERO POINT REFERENCE REFERENCE POINT NOTES PROC OR SENS NUMBER OF SENSORS HOW PROCESSED SENSOR LOCATIONS ALARM/TRIP SET POINTS NI DET.
POWER CUT OFF NI DET.
POWER CUT ON INSTR. FAILURE MODE DP XMITTER TEMP. COMP.
LEVEL REFERENCE LEG
- 10/27/05
- VS1
- N/A
- STAB CLASS
- M9204
- 61 -
10 METER DELTA T
- AIR STABILITY AT REACTOR SITE A
- DEGF
- LINEAR CONVERSION
- -7.0
- 18.0
- N/A
- N/A
- S
- 2
- N/A
- PRIMARY MET TOWER
- NONE
- N/A
- N/A
- LOW N
- N/A UNIQUE SYSTEM DESCRIPTION A delta temperature is derived electronically from the 61 meter and 10 meter temperature elements at the primary meteorological station. The 61-10 meter delta T provides an indication of atmospheric stability class (Pasquill Category) as follows:
Pasquill Category A
B C
D E
F G
Stability Class 61-10 Meter Delta T (DEGF)
Extremely Unstable Moderately Unstable Slightly Unstable Neutral Slightly Stable Moderately Stable Extremely Stable
-1.75 or less from -1.74 to -1.56 from -1.55 to -1.38 from -1.37 to -0.46 from -0.45 to +1.37 from +1.38 to +3.67
+3.67 or greater