' RIVER BEND STATION UNIT -1 REPORT NO.-
'R-87-012 DATE Jan. 14, 1988 COMPLETED BY R.
E.
Cole TITLE
~Ir. Systems Eng.
TELEPHONE 635-6094 X4826-MONTH-DECEMBER, 1987 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Ne t ).
1.
0 17.
0 2
0 18.
0 3
0 19.
0 4.
0 20.
0 5.
0 21.
0 6.
0 22.
O 7.
0 23.
0 8.
0-24.
0 9.
0 25 0
10.
0 26, 95 11.
0
.27.
238 12.
0 28, 270~
13 0
29.
'558 14.
0 30.
421 15.
0 31, 838 16.
0 8801260473 871231 PDR ADOCK 05000458 R
PDR Ifl
DOCKET NO.
50/458 FIVER BEND STATION UNIT 1 REPORT NO.
R-87-012 DATE Jan. 14, 1988 COMPLETED BY R.
E.
Cole TITLE Sr. Svstems Eng.
TELEPHONE 635-6094 X4826 PAGE 1
OF 2
OPERATING STATUS 1.
REPORTING PERIOD: DECEMBER, 1987 GROSS HOURS IN -REPORTING PERIOD:
744 2.
CURRENTLY AdTHORIZED POWER LEVEL (Mwt):
2894 MAX. DEPEND CAPACITY (MWe-Ne t) :
936 DESIGN ELECTRICAL RATING (Mwe-Ne t ) :
936 3.
POWER LEVEL TO WHICH RESTRICTED (IF ANY) (MWe-Ne t) :
N/A 4.
REASONS FOR RESTRICTION (IP ANY):
N/A THIS YR TO CUMU-MONTH DATE LATIVE 5.
NUMBER OF HOURS REACTOR WAS CPITICAL...
215.1 5995.1 12.243.1 6.
REACTOR RESERVE SHUTDOWN HOURS.........
0.0 0.0 0.0 7.
HOURS GENERATOR ON LINE...............
139.0 5837.7 10,531.7 8
UNIT RESERVE SHUTDOWN HOURS...........
0.0 0.0 0.0 9.
, GROSS THERMAL ENERGY GENERATED (MWH)..
214,520 15,469,328 25,599,812 10 GROSS ELECTRICAL ENERGY GENERATED (MWH) 63,527.0 5,301,419.3 8,6:21,374.7 11.
NET ELECTRICAL ENERGY GENERATED (MWH).
58,070,0 4,964,440.0 8,055,207.0
\\
DOCKET NO. 50/458 RIVER BEND STATION UNIT 1 REPORT NO.
R-87-012 DATE Ihn. 14, 1988 COMPLETED BY R.
E. Cole TITLE Sr. Systems Eng.
TELEPHONE 635-6094 X4826 PAGE 2
OF 2
OPERATING STATUS THIS YR TO CUMU-MONTH DATE LATIVE 12.
REACTOR SERVICE FACTOR...........
28.9 68.4 64.5 13.
REACTOR AVAILABILITY FACTOR......
28.9 68.4
__64.5 14.
UNIT SERVICE FACTOR..............
18.7 66.6 61.5 15 UNIT AVAILABILITY FACTOR 18.7 66.6 61.5 16.
UNIT CAPACITY FACTOR (Using MDC)..
8.3 60.5 55.9 17 UNIT CAPACITY FACTOR (Using Design MWe)
...................... _ 8.3 60.5 55.9 18 UNIT FORCED OUTAGE RATE..........
54.1 9.2
- 13. <4 19.
SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):
NONE 20.
IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
N/A 21.
UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION) :
FORECAST ACHIEVED INITIAL CRITICALITY N/A 10-31-85 1
INITIAL ELECTRICIT'l N/A 12-03-85 COMMERCIAL OPERATION N/A 6-16-86 1
1
~
INIT SIKTIDOWS APO POWER RHXCTIONS TIME TIME STAIT RB00VER OF MEM DURATION TYPE REASON ME"IHOD CORRPCTIVE ACTIGE/OCMENIS NO.
DATE OOCURRANCE OOCURRANCE (IKXIRS)
NOIE (1)
NUIE (2) NOIE (3) 87-09 871201 0000 0918 441.3 S
C 1
Planned as part of First Refueling Outage.
871219 871219 0918 0510 F
II 1
Manual Scram due to CRD valve line up 871221 because of deficient procedure. LER-87-032 871221 0510 1429 F
A 3
Autanatic scram fran manual half scram due 871222 to spurious IRM A spike. LER-87-034 871222 1429 0501 163.7 F
A 1
Manual scram to correct water level 871226 instrumentation on Range B.
SU WARY: Carpletea First Refueling Outage. Total auration was 2310.23 hours2.662037e-4 days <br />0.00639 hours <br />3.80291e-5 weeks <br />8.7515e-6 months <br /> scheaulea ana 163.7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br /> forced.
NUIE (1) TYPE OF OOCURRANCE: ENTER CODE DOCKET NO. 50/458 F: FORCED RIVER BEND STATION UNIT 1 S: SCHEDULED REPORT NO.
R-87-012 NOTE (2)
REASON FOR OCCURRANCE: DEER CODE A: EQUIPMENT FAILURE (EXPIAIN IN CORFECTIVE ACTIONS /CWMENTS)
REPORT FONITI December, 1987 B: MAINTENANCE OR TEST C: REFUELING D: REGULATORY RESTRICTION E: OPERATOR TRAINING AND LICENSE EXAMINATION DATE January 14, 1988 F: ADMINISTRATIVE G: OPERATIONAL ERROR (EXPIAIN IN CORRECTIVE ACTIONS /COMMEtES)
R. E. Cole H: CfIFER (EXPIAIN IN CORRECTIVE ACTIONS /COETENTS)
COMPIIT. ED BY:
WOIE (3) MEIY10D OF SIRTITING DOWN REACIOR OR REDUCING POWER: ENTER CODE 1: MANUAL SIGNA 1UPE 2: MANUAL SCRAM i
3: ALTIOMATIC SCRAM Sr. Systens Engineer 1
4: 01 TIER (EXPIAIN IN CORRECTIVE ACTION /OOMMENTS) mLE TELEPHONE 504 635 6 s4@26
o GULF STATES UTILITIES COMPANY RIVER BEND STATION POST OFFICE BOX 220 St. FR ANOSvfLLE LOutstAM 70775 AAEA CODE SO4 635 6094 346 8651 January 15, 1987 RBC-27293 File Nos. G9.5, G9.25.1.5 U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.
20555 Gentlemen:
River Bend Station Unit 1 Docket No. 50-458 Enclosed is Gulf States Utilities Company's Monthly Operating Report for December 1987 for River Bend Station (RBS) - fnit 1.
This report is submitted in accordance with RBS '.echnical Specification 6.9.1.6.
Sincerely, b.
J. E. Booker Manager-River Bend Oversight River Bend Nuclear Group Enclosure ec:
U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 1000 Arlington, TX 76011 NRC Resident Inspector P.O. Box 1051 St. Francisville, LA 70775 INPO Records Center 1100 Circle 75 Parkway Atlanta, GA 30339 Cajun Electric Power Coop., Inc, q
i
,