PNO-II-93-076A, on 931229,AIT Begun Investigation of Loss of of Unit 2 off-site Power Event That Occurred on 931227.CAL Issued.Restart of Unit Requires Concurrence of Nrc.Licensee Initiated Seit to Investigate Root Cause of Event
ML20059G114 | |
Person / Time | |
---|---|
Site: | Mcguire |
Issue date: | 12/30/1993 |
From: | Harris G NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
To: | |
References | |
CAL, PNO-II-93-076A, PNO-II-93-76A, NUDOCS 9401240001 | |
Download: ML20059G114 (1) | |
Similar Documents at Mcguire | |
---|---|
Category:PRELIMINARY NOTIFICATION OF EVENT OR OCCURRENCE (PNO
MONTHYEARPNO-II-98-030, on 980603,loss of Offsite Power Occurred,Due to Loss of 1B Bus.Caused by Faulted 230 Kv Switchyard Current Transformer.Resident Inspectors Onsite & Responded to Event & Will Continue to Evaluate Activities W/Event1998-06-0404 June 1998
[Table view]PNO-II-98-030:on 980603,loss of Offsite Power Occurred,Due to Loss of 1B Bus.Caused by Faulted 230 Kv Switchyard Current Transformer.Resident Inspectors Onsite & Responded to Event & Will Continue to Evaluate Activities W/Event PNO-II-97-051, on 970906,McGuire Units 1 & 2 Automatically Tripped.Porvs Utilized Until Steam Dumps Could Be Made Available.Steam Relieved Through Main Steam PORVs Until Power to Bus Kxa Restored & MSIVs Reopened1997-08-0909 August 1997 PNO-II-97-051:on 970906,McGuire Units 1 & 2 Automatically Tripped.Porvs Utilized Until Steam Dumps Could Be Made Available.Steam Relieved Through Main Steam PORVs Until Power to Bus Kxa Restored & MSIVs Reopened PNO-II-97-015, Re Media Interest in Evacuation of Site Environ Lab,Due to Potentially Explosive Matl.Acid Was re-established,diluted & Stored in Licensee Hazardous Matl Area for Routine Disposal1997-03-0606 March 1997 PNO-II-97-015 Re Media Interest in Evacuation of Site Environ Lab,Due to Potentially Explosive Matl.Acid Was re-established,diluted & Stored in Licensee Hazardous Matl Area for Routine Disposal PNO-II-96-075, on 961031,shutdowns Required by TS After C Battery Failed to Meet Required Capacity Criteria During Modified Performance Test.C Vital DC Bus cross-connected to a Battery.Decrease in Capacity Unexpected1996-10-31031 October 1996 PNO-II-96-075:on 961031,shutdowns Required by TS After C Battery Failed to Meet Required Capacity Criteria During Modified Performance Test.C Vital DC Bus cross-connected to a Battery.Decrease in Capacity Unexpected PNO-II-93-053, on 931005,operators Detected Increasing Activity from Condenser Air Ejector Radiation Monitor Indicating Steam Generator Tube Leakage.Region II Will Continue to Monitor Licensee Actions to Find Nature of Leak1993-10-0606 October 1993 PNO-II-93-053:on 931005,operators Detected Increasing Activity from Condenser Air Ejector Radiation Monitor Indicating Steam Generator Tube Leakage.Region II Will Continue to Monitor Licensee Actions to Find Nature of Leak PNO-II-93-038, on 930821,unit Experienced SG Tube Leak Resulting in Shutdown.Region II Will Continue to Monitor Licensee Actions to Determine Nature of Leak1993-08-23023 August 1993 PNO-II-93-038:on 930821,unit Experienced SG Tube Leak Resulting in Shutdown.Region II Will Continue to Monitor Licensee Actions to Determine Nature of Leak PNO-II-90-068, on 901101,contract Employee Found Deceased in Staging Area Restroom1990-11-0101 November 1990 PNO-II-90-068:on 901101,contract Employee Found Deceased in Staging Area Restroom PNO-II-89-043, on 890604,util Employee & Visitors Caused 3 Consecutive Alarms of Portal Monitor While Exiting Site After Tour.No Contamination Surveys Conducted.Util Surveyed Homes of Employee & Visitors.No Contamination Found1989-06-0909 June 1989 PNO-II-89-043:on 890604,util Employee & Visitors Caused 3 Consecutive Alarms of Portal Monitor While Exiting Site After Tour.No Contamination Surveys Conducted.Util Surveyed Homes of Employee & Visitors.No Contamination Found PNO-II-89-019, on 890307,Unit 1 Manually Tripped Due to Drop in Pressurizer Level,Increase in Main Steam Line Radiation & Increased Charging Flow Revealed Primary to Secondary Leak. Alert Declared & Onsite Emergency Response Activated1989-03-0808 March 1989 PNO-II-89-019:on 890307,Unit 1 Manually Tripped Due to Drop in Pressurizer Level,Increase in Main Steam Line Radiation & Increased Charging Flow Revealed Primary to Secondary Leak. Alert Declared & Onsite Emergency Response Activated PNO-II-89-019A, on 890308,auxiliary Feedwater Initiated to Effected Steam Generator,Backfeeding Primary Sys Through Break.Licensee Will Maintain Alert Condition Until DHR Sys Placed in Svc1989-03-0808 March 1989 PNO-II-89-019A:on 890308,auxiliary Feedwater Initiated to Effected Steam Generator,Backfeeding Primary Sys Through Break.Licensee Will Maintain Alert Condition Until DHR Sys Placed in Svc PNO-II-86-076, on 861015,29 of 53 Sirens Failed to Activate During Annual Emergency Exercise.Siren Sys Encoder Replaced & Radio Transmitters Checked.Further Testing Will Be Performed to Ascertain & Correct Cause1986-10-16016 October 1986 PNO-II-86-076:on 861015,29 of 53 Sirens Failed to Activate During Annual Emergency Exercise.Siren Sys Encoder Replaced & Radio Transmitters Checked.Further Testing Will Be Performed to Ascertain & Correct Cause PNO-II-86-046, on 860726,during Visual Insp of Reactor Vessel Internals,Five Objects Identified Around Baffle Wall.On 860628,w/Westinghouse Assistance,Objects Confirmed to Be Irradiated Fuel Pellets from Broken Fuel Pin1986-07-0101 July 1986 PNO-II-86-046:on 860726,during Visual Insp of Reactor Vessel Internals,Five Objects Identified Around Baffle Wall.On 860628,w/Westinghouse Assistance,Objects Confirmed to Be Irradiated Fuel Pellets from Broken Fuel Pin PNO-II-86-030, on 860414 & 15,one Pressurizer Level Channel Failed & Unidentified Leak Found During Subsequent Containment Entry,Respectively.Gradual Shutdown Started. Repairs Made During Containment Entry1986-04-15015 April 1986 PNO-II-86-030:on 860414 & 15,one Pressurizer Level Channel Failed & Unidentified Leak Found During Subsequent Containment Entry,Respectively.Gradual Shutdown Started. Repairs Made During Containment Entry PNO-II-86-021, on 860310,unit Returned to Operation After Being Out of Svc Since 860307 for Repair of Leaking Sludge Lance Cover on Steam Generator.Unit Operating at 100% Power1986-03-10010 March 1986 PNO-II-86-021:on 860310,unit Returned to Operation After Being Out of Svc Since 860307 for Repair of Leaking Sludge Lance Cover on Steam Generator.Unit Operating at 100% Power PNO-II-85-090, on 850920,false Bomb Threat Reported at Plant.Search Conducted & Empty Briefcase Found1985-09-23023 September 1985 PNO-II-85-090:on 850920,false Bomb Threat Reported at Plant.Search Conducted & Empty Briefcase Found PNO-II-80-049, Safe Energy Alliance Is Planning Forum on 800329 at Park Outside Plant Gate.Group Has Demonstrated Peacefully Before at Plant1980-03-28028 March 1980 PNO-II-80-049:Safe Energy Alliance Is Planning Forum on 800329 at Park Outside Plant Gate.Group Has Demonstrated Peacefully Before at Plant PNO-II-80-021, on 800208,QC Inspectors Qualified for Inspecting Pipe Hangers Terminated for Cheating on Test That Would Have Expanded Expertise.Licensee Expects Employees to Create Media Interest1980-02-0808 February 1980 PNO-II-80-021:on 800208,QC Inspectors Qualified for Inspecting Pipe Hangers Terminated for Cheating on Test That Would Have Expanded Expertise.Licensee Expects Employees to Create Media Interest 1998-06-04 Category:TEXT-INSPECTION & AUDIT & I&E CIRCULARS MONTHYEARIR 05000369/19990061999-10-0404 October 1999
[Table view]Insp Repts 50-369/99-06 & 50-370/99-06 on 990801-0911. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 05000369/19990051999-08-26026 August 1999 Insp Repts 50-369/99-05 & 50-370/99-05 on 990620-0731.Two Violations Noted Being Treated as Ncv.Major Areas Inspected: Operations,Maint,Engineering & Plant Support IR 05000369/19990041999-07-13013 July 1999 Insp Repts 50-369/99-04 & 50-370/99-04 on 990509-0619.Four Violations of NRC Requirements Occurred & Being Treated as Ncvs.Major Areas Inspected:Aspects of Licensee Operations, Maint,Engineering & Plant Support IR 05000369/19990101999-06-16016 June 1999 Insp Repts 50-369/99-10 & 50-370/99-10 on 990322-26.No Violations Noted.Major Areas Inspected:Aspect of Licensee Health Physics Activities During Unit 2 Refueling Outage IR 05000369/19990031999-06-0202 June 1999 Insp Repts 50-369/99-03 & 50-370/99-03 on 990328-0508. Non-cited Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support IR 05000369/19990021999-04-23023 April 1999 Insp Repts 50-369/99-02 & 50-370/99-02 on 990214-0327.No Violations Noted.Major Areas Inspected:Licensee Operations, Maint,Engineering & Plant Support IR 05000369/19993011999-03-18018 March 1999 NRC Operator Licensing Exam Repts 50-369/99-301 & 50-370/99-301 (Including Completed & Graded Tests) for Tests Administered on 990125-0205.Five SRO & Six RO Candidates Received Written Exams & Operating Tests IR 05000369/19990011999-03-10010 March 1999 Insp Repts 50-369/99-01 & 50-370/99-01 on 990103-0213.No Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 05000369/19980101998-12-18018 December 1998 Insp Repts 50-369/98-10 & 50-370/98-10 on 981004-1121.No Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 05000369/19980091998-10-30030 October 1998 Insp Repts 50-369/98-09 & 50-370/98-09 on 980823-1003.No Violations Noted.Major Areas Inspected:Aspects of Licensee Operations,Maint,Engineering & Plant Support IR 05000369/19980081998-09-21021 September 1998 Insp Repts 50-369/98-08 & 50-370/98-08 on 980712-0822.No Violations Noted.Major Areas Inspected:Aspects of Licensee Operations,Maint,Engineering & Plant Support ML20154C4131998-09-21021 September 1998 Notice of Violation from Insp on 980712-0822.Violation Noted:On or Before 971217,operations Personnel Failed to Designate Appropriate Vent Valves for Venting to Properly Return Sys to Svc as Required by Omp 7-1 IR 05000369/19980111998-08-27027 August 1998 Insp Repts 50-369/98-11 & 50-370/98-11 on 980601-26 & 0805-07.No Violations Noted.Major Areas Inspected:Maint & Engineering Programs.Rept Reviewed Maintenance,Surveillance & Matl Condition of Mcquire,Unit 1 Ice Condenser System IR 05000369/19980071998-08-0707 August 1998 Insp Rept 50-369/98-07 & 50-370/98-07 on 980531-0711. Violations Noted.Major Areas Inspected:Licensee Operations, Maint,Engineering & Plant Support ML20237B1561998-08-0707 August 1998 Notice of Violation from Insp on 980531-0711.Violation Noted:Licensee Failed to Establish Procedural Guidance for Abnormal Vent Path Used for Degassing Unit 1 Volume Control Tank to Environ IR 05000369/19980061998-06-25025 June 1998 Insp Repts 50-369/98-06 & 50-370/98-06 on 980419-0530.No Violations Noted.Major Areas Inspected:Aspects of Licensee Operations,Maint,Engineering & Plant Support IR 05000369/19980041998-06-0404 June 1998 Insp Repts 50-369/98-04 & 50-370/98-04 on 980413-24. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support PNO-II-98-030, on 980603,loss of Offsite Power Occurred,Due to Loss of 1B Bus.Caused by Faulted 230 Kv Switchyard Current Transformer.Resident Inspectors Onsite & Responded to Event & Will Continue to Evaluate Activities W/Event1998-06-0404 June 1998 PNO-II-98-030:on 980603,loss of Offsite Power Occurred,Due to Loss of 1B Bus.Caused by Faulted 230 Kv Switchyard Current Transformer.Resident Inspectors Onsite & Responded to Event & Will Continue to Evaluate Activities W/Event ML20249A2451998-06-0404 June 1998 Notice of Violation from Insp on 980413-24.Violation Noted: Procedure Investigation Processes 2-M96-1440 & 0-M97-1933 Were Not Initiated within 24 H After Realization That Procedure Investigation Process Should Have Been Written IR 05000369/19980031998-05-18018 May 1998 Insp Repts 50-369/98-03 & 50-370/98-03 on 980308-0418.No Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support ML20216H6051998-04-0606 April 1998 Notice of Violation from Insp on 980125-0307.Violation Noted:Licensee Failed to Adequately Establish or Adhere to Procedural Guidance for Repair of Two safety-related Containment Isolation Valves as Evidenced ML20216H6171998-04-0606 April 1998 Insp Repts 50-369/98-02 & 50-370/98-02 on 980125-0307. Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support IR 05000369/19970201998-02-23023 February 1998 Insp Repts 50-369/97-20 & 50-370/97-20 on 971214-980124. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support,Including Review of Radiological Protection Practices & Plant Physical Security ML20203F5921998-02-23023 February 1998 Notice of Violation from Insp on 980105-08.Violations Noted: Licensee Failed to Follow Procedures for Security Badge & Access Control IR 05000369/19980011998-02-17017 February 1998 Partially Withheld Insp Repts 50-369/98-01 & 50-370/98-01 on 980114-15 (Ref 10CFR2.790).No Violations Noted.Major Areas Inspected:Plant Support,Including Malevolent Use of Vehicles at Plant & Vehicle Barrier Sys IR 07100102/20120131998-01-12012 January 1998 Notice of Violation from Insp on 971102-1213.Violation Noted:Inadequate Measures Were Provided for Verification or Checking Adequacy of Design Documents ML20198P3771998-01-12012 January 1998 Insp Repts 50-369/97-18 & 50-370/97-18 on 971102-1213. Violations Noted.Major Areas Inspected:Integrated Insp Included Aspects of Licensee Operation,Maint,Engineering & Plant Support ML20199B1571998-01-0505 January 1998 Notice of Violation from Insp on 971205-06.Violation Noted: an Event Occurred on 971202 in Which Person or Persons Made Credible Threat to Commit or Cause Significant Physical Damage to Power Reactor & Not Reported within One Hour ML20199B1641998-01-0505 January 1998 Insp Repts 50-369/97-19 & 50-370/97-19 on 971205-06. Violations Noted.Major Areas Inspected:Licensee Response to 971202 Event Involving Seal Damage Event at Four Air Lock Doors of Unit 2 Containment Bldg ML20203M4471998-01-0505 January 1998 Errata to Notice of Violation for Insp Repts 50-369/97-19 & 50-370/97-19.Statement in Nov,Page 2, Under Authority of Section 182 of Act.42USC 2232,this Response Shall Be Submitted Under Oath or Affirmation, Was Incorrect IR 05000369/19970171997-12-0101 December 1997 Insp Repts 50-369/97-17 & 50-370/97-17 on 970921-1101.No Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 05000369/19970151997-10-20020 October 1997 Insp Repts 50-369/97-15 & 50-370/97-15 on 970810-0920. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support ML20198N4701997-10-20020 October 1997 Notice of Violation from Insp on 970810-0920.Violation Noted:On 960420,ET Guidelines,Apps C & E Were Not Implemented as Evidenced By;Resolution Analyst Revised & Overruled Reexam Request for SG 2A Tube R7C60 ML20212A0361997-10-0808 October 1997 Notice of Violation from Insp on 970712-0827.Violation Noted:As of 970717,10 of 48 Ice Condenser Inlet Doors on Unit 2 Required Initial Opening Torque in Ixcess of 675 inch-pound Operability Limit ML20211K9431997-09-26026 September 1997 Notice of Violation from Insp on 970721-26.Violation Noted: Licensee Failed to Follow Procedures for Security Badges & Access Control of Facility IR 05000369/19970121997-09-22022 September 1997 Insp Repts 50-369/97-12 & 50-370/97-12 on 970804-08.No Violations Noted.Major Areas Inspected:Observation & Evaluation of Biennial Emergency Preparedness Exercise ML20211E7981997-09-16016 September 1997 Insp Repts 50-369/97-16 & 50-370/97-16 on 970712-0827. Violations Being Considered for Escalated Eas.Major Areas Inspected:Review of Aspects of Problem Involving Inoperable Unit 2 Ice Condenser Lower Inlet Doors IR 05000369/19970101997-09-0808 September 1997 Insp Repts 50-369/97-10 & 50-370/97-10 on 970629-0809.No Violations Noted.Major Areas Inspected:Operations, Engineering,Maint & Plant Support IR 05000369/19973001997-08-29029 August 1997 NRC Operator Licensing Exam Repts 50-369/97-300 & 50-370/97-300 (Including Completed & Graded Tests) for Test Administered on 970728-31.Exam Results:Five SRO & One RO Passed Exam & One SRO Failed Exam IR 05000369/19970131997-08-22022 August 1997 Insp Repts 50-369/97-13 & 50-370/97-13 on 970721-24.No Violations Noted.Major Areas Inspected:Licensees Program for Compensatory Measures for Degraded Security Equipment ML20217R1161997-08-18018 August 1997 EN-97-076:on 970818,order Prohibiting Involvement in NRC- Licensed Activities for a Period of One Year Will Be Issued. Action Based on Investigation Conducted by Oi,Which Determined Falsification of QA Document PNO-II-97-051, on 970906,McGuire Units 1 & 2 Automatically Tripped.Porvs Utilized Until Steam Dumps Could Be Made Available.Steam Relieved Through Main Steam PORVs Until Power to Bus Kxa Restored & MSIVs Reopened1997-08-0909 August 1997 PNO-II-97-051:on 970906,McGuire Units 1 & 2 Automatically Tripped.Porvs Utilized Until Steam Dumps Could Be Made Available.Steam Relieved Through Main Steam PORVs Until Power to Bus Kxa Restored & MSIVs Reopened ML20149L5751997-07-28028 July 1997 Insp Repts 50-369/97-09 & 50-370/97-09 on 970518-0628. Violations Noted.Major Areas Inspected:Aspects of Licensee Operations,Engineering,Maint & Plant Support ML20149L5701997-07-28028 July 1997 Notice of Violation from Insp on 970518-0628.Violation Noted:Procedure IP/0/A/3250/12B Inadequate to Provide Sufficient Guidance to Properly Test Emergency Diesel Generator Sequencer Logic Circuitry ML20149G6881997-06-16016 June 1997 Insp Repts 50-369/97-08 & 50-370/97-08 on 970406-0517. Violations Noted.Major Areas Inspected:Licensee Operations, Engineering,Maint & Plant Support ML20149G6771997-06-16016 June 1997 Notice of Violation from Insp on 970406-0517.Violation Noted:Procedure PT/1/A/4600/014D Was Inadequate in Providing Sufficient Guidance to Bypass Properly RPS Functions of an Inoperable N-41 Channel to Permit Testing of Channel N-42 IR 05000369/19970071997-06-0202 June 1997 Insp Rept 50-369/97-07 on 970406-0503.Violations Noted.Major Areas Inspected:Sg Replacement Project Activities in Areas of Maint & Engineering IR 05000369/19970041997-05-0505 May 1997 Insp Repts 50-369/97-04 & 50-370/97-04 on 970223-0405. Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support ML20148B9621997-05-0505 May 1997 Notice of Violation from Insp on 970223-0405.Violation Noted:Prior to 961130,activities Affecting Quality,Not Accomplished in Accordance W/Instructions,Procedures or Drawings IR 05000369/19970051997-04-28028 April 1997 Insp Rept 50-369/97-05 on 970309-0405.No Violations Noted. Major Areas Inspected:Maint,Engineering & Plant Support 1999-08-26 |
y W
~
G . . .
' ' ' December 30, 1993
[EBELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE PNO-II-93-076A 1 -This preliminary notification constitutes EARLY notice of events of POSSIBLE safety or public interest significance. The'information is as initially recalved'without verification or evaluation, and is basically all that is
.hnown by the Region II staff on this date.
- E.acility Licensee Emercancy Classification
- Duke Power Co. Notification of Unusual Event
- Mcguire.2 Alert -;
.Cornelius, North Carolina Site Area Emergency ;
Dockets: _50-370 Genor=1 Emergency !
X Not Applicable
Subject:
UPDATE - SWITCHYARD INSULATOR FAILJRE LEADING TO LOSS OF OFFSITE POWER l
(;
The Augmented Inspection Team (AIT) arrived at McGuire on December 29, 1993. The team has begun its investigation of f e loss of'the off-site power-event that occurred on December 27, 1993. A Confirmation of Action ,
tLetter has been issued that requires the licensee to evaluate equipment andfpersonnel response for the event including the cause of the electrical faults, the "B" main steam isolation valve failure anu .he 4
- evaluation of the integrity and impact of the dry steam generator.
Restart of the Unit requires concurrence of the NRC. '
Press: releases have been issued by the NRC and licensee. At the present '
time'the licensee has not issued a recovery schedule. The licensee has initiated a Recovery Team and a Significant Event Investigation Team (SEF") to investigate the root cause of the event.