NRC Generic Letter 80-10, Issuance of NUREG-0588, "Interim Staff Position on Equipment Qualifications of Safety-Related Electrical Equipment"

From kanterella
Jump to navigation Jump to search

text

GL80010

FEB 05 1980

TO ALL CONSTRUCTION PERMIT AND OPERATING LICENSE APPLICANTS

SUBJECT: ISSUANCE OF NUREG-0588, "INTERIM STAFF POSITION ON EQUIPMENT QUALIFICATION OF SAFETY-RELATED ELECTRICAL EQUIPMENT"

A task force composed of members of the NRC staff has prepared a report entitled "Interim Staff Position on Environmental Qualification of Safety-

Related Electrical Equipment" (NUREG-0588), dated November 1979. The report provides the staff's resolution of the NRC's Generic Technical Activity A-

24, which is an "Unresolved Safety Issue" pursuant to SEction 210 of the Energy Reorganization Act of 1974. Copies of this "For Comment" edition of the report were mailed to all applicants on January 9, 1980. A notice of issuance and availability was published in the Federal Register (Vol. 45, No. 11, page 3124) on January 16, 1980. A copy of the notice is enclosed.

NUREG-0588 provides the NRC staff's technical positions on selected areas of environmental qualification, and provides guidance and describes methods which, when implemented, will ensure compliance with the Commission's requirements. The areas addressed include requirements for establishing the service conditions for areas inside and outside containment, to which equipment should be qualified; the selection of the qualification methods to be used for the equipment in these areas; and the preparation of qualification documentation. This report also defines the applicability of these positions to the different vintage plants undergoing a review for a construction permit or an operating license, that are required to conform to either the 1971 or the 1974 version of IEEE Standard 323.

In Implementing the positions described in NUREG-0588 the staff will require that applicants for operating licenses document the degree to which their qualification programs comply with the staff's positions described in NUREG-

0588, and their basis for any deviations. You will shortly receive, by separate letter, a request for additional information to be inserted in Section 3.11 of your Final Safety Analysis Report.

In addition, the staff plans to modify slightly its implementation of IEEE Std. 323-1974. Regulatory Guide 1.89, issued in November of 1974, requires that all CP applications for which a staff Safety Evaluation Report was issued after July 1, 1974, should comply with the requirements of IEEE Std. 323-1974. It has been staff practice to require that all other applicants comply with IEEE Std. 323-1971. This continues to be the staff practice with the following exceptions.TO ALL PWR AND BWR APPLICANTSFEB 05 1980

Equipment which would normally be qualified in accordance with IEEE Std. 323-1971, but which has not yet undergone qualification testing, should be qualified in accordance with IEEE Std. 323-1974. In implementing this guidance, the staff will use IEEE Std. 323-1974 and the provisions of Sections 2 through 5 of the Category I positions described in NUREG-0588 in assessing the adequacy of all equipment purchased six months from the date of issuance of NUREG-0588. The service conditions developed in accordance with Section 1, Category II of NUREG-0588 may be used in meeting this requirement.


Beginning 12 months from the date of issuance of NUREG-0588, equipment which must undergo requalification testing should also be qualified in accordance with IEEE Std. 323-1974 and the provisions of Sections 2 through 5 of Category I positions described in NUREG-0588. The service conditions developed in accordance with Section I, Category II may be used in meeting this requirement.

Public comments are being solicited from interested organizations, groups, and individuals. Because of the need to review and resolve any comments received from the public, we do not anticipate full implementation of these requirements until May 1980. However, in the interim, the positions described in NUREG-0588 are being used as guidance to the staff in reviewing applicants's qualification programs.

At the completion of the 60-day period, the staff will evaluate the comments received and, if needed, will issue a supplement or revision to NUREG-0588. The target for issuing the supplement or revision is late April 1980.

All comments on NUREG-0588 and this letter should be forwarded to Mr. Andrew J. Szukiewicz, Instrumentation and Control Systems Branch, Nuclear Regulatory Commission, Washington, D. C. 20555 by March 17, 1980.

Sincerely,

D. F. Ross, Jr., Acting Director Division of Project Management Office of Nuclear Reactor Regulation

Enclosure:

As stated