ea:
a Doughts R. Gipson Seruor Vice President Nuclear Generation Fermi 2' 6400 North Dixie Hignway
.(
Newport, Michigan 48166 '
. 313) 586-5249
(
' Reg Guide 1.16 April 13, 1995 NRC-95-0037 U. S. Nuclear Regulatory Commission Attention: Document Control Desk Nashington, D.C.
20555 i
Reference:
Feral 2 NRC Docket No. 50-341 NRC Operating-License No. NPF-43
Subject:
Monthly Operatinat Status Report for March, 1995 Enclosed for your information and use is the Fermi 2 Monthly Operating Status Report for March,-1995. This report includes the Operating Data Report, Average Daily Unit' Power Level,'and the Summary of Unit Shutdowns and Power Reductions identified j
in NRC Regulatory Guide 1.16 and Fermi 2 Technical Specification 6.9.1.6.
If you have'any questions, please contact Brian Stone, at' (313) 586-5148.
Sincerely, l
Enclosure oc:
T. G. Colburn D. R. Hahn J. B. Martin M. P. Phillips P. L. Torpy A.
Vegel cren
]" L,s L U lh lt PDR AD CK O O PR 1
R
OPERATING DATA REPORT 7
DOCKET NO. 50-341 COMPLETED BY B. J. Stone DATE.
April 13, 1995 TELEPHONE D13)586-5148 j
~
OPERATING STATUS 1.
UNIT NAME:
Fermi 2 l Notes:
(1.i Calculated using weight-l 2.
REPORTING PERIOD: March, 1995 I ed averages to reflect variations l
l 3
LICENSED THERMAL POWER (MWt): 3430 l in rating (MDC and DER).
l 4.
NAMEPLATE RATING (GROSS MWe):
1179 l (2) Currently limiting power to l
5.
DESIGN ELECT RATING (Net MWe): 1116 l 80% CTP maximum for Startup Test l
6.
MAX DEPENDABLE CAP (GROSS MWe):1135 I Program. All ratings reflect 98%
l 7.
MAX DEPENDABLE CAP (Net NWe):1085 l CTP due to turbine throttle valve l
l limitations.
l j
8.
IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS FUMBER 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS:
N/A 9
4 POWER LEVEL TO WHICH RESTRICTED, IF ANY (MWe Net): 80% CTP/2744 My'
- 10. REASONS FOR RESTRICTION, IF ANY:
(2)
THIS MONTH YR TO DATE CUMULATIVE
{
- 11. HRS IN REPORTING PERIOD 744 2,160 62,990
- 12. HRS REACTOR WAS CRITICAL 597.1 1,540.9 42,276.5 2
- 13. REACTOR RESERVE SHUTDOWN HRS 0
0 0
- 14. HOURS GENERATOR ON-LINE 355.4 598.8 39,723.2 1
l
- 15. UNIT RESERVE SHUTDOWN HOURS 0
0 0
- 16. GROSS THERMAL ENERGY GEN (MWH) 868,176 1,477,056 121.191,107 i
- 17. GROSS ELECT ENERGY GEN (MWH) 210,760 296,820 40,270,777 I
- 18. NET ELECT ENERGY GEN (MWH) 196,038 273,976 38,507.691 i
- 19. UNIT SERVICE FACTOR 47.8 27.7 63 1
- 20. Uh77 AVAILABILITY FACTOR 47.8 27.7 63.1
{
- 22. UNIT CAP FACTOR (USING DER NET) 23.6 11.4 55.5 j
- 23. UNIT FORCED OUTAGE RATE 49.6 70.0 22.9
- 24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, DURATION OF EACH):
- 25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
FORECAST ACHIEVED i
INITIAL CRITICALITY N/A N/A INITIAL ELECTRICITY N/A N/A COMMERCIAL OPERATION N/A N/A 4
r AVERAGE DAILY UNIT POWER LEVEL
s
-DOCKET NO.
50-341 UNIT FERMI 2 DATE April 13, 1995 i.
COMPLETED BY B. Stone 1
TELEPHONE (313) 586-5148
{
Month March, 1995 1
1 l
)
DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWEB LEVEL l
(MWe-Net)
(MWe-Net) 1 0
17 87 1
i 2
0 18 604 t
i i
3 0
19 648 i
4 0
20 700 3
5 0
21 620 6
0 22 615 7
0 23 616 8
0 24 616 1
9 0
25 615 10 0
26 228 l
11 0
27 0
12 0
28 67 1
i 13 79 29 627 1
j 14 26 30.
712 4
15 353 31.
713 16 239 i
j i
l l
I t
e
UNIT SHUTDOWNS AND POWE1 f. EDUCTIONS DOCKET NO.
50-31*
DATE April 13.
1*"5 5
UNIT NAME' Fermi _{
COMPLETED 11Y S. J.
Stann TELEPHONE (313) 586-5148 REPORT MONTH March. 1995 i
METHOD OF SHUTTING DOWN LER SYS COMP CAUSE & CORRECTIVE NO.
DATE TYPE DUR REASON THE REACTOR NO.
CODE-CODE ACTION TO PREVENT (1)
(HRS)
(2)
OR. REDUCING (4)
(5)
RECURRENCE (6)
(7)
POWER (3) 595-03 950213 F
302.1 B
1 N/A TD -
PSP Turbine taken off-line to repair (8) turbine jacking oil. system structural concerns.
t 595-04 950314 5
18.1 B
N/A
'N/A TA TRB Turbine taken off-line to perform i
post outage balancing.
I S95-05 950316 5
20.6 B
N/A N/A TA TRB Turbine taken off-line to obtain turbine coastdown bearing vibration data.
595-06 950326 F
47.8-B N/A N/A TJ.
PSP Turbine taken off-line to repair
+
a stator cooling water vent line leak.
(1) F FORCED (2) REASON:
(3) METHOD:
(4) INSTRUCTIONS FOR 5: SCHEDULED' A - EQUIPMENT FAILURE (EXPLAIN) 1 - MANUAL PREPARATION OF DATA S - MAINTENANCE OR TEST 2 - MANUAL SCRAM ENTRY SHEETS FOR LICENSEE C - REFUELING 3 - AUTOMATIC SCRAM EVENT REPORT (LER). FILE D - REGULATORY RESTRICTION 4 - CONTINUED (NUREG-1022)
E - OPERATOR TRAINING & LICENSE EXAMINATION 5 - REDUCED LOAD F'- ADMINISTRATIVE
'9 - OTHER G - OPERATIONAL ERROR (EXPLAIN)
H - OTHER (EXPLAIN)
(S) 1AME SOURCE AS (4)
(6) R - PREFIX INDICATES POWER REDUCTION.
S - PREFIX INDICATES PLANT SHUTDOWN.
(7) DURATION OF REDUCTIONS REPORTED AS ZERO PER REG.
GUIDE 1.16 REV. 4
-(8)
Outage hours are a continuation of the outage which began on 02/13/95.
I 4
s
~
- ~.
- ~
.