NRC-93-0057, Monthly Operating Rept for May 1993 for Fermi 2

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for May 1993 for Fermi 2
ML20045C173
Person / Time
Site: Fermi DTE Energy icon.png
Issue date: 05/31/1993
From: Gipson D, Pirkle R
DETROIT EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
CON-NRC-93-0057, CON-NRC-93-57 NUDOCS 9306220155
Download: ML20045C173 (4)


Text

A b

4 g.

Douglas R. G,pson Senior Vete Presdemt Nudear Genmalen

' Detroit r.- 2 an, a.. e,

' EC ISO'D f4eep'A1.fAf hqrt 4 ft1b (313) 's%-!J 49 Reg Guide 1.16 June 15, 1993 NRC-93-0057 U. S. Nuclear Regulatory Commission Attention:

Document Control Desk Washington, D.C.

20555

Reference:

Fermi 2 NRC Docket No. 50-341 NRC Operating License No. NPF 63

Subject:

Monthly Operating Status Report for May, 1993 Enclosed for your information and use is the Fermi 2 Monthly Operating Status Report for Hay, 1993 This report includes the Operating Data Report, Average Daily Unit Power Level, and the Summary of Unit Shutdowns and Power Reductions identified in NRC Regulatory Guide 1.16 and Fermi 2 Technical Specification 6.9.1.6.

If you have any questions, please contact Brian Stone, at (313) 586-5148.

Sincerely, Enclosure cc:

T. G. Colburn D. R. Ilahn W. J. Kropp J. B. Martin M. P. Phillips P. L. Torpey A 'A

a. v. u.w

,I i

9306220155 930531 e

$DR ADOCK 05000341 l8 PDR fj

l

~

p-OPERATING DATA REIORT DOCKET NO.

50-341 COMPLETED BY B. J. Stone DATE June 15, 1993 TELEPHONE (313) 586-5148 OPEftATING STATUS 1.

UNIT NAME:

Fermi 2 l Notes:

(1) Calculated using weight-l 2.

ItEPORTING PERIOD:

May, 1993 l ed averages to reflect variations i

3 LICENSED TiiERMAL POWER (MWt):

3430 l In rating (MDC and DER).

l 4.

NAMEPLATE RATING (GROSS MWe):

1179 l (2) Currently limiting power to l

S.

DESIGN ELECT RATING (Net MWe):_1116 I 93 5% CTP maximum to limit turbine l

6.

MAX DEPENDABLE CAP (GROSS MWe):1135 I component vibration. All ratings l

7 MAX DEPENDABLE CAP (Net MWe):1085 l reflect 98% CTP due to turbine l throttle valve limitations.

l 8.

IF CilANGES OCCUR IN CAPACITY RATINGS (ITEMS NUMBER 3 TilROUGH 7) SINCE LAST llEPORT, GIVE REASONS:

N/A 9

POWEli LEVEL TO WHICli ItESTRICTED, IP ANY (MWe Net):

(2)

10. HE!. SONS FOR RESTRICTION, IF ANY:

(2)

THIS MONTH YR TO DATE CUMULATIVE

11. IIRS IN REP 0ftTING PERIOD 744 3,623 46,933
12. HRS ItEACTOR WAS CRITICAL 744 3,273.6 35,676.8
13. REACTOR RESERVE SIIUTDOWN llRS 0

0 0

14. Il0URS GENERATOR ON-LINE 744.0 3,236.5 34,283.6
15. UNIT RESEltVE SliUTDOWN HOURS 0

0 0

16. GitOSS TilERMAL ENEftGY GEN (HWil) 2,378,400 10,430,544 104,517,839.4
17. GitOSS ELECT ENERGY GEN (MWH) 804,140 3,561,110 34,888,857
18. NET ELECT ENERGY GEN (HWil) 769,928 3,419,819 33,368,820
19. UNIT SERVICE FACTOR 100.0 89.3 73.0
20. UNIT AVAILABILITY FACTOR 100.0 89.3 73.0
21. UNIT CAP FACTOR (USING MDC NET) 95.4 87.0 66.4 (1)
22. UNIT CAP FACTOR (USING DER NET) 92.7 84.6 64.9 (1)
23. UNIT FORCED OUTAGE RATE 0.0 4.3 7.5
24. SIIUTDOWNS SCilEDULED OVER NEXT 6 MONTilS (TYPE, DATE, DURATION OF EACil):
25. IF SHUT DOWN AT END OF REP 0ftT PERIOD, ESTIMATED DATE OF STARTUP:
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):

FORECAST ACllIEVED INITIAL CRITICALITY N/A N/A INITIAL ELECTRICITY N/A N/A I

COMMEllCI AL OPERATION N/A N/A

F AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.

50-341 UNIT FERMI 2 DATE June 15, 1993 COMPLETED BY R. Pirkle TELEPHONE 1313)586-5027 Month May, 1993 DAY AVERAGE DAILY POL'ER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Set)

(MWe-Net) 1 1043 17 1039 2

1041 18 1040 3

1032 19 1044 4

1033 20 1045 5

1027 21 1044 6

1034 22 1041 7

1037 23 1032 8

1032 24 1019 9

1036 25 1036 10 1032 26 1034 11 1030 27 1042 12 1029 28

__ 1024 13 1047 29 1044 14 1035 30 1042 15 1023 31 1036 16 1042

UNIT SMJTDOWNS AND POWER REDUCTIONS s

DDCKET NC 9D-34' DATE June

'E

'993 UNIT NAME 5e-mi 2

CCvPLETED SN B.

m Stone TELED"ONE (3'?? 596-514e REPCRT MONTH May, 1993 v E l sO;- Oc j

SHUTTING DOwN uER Sv5 CDUD CAUSE & CORRECTIVE NO.

DATE T*?r DLR REASON THE REACTOR 1

NO.

CCDE i CODE ACTION TO PREVEN 7 i

I

(?!

(~RS);

(2i CR REDUCING I

(4) i (5)

RECURRENCE l

(0!

I71 PO*ER (31 i

6 t

+

i i

j 1

l

___ [

j I

l 6

(1) F: FORCED (2) REASON:

(3) VETHOD:

(4) INSTRUCTIONS FOR 5: SCHEDUL'cD A - EOJIPVENT SAILURE (EAPuAIN) 1 - VANUAL PREPARATION OF DATA B - MAINTENANCE 04 TEST 2 - VANUAL SCRAV ENTRY SHEETS FOR LICENSEE C - EEFUELING 3 - AUTOVATIC SCRAV EVENT REPORT (LER) FILE D - FEGuLATORv RESTRICTION 4 - CONTINUED (NUREG-1022)

E - DDERATOR TRAINING & LICENSE EAAv! NATION 5 - REDUCED LOAD F - ADMINISTRATIVE 9 - OTHER G-OPERATIONA. ER20R (EXPLAIN)

-H

- DTHER (EXPLAIN)

(5) SAME SOURCE A5 (4)

(6) R - PR E C I )-

INDICATES POWER REDUTTION.

5 - PRE *IX INDICATES PLANT SHUTDOWN.

(7) DURATION 08 REDUCTIONS REPORTED A5 ZERO PER REG.

GUIDE 1.16 REV. 4 i

l 1

-