NOC-AE-02001307, Fire Hazards Analysis Report, Amendment 14

From kanterella
Jump to navigation Jump to search
Fire Hazards Analysis Report, Amendment 14
ML021260711
Person / Time
Site: South Texas  STP Nuclear Operating Company icon.png
Issue date: 04/22/2002
From: Sheppard J
South Texas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NOC-AE-02001307
Download: ML021260711 (168)


Text

Nuclear Operating Company South Texas ProlectElectric GeneaingStation PO. Box 289 Wadsworth, Texas 77483 /

April 22, 2002 NOC-AE-02001307 10CFR50.71 U. S. Nuclear Regulatory Commission Attention: Document Control Desk One White Flint North 11555 Rockville Pike Rockville, MD 20852 South Texas Project Units 1 and 2 Docket Nos. STN 50-498, STN 50-499 Fire Hazards Analysis Report, Amendment 14 Pursuant to 10CFR50.71, STP Nuclear Operating Company submits Amendment 14 to the South Texas Project Fire Hazards Analysis Report (FHAR) as Attachment 2. includes a summary of changes in FHAR Amendment 14 that were made under the provisions of 10CFR50.59 or in accordance with the guidance of NEI 98-03 and NEI 96-07.

Copies of the Fire Hazards Analysis Report, Amendment 14 are provided in accordance with the distribution requirements of 10CFR50.4 (b) (1). A copy of this transmittal is attached to each Fire Hazards Analysis Report, Amendment 14.

If you should have any questions on this submittal, please contact Mr. S.M. Head at (361) 972-7136 or me at (361) 972-8757.

I declare under penalty of perjury that the foregoing is tue and correctf.

Executed on '+ 1 ý'40., - . r,

  • ' e Presidaen~t Engineering &

Technical Services MKJ : Fire Hazards Analysis Report Summary of Changes Made Under the Provisions of 10CFR50.59 or in accordance with the Guidance of NEI 96 07 and NEI 98-03 Attachment 2: Fire Hazards Analysis Report, Amendment 14 OA\QUALITYAND LICENSING\NL\NRC-WK\MISC-02\NOC-AE-02001307 STI 31435536

NOC-AE-02001307 Page 2 of 2 cc:

(paper copy) (electronic copy)

  • Ellis W. Merschoff A. H. Gutterman, Esquire Regional Administrator, Region IV Morgan, Lewis & Bockius LLP U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 400 M. T. Hardt/W. C. Gunst Arlington, Texas 76011-8064 City Public Service
  • U. S. Nuclear Regulatory Commission Mohan C. Thadani Attention: Document Control Desk U. S. Nuclear Regulatory Commission One White Flint North 11555 Rockville Pike R. L. Balcom/D. G. Tees Rockville, MD 20852 Reliant Energy, Inc.

Richard A. Ratliff A. Ramirez Bureau of Radiation Control City of Austin Texas Department of Health 1100 West 49th Street C. A. Johnson/A. C. Bakken III Austin, TX 78756-3189 AEP - Central Power and Light Company Cornelius F. O'Keefe Jon C. Wood U. S. Nuclear Regulatory Commission Matthews & Branscomb P. O. Box 289, Mail Code: MN116 Wadsworth, TX 77483 C. M. Canady City of Austin Electric Utility Department 721 Barton Springs Road Austin, TX 78704 Note: The above copies distributed without Attachments except as noted by the asterisk.

Instruction Sheet for STP Final Hazards Analysis Report - Amendment 14)

Remove Pages/Figures Insert Pages ACNV Volume TABLE OF CONTENTS dated 3/20/02 TABLE OF CONTENTS dated 4/18/02 CN-2598 CN-2599 Volume 1 Insert in Front of FHAR Volume 1 FHAR Summary of Changes

[1 page]

FHAR List of Effective Pages

[ 12 pages]

Chapter 2 2-17 2-17 2-28 2-28 2-30 2-30 Chapter 3 3.1-1 3.1-1 3.1-2 3.1-2 3.2-8 3.2-8 3.2-18 3.2-18 3.2-19 3.2-19 3.2-20 through 3.2-26 3.2-20 through 3.2-26 3.2-28 3.2-28 3.2-30 3.2-30 3.2-31 3.2-31 3.2-33 through 3.2-35 3.2-33 through 3.2-35 3.2-46 through 3.2-48 3.2-46 through 3.2-48 3.2-50 through 3.2-55 3.2-50 through 3.2-55 3.2-57 3.2-57 3.2-58 3.2-58

Instruction Sheet for STP Final Hazards Analysis Report - Amendment 14)

Remove Pages/Figures Insert Pages 3.2-60 3.2-60 3.2-64 through 3.2-69 3.2-64 through 3.2-69 3.2-71 3.2-71 3.2-76 3.2-76 3.2-83 3.2-83 3.2-84 3.2-84 3.2-88 3.2-88 3.2-91 3.2-91 3.2-93 3.2-93 3.2-118 3.2-118 3.2-124 3.2-124 3.2-131 3.2-131 3.2-132 3.2-132 3.2-136 3.2-136 3.2-141 3.2-141 3.2-144 3.2-144 3.2-148 through 3.2-152 3.2-148 through 3.2-152 3.2-154 3.2-154 3.2-158 3.2-158 3.2-160 3.2-160 3.2-163 3.2-163 3.2-168 3.2-168 3.2-169 3.2-169 3.2-171 3.2-171 3.2-173 through 3.2-179 3.2-173 through 3.2-179 3.2-182 3.2-182 3.2-185 3.2-185 3.2-188 3.2-188 3.2-191 3.2-191 3.2-194 3.2-194 3.2-197 3.2-197 3.2-201 3.2-201 3.2-203 3.2-203 3.2-206 3.2-206 3.2-207 3.2-207 3.2-209 3.2-209 3.2-211 3.2-211 3.2-214 3.2-214 3.2-216 3.2-216 3.2-218 3.2-218 3.2-220 3.2-220 3.2-223 3.2-223

Instruction Sheet for STP Final Hazards Analysis Report - Amendment 14)

Remove Pages/Figures Insert Pages 3.2-224 3.2-224 3.3-7 3.3-7 3.3-12 3.3-12 3.3-13 3.3-13 3.4-4 3.4-4 3.4-8 3.4-8 3.4-12 3.4-12 3.4-25 3.4-25 3.4-28 3.4-28 3.4-31 3.4-31 3.4-34 3.4-34 3.4-37 3.4-37 3.4-40 3.4-40 3.5-5 3.5-5 3.5-6 3.5-6 3.5-11 3.5-11 3.5-12 3.5-12 3.5-17 3.5-17 3.5-18 3.5-18 3.5-23 3.5-23 3.5-24 3.5-24 3.5-25 3.5-25 3.6-5 3.6-5 3.6-9 3.6-9 3.6-14 3.6-14 3.6-17 3.6-17 3.6-20 3.6-20 3.6-23 3.6-23 3.8-13 3.8-13 3.8-14 3.8-14 3.8-17 through 3.8-42 3.8-17 through 3.8-42 3.9-4 3.9-4 Chapter 4 4.2-42 4.2-42

ATTACHMENT 1 NOC-AE-02001307 Page 1 of 1 Attachment 1 Fire Hazards Analysis Report Summary of Changes Made Under the Provisions of 10CFR50.59 or in accordance with the Guidance of NEI 96-07 and NEI 98-03 Chapter 2, "Safe Shutdown Assessment"

1. Removed 150-ton chillers from safe shutdown equipment list.

[ Table 2-2] (CN-2599)

Chapter 3, "Fire Hazards Analysis"

1. Clarified note to state the use of maximum permitted load (MPL) as described in calculation. [3.1.2] (CN-2598) {NEI 96-07}
2. Revised the document number for safe shutdown cable listings in all Fire Zone Tables. (CN-2598) {NEI 96-071
3. Revised wording to remove the word "all" and replace with "some". [G.4]

(CN-2598) {NEI 96-07}

Chapter 4, "Comparison APCSB 9.5-1 Appendix A and 10CFR50 Appendix R"

1. Incorporated information regarding the Human Interface Module. (CN-2205)

[Table 4.2]

ATTACHMENT 2 TABLE 2-2 SAFE SHUTDOWN EQUIPMENT LIST (Note 2)

Elec/Proc. Current Room Train Amendment Fire Area Number System Equipment Tag Number (Note 1) Equipment Description Function Number 02Z128 067 CC 3R20INPAI01A A/A CCW Pump IA CCW Support 3 02Z128 067 HM 3VIO0VAHOOI A/A CCW Pump IA Supplementary Cooler HVAC Support 3 02Z128 067 HM 3VIOVAH019 A/A Essential Chiller Area AHU-Train A HVAC Support 6 ,z 02Z128 067 CH 3VlIVCH004 A/A EAB Essential Chiller #4 HVAC Support 6 02Z128 067 CH 3V 1IIZLP620 A/A HVAC Chiller Panel #1 HVAC Support 7 02Z128 067 CH 3V1 I1ZLP623 A/A HVAC Chiller Panel #1 HVAC Support 7 H

I1 02Z128 067 CH 3V IIIVPA004 A/A Essential Chilled Water Pump Train A HVAC Support 3 03Z031 201 HE 3VI IIVFN031 B/B Elect. Penet. Area HVAC Emerg. Fan HVAC Support 3 03Z031 201 HE 3V I I1VAH005 B/B Pen. Space HVAC Emerg. AHU HVAC Support 7 03Z031 201 PF NIPFEMC01 B5 N/* 480 VAC Non Vital MCC IB5 Electrical Distribution 6 03Z031 201 PN NI PNERR 113 N/* Auxiliary Relay Rack 113 Electrical Distribution 6 03Z031 201 PN NIPNERRI15 N/* Auxiliary Relay Rack 115 Electrical Distribution 6 03Z038 HE AI HEFV9673 A/A Control Room Exhaust Isolation Damper HVAC Support 03Z038 HE A l HEFV9674 B/B Control Room Exhaust Isolation Damper HVAC Support 03Z038 HE A IHEFY9673 A/A Solenoid for FV9673 HVAC Support 03Z038 HE A IHEFY9674 B/B Solenoid for FV9674 HVAC Support 03Z038 HE AI1HESC9673 A/A Limit Switch for FV9673 HVAC Support 03Z038 HE A IHESC9674 B/B Limit Switch for FV9674 HVAC Support 03Z039 206 HE 3V I I1VAH008 B/B Control Room Envelope AHU II B &Supply Fan HVAC Support 7 03Z039 206 HE B IHEFY9697 B/B Control Room Retum Air Control Damper (FV-9697) HVAC Support 6 4:a

TABLE 2-2 SAFE SHUTDOWN EQUIPMENT LIST (Note 2)

Elec/Proc. Current Train Amendment Room Number Fire Area Number System Equipment Tag Number (Note 1) Equipment Description Function 27Z127 048 CV 2R171XCV0102 */* Isol. Valve for PCV0135 RCS Letdown CV */* Isol. Valve for PCVO135 RCS Letdown 27Z127 048 2RI71XCV0103 CV */* CVCS Flow Valve to RHT RCS Letdown 27Z127 226 2R171TCV0193 079 CV 2R171TCV0225

  • ]* PDP Recirc. Manual Valve RCS Charging 27Z127 CV 2R171TCV0255 *1* Loop Charging Bypass Valve RCS Charging 8 27Z127 079 Charging Flow Control Vlv. RCS Boration 3 27Z127 079A CV A 1CV-FCV-0205 Charging Flow Control (FCV-205) Sol. Vlv. RCS Boration 3 27Z127 079A CV A ICV-FY-0205 Chg. Pmp. lB Isol. Viv. RCS Boration 3 27Z127 079A CV Al CV-MOV-8377B 27Z127 079B CV CICV-MOV-8348 (Deleted) 27Z127 079B CV CI CV-MOV-8377A Chg. Pmp. IA Isol. VIv. RCS Boration H CV 2RI71-XCV-0170 A/* Excess and Seal Letdown Return to VCT Isolation Valve RCS Letdown T1 27Z127 050

,tQ CV 2R171-XCV-0171 A/* Excess and Seal Letdown Return to Charging Pump Suction RCS Letdown tQ 27Z 127 050 00 050 CV 2R17 1-XCV-0693 A/* Excess and Seal Letdown Return to VCT Isolation Valve RCS Letdown 27Z127 046 CV NICVPCV0135

  • /* Outlet of Letdown HX RCS Letdown 27Z127
  • [* RCS Letdown 27Z127 046 CV N ICVPY3164 Ito P for PCVO135 037 CV 2RI71NPDIOIA C/* PDCP Suction Stabilizer RCS Boration 27Z127 C/
  • CC N I CC-TV-4494 CCW Outlet from Letdown HX IA CCW Support 27Z127 046 *]*

CC N I CC-TY-4494 Cntrlr. for TV4494 CCW Support 27Z127 046 CV Seal Injection ISO Vlv RCS Charging 27Z127 079C C ICVHCV0218 079C CV C1CVHY3171A Solenoid for CI CVHCV0218 RCS Charging 27Z127 079A CV 2R171XCV0254A Loop Charging Isolation Valve RCS Charging 27Z127 C/C CCW Pump IC CCW Support 27Z139 067F CC 3R201NPA1OIC 27Z139 067F HM 3V 101VAH003 C/C CCW Pump IC Supplementary Cooler HVAC Support C/C Essential Chiller Area AHU HVAC Support z

27Z139 067F HM 3VI0lVAH021

TABLE 2-2 SAFE SHUTDOWN EQUIPMENT LIST (Note 2)

Elec/Proc. Current Room Train Amendment Fire Area Number System Equipment Tag Number (Note 1) Equipment Description Function Number 27Z142 106 CC B ICC-MOV-0644 B/B CCW HX I B Bypass Vlv. CCW Support 3 27Z142 106 CC B ICC-MOV-0645 B/B CCW HX I B Disch. Vlv. CCW Support 3 27Z142 106 CC CICC-MOV-0646 C/C CCW HX IC Bypass Valve CCW Support 3 27Z142 106 CC C ICC-MOV-0647 C/C CCW HX I C Disch. Valve CCW Support 3 29Z140 067E CC 3R20INPAI0IB B/B CCW Pump lB CCW Support 3 29Z140 067E HM 3V101VAH002 B/B CCW Pump I B Supplementary Cooler HVAC Support 3 n

29Z140 067E HM 3V101VAH020 B/B Essential Chiller Area AHU HVAC Support 3 z, 29Z140 067E CH 3V I I1VCH005 B/B Essential Chiller Train B HVAC Support 29Z140 067E CH 3VI IIVPA005 B/B Essential Chilled Water Pump Train B HVAC Support 29Z140 067E CH 3V1 I IZLP621 B/B HVAC Chiller Panel #2 HVAC Support 7 7

7r1 29Z140 067E CH 3V 11ZLP624 B/B HVAC Chiller Panel #2 HVAC Support t'.

31 Z047 302 PN 3EI21ETCBOI (Deleted) 6 31 Z047 302 PN 3EI2IETCB02 (Deleted) 6 31 Z047 302 PN 3E 121 ETCB03 (Deleted) 6 31 Z047 302 PN 3E 121 ETCB04 (Deleted) 6 31 Z047 302 PN 3E 121ETCB05 (Deleted) 6 32Z122 324B CC 3R20INTSIO0A

  • /
  • CCW Surge Tank CCW Support 3 35Z310 305 HF 9VI21VAHOOI (Deleted) 6 2 35Z310 305 AP 9Z541ZLP665 (Deleted) 6 a

CD 35Z310 305 AP 9Z541ZLP666 (Deleted) 6

STP FHAR 3.0 FIRE HAZARDS ANALYSIS

3.1 INTRODUCTION

This section contains the Fire Hazards Analysis (FHA) and the details that form the basis for it. The FHA, in the form of a narrative and table, is the data base supporting the conclusion that applicable requirements of Appendix R have been met. This data is presented on a building basis, with each fire area within the building being discussed. Where appropriate, the fire areas are further divided into fire zones and a table provided for each zone. Fire zone locations and descriptions are summarized in Table 3.1-1.

Fire area drawings, depicting the items noted in the discussion as well as the physical plant layout, are included at the end of Chapter 3.0.

It should be noted that although the analysis is written in terms of Unit 1, both Units 1 and 2 are essentially identical and therefore the analysis is applicable to both. The Unit 2 design differences will be evaluated.

3.1.1 Methodology The methodology used in performing this FHA for STP is discussed in Section 1.6 of this report.

3.1.2 Fire Area and Zone Tables The description of fire areas and fire zones is done in terms of the items defined below:

"* Equipment Equipment required for safe shutdown is listed in Table 2-2, the Safe Shutdown Equipment List, which includes the area in which the equipment is located.

"* Circuits A reference as to where a listing of the safe-shutdown circuits in the fire area or zone is to be found.

"* Combustibles In-situ and potential transient combustibles are considered for the fire loading in the fire area or zone. For transient combustibles, this is an estimate which is not to be used for Fire Protection Program limitations. The combustible loading of a fire zone is considered negligible when it is calculated to be less than 5 minutes in duration.

NOTE: The combustible load values shown are based on: a) actual cable loading as tabulated in Plant Data Management System (PDMS), b) permanent plant fire loading of the area, c) a specified amount of transient fire 00 load as allowed by administration limits; and are bounded by the construction of the fire barrier. This value is used 3.1-1 Amendment 14

STP FHAR in the combustible calculation as maximum permitted load (MPL).

"* Detection. Type of fire detection system(s) in the fire area or zone.

A summary of detection-zone locations and descriptions is presented in Table 3.1-2.

"* Suppression Type of fire suppression system(s) applicable to the fire area or zone.

"* Radioactive/ Existence of any radioactive or toxic Toxic Material material in the fire area or zone. When no quantities of toxic material is given, the toxic material is PVC in negligible quantities.

Communications Identifies whether or not emergency communication is located in the room.

"* Emergency Identifies whether or not emergency Lightning lighting (in the form of 8-hour battery packs) is located in the room.

"* Redundant Safe Identifies the conclusions derived from Shutdown Assessment the Appendix R,Section III.G evaluation.

3.1.3 Spurious Actuation, Common Power Source and Common Enclosure 3.1.3.1 Spurious Actuation The consequences of spurious operation of equipment have been mitigated by protection of cables or by manual compensating operator action. These operator actions include verification of the equipment status, de-energizing electrical equipment and manually repositioning valves. Specifics of the mitigation provided are listed in report no. 5AO19MFPOO1 titled "Post Fire Operator Actions and Equipment Protection Requirements".

3.1.3.2 Common Power Source During the Appendix R, Section llI.G evaluation, potential associated circuits (using common power supplies) that may affect safe shutdown were identified. Where the breakers or fuses of these circuits do not coordinate these circuits are listed in document 5E019EL002 "Safe Shutdown Circuit Listing" as associated circuits of concern (category ASC). Where coordination is required in a specific fire area, the coordination in that fire area has been analyzed. Where coordination does not exist in the specific fire area, the appropriate cables are protected.

The STP evaluation of multiple high impedance cable failures concluded that in no case could simultaneous multiple high impedance faults cause loss of power to any circuit not directly affected by the fire.

3.1-2 Amendment 14

STP FHAR FIRE ZONE TABLE 1-1 FIRE AREA NO. 1 FIRE ZONE Z032 RELAY CABINET AREA OF CONTROL ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits Z

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 4,110 ft2)

Detection: Ionization Suppression: Automatic Total Flooding Halon System Hand-Held Carbon Dioxide Hand-Held Pressurized Water Hose Cabinet Outside Zone: HC-4 Hose Reel Outside Zone: HR-6 Rad/Toxic Material: N/Y Communications: Y Emergency Lighting: Y 3.2-8 Amendment 14

STP FHAR FIRE ZONE TABLE 2-1 FIRE AREA NO. 2 FIRE ZONE ZOO CHANNEL II DISTRIBUTION ROOM See Table 2-2 for Safe Shutdown List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 584 ft2)

Detection: Ionization Suppression: Hose Cabinets Outside Zone: HC-1 and HC-3 Hand-held Carbon Dioxide Rad/Toxic Material: N/Y Communications: N Emergency Lighting: Y 3.2-18 Amendment 14

STP FHAR FIRE ZONE TABLE 2-2 FIRE AREA NO. 2 FIRE ZONE Z002 CHANNEL II BATTERY ROOM SEE TABLE 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation."

Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 442 ft2)

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-1 Hand-held Carbon Dioxide Rad/Toxic Material: N/Y Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-19 Amendment 14

STP FHAR FIRE ZONE TABLE 2-3 FIRE AREA NO. 2 FIRE ZONE Z003 CHANNEL I DISTRIBUTION ROOM See Table 2-2 for Safe Shutdown List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btulft2 (Area: 533 ft2 )

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-1 Hand-held Carbon Dioxide Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-20 Amendment 14

STP FHAR FIRE ZONE TABLE 2-4 FIRE AREA NO. 2 FIRE ZONE Z004 ESF SWITCHGEAR ROOM, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btu/ft 2 (Area: 3397 ft2)

DETECTION: Ionization Suppression: Manual Hose Cabinets Outside Zone: HC-7 and HC-3 Hand-Held Carbon Dioxide Manually actuated, dry pipe, close head, special hazard Sprinkler System for cable trays RadlToxic Material: N/N Communications: Y Emergency Lighting: Y 3.2-21 Amendment 14

STP FHAR FIRE ZONE TABLE 2-5 FIRE AREA NO. 2 FIRE ZONE Z005 HVAC EQUIPMENT ROOM, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits

,z A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles

  • See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 1276 ft2)

Detection: Ionization for Area Thermal for Charcoal Filter Suppression: Hose Cabinet Outside Zone: HC-12 Hand-held Carbon Dioxide Deluge System for Charcoal Filter HVAC EQUIPMENT ROOM, TRAIN A Rad/Toxic Material: Y/N Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit
    • Fire zone Z005 includes the Control Room Cleanup Unit (Charcoal Filter).

This Cleanup Unit has been assigned the fire detection zone Z086.

3.2-22 Amendment 14

STP FHAR FIRE ZONE TABLE 2-6 FIRE AREA NO. 2 FIRE ZONE Z006 ELECTRICAL PENETRATION AREA, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011 MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 5190 ft2)

Detection: Ionization Suppression: Hose Reel inside Zone: HR-5 Hand-held carbon dioxide Automatic wet pipe sprinkler system at ceiling level.

Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-23 Amendment 14

STP FHAR FIRE ZONE TABLE 2-7 FIRE AREA NO. 2 FIRE ZONE Z010 POWER CABLE VAULT, TRAIN A See Table 2-2 for Safe Shutdown Equipment List.

Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 7455 ft2 )

Detection: Ionization Suppression: Automatic Sprinklers, at Ceiling Level Hose Reels Inside Zone: HR-1 and HR-9 Hand-held Dry Chemical Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-24 Amendment 14

STP FHAR FIRE ZONE TABLE 2-8 FIRE AREA NO. 2 FIRE ZONE Z013 EQUIPMENT ROOM, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 485 ft2 )

Detection: Ionization Suppression: Hose Reel Outside Zone: HR-9 Hose Cabinet Outside Zone: HC-12 Hand-held Carbon Dioxide Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-25 Amendment 14

STP FHAR FIRE ZONE TABLE 2-9 FIRE AREA NO. 2 FIRE ZONE Z016 CORRIDOR AT ELEVATION 10' See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area: 2868 ft2)

Detection: Ionization Suppression: Hose Reels Outside Zone: HR-9 and HR-5 Hose Cabinets Inside Zone: HC-1, HC-3, HC-7, and HC-12 Hand-held Carbon Dioxide Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-26 Amendment 14

STP FHAR FIRE ZONE TABLE 2-11 FIRE AREA NO. 2 FIRE ZONE Z027 ELECTRICAL CHASE, TRAIN A See Table 2-2 for Safe Shutdown Equipment List.

Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 162 ft2)

Detection: Ionization Suppression: Hose Reel outside Zone: HR-10 Hand-held carbon dioxide Automatic wet pipe sprinkler system at ceiling level.

Rad/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-28 Amendment 14

STP FHAR FIRE ZONE TABLE 2-13 FIRE AREA NO. 2 FIRE ZONE Z029 EMERGENCY SWITCHGEAR AREA See Table 2-2 for Safe Shutdown Equipment List Circuits*

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 0 Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-27 Hand-held Carbon Dioxide Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-30 Amendment 14

STP FHAR FIRE ZONE TABLE 2-14 FIRE AREA NO. 2 FIRE ZONE Z030 NONRADIOACTIVE PIPE CHASE Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles

  • See Calculation MC-5800 for listing of combustibles.

Combustible Load: 0 Detection: None Suppression: Hose Cabinet Outside Zone: HC-12 Hand-held Carbon Dioxide Rad/Toxic Material: N/N Communications: N Emergency Lighting: N

  • All electrical cables in this fire zone are installed in conduit.

3.2-31 Amendment 14

STP FHAR FIRE ZONE TABLE 2-16 FIRE AREA NO. 2 FIRE ZONE Z084 CHANNEL I BATTERY ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles

  • See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 515 ft2)

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-1 Hand-held Carbon Dioxide Rad/Toxic Material: N/Y Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-33 Amendment 14

STP FHAR FIRE ZONE TABLE 2-17 FIRE AREA NO. 2 FIRE ZONE ZI 11 ELECTRICAL CHASE, TRAIN A Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011 MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 147 ft2)

Detection: Ionization Suppression: Hose Cabinet outside Zone: HC-19 Automatic wet pipe sprinkler system at ceiling level.

Rad/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-34 Amendment 14

STP MHAR FIRE ZONE TABLE 2-18 FIRE AREA NO. 2 FIRE ZONE Z128 CCW PUMP & CHILLER, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 1860 ft)

Detection: Ionization Suppression: Hose Reel Outside Zone: HR-15 Hose Cabinet Outside Zone: HC-16 Hand-held Dry Chemical Rad/Toxic Material: N/Y Communications: N Emergency Lighting: Y 3.2-35 Amendment 14

STP FHAR The minimum and maximum separation distances between the A via and the C Train vias in the overhead is approximately 43' and 78' respectively. The intervening potential combustibles include the suspended ceiling and cables within z cable trays. The ceiling material is noncombustible, and some trays contain covers, minimizing the potential of a fire spreading from cable tray to cable tray.

Additionally, administrative controls exist which prevent the storage of permanent or transient combustibles in this zone. Periodic surveillances verify the area is free of other combustible material. Since Zone 03Z147 is protected by automatic suppression and detection systems above and below the suspended ceiling, and the subject trays are always more than 20' apart, with negligible intervening combustibles, it can be reasonably concluded that a fire in the area of 03Z147 affecting the C train cable trays will not affect the subject A train cable tray and vice versa.

3.2-46 Amendment 14

STP FHAR FIRE ZONE TABLE 3-1 FIRE AREA NO. 3 FIRE ZONE Z031 ELECTRICAL PENETRATION AREA, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft 2 (Area: 5194 ft2)

Detection: Ionization Suppression: Hose Reel Inside Zone: HR-6 Hand-Held Carbon Dioxide Automatic Wet Pipe Sprinkler at ceiling level Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-47 Amendment 14

STP FHAR FIRE ZONE TABLE 3-2 FIRE AREA NO. 3 FIRE ZONE Z036 CORRIDOR & OFFICES, ELEVATION 35' Equipment Safe Shutdown Safety Related Train None. None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. [

5A011MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 2951 ft2)

Detection: Ionization (detectors are located below suspended ceilings)

Suppression: Hose Cabinets Inside Zone: HC-4, HC-8, HC-10, and HC-13 Hand-Held Carbon Dioxide Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-48 Amendment 14

STP FHAR FIRE ZONE TABLE 3-4 FIRE AREA NO. 3 FIRE ZONE Z039 HVAC EQUIPMENT ROOM, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011 MC6023 "Appendix R Evaluation."

Oc Combustibles

  • See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area: 967 ft2)

Detection: Ionization for area Thermal for charcoal filters Suppression: Deluge System for Charcoal Filters Hose Cabinets Outside Zone: HC-10 and HC-13 Hand-Held C Communications:

Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-50 Amendment 14

STP FHAR FIRE ZONE TABLE 3-5 FIRE AREA NO. 3 FIRE ZONE Z042 ESF SWITCHGEAR ROOM, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 3471 ft2)

Detection: Ionization Suppression: Hose Cabinets outside Zone: HC-8, HC-4 and HC-13 Hose Reel outside Zone: HR-40 Hand-held carbon dioxide Manually actuated dry pipe, closed head, special hazard sprinkler system.

Rad/Toxic Material: N/N Communications: Y Emergency Lighting: Y 3.2-51 Amendment 14

STP FHAR FIRE ZONE TABLE 3-6 FIRE AREA NO. 3 FIRE ZONE Z043 CHANNEL III BATTERY & DISTRIBUTION ROOMS See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 0 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 841 ft2 )

Detection: Ionization Suppression: Hose Reels Inside Zone: HR-40 and HR-39 Hose Cabinet Inside Zone: HC-2 Hand-Held Carbon Dioxide Rad/Toxic Material: N/Y Communications: N Emergency Lighting: Y 3.2-52 Amendment 14

STP FHAR FIRE ZONE TABLE 3-7 FIRE AREA NO. 3 FIRE ZONE Z045 PLANT COMPUTER ROOM, SUB-FLOOR AREA & ASSOCIATED BATTERY ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits n

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation."0 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 1911 ft2)

Detection: Ionization detectors are located above and below suspended ceiling and below the raised access floor Suppression: Automatic Halon System, (Solely for property protection)

Hose Cabinet Outside Zone: HC-4 Hand-Held Carbon Dioxide Rad/Toxic Material: N/Y Communications: Y Emergency Lighting: Y Includes Detection Zone Z009 in sub-floor area of computer room 3.2-53 Amendment 14

STP FHAR FIRE ZONE TABLE 3-8 FIRE AREA NO. 3 FIRE ZONE Z1 15 RADWASTE CONTROL & COUNTING ROOMS See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 1466 ft2 )

Detection: Ionization Suppression: Hose Reel Outside Zone:

Hose Cabinet Inside Zone: HR-21 Hand-Held Carbon Dioxide Rad/Toxic Material: Y/Y Communications: N Emergency Lighting: Y 3.2-54 Amendment 14

STP FHAR FIRE ZONE TABLE 3-9 FIRE AREA NO. 3 FIRE ZONE Z1 16 NONRADIOACTIVE PIPING PENETRATION AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 4241 ft2)

Detection: Ionization Suppression: Hose Reels inside Zone: HR-21 and HR-23 Hand-Held dry chemical Automatic sprinkler system at ceiling level.

Rad/Toxic Material: N/Y Communication: Y Emergency Lighting: Y 3.2-55 Amendment 14

STP FHAR FIRE ZONE TABLE 3-11 FIRE AREA NO. 3 FIRE ZONE Z1 19 VOLUME CONTROL TANK & VALVE ROOMS See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles

  • See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btu/ft (Area: 626 ft2)

Detection: None Suppression: Hose Reel Outside Zone: HR-32 Hose Cabinet Outside Zone: HC-18 Hand-held Dry Chemical Rad/Toxic Material: Y/N Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-57 Amendment 14

STP FHAR FIRE ZONE TABLE 3-12 FIRE AREA NO. 3 FIRE ZONE Z130 SERVICE AREAS & BRS RECYCLE HOLDUP TANKS See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

00 5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 10,389 ft 2

)

SERVICE AREAS & BRS RECYCLE HOLDUP TANKS Detection: Ionization: areas other than Charcoal Filter Thermal: Charcoal Filter Suppression: Automatic wet pipe sprinkler system: Laundry Room (solely for property protection)

Deluge System: Charcoal Filter for Sample Room and Radio. Chem. Lab (Solely for property protection)

Hose Reel outside Zone: HR-23 Hose Reels inside Zone: HR-17, HR-31, and HR-32 Hose Cabinets inside Zone: HC-29 and HC-18 Hand-held dry chemical extinguisher Rad/Toxic Material: Y/Y Communications: Y (Located in hallways only)

Emergency Lighting: Y (Located in hallways only) 3.2-58 Amendment 14

STP FHAR FIRE ZONE TABLE 3-14 FIRE AREA NO. 3 FIRE ZONE Z147 LOCKER ROOMS & CLOTHING ISSUE See Table 2-2 for Safe Shutdown Equipment List Circuits

z A listing of safe shutdown cables routed through this zone is contained in Calculation no. 00 5A01 1MC6023 "Appendix R Evaluation."

Combustibles Below Suspended Ceiling See Calculation MC-5800 for listing of combustibles.

2 Combustible Load Below Susp. Ceiling: 80,000 Btu/ft (Area: 8,642 ft2)

Combustibles Above Suspended Ceiling See Calculation MC-5800 for listing of combustibles.

2 Combustible Load Above Susp. Ceiling: 120,000 Btu/ft (Area: 8,066 ft2)

Detection: Ionization Above and Below Suspended Ceiling Line-type Above Susp. Ceiling Suppression: Wet Pipe Sprinkler System Below Suspended Ceiling Wet Pipe Sprinkler Coverage Above Suspended Ceiling Hose Cabinets and Reels Outside Zone: HC-18, HR-17 and HR-32 Hose Cabinets and Reels Inside Zone: HC-20, and HC-23 Hand-held Dry Chemicals RadlToxic Material: Y/Y Communications: Y (located in hallways only)

Emergency Lighting: Y (located in hallways only) 3.2-60 Amendment 14

STP FHAR FIRE ZONE TABLE 4-1 FIRE AREA NO. 4 FIRE ZONE Z046 ELECTRICAL PENETRATION AREA, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 5303 ft2 )

Detection: Ionization Suppression: Hose Cabinet outside Zone: HC-6 Hose Reel inside Zone: HR-7 Hand-Held carbon dioxide Automatic wet pipe sprinkler system at ceiling level.

Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-64 Amendment 14

STP FHAR FIRE ZONE TABLE 4-2 FIRE AREA NO. 4 FIRE ZONE Z049 HVAC EQUIPMENT ROOM, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5 A011MC6023 "Appendix R Evaluation."

Combustibles

  • See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 1058 ft2)

Detection: Ionization for Area Thermal for Charcoal Filters Suppression: Hand-Held Carbon Dioxide Deluge System for Charcoal Filter HVAC EQUIPMENT ROOM, TRAIN C Radioactive/Toxic Material: Y/N Communications: Y Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-65 Amendment 14

STP FHAR FIRE ZONE TABLE 4-3 FIRE AREA NO. 4 FIRE ZONE Z050 CORRIDOR, OFFICES, CAS BATTERY ROOM AND ELECTRICAL EQUIPMENT See Table 2-2 for Safe Shutdown Equipment List Circuits

,z A listing of safe shutdown cables routed through this zone is contained in Calculation no. Un 5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 3424 ft2)

Detection: Ionization Suppression: Hose Reels Outside Zone: HR-11 and HR-7 Hose Cabinets Inside Zone: HC-5, HC-6 and HC-9 Automatic Wet Pipe Sprinkler at ceiling level cover area(s) of concentrated cabling only)

Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: Y 3.2-66 Amendment 14

STP FHAR FIRE ZONE TABLE 4-4 FIRE AREA NO. 4 FIRE ZONE Z052 ESF SWITCHGEAR ROOM, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits Z

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btu/ft 2 (Area: 3524 ft2)

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-5 and HC-9 Hand-Held Carbon Dioxide Manually operated, dry pipe, closed head, special hazard Sprinkler System for cable trays Radioactive/Toxic Material: N/N Communications: Y Emergency Lighting: Y 3.2-67 Amendment 14

STP FHAR FIRE ZONE TABLE 4-5 FIRE AREA NO. 4 FIRE ZONE Z053 CHANNEL IV BATTERY AND DISTRIBUTION ROOMS See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft 2 (Area: 1030 ft2)

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-5 and HC-6 Hand-Held Carbon Dioxide Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: Y 3.2-68 Amendment 14

STP FHAR FIRE ZONE TABLE 4-6 FIRE AREA NO. 4 FIRE ZONE Z054 MOTOR GENERATOR ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. týQ 5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 639 ft2)

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-5 Hand-Held Carbon Dioxide Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-69 Amendment 14

STP FHAR FIRE ZONE TABLE 4-8 FIRE AREA NO. 4 FIRE ZONE Z056 CONTROL ROD DRIVE ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits z

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 1103 ft2)

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-6 Hand-Held Carbon Dioxide Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: Y 3.2-71 Amendment 14

STP FHAR FIRE ZONE TABLE 5-1 FIRE AREA NO. 5 FIRE ZONE Z014 STAIRWELL NO. 1 AND ELEVATOR NO. 4 See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area: 251 ft2)

Detection: Ionization (Elevator equipment room only)

Suppression: Hose Reels Outside Zone: HR-9, HR-10, HR-1I and HR-38 Hose Cabinets Outside Zone: HC-12, HC-27, HC-10 and HC-13 Hand-held Carbon Dioxide and Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y

  • All electrical cable in this fire zone is installed in conduit.

3.2-76 Amendment 14

STP FHAR FIRE ZONE TABLE 6-5 FIRE AREA NO. 6 FIRE ZONE Z085 HVAC EQUIPMENT Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A0 11MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 1968 ft 2)

Detection: Ionization Suppression: Hose Reel Inside Zone: HR-38 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-83 Amendment 14

STP FHAR FIRE ZONE TABLE 6-6 FIRE AREA NO. 6 FIRE ZONE Z097 HVAC EQUIPMENT Equipment Safe Shutdown Safety Related Train None None None None Circuits z

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btulft 2 (Area: 1995 ft2 )

Detection: None Suppression: None Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-84 Amendment 14

STP FHAR FIRE ZONE TABLE 7-1 FIRE AREA NO. 7 FIRE ZONE Z071 AUXILIARY SHUTDOWN AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A0 1IMC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btulft2 (Area: 950 ft2)

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-12 Hand-Held Carbon Dioxide Radioactive/Toxic Material: N/Y Communications: Y Emergency Lighting: Y 3.2-88 Amendment 14

STP FHAR FIRE ZONE TABLE 8-1 FIRE AREA NO. 8 FIRE ZONE Z072 QDPS ROOM, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles

  • See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 214 ft2)

Detection: Ionization Suppression: Hose Cabinets Outside Zone: HC-7 and HC-12 Hand-held Carbon Dioxide Radioactive/Toxic Material: N/Y Communications: Y Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-91 Amendment 14

STP FHAR FIRE ZONE TABLE 9-1 FIRE AREA NO. 9 FIRE ZONE Z073 QDPS ROOM, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles

  • See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/FT2 (Area: 171 ft 2)

Detection: Ionization Suppression: Hose Cabinets Outside Zone: HC-7 and HC-12 Hand-held Carbon Dioxide Radioactive/Toxic Material: N/Y Communications: Y Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-93 Amendment 14

STP FHAR FIRE ZONE TABLE 18-1 FIRE AREA NO. 18 FIRE ZONE Z020 ELECTRICAL CHASE, TRAIN A Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation."0 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 75 ft2)

Detection: Ionization Suppression: Hose Cabinets Outside Zone: HC-12, HC-13, and HC-9 Hand-held Carbon Dioxide Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-118 Amendment 14

STP FHAR FIRE ZONE TABLE 20-1 FIRE AREA NO. 20 FIRE ZONE Z129 NONRADIOACTIVE PIPE CHASE See Table 2-2 for Safe Shutdown Equipment List NONRADIOACTIVE PIPE CHASE Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft 2 (Area: 2336 ft2)

Detection: Ionization Suppression: Hose Reels and Cabinets outside Zone: HR-16, HC-19, & HC-17 Hand-held dry chemical Automatic wet pipe sprinkler system at ceiling level.

Radioactive/Toxic Material: N/N Communications: Y Emergency Lighting: Y 3.2-124 Amendment 14

STP FHAR FIRE ZONE TABLE 22-2 FIRE AREA NO. 22 FIRE ZONE Z132 MCC ROOM, 480 VOLT See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 IMC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft 2 (Area: 1113 ft2)

Detection: Ionization Suppression: Hose Reels Outside Zone: HR-15 and HR-19 Hand-Held Carbon Dioxide Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-131 Amendment 14

STP FHAR FIRE ZONE TABLE 22-3 FIRE AREA NO. 22 FIRE ZONE Z133 PIPE PENETRATION ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

00 5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 5553 ft2 )

Detection: Ionization Suppression: Automatic Sprinkler System at ceiling level Hose Reel Inside Zone: HR-19 Hand-Held Dry Chemical Radioactive/Toxic Material: N/Y Communications: Y Emergency Lighting: Y 3.2-132 Amendment 14

STP FHAR FIRE ZONE TABLE 24-1 FIRE AREA NO. 24 FIRE ZONE Z102 CORRIDOR AND NONRADIOACTIVE PIPE CHASE See Table 2-2 for Safe Shutdown Equipment List Circuits Z

t A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." *,00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 4814 ft2)

Detection: Ionization Suppression: Wet pipe sprinkler system (partial coverage 1 area)

Hose Cabinets and Reels Inside Zone: HC-30, HR-15, HR-30 Hand-Held Dry Chemical Radioactive/Toxic Material: N/Y Communications: Y Emergency Lighting: Y (Room/Corridor 067B only)

Area wide automatic fire suppression has not been provided for the following reasons:

1. A single safe-shutdown path per Appendix R requirements will be available following a fire in this zone.
2. Manual operator action can be taken to mitigate the consequences of SOE.
3. Detection system and manual fire suppression equipment are provided in this zone.
4. The concentrated cable area in this zone is provided with wet pipe sprinkler system.
5. Other areas are easily accessible for manual fire fighting.
6. The fire detection will provide alarm and indication locally and in the control room for implementing immediate Fire Brigade response.
7. IEEE 383 cables and R.G. 1.75 separation criteria were utilized in cable layout design.

3.2-136 Amendment 14

STP FHAR FIRE ZONE TABLE 25-1 FIRE AREA NO. 25 FIRE ZONE Z124 CVCS CENTRIFUGAL CHARGING PUMP lB AND VALVE ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 20,000 Btu/ft 2 (Area: 456 ft2 )

Detection: Ionization Suppression: Hose Reels Outside Zone: HR-15 and HR-30 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-141 Amendment 14

STP FHAR FIRE ZONE TABLE 26-1 FIRE AREA NO. 26 FIRE ZONE Z123 CVCS CENTRIFUGAL CHARGING PUMP IA AND VALVE ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 IMC6023 "Appendix R Evaluation." 00 Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 20,000 Btu/ft2 (Area: 486 ft2)

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-16 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N

  • All electrical cables in this fire zone are installed in conduit.

3.2-144 Amendment 14

STP FHAR FIRE ZONE TABLE 27-1 FIRE AREA NO. 27 FIRE ZONE Z108 BORIC ACID TANK AND PUMP ROOMS See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles

  • See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 1,041 ft 2)

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-16 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: Y (Room 018 only)

Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-148 Amendment 14

STP FHAR FIRE ZONE TABLE 27-2 FIRE AREA NO. 27 FIRE ZONE Z109 ELECTRICAL CHASE, TRAIN C See Table 2-2 for Safe Shutdown Equipment List.

Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. k) 5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 200 ft2)

Detection: Ionization Suppression: Hose Cabinets Outside Zone: HC-17 and HC-19 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-149 Amendment 14

STP FHAR FIRE ZONE TABLE 27-3 FIRE AREA NO. 27 FIRE ZONE Z127 CVCS EQUIPMENT ROOMS See Table 2-2 for Safe Shutdown Equipment List Circuits z

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area: 3,698 ft2 )

Detection: Ionization Suppression: Hose Cabinets Outside Zone: HC-16 and HC-28 Radioactive/Toxic Material: N/N Communications: N CVCS EQUIPMENT ROOMS Emergency Lighting: N

  • All electrical cables in this fire zone are installed in conduit.

NOTE 1: Powered by TSC Diesel 3.2-150 Amendment 14

STP FHAR FIRE ZONE TABLE 27-4 FIRE AREA NO. 27 FIRE ZONE Z138 CORRIDOR AND PIPE AND HVAC CHASE See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft 2 (Area: 2,650 ft2)

Detection: Ionization Suppression: Hose Cabinets Inside Zone: HC-16 and HC-28 Hand-held Dry Chemical Automatic Wet Pipe Sprinkler at Ceiling Level (over area(s) of concentrated cabling only).

Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-151 Amendment 14

STP FHAR FIRE ZONE TABLE 27-5 FIRE AREA NO. 27 FIRE ZONE Z139 CCW PUMP AND CHILLER, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. t',

5A01 1MC6023 "Appendix R Evaluation."0 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area: 2,930 ft2)

Detection: Ionization Suppression: Hose Reels and Cabinets Outside Zone: HR-15 and HC-16 Hand-held Dry Chemical Automatic Wet Pipe Sprinkler at Ceiling Level over Concentrated Cabling Only.

Radioactive/Toxic Material: N/Y Communications: Y Emergency Lighting: Y Automatic fire suppression has not been provided for the following reasons:

1. A single safe-shutdown path per Appendix R requirements will be available following a fire in this zone.
2. Detection system and manual fire suppression equipment are provided in this zone.
3. All areas of this zone are easily accessible for manual fire fighting.
4. The fire detection will provide alarm and indication locally and in the control room for implementing immediate Fire Brigade response.
5. IEEE 383 cables and R.G. 1.75 separation criteria were utilized in cable layout design.

3.2-152 Amendment 14

STP FHAR FIRE ZONE TABLE 27-7 FIRE AREA NO. 27 FIRE ZONE Z142 CCW HEAT EXCHANGERS See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. tZ 5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 5,082 ft2)

Detection: Ionization Suppression: Hose Cabinets Inside Zone: HC-17 and HC-19 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: Y Emergency Lighting: Y 3.2-154 Amendment 14

STP FHAR FIRE ZONE TABLE 29-1 FIRE AREA NO. 29 FIRE ZONE Z140 CCW PUMP AND CHILLER, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 1496 ft2 )

Detection: Ionization Suppression: Hose Cabinets and Reels Outside Zone: HC-16 and HR-15 Hand-held Dry Chemical Radioactive/Toxic Material: N/Y Communications: Y Emergency Lighting: Y 3.2-158 Amendment 14

STP FHAR FIRE ZONE TABLE 30-1 FIRE AREA NO. 30 FIRE ZONE Z144 MEAB STAIRWELL NO. 2 AND ELEVATOR FOYER See Table 2-2 for Safe Shutdown Equipment List.

Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011 MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 120,000 Btu/ft2 (Area: 476 ft2)

Detection: Ionization Suppression: Hose Reels and Cabinets outside Zone: HR-17 Hand-held dry chemical Automatic wet pipe sprinkler system at ceiling level.

Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-160 Amendment 14

STP FHAR FIRE ZONE TABLE 31-1 FIRE AREA NO. 31 FIRE ZONE Z047 CABLE SPREADING/POWER CABLE AREA AND CABLING AREA, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btu/ft 2 (Area: 5,945 ft2)

Detection: Ionization Suppression: Automatic Sprinkler at Ceiling Level Hose Reel Outside Area: HR-7 (For Room 301 B Only)

Hose Reels Inside Area: HR-3 and HR- 11 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-163 Amendment 14

STP FHAR FIRE ZONE TABLE 32-1 FIRE AREA NO. 32 FIRE ZONE Z103 REACTOR MAKEUP WATER AND LASR STORAGE TANK AND PUMP ROOMS See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles:*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 2640 ftW)

Detection: Ionization Suppression: Hose Reel Inside Zone: HR-36 Hand-Held Dry Chemical Radioactive/Toxic Material: Y/N Communications: N Emergency Lighting: N

  • All electrical cables in this fire zone are installed in conduit.

3.2-168 Amendment 14

STP FHAR FIRE ZONE TABLE 32-2 FIRE AREA NO. 32 FIRE ZONE Z104 REFUELING WATER STORAGE TANK ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. k_)

5A01 1MC6023 "Appendix R Evaluation." \0 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 3614 ft2)

Detection: Ionization Suppression: Hose Reel Inside Zone: HR-36 and HR-23 Hand-Held Dry Chemical Radioactive/Toxic Material: Y/N Communications: N Emergency Lighting: N 3.2-169 Amendment 14

STP FHAR FIRE ZONE TABLE 32-4 FIRE AREA NO. 32 FIRE ZONE Z114 RADIOACTIVE AND NONRADIOACTIVE PIPE CHASES See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles:*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btulft2 (Area: 17,676 ft2)

Detection: Ionization Suppression: Hose Reel Inside Zone: HR-22 Hose Cabinet Inside Zone: HC-31 Hand-Held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-171 Amendment 14

STP FHAR FIRE ZONE TABLE 32-6 FIRE AREA NO. 32 FIRE ZONE Z122 HVAC INTAKE AND HOT MACHINE SHOP See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 14,927 ft2)

Detection: Ionization Suppression: Hose Reels inside Zone: HR-13, HR-18, HR-14, and HR-33 Hose Reel outside Zone: HR-24 Hand-held dry chemical and Hand-held carbon dioxide outside Zone Automatic wet pipe sprinkler system over concentrated cabling.

Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: Y 3.2-173 Amendment 14

STP FHAR FIRE ZONE TABLE 32-7 FIRE AREA NO. 32 FIRE ZONE Z126 480 V NON-ESF SWITCHGEAR See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft 2 (Area: 1,376 ft2)

Detection: Ionization Suppression: Hose Reel Outside Zone: HR-13 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-174 Amendment 14

STP FHAR FIRE ZONE TABLE 32-8 FIRE AREA NO. 32 FIRE ZONE Z131 FILTER AND DEMINERALIZER AREA See Table 2-2 for Safe Shutdown Equipment List Circuits r)

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles:*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft 2 (Area: 8,355 ft2 )

Detection: None Suppression: Hose Reel Outside Zone: HR-32 and HR-33 Hose Reel Inside Zone: HR-34 and HR-35 Hand-Held Dry Chemical Radioactive/Toxic Material: Y/Y Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

(Unit 2 Only) 3.2-175 Amendment 14

STP FHAR FIRE ZONE TABLE 32-9 FIRE AREA NO. 32 FIRE ZONE Z134 NON RADIOACTIVE PIPE CHASE See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 2622 ft2)

Detection: Ionization Suppression: Hose Reel Outside Zone: HR-20 Hose Reel Inside Zone: HR-16 Hand-held Dry Chemical Automatic wet pipe sprinkler system over concentrated cabling.

Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-176 Amendment 14

STP FHAR FIRE ZONE TABLE 32-10 FIRE AREA NO. 32 FIRE ZONE Z135 RADIOACTIVE PIPE PENETRATION AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles:*

See Calculation MC-5800 for listing of Combustibles.

Combustible Load: 0 Detection: Ionization Suppression: Hose Reel Inside Zone: HR-20, HR-22 Hose Reel Outside Zone: HR-16 Hand-Held Dry Chemical Radioactive/Toxic Material: N/N Communications: Y Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-177 Amendment 14

STP FHAR FIRE ZONE TABLE 32-11 FIRE AREA NO. 32 FIRE ZONE Z145 PERSONNEL ACCESS TO CONTAINMENT See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 IMC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 3624 ft 2)

Detection: Ionization Suppression: Automatic Sprinkler System at ceiling level over concentrated cabling (i.e. partial coverage)

Hose Reel Outside Zone: HR-25 Hose Reel Inside Zone: HR-24 Hand-held Carbon Dioxide and Dry Chemical extinguishers Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: Y 3.2-178 Amendment 14

STP FHAR FIRE ZONE TABLE 32-12 FIRE AREA NO. 32 FIRE ZONE Z146 HVAC OUTSIDE EXHAUST EQUIPMENT See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 7053 ft2)

Detection: Ionization Suppression: Hose Reels Inside Zone: HR-25, HR-26, HR-27, HR-28, and HR-29 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-179 Amendment 14

STP FHAR FIRE ZONE TABLE 33-1 FIRE AREA NO. 33 FIRE ZONE Z018 CABLING AREA TRAIN B Equipment Safe Shutdown Safety Related Train None N N N Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. ]z 5A01 1MC6023 "Appendix R Evaluation."0 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 2921 ft)

Detection: Ionization Suppression: Wet Pipe Sprinkler System (Partial Coverage)

Hose Cabinet Outside Zone: HC-4 Hand-Held Carbon Dioxide Hose Reels in Zone: HR39 and HR40 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-182 Amendment 14

STP FHAR FIRE ZONE TABLE 34-1 FIRE AREA NO. 34 FIRE ZONE Z060 CABLING AREA, TRAIN C Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btu/ft 2 (Area: 2921 ft2)

Detection: Ionization Suppression: Wet Pipe Sprinkler System (Partial Coverage)

Hose Reel Inside Zone: HR-8 Hand-held Carbon Dioxide Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-185 Amendment 14

STP FHAR FIRE ZONE TABLE 64-1 FIRE AREA NO. 64 FIRE ZONE Z026 CABLE SPREADING ROOM, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 7204 ft2)

Detection: Ionization Suppression: Automatic Sprinklers at Ceiling Level Hose Reels HR-2 and HR-10, Hand-Held Carbon Dioxide Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-188 Amendment 14

STP FHAR FIRE ZONE TABLE 65-1 FIRE AREA NO. 65 FIRE ZONE Z057 CABLE SPREAD/POWER CABLE AREA, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A011MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btu/ft 2 (Area: 5484 ft2)

Detection: Ionization Suppression: Automatic Sprinklers at Ceiling Level Hose Reels Inside Zone: HR-4 and HR-12 Hand-Held Carbon Dioxide Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-191 Amendment 14

STP FHAR FIRE ZONE TABLE 66-1 FIRE AREA NO. 66 FIRE ZONE Z025 CABLING AREA, TRAIN A Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A011MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 2836 ft2)

Detection: Ionization Suppression: Hose Reel inside Zone HR-37 Hand-Held carbon dioxide Automatic wet pipe sprinkler system at ceiling level.

Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-194 Amendment 14

STP FHAR FIRE ZONE TABLE 67-1 FIRE AREA NO. 67 FIRE ZONE Z058 TSC OPERATIONS, RECORDS STORAGE, AND MISCELLANEOUS AREAS See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011 MC6023 "Appendix R Evaluation."0 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 3698 ft2)

Detection: Ionization Suppression: Hose Cabinets Inside Zone: HC-1 1 and HC-15 Hand-Held Dry Chemical Automatic Wet Pipe System at Ceiling Level Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: N 3.2-197 Amendment 14

STP FHAR FIRE ZONE TABLE 68-1 FIRE AREA NO. 68 FIRE ZONE Z01 1 ELECTRICAL CHASE, TRAIN B Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. Z 5A01 1MC6023 "Appendix R Evaluation."

cc Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 240,000 Btu/ft 2 (Area: 84 ft2)

Detection: Ionization Suppression: Hose Reels Outside Zone: HR-1, HR-3, and HR-4 Hand-held Carbon Dioxide Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-201 Amendment 14

STP FHAR FIRE ZONE TABLE 69-1 FIRE AREA NO. 69 FIRE ZONE Z008 ELECTRICAL CHASE, TRAIN C Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 240,000 Btu/ft2 (Area: 82 ft2)

Detection: Ionization Suppression: Hose Reels Outside Zone: HR-5 and HR-6 Hand-Held Carbon Dioxide Automatic Wet Pipe Sprinkler System at Ceiling Level Radioactive/Toxic Material: NiN Communications: N Emergency Lighting: N 3.2-203 Amendment 14

STP FUAR FIRE ZONE TABLE 70-1 FIRE AREA NO. 70 FIRE ZONE Z023 ELECTRICAL CHASE, BOP Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. ,

5A0 11MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 885,000 Btu/ft2 (Area: 76 ft2)

Detection: Ionization Suppression: Hose Cabinets Outside Zone: HC-12, HC-13, and HC-9 Hand-Held Carbon Dioxide Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-206 Amendment 14

STP FHAR FRE ZONE TABLE 70-2 FIRE AREA NO. 70 FIRE ZONE Z068 ELECTRICAL CHASE, TRAIN C Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 350,000 Btu/ft2 (Area: 76 ft2)

Detection: Ionization Suppression: Hose Cabinets Outside Zone: HC-12, HC-10, and HC-9 Hand-Held Carbon Dioxide Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-207 Amendment 14

STP FHAR FIRE ZONE TABLE 71-1 FIRE AREA NO. 71 FIRE ZONE Z007 ELECTRICAL CHASE, TRAIN B Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 53 ft2 )

Detection: Ionization Suppression: Hose Reel Outside Zone: HR-5 Hand-Held Carbon Dioxide Automatic Wet Pipe Sprinkler System at Ceiling Level Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-209 Amendment 14

STP FHAR FIRE ZONE TABLE 72-1 FIRE AREA NO. 72 FIRE ZONE Z024 ELECTRICAL CHASE, TRAIN B Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 52 ft2 )

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-3 Hand-Held Carbon Dioxide Rad/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-211 Amendment 14

STP FHAR FIRE ZONE TABLE 73-1 FIRE AREA NO. 73 FIRE ZONE Z070 ELECTRICAL CHASE, TRAIN B Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A011MC6023 "Appendix R Evaluation." tJ' 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 350,000 Btu/ft 2 (Area: 75 ft2 )

Detection: Ionization Suppression: Hose Cabinets Outside Zone: HC-9 and HC-13 Hand-Held Carbon Dioxide Rad/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-214 Amendment 14

STP FHAR FIRE ZONE TABLE 74-1 FIRE AREA NO. 74 FIRE ZONE Z012 ELECTRICAL CHASE, TRAIN C Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011 MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 240,000 Btu/ft2 (Area: 90 ft2 )

Detection: Ionization Suppression: Hose Reels Outside Zone: HR-1, HR-3, HR-4, and HR-12 Hand-Held Carbon Dioxide Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-216 Amendment 14

STP FHAR FIRE ZONE TABLE 75-1 FIRE AREA NO. 75 FIRE ZONE ZI 12 ELECTRICAL CHASE, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 240,000 Btu/ft2 (Area: 775 ft2)

Detection: Ionization Suppression: Hose Reels outside Zone: HC-18, HR-21, and HR-16 Hand-held dry chemical extinguisher Automatic wet pipe sprinkler system at ceiling level.

Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.2-218 Amendment 14

STP FHAR FIRE ZONE TABLE 76-1 FIRE AREA NO. 76 FIRE ZONE Z017 QDPS, ROOM TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits z

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 (Area: 214 ft2)

Detection: Ionization Suppression: Hose Cabinets Outside Zone: HC-12 and HC-7 Hand-held Carbon Dioxide Rad/Toxic Material: N/Y Communications: Y Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.2-220 Amendment 14

STP FHAR FIRE ZONE TABLE 77-1 FIRE AREA NO. 77 FIRE ZONE Z093 HVAC AND ELECTRICAL ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits z

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area 4,200 ft2 )

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-31 Hand-held Dry Chemical Deluge System (charcoal filter) (solely for property protection)

Rad/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.2-223 Amendment 14

STP FHAR FIRE ZONE TABLE 77-2 FIRE AREA NO. 77 FIRE ZONE Z096 MECHANICAL ELECTRICAL AUXILIARY BUILDING ROOF See Table 2-2 for Safe Shutdown Equipment List Circuits

,z A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area 14,884 ft 2)

Detection: None Suppression: Hose Cabinets Outside Zone: HC-31 Hand-held Dry Chemical Rad/Toxic Material: N/N Communications: N 3.2-224 Amendment 14

STP FHAR FIRE ZONE TABLE 35-1 FIRE AREA NO. 35 FIRE ZONE Z301 FHB ELEVATOR NO. 6 See Table 2-2 for Safe Shutdown Equipment List Circuits z

A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011 MC6023 "Appendix R Evaluation." 00 Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area: 124 ft2)

Detection: Ionization Suppression: Hose Cabinet Outside Zone: HC-9 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N

  • All electrical cables in this fire zone are installed in conduit.

3.3-7 Amendment 14

STP FHAR FIRE ZONE TABLE 35-6 FIRE AREA NO. 35 FIRE ZONE Z310 FUEL TRANSFER AND LOADING AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. N) 5A011 MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btulft 2* (Area: 14,265 ft2)

Detection: Optical Detectors Suppression: Hose Cabinets Inside Zone: HC-4, HC-7, HC-8, and HC-9 Hose Reels Inside Zone: HR-3 and HR-5 Hose Reel Outside Zone: HR-4 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y Note 1: Powered by TSC diesel

  • During Refueling 3.3-12 Amendment 14

STP FHAR FIRE ZONE TABLE 35-7 FIRE AREA NO. 35 FIRE ZONE Z311 SPENT FUEL POOL AUXILIARY AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 oo Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 3,000 ft2)

Detection: Ionization Suppression: Hose Cabinet Inside Zone: HC-6 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.3-13 Amendment 14

STP FHAR FIRE ZONE TABLE 36-1 FIRE AREA NO. 36 FIRE ZONE Z500 DIESEL GENERATOR NO. 13 TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits Z2 A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 IMC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 2,800 ft 2)

Detection: Spot-Type Thermal Suppression: Preaction Sprinklers Hose Reels Outside Zone: HR-5, HR-6 Hand-Held Dry Chemical Radioactive/Toxic Material: N/N Communications: Y Emergency Lighting: Y 3.4-4 Amendment 14

STP FHAR FIRE ZONE TABLE 37-1 FIRE AREA NO. 37 FIRE ZONE Z501 DIESEL GENERATOR NO. 12, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft 2 (Area: 2,800 ft 2)

Detection: Spot-type Thermal Suppression: Preaction Sprinklers Hose Reels Outside Zone: HR-3 and HR-4 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: Y Emergency Lighting: Y 3.4-8 Amendment 14

STP FHAR FIRE ZONE TABLE 38-1 FIRE AREA NO. 38 FIRE ZONE Z502 DIESEL GENERATOR NO. 11, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 192,000 Btu/ft2 (Area: 2,800 ft2)

Detection: Spot-type Thermal Suppression: Preaction Sprinklers Hose Reel Outside Zone: HR-I and HR-2 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: Y Emergency Lighting: Y 3.4-12 Amendment 14

STP FHAR FIRE ZONE TABLE 42-1 FIRE AREA NO. 42 FIRE ZONE Z506 DIESEL GENERATOR STAIRWELL, TRAIN C Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 190 ft2 )

Detection: Ionization Suppression: Hose Reel Inside Zone: HR-6 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.4-25 Amendment 14

STP FHAR FIRE ZONE TABLE 43-1 FIRE AREA NO. 43 FIRE ZONE Z507 DIESEL GENERATOR STAIRWELL, TRAIN B Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 190 ft2)

Detection: Ionization Suppression: Hose Reel Inside Zone: HR-4 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.4-29 Amendment 14

STP FHAR FIRE ZONE TABLE 44-1 FIRE AREA NO. 44 FIRE ZONE Z508 DIESEL GENERATOR STAIRWELL, TRAIN A Equipment Safe Shutdown Safety Related Train None None None None Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 190 ft2 )

Detection: Ionization Suppression: Hose Reel Inside Zone: HR-2 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.4-31 Amendment 14

STP FHAR FIRE ZONE TABLE 45-1 FIRE AREA NO. 45 FIRE ZONE Z509 HVAC FAN/ENTRY, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 0 Detection: Ionization Suppression: Hose Reel Outside Zone: HR-6 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.4-34 Amendment 14

STP FHAR FIRE ZONE TABLE 46-1 FIRE AREA NO. 46 FIRE ZONE Z510 HVAC FAN/ENTRY, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. j*

5A011MC6023 "Appendix R Evaluation."o0 Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 0 Detection: Ionization Suppression: Hose Reel Outside Zone: HR-4 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.4-37 Amendment 14

STP FHAR FIRE ZONE TABLE 47-1 FIRE AREA NO. 47 FIRE ZONE Z511 HVAC FAN/ENTRY, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 0 Detection: Ionization Suppression: Hose Reel Outside Zone: HR-2 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.4-40 Amendment 14

STP FHAR FIRE ZONE TABLE 48-1 FIRE AREA NO. 48 FIRE ZONE Z403 AUXILIARY FEEDWATER PUMP, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. 5A01 1MC6023 Z "Appendix R Evaluation."

Co Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 439 ft2)

Detection: Ionization Suppression: Hose Reel Outside Zone: HR-2 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: Y 3.5-5 Amendment 14

STP FHAR FIRE ZONE TABLE 48-2 FIRE AREA NO. 48 FIRE ZONE Z406 MAIN STEAM & FEEDWATER PENETRATION AREA, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. 5A01 1MC6023 Z "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 673 ft2)

Detection: Smoke Suppression: Hose Reel Inside Zone: HR-6 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communication: N Emergency Lighting: Y 3.5-6 Amendment 14

STP FHAR FIRE ZONE TABLE 49-1 FIRE AREA NO. 49 FIRE ZONE Z402 AUXILIARY FEEDWATER PUMP, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. 5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 416 ft2)

Detection: Ionization Suppression: Hose Reel Outside Zone: HR-2 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communication: N Emergency Lighting: Y 3.5-11 Amendment 14

STP FHAR FIRE ZONE TABLE 49-2 FIRE AREA NO. 49 FIRE ZONE Z407 MAIN STEAM & FEEDWATER PENETRATION AREA, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. 5A01 1MC6023 Z "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 650 ft2)

Detection: Smoke Suppression: Hose Reel Inside Zone: HR-5 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communication: N Emergency Lighting: Y 3.5-12 Amendment 14

STP FHAR FIRE ZONE TABLE 50-1 FIRE AREA NO. 50 FIRE ZONE Z401 AUXILIARY FEEDWATER PUMP, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 416 ft2)

Detection: Ionization Suppression: Hose Reel Outside Zone: HR-i Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communication: N Emergency Lighting: Y 3.5-17 Amendment 14

STP FHAR FIRE ZONE TABLE 50-2 FIRE AREA NO. 50 FIRE ZONE Z408 MAIN STEAM AND FEEDWATER PENETRATION AREA, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. 5A01 1MC6023 Z "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 80,000 Btu/ft 2 (Area: 650 ft2 )

Detection: Smoke Suppression: Hose Reel Inside Zone: HR-4 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communication: N Emergency Lighting: Y 3.5-18 Amendment 14

STP FHAR FIRE ZONE TABLE 51-1 FIRE AREA NO. 51 FIRE ZONE Z400 TURBINE-DRIVEN AUXILIARY FEEDWATER PUMP, TRAIN D See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. 5A01 1MC6023 Z "Appendix R Evaluation."

00 Combustibles*

See Calculation MC-5800 for list of combustibles.

Combustible Load: 40,000 Btu/ft 2 (Area: 439 ft2)

Detection: Ionization Suppression: Hose Reel Outside Zone: HR-1 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communication: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.5-23 Amendment 14

STP F14AR FIRE ZONE TABLE 51-2 FIRE AREA NO. 51 FIRE ZONE Z405 STEAM GENERATOR RECIRCULATING PUMP ROOM See Table 2-2 for Safe Shutdown Equipment List CIRCUITS A listing of safe shutdown cables routed through this zone is contained in Calculation no. 5A01 1MC6023 ,

"Appendix R Evaluation."

00 Combustibles*

See Calculation MC-5800 for list of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area: 1170 ft2)

Detection: Ionization Suppression: Hose Reels Inside Zone: HR-1, HR-2 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communication: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.5 -24 Amendment 14

STP MHAR FIRE ZONE TABLE 51-3 FIRE AREA NO. 51 FIRE ZONE Z409 MAIN STEAM AND FEEDWATER PENETRATION AREA, TRAIN D See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. 5A01 1MC6023 Z "Appendix R Evaluation." CA 00 Combustibles*

See Calculation MC-5800 for list of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 673 ft2)

Detection: Smoke Suppression: Hose Reel Inside Zone: HR-3 Hand-held Dry Chemical Radioactive/Toxic Material: N/N Communication: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.5-25 Amendment 14

STP FHAR FIRE ZONE TABLE 53-1 FIRE AREA NO. 53 FIRE ZONE Z600 ESSENTIAL COOLING WATER (ECW) PUMP ROOM, TRAIN A (Unit 1)

See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A011MC6023 "Appendix R Evaluation." 00 Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 20,000 Btu/ft 2 (Area: 834 ft2)

Detection: Thermal, spot-type Suppression: Hand-Held Carbon Dioxide Yard Fire Hydrant Radioactive/Toxic Material: N/Y

  • All electrical cables in this fire zone are installed in conduit.

3.6-5 Amendment 14

STP FHAR FIRE ZONE TABLE 54-1 FIRE AREA NO. 54 FIRE ZONE Z601 ESSENTIAL COOLING WATER (ECW) PUMP ROOM, TRAIN B (Unit 1)

See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A0 11MC6023 "Appendix R Evaluation."

Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 20,000 Btu/ft2 (Area: 834 ft2 )

Detection: Thermal, spot-type Suppression: Hand-Held Carbon Dioxide Yard Fire Hydrant Radioactive/Toxic Material: N/Y

  • All electrical cables in this fire zone are installed in conduit.

3.6-9 Amendment 14

STP FHAR FIRE ZONE TABLE 55-1 FIRE AREA NO. 55 FIRE ZONE Z602 ESSENTIAL COOLING WATER (ECW) PUMP ROOM, TRAIN C (Unit 1)

See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 0 Combustibles*

See Calculation MC-5800 for listing of combustibles.

Combustible Load: 20,000 Btu/ft2 (Area: 834 ft2)

Detection: Thermal, spot-type Suppression: Hand-Held Carbon Dioxide Yard Fire Hydrant Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: Y

  • All electrical cables in this fire zone are installed in conduit.

3.6-14 Amendment 14

STP FHAR FIRE ZONE TABLE 56-1 FIRE AREA NO. 56 FIRE ZONE Z603 ESSENTIAL COOLING WATER (ECW) PUMP ROOM, TRAIN C (Unit 2)

SEE TABLE 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 20,000 Btu/ft2 (Area: 834 ft2 )

Detection: Thermal, spot-type Suppression: Hand-Held Carbon Dioxide Yard Fire Hydrant Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: Y 3-6-17 Amendment 14

STP FHAR FIRE ZONE TABLE 57-1 FIRE AREA NO. 57 FIRE ZONE Z604 ESSENTIAL COOLING WATER (ECW) PUMP ROOM, TRAIN B (Unit 2)

SEE TABLE 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 20,000 Btu/ft2 (Area: 834 ft2)

Detection: Thermal, spot-type Suppression: Hand-Held Carbon Dioxide Yard Fire Hydrant Radioactive/Toxic Material: N/Y Communication: N Emergency Lighting: Y 3.6-20 Amendment 14

STP FHAR FIRE ZONE TABLE 58-1 FIRE AREA NO. 58 FIRE ZONE Z605 ESSENTIAL COOLING WATER (ECW) PUMP ROOM, TRAIN A (Unit 2)

SEE TABLE 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 20,000 Btu/ft2 (Area: 834 ft2 )

Detection: Thermal, spot-type Suppression: Hand-Held Carbon Dioxide Yard Fire Hydrant Radioactive/Toxic Material: N/Y Communications: N 3.6-23 Admendment 14

STP FHAR FIRE ZONE TABLE 63-1 FIRE AREA NO. 63 FIRE ZONE Z201 ELEVATOR NO. 3 See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation." 00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 77 ft2 )

Detection: None Suppression: Hose Cabinets Outside Zone: HC-3, HC-13, and HC-17 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-13 Amendment 14

STP FHAR FIRE ZONE TABLE 63-2 FIRE AREA NO. 63 FIRE ZONE Z202 CENTRAL REACTOR AREA (UPPER)

See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 13,629 ft2)

Detection: Line-Type Thermal (Cable Tray)

Suppression: Hose Cabinets Inside Zone: HC-23, HC-24, HC-25, and HC-26 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3-8-14 Amendment 14

STP FHAR FIRE ZONE TABLE 63-4 FIRE AREA NO. 63 FIRE ZONE Z204 NW PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 1814 ft2)

Detection: Line-Type Thermal (Cable Tray)

Thermistor (Carbon Filter)

Suppression: Hose Cabinets Inside Zone: HC-19 Deluge System (Charcoal Filter) (solely for property protection)

Radioactive/Toxic Material: Y/N Communications: N Emergency Lighting: N 3.8-17 Amendment 14

STP FHAR FIRE ZONE TABLE 63-5 FIRE AREA NO. 63 FIRE ZONE Z205 NE PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 2061 ft2)

Detection: Line-Type Thermal (Cable Tray)

Suppression: Hose Cabinet Inside Zone: HC-20 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-18 Amendment 14

STP FHAR FIRE ZONE TABLE 63-6 FIRE AREA NO. 63 FIRE ZONE Z206 SE PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z(.

5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 1613 ft2 )

Detection: Line-Type Thermal (Cable Tray)

Thermistor (Carbon Filter)

Suppression: Hose Cabinet Inside Zone: HC-21 Deluge System (Charcoal Filter) (solely for property protection)

Radioactive/Toxic Material: Y/N Communications: N Emergency Lighting: N 3-8-19 Amendment 14

STP FHAR FIRE ZONE TABLE 63-7 FIRE AREA NO. 63 FIRE ZONE Z207 SW PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. Z 5A0 11MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 1802 ft2 )

Detection: Line-Type Thermal (Cable Tray)

Suppression: Special Hazard Spray System Hose Cabinet Inside Zone: HC-1 8 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3-8-20 Amendment 14

STP FHAR FIRE ZONE TABLE 63-8 FIRE AREA NO. 63 FIRE ZONE Z208 NW PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 1814 ft2)

Detection: Line-Type Thermal (Cable Tray)

Suppression: Special Hazard Spray System Hose Cabinet Inside Zone: HC-15 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-21 Amendment 14

STP MHAR FIRE ZONE TABLE 63-9 FIRE AREA NO. 63 FIRE ZONE Z209 NE PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft 2 (Area: 1869 ft2)

Detection: Line-Type Thermal (Cable Tray)

Suppression: Special Hazard Spray System Hose Cabinet Inside Zone: HC-16 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-22 Amendment 14

STP FHAR FIRE ZONE TABLE 63-10 FIRE AREA NO. 63 FIRE ZONE Z210 SE PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 1761 ft2)

Detection: Line-Type Thermal (Cable Tray)

Suppression: Special Hazard Spray System Hose Cabinet Inside Zone: HC-17 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3-8-23 Amendment 14

STP FHAR FIRE ZONE TABLE 63-11 FIRE AREA NO. 63 FIRE ZONE Z211 SW PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft 2 (Area: 1877 ft2 )

Detection: Line-Type Thermal (Cable Tray)

Suppression: Hose Cabinet Inside Zone: HC-14 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3-8-24 Amendment 14

STP FHAR FIRE ZONE TABLE 63-12 FIRE AREA NO. 63 FIRE ZONE Z212 NW PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. ,

5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 2110 ft2 )

Detection: Line-Type Thermal (Cable Tray)

Suppression: Hose Cabinet Inside Zone: HC-10 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-25 Amendment 14

STP FHAR FIRE ZONE TABLE 63-13 FIRE AREA NO. 63 FIRE ZONE Z213 NE PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. ,

5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft 2 (Area: 2110 ft2)

Detection: Line-Type Thermal (Cable Tray)

Suppression: Hose Cabinet Inside Zone: HC-11 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-26 Amendment 14

STP FHAR FIRE ZONE TABLE 63-14 FIRE AREA NO. 63 FIRE ZONE Z214 SE PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. Z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btulft 2 (Area: 2,049 ft2)

Detection: Line-Type Thermal (Cable Tray)

Suppression: Hose Cabinet Inside Zone: HC-13 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-27 Amendment 14

STP FHAR FIRE ZONE TABLE 63-15 FIRE AREA NO. 63 FIRE ZONE Z215 SW PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 1,995 ft2)

Detection: None.

Suppression: Hose Cabinet Inside Zone: HC-4 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3-8-28 Amendment 14

STP FHAR FIRE ZONE TABLE 63-16 FIRE AREA NO. 63 FIRE ZONE Z216 NW PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 1,973 ft2)

Detection: None.

Suppression: Hose Cabinets Inside Zone: HC-1 and HC-5 Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: N 3.8-29 Amendment 14

STP FHAR FIRE ZONE TABLE 63-17 FIRE AREA NO. 63 FIRE ZONE Z217 SE PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 2,056 ft2)

Detection: None.

Suppression: Hose Cabinet Outside Zone: HC-5 Hose Cabinet Inside Zone: HC-2 Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: N 3.8-30 Amendment 14

STP MHAR FIRE ZONE TABLE 63-18 FIRE AREA NO. 63 FIRE ZONE Z218 SE PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 160,000 Btu/ft2 (Area: 2,047 ft2)

Detection: None.

Suppression: Hose Cabinets Inside Zone: HC-3 and HC-7 Radioactive/Toxic Material: Y/Y Communications: N Emergency Lighting: N 3.8-31 Amendment 14

STP FHAR FIRE ZONE TABLE 63-19 FIRE AREA NO. 63 FIRE ZONE Z219 CENTRAL REACTOR AREA (LOWER)

See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 40,000 Btu/ft 2 (Area: 7,181 ft2)

Detection: None.

Suppression: Hose Cabinets Outside Zone: HC-1 and HC-4 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-32 Amendment 14

STP FHAR FIRE ZONE TABLE 63-20 FIRE AREA NO. 63 FIRE ZONE Z220 STEAM GENERATOR 1D See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 918 ft2 )

Detection: Stop-Type Thermal (RC Pumps)

Suppression: Hose Cabinet Outside Zone: HC-9 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-33 Amendment 14

STP FHAR FIRE ZONE TABLE 63-21 FIRE AREA NO. 63 FIRE ZONE Z221 STEAM GENERATOR 1A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A011MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft2 (Area: 918 ft2)

Detection: Stop-Type Thermal (RC Pumps)

Suppression: Hose Cabinet Inside Zone: HC-9 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-34 Amendment 14

STP FHAR FIRE ZONE TABLE 63-22 FIRE AREA NO. 63 FIRE ZONE Z222 STEAM GENERATOR 1B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A011 MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btu/ft 2 (Area: 918 ft 2)

Detection: Stop-Type Thermal (RC Pumps)

Suppression: Hose Cabinets Outside Zone: HC-1 1 and HC-12 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-35 Amendment 14

STP FHAR FIRE ZONE TABLE 63-23 FIRE AREA NO. 63 FIRE ZONE Z223 STEAM GENERATOR 1C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 80,000 Btulft 2 (Area: 918 ft2)

Detection: Stop-Type Thermal (RC Pumps)

Suppression: Hose Cabinet Inside Zone: HC-12 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-36 Amendment 14

STP FHAR FIRE ZONE TABLE 63-24 FIRE AREA NO. 63 FIRE ZONE Z224 PRESSURIZER ENCLOSURE See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles See Calculation MC-5800 for listing of combustibles.

Combustible Load: 40,000 Btu/Ft 2 (Area: 279 ft2)

Detection: None Suppression: Hose Cabinet Outside Zone: HC-23 and HC-26 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N 3.8-37 Amendment 14

STP FHAR FIRE ZONE TABLE 63-25 FIRE AREA NO. 63 FIRE ZONE Z225 SE PERIPHERAL AREA See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

I'.)

Combustibles* 00 See Calculation MC-5800 for list of combustibles.

Combustible Load: 0 Detection: None Suppression: Hose Cabinet Outside Zone: HC-13 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N

  • All electrical cables in this fire zone are installed in conduit.

3.8-38 Amendment 14

STP F-AR FIRE ZONE TABLE 63-26 FIRE AREA NO. 63 FIRE ZONE Z226 RHR CUBICLE, TRAIN A See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no.

5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles*

See Calculation MC-5800 for list of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area: 187 ft2)

Detection: None Suppression: Hose Cabinet Inside Zone: HC-15 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N

  • All electrical cables in this fire zone are installed in conduit.

3.8-39 Amendment 14

STP FHAR FIRE ZONE TABLE 63-27 FIRE AREA NO. 63 FIRE ZONE Z227 RHR CUBICLE, TRAIN B See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. ,z 5A01 IMC6023 "Appendix R Evaluation."

0o Combustibles*

See Calculation MC-5800 for list of combustibles.

Combustible Load: 40,000 Btu/ft2 (Area: 187 ft2)

Detection: None Suppression: Hose Cabinets Outside Zone: HC-15 and HC-16 Radioactive/Toxic Material: N/Y Communications: N Emergency Lighting: N

  • All electrical cables in this fire zone are installed in conduit.

3.8-40 Amendment 14

STP FHAR FIRE ZONE TABLE 63-28 FIRE AREA NO. 63 FIRE ZONE Z228 RHR CUBICLE, TRAIN C See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A011MC6023 "Appendix R Evaluation." I'D 00 Combustibles*

See Calculation MC-5800 for list of combustibles.

Combustible Load: 40,000 Btu/ft 2 (Area: 265 ft2 )

Detection: None Suppression: Hose Cabinet Outside Zone: HC-17 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N

  • All electrical cables in this fire zone are installed in conduit.

3.8-41 Amendment 14

STP FHAR FIRE ZONE TABLE 63-29 FIRE AREA NO. 63 FIRE ZONE Z229 REGENERATIVE HEAT EXCHANGER ENCLOSURE See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. z 5A01 1MC6023 "Appendix R Evaluation."

00 Combustibles*

See Calculation MC-5800 for list of combustibles.

Combustible Load: 0 Detection: None Suppression: Hose Cabinet Outside Zone: HC-16 Radioactive/Toxic Material: N/N Communications: N Emergency Lighting: N

  • All electrical cables in this fire zone are installed in conduit.

3.8-42 Amendment 14

STP MHAR FIRE ZONE TABLE 78-1 FIRE AREA NO. 78 FIRE ZONE Z703 BOP DIESEL GENERATOR ROOM See Table 2-2 for Safe Shutdown Equipment List Circuits A listing of safe shutdown cables routed through this zone is contained in Calculation no. 00 5A01 1MC6023 "Appendix R Evaluation."

Combustibles See Calculation MC-5800 for list of combustibles.

Combustible Load: 192,000 Btu/Ft2 (Area: 576 ft2)

Detection: Thermal spot-type Suppression: Hose Reel Outside Zone: HR-P-17 Hand Held Dry Chemical Hand Held Carbon Dioxide Radioactive/Toxic Material: N/N Communications: (LATER) 3.9-4 Admendment 14

4.2 COMPARISON TO APPENDIX A OF CPCSB 9.5-1 APPENDIX A OF APCSB 9.5-1 STP POSITION E. Fire Detection and Suppression E. Fire Detection and Suppression E. I. Fire Detection E. 1. Fire Detection E. .a. Fire detection systems should as a minimum comply E. L.a. Detection systems are provided for areas of safety with NFPA 72D, "Standard for the Installation, related buildings that contain or present a fire exposure Maintenance and Use Proprietary Protective Signaling to safe shutdown systems. In some areas of the plant, Systems." detectors were not installed due to the presence of high radiation levels, low combustible loadings, etc. These areas can be organized into nine groups. The groups and basis for deciding that plant safety is not enhanced by their addition are listed in table 4.2

2. The fire detectors are located in accordance with NFPA 72-E, 1978. These detection systems comply with the requirements as defined in NFPA 72 D, 1975, H except for: 1) The connection wiring between each local r1 addressable module associated with either a "spot" thermal detector or manually activated station. This is not considered to be a significant deviation since each local addressable module is located inside a common enclosure with either the "spot" thermal detector or manually activated station, utilizing connections less than 12" in length. For further details describing this deviation, see FHAR section 3.10.4.

E. L.b. Fire detection systems should give audible and visual E. L.b Fire alarm bells and systems trouble alarm horns provide alarm and annunciation in the control room. Local audible alarms at the local control panels that provide the audible alarms should also sound at the location of the fire protection system control for each fire hazard.

fire. These local control panels are normally located in the CD vicinity of the fire hazards that they protect. Fire protection alarms are annunciated in the control room, n CD with an audible tone and visually displayed on a display Z t!1) screen located within the control room. tQ

LIST OF EFFECTIVE PAGES STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Page i 11 Page 2-1 11 Page ii 11 Page 2-2 8 Page iii 11 Page 2-3 8 Page iv 11 Page 2-4 8 Page v 11 Page 2-5 11 Page vi 11 Page 2-6 11 Page vii 11 Page 2-7 8 Page viii 11 Page 2-8 9 Page ix 11 Page 2-9 8 Page x 11 Page 2-10 8 Page 1-1 11 Page 2-11 8 Page 1-2 11 Page 2-12 11 Page 1-3 11 Page 2-13 8 Page 1-4 11 Page 2-14 8 Page 1-5 11 Page 2-15 8 Page 1-6 11 Page 2-16 8 Page 1-7 8 Page 2-17 14 Page 1-8 11 Page 2-18 8 Page 1A-i 13 Page 2-19 8 Page 1A-1 13 Page 2-20 8 Page 1A-2 13 Page 2-21 8 Page 1A-3 13 Page 2-22 8 Page 1A-4 13 Page 2-23 8 Page 1A-5 13 Page 2-24 8 Page 1A-6 13 Page 2-25 8 Page 1A-7 13 Page 2-26 8 Page 1A-8 13 Page 2-27 8 Page lB-i 8 Page 2-28 14 Page lB-1 8 Page 2-29 11 Page 1B-2 8 Page 2-30 14 Page 1B-3 8 Page 2-31 8 Page 1B-4 8 Page 2-32 8 Page 1B-5 8 Page 2-33 8 Page 1B-6 8 Page 2-34 8 Page 1C-i 8 Page 2-35 8 Page 1C-1 8 Page 2-36 8 Page 1C-2 8 Page 2-37 8 Page IC-3 11 Page 2-38 8 Page IC-4 12 Page 2-39 8 Fig. 1-1 9 Page 2-40 8 Fig. 1-2 9 Page 2-41 8 Fig. 1-3 9 Page 2-42 8 D:.whar 14\FHARLOEP anxi 14.doc 1 Amendment 14 Last update 04I17/02

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Page 2-43 8 Fig. 2-6 Page 2-44 8 (Unit 1) 9 Page 2-45 8 Fig. 2-6 Page 2-46 8 (Unit 2) 9 Page 2-47 8 Fig. 2-7 Page 2-48 8 (Unit 1) 9 Page 2-49 8 Fig. 2-7 Page 2-50 8 (Unit 2) 9 Page 2-51 8 Fig. 2-8 Page 2-52 11 (Unit 1) 10 Page 2-53 8 Fig. 2-8 Page 2-54 11 (Unit 2) 9 Page 2-55 8 Fig. 2-9 Page 2-56 8 (Unit 1) 11 Page 2-57 8 Fig. 2-9 Page 2-58 8 (Unit 2) 11 Page 2-59 8 Fig. 2-10 Page 2-60 8 (Unit 1) 11 Page 2-61 8 Fig. 2-10 Page 2-62 8 (Unit 2) 11 Page 2-63 8 Fig. 2-11 Page 2-64 8 (Unit 1) 11 Page 2-65 8 Fig. 2-11 Page 2-66 8 (Unit 2) 11 Page 2-67 8 Fig. 2-12 Page 2-68 8 (Unit 1) 11 Page 2-69 8 Fig. 2-12 Fig. 2-1 9 (Unit 2) 11 Fig. 2-2 9 Fig. 2-13 Fig. 2-3 (Unit 1) 9 (Unit 1) 10 Fig. 2-13 Fig. 2-3 (Unit 2) 9 (Unit 2) 9 Fig. 2-13A Fig. 2-4 (Unit 1) 9 (Unit 1) 9 Fig. 2-13A Fig. 2-4 (Unit 2) 9 (Unit 2) 9 Fig. 2-14 Fig. 2-5 (Unit 1) 11 (Unit 1) 9 Fig. 2-14 (Unit 2) 11 Fig. 2-5 Fig. 2-15 (Unit 2) 9 (Unit 1) 10 D:Fhar 14\4HARLOEP and_ 14.doc 2 Amendment 14 Last update 04117/02

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Fig. 2-15 Page 3.1-19 11 (Unit 2) 11 Page 3.1-20 11 Fig. 2-16 Page 3.2-1 8 (Unit 1) 9 Page 3.2-2 11 Fig. 2-16 Page 3.2-3 8 (Unit 1) 9 Page 3.2-4 8 Fig. 2-17 Page 3.2-5 8 11 Page 3.2-6 8 (Unit 1&2)

Fig. 2-18 Page 3.2-7 8 (Unit 1) 9 Page 3.2-8 14 Fig. 2-18 Page 3.2-9 12 (Unit 2) 9 Page 3.2-10 12 Fig. 2-19 Page 3.2-11 11 (Unit 1) 9 Page 3.2-12 11 Fig. 2-19 Page 3.2-13 11 (Unit 2) 9 Page 3.2-14 11 Fig. 2-20 Page 3.2-15 11 (Unit 1) 9 Page 3.2-16 12 Fig. 2-20 Page 3.2-17 11 (Unit 2) 9 Page 3.2-18 14 Fig. 2-21 Page 3.2-19 14 (Unit 1) 9 Page 3.2-20 14 Fig. 2-21 Page 3.2-21 14 (Unit 2) 9 Page 3.2-22 14 Page 3.1-1 14 Page 3.2-23 14 Page 3.1-2 14 Page 3.2-24 14 Page 3.1-3 11 Page 3.2-25 14 Page 3.1-4 11 Page 3.2-26 14 Page 3.1-5 11 Page 3.2-27 11 Page 3.1-6 11 Page 3.2-28 14 Page 3.1-7 11 Page 3.2-29 12 Page 3.1-8 11 Page 3.2-30 14 Page 3.1-9 11 Page 3.2-31 14 Page 3.1-10 11 Page 3.2-32 12 Page 3.1-11 11 Page 3.2-33 14 Page 3.1-12 11 Page 3.2-34 14 Page 3.1-13 11 Page 3.2-35 14 Page 3.1-14 11 Page 3.2-36 12 Page 3.1-15 11 Page 3.2-37 11 Page 3.1-16 11 Page 3.2-38 11 11 Page 3.2-39 11 Page 3.1-17 Page 3.1-18 11 Page 3.2-40 11 D:\Fhar_14\FHARLOEP anmd14.doc 3 Amendment 14 Last update 04/17/02

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Page 3.2-41 11 Page 3.2-83 14 Page 3.2-42 11 Page 3.2-84 14 Page 3.2-43 11 Page 3.2-85 11 Page 3.2-44 11 Page 3.2-86 11 Page 3.2-45 11 Page 3.2-87 11 Page 3.2-46 14 Page 3.2-88 14 Page 3.2-47 14 Page 3.2-89 11 Page 3.2-48 14 Page 3.2-90 11 Page 3.2-49 12 Page 3.2-91 14 Page 3.2-50 14 Page 3.2-92 11 Page 3.2-51 14 Page 3.2-93 14 Page 3.2-52 14 Page 3.2-94 11 Page 3.2-53 14 Page 3.2-95 11 Page 3.2-54 14 Page 3.2-96 11 Page 3.2-55 14 Page 3.2-97 11 Page 3.2-56 12 Page 3.2-98 11 Page 3.2-57 14 Page 3.2-99 11 Page 3.2-58 14 Page 3.2-100 11 Page 3.2-59 12 Page 3.2-101 11 Page 3.2-60 14 Page 3.2-102 11 Page 3.2-61 11 Page 3.2-103 11 Page 3.2-62 11 Page 3.2-104 11 Page 3.2-63 11 Page 3.2-105 11 Page 3.2-64 14 Page 3.2-106 11 Page 3.2-65 14 Page 3.2-107 11 Page 3.2-66 14 Page 3.2-108 11 Page 3.2-67 14 Page 3.2-109 11 Page 3.2-68 14 Page 3.2-110 11 Page 3.2-69 14 Page 3.2-111 11 Page 3.2-70 12 Page 3.2-112 11 Page 3.2-71 14 Page 3.2-113 11 Page 3.2-72 12 Page 3.2-114 11 Page 3.2-73 12 Page 3.2-115 11 Page 3.2-74 11 Page 3.2-116 11 Page 3.2-75 11 Page 3.2-117 11 Page 3.2-76 14 Page 3.2-118 14 Page 3.2-77 11 Page 3.2-119 11 Page 3.2-78 11 Page 3.2-120 11 Page 3.2-79 12 Page 3.2-121 11 Page 3.2-80 12 Page 3.2-122 11 Page 3.2-81 12 Page 3.2-123 11 Page 3.2-82 12 Page 3.2-124 14 DAFhar 14\'HARLOEP anxI 14.doc 4 Amendment 14 Las update 0.1/17102

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Page 3.2-125 11 Page 3.2-167 11 Page 3.2-126 11 Page 3.2-168 14 Page 3.2-127 12 Page 3.2-169 14 Page 3.2-128 11 Page 3.2-170 11 Page 3.2-129 11 Page 3.2-171 14 Page 3.2-130 11 Page 3.2-172 12 Page 3.2-131 14 Page 3.2-173 14 Page 3.2-132 14 Page 3.2-174 14 Page 3.2-133 11 Page 3.2-175 14 Page 3.2-134 11 Page 3.2-176 14 Page 3.2-135 11 Page 3.2-177 14 Page 3.2-136 14 Page 3.2-178 14 Page 3.2-137 12 Page 3.2-179 14 Page 3.2-138 12 Page 3.2-180 11 Page 3.2-139 11 Page 3.2-181 11 Page 3.2-140 12 Page 3.2-182 14 Page 3.2-141 14 Page 3.2-183 11 Page 3.2-142 11 Page 3.2-184 11 Page 3.2-143 12 Page 3.2-185 14 Page 3.2-144 14 Page 3.2-186 11 Page 3.2-145 11 Page 3.2-187 11 Page 3.2-146 11 Page 3.2-188 14 Page 3.2-147 11 Page 3.2-189 11 Page 3.2-148 14 Page 3.2-190 11 Page 3.2-149 14 Page 3.2-191 14 Page 3.2-150 14 Page 3.2-192 11 Page 3.2-151 14 Page 3.2-193 11 Page 3.2-152 14 Page 3.2-194 14 Page 3.2-153 11 Page 3.2-195 11 Page 3.2-154 14 Page 3.2-196 11 Page 3.2-155 11 Page 3.2-197 14 Page 3.2-156 11 Page 3.2-198 12 Page 3.2-157 11 Page 3.2-199 11 Page 3.2-158 14 Page 3.2-200 11 Page 3.2-159 11 Page 3.2-201 14 Page 3.2-160 14 Page 3.2-202 11 Page 3.2-161 11 Page 3.2-203 14 Page 3.2-162 11 Page 3.2-204 11 Page 3.2-163 14 Page 3.2-205 11 Page 3.2-164 11 Page 3.2-206 14 Page 3.2-165 11 Page 3.2-207 14 Page 3.2-166 11 Page 3.2-208 11 D:\Fhar 14THARLOEP amd 14.doc 5 Amendment 14 Last update 04/17/02

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Page 3.2-209 14 Page 3.4-8 14 Page 3.2-210 11 Page 3.4-9 12 Page 3.2-211 14 Page 3.4-10 11 Page 3.2-212 11 Page 3.4-11 11 Page 3.2-213 11 Page 3.4-12 14 Page 3.2-214 14 Page 3.4-13 12 Page 3.2-215 11 Page 3.4-14 8 Page 3.2-216 14 Page 3.4-15 11 Page 3.2-217 11 Page 3.4-16 12 Page 3.2-218 14 Page 3.4-17 8 Page 3.2-219 11 Page 3.4-18 11 Page 3.2-220 14 Page 3.4-19 12 Page 3.2-221 11 Page 3.4-20 11 Page 3.2-222 11 Page 3.4-21 11 Page 3.2-223 14 Page 3.4-22 12 Page 3.2-224 14 Page 3.4-23 11 Page 3.3-1 8 Page 3.4-24 11 Page 3.3-2 8 Page 3.4-25 14 Page 3.3-3 8 Page 3.4-26 11 Page 3.3-4 11 Page 3.4-27 8 Page 3.3-5 8 Page 3.4-28 14 Page 3.3-6 8 Page 3.4-29 11 Page 3.3-7 14 Page 3.4-30 11 Page 3.3-8 12 Page 3.4-31 14 Page 3.3-9 12 Page 3.4-32 11 Page 3.3-10 12 Page 3.4-33 11 Page 3.3-11 12 Page 3.4-34 14 Page 3.3-12 14 Page 3.4-35 11 Page 3.3-13 14 Page 3.4-36 11 Page 3.3-14 12 Page 3.4-37 14 Page 3.3-15 12 Page 3.4-38 11 Page 3.3-16 12 Page 3.4-39 11 Page 3.3-17 12 Page 3.4-40 14 Page 3.3-18 10 Page 3.5-1 8 Page 3.3-19 10 Page 3.5-2 8 Page 3.4-1 8 Page 3.5-3 11 Page 3.4-2 11 Page 3.5-4 11 Page 3.4-3 11 Page 3.5-5 14 Page 3.4-4 14 Page 3.5-6 14 Page 3.4-5 12 Page 3.5-7 11 Page 3.4-6 8 Page 3.5-8 8 Page 3.4-7 11 Page 3.5-9 11 D:Fhar 14THARLOEP anmd14.doc 6 Amendment 14 Last update 04/17/02

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Page 3.5-10 8 Page 3.6-23 14 Page 3.5-11 14 Page 3.7-1 8 Page 3.5-12 14 Page 3.7-2 8 Page 3.5-13 11 Page 3.7-3 12 Page 3.5-14 8 Page 3.7-4 8 Page 3.5-15 11 Page 3.7-5 12 Page 3.5-16 8 Page 3.7-6 8 Page 3.5-17 14 Page 3.7-7 12 Page 3.5-18 14 Page 3.7-8 12 Page 3.5-19 11 Page 3.8-1 11 Page 3.5-20 8 Page 3.8-2 8 Page 3.5-21 11 Page 3.8-3 8 Page 3.5-22 11 Page 3.8-4 8 Page 3.5-23 14 Page 3.8-5 8 Page 3.5-24 14 Page 3.8-6 8 Page 3.5-25 14 Page 3.8-7 11 Page 3.5-26 11 Page 3.8-8 11 Page 3.5-27 8 Page 3.8-9 11 Page 3.5-28 8 Page 3.8-10 11 Page 3.5-29 10 Page 3.8-11 8 Page 3.6-1 8 Page 3.8-12 12 Page 3.6-2 11 Page 3.8-13 14 Page 3.6-3 11 Page 3.8-14 14 Page 3.6-4 8 Page 3.8-15 12 Page 3.6-5 14 Page 3.8-16 12 Page 3.6-6 8 Page 3.8-17 14 Page 3.6-7 11 Page 3.8-18 14 Page 3.6-8 11 Page 3.8-19 14 Page 3.6-9 14 Page 3.8-20 14 Page 3.6-10 8 Page 3.8-21 14 Page 3.6-11 11 Page 3.8-22 14 Page 3.6-12 11 Page 3.8-23 14 Page 3.6-13 8 Page 3.8-24 14 Page 3.6-14 14 Page 3.8-25 14 Page 3.6-15 11 Page 3.8-26 14 Page 3.6-16 11 Page 3.8-27 14 Page 3.6-17 14 Page 3.8-28 14 Page 3.6-18 11 Page 3.8-29 14 Page 3.6-19 10 Page 3.8-30 14 Page 3.6-20 14 Page 3.8-31 14 Page 3.6-21 11 Page 3.8-32 14 Page 3.6-22 11 Page 3.8-33 14 D:\Fhar 14\FHARLOEPaimd_ 14.doc 7 Amendment 14 Last update 04/17/02

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Page 3.8-34 14 Fig. 3-3 Page 3.8-35 14 (Unit 1) 9 Page 3.8-36 14 Fig. 3-3 Page 3.8-37 14 (Unit 2) 9 Page 3.8-38 14 Fig. 3-4 Page 3.8-39 14 (Unit 1) 9 Page 3.8-40 14 Fig. 3-4 Page 3.8-41 14 (Unit 2) 9 Page 3.8-42 14 Fig. 3-5 Page 3.9-1 10 (Unit 1) 9 Page 3.9-2 10 Fig. 3-5 Page 3.9-3 8 (Unit 2) 9 Page 3.9-4 14 Fig. 3-6 Page 3.10-1 8 (Unit 1) 10 Page 3.10-2 8 Fig. 3-6 Page 3.10-3 9 (Unit 2) 9 Page 3.10-4 8 Fig. 3-7 Page 3.10-5 8 (Unit 1) 9 Page 3.10-6 8 Fig. 3-7 Page 3.10-7 8 (Unit 2) 10 Page 3.10-8 8 Fig. 3-8 Page 3.10-9 8 (Unit 1) 11 Page 3.10-10 8 Fig. 3-8 Page 3.10-11 8 (Unit 2) 9 Page 3.10-12 8 Fig. 3-9 Page 3.10-13 8 (Unit 1) 9 Page 3.10-14 8 Fig. 3-9 Page 3.10-15 8 (Unit 2) 9 Page 3.10-16 8 Fig. 3-10 Page 3.10-17 12 (Unit 1) 9 Page 3.10-18 11 Fig. 3-10 Page 3.10-19 11 (Unit 2) 9 Page 3-i 8 Fig. 3-11 Page 3-ii 8 (Unit 1) 9 Fig. 3-1 Fig. 3-11 (Unit 1) 10 (Unit 2) 9 Fig. 3-1 Fig. 3-12 (Unit 2) 9 (Unit 1) 10 Fig. 3-2 Fig. 3-12 (Unit 1) 9 (Unit 2) 9 Fig. 3-2 Fig. 3-13 (Unit 2) 9 (Unit 1) 10 D:Fhar 14AFHARLOEP anxl 14.doc 8 Amendment 14 Last update 04/17/02

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Fig. 3-13 Fig. 3-24 (Unit 2) 10 (Unit 1) 11 Fig. 3-14 Fig. 3-24 (Unit 1) 11 (Unit 2) 11 Fig. 3-14 Fig. 3-25 (Unit 2) 11 (Unit 1) 9 Fig. 3-15 Fig. 3-25 (Unit 1) 11 (Unit 2) 9 Fig. 3-15 Fig. 3-26 (Unit 2) 11 (Unit 1) 11 Fig. 3-16 Fig. 3-26 (Unit 1) 11 (Unit 2) 11 Fig. 3-16 Fig. 3-27 (Unit 2) 11 (Unit 1) 9 Fig. 3-17 Fig. 3-27 (Unit 1) 11 (Unit 2) 9 Fig. 3-17 Fig. 3-28 (Unit 2) 11 (Unit 1) 9 Fig. 3-18 Fig. 3-28 (Unit 1) 9 (Unit 2) 9 Fig. 3-18 Fig. 3-29 (Unit 2) 9 (Unit 1) 11 Fig. 3-19 Fig. 3-29 (Unit 1) 9 (Unit 2) 11 Fig. 3-19 Fig. 3-30 (Unit 2) 9 (Unit 1) 11 Fig. 3-20 Fig. 3-30 (Unit 1) 11 (Unit 2) 11 Fig. 3-20 Fig. 3-31 (Unit 2) 11 (Unit 1) 11 Fig. 3-21 Fig. 3-31 (Unit 1) 9 (Unit 2) 11 Fig. 3-21 Fig. 3-32 (Unit 2) 9 (Unit 1) 10 Fig. 3-22 Fig. 3-32 (Unit 1) 10 (Unit 2) 11 Fig. 3-22 Fig. 3-33 (Unit 2) 10 (Unit 1) 9 Fig. 3-23 Fig. 3-33 (Unit 1) 9 (Unit 2) 9 Fig. 3-23 Fig. 3-34 (Unit 2) 13 9 (Unit 1&2)

D:Whar 14\FHARLOEP amd_14.doc 9 Amendment 14 Last update 04/17102

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Fig. 3-35 Page 4-i 8 (Unit 1) 9 Page 4.1-1 8 Fig. 3-35 Page 4.1-2 8 (Unit 2) 9 Page 4.1-3 8 Fig. 3-36 Page 4.1-4 8 (Unit 1) 9 Page 4.1-5 8 Fig. 3-36 Page 4.1-6 8 (Unit 2) 9 Page 4.1-7 8 Fig. 3-37 Page 4.1-8 9 (Unit 1) 9 Page 4.1-9 9 Fig. 3-37 Page 4.1-10 8 (Unit 2) 9 Page 4.1-11 8 Fig. 3-38 Page 4.1-12 12 (Unit 1) 9 Page 4.1-13 11 Fig. 3-38 Page 4.1-14 8 (Unit 2) 9 Page 4.1-15 8 Fig. 3-39 Page 4.1-16 8 (Unit 1) 9 Page 4.1-17 8 Fig. 3-39 Page 4.1-18 8 (Unit 2) 9 Page 4.1-19 8 Fig. 3-40 Page 4.1-20 8 (Unit 1) 9 Page 4.1-21 8 Fig. 3-40 Page 4.1-22 13 (Unit 2) 9 Page 4.1-23 11 Fig. 3-41 Page 4.1-24 8 (Deleted) 8 Page 4.1-25 8 Fig. 3-42 Page 4.1-26 8 (Deleted) 8 Page 4.1-27 8 Fig. 3-43 Page 4.1-28 8 (Deleted) 8 Page 4.1-29 8 Fig. 3-44 Page 4.1-30 8 (Deleted) 8 Page 4.1-31 8 Fig. 3-45 Page 4.1-32 8 (Unit 1) 9 Page 4.1-33 8 Fig. 3-45 Page 4.1-34 8 (Unit 2) 9 Page 4.1-35 8 Fig. 3-46 Page 4.1-36 8 (Deleted) Page 4.1-37 8 Fig. 3-47 9 Page 4.1-38 8 Fig. 3-48 9 Page 4.1-39 8 Fig. 3-49 9 Page 4.1-40 8 Fig. 3-50 9 Page 4.1-41 8 D:Thar 14WHARLOEP amd 14.doc 10 Amendment 14 Last update 04/17/02

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Page 4.1-42 11 Page 4.2-40 8 Page 4.1-43 8 Page 4.2-41 8 Fig. 4.1-1 8 Page 4.2-42 14 Page 4.2-1 8 Page 4.2-43 8 Page 4.2-2 8 Page 4.2-44 8 Page 4.2-3 8 Page 4.2-45 10 Page 4.2-4 8 Page 4.2-46 8 Page 4.2-5 8 Page 4.2-47 8 Page 4.2-6 8 Page 4.2-48 8 Page 4.2-7 8 Page 4.2-49 8 Page 4.2-8 8 Page 4.2-50 12 Page 4.2-9 8 Page 4.2-51 8 Page 4.2-10 8 Page 4.2-52 10 Page 4.2-11 8 Page 4.2-53 8 Page 4.2-12 8 Page 4.2-54 8 Page 4.2-13 8 Page 4.2-55 8 Page 4.2-14 13 Page 4.2-56 8 Page 4.2-15 8 Page 4.2-57 8 Page 4.2-16 8 Page 4.2-58 8 Page 4.2-17 8 Page 4.2-59 8 Page 4.2-18 8 Page 4.2-60 10 Page 4.2-19 8 Page 4.2-61 8 Page 4.2-20 8 Page 4.2-62 8 Page 4.2-21 8 Page 4.2-63 8 Page 4.2-22 10 Page 4.2-64 8 Page 4.2-23 8 Page 4.2-65 8 Page 4.2-24 8 Page 4.2-66 8 Page 4.2-25 12 Page 4.2-67 8 Page 4.2-26 11 Page 4.2-68 8 Page 4.2-27 8 Page 4.2-69 8 Page 4.2-28 8 Page 4.2-70 8 Page 4.2-29 8 Page 4.2-71 8 Page 4.2-30 8 Page 4.2-72 8 Page 4.2-31 8 Page 4.2-73 8 Page 4.2-32 8 Page 4.2-74 8 Page 4.2-33 12 Page 4.2-75 8 Page 4.2-34 8 Page 4.2-76 8 Page 4.2-35 8 Page 4.2-77 8 Page 4.2-36 8 Page 4.2-78 8 Page 4.2-37 8 Page 4.2-79 8 Page 4.2-38 8 Page 4.2-80 8 Page 4.2-39 8 Page 4.2-81 8 D:W\har 14\FHARLOEP_andJ 14.doc 11 Amendment 14 Last update 04117102

STP FHAR LIST OF EFFECTIVE PAGES Page/Figure Amendment Page/Figure Amendment Page 4.2-82 8 Page 4.2-83 8 Page 4.2-84 8 Page 4.2-85 11 Page 4.2-86 11 Page 4.2-87 11 Page 4.2-88 11 Page 4.2-89 12 Page 4.2-90 8 Page 4.2-91 8 Page 4.2-92 8 Page 4.2-93 10 Page 4.2-94 8 Page 4.2-95 10 Page 4.2-96 8 Page 4.2-97 10 Page 4.2-98 8 Page 4.2-99 8 Page 4.2-100 8 Page 4.2-101 8 Page 4.2-102 8 Page 4.2-103 8 Fig. 4-1 9 Fig. 4-2 9 D:\har_ 14\FHARLOEPamid_ 14.doc 12 Amendment 14 Last update 04117102