Category:Letter type:NL
MONTHYEARNL-24-0364, Notification of Deferral of Baffle Former Bolt Inspections from Farley 1R33 to 1R342024-10-31031 October 2024 Notification of Deferral of Baffle Former Bolt Inspections from Farley 1R33 to 1R34 NL-24-0392, Response to Requests for Additional Information Related to Proposed Alternative GEN-ISI-AL T-2024-0022024-10-28028 October 2024 Response to Requests for Additional Information Related to Proposed Alternative GEN-ISI-AL T-2024-002 NL-24-0396, Response to Request for Additional Information Related to Relief Request to Defer Charging Pump and Mini-Flow Isolation Valve Inservice Testing2024-10-25025 October 2024 Response to Request for Additional Information Related to Relief Request to Defer Charging Pump and Mini-Flow Isolation Valve Inservice Testing NL-24-0384, Request for Alternative RR-PR-04 for Inservice Testing of the 2A, 2B, and 2C Charging Pumps and Mini-Flow Isolation Valves2024-10-18018 October 2024 Request for Alternative RR-PR-04 for Inservice Testing of the 2A, 2B, and 2C Charging Pumps and Mini-Flow Isolation Valves NL-24-0320, License Amendment Request Proposing a New Set of Fission Gas Gap Release Fractions for High Burnup Fuel Rods That Exceed the Linear Heat Generation Rate Limit Detailed in Regulatory Guide 1.183, Table 3,.2024-09-27027 September 2024 License Amendment Request Proposing a New Set of Fission Gas Gap Release Fractions for High Burnup Fuel Rods That Exceed the Linear Heat Generation Rate Limit Detailed in Regulatory Guide 1.183, Table 3,. NL-24-0349, Units 1 and 2 - 10 CFR 26.719(c)(1) 30-Day Report Blind Performance Test Results Inconsistent with Sample Provided2024-09-20020 September 2024 Units 1 and 2 - 10 CFR 26.719(c)(1) 30-Day Report Blind Performance Test Results Inconsistent with Sample Provided NL-24-0341, Response to Request for Additional Information Related to the Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency2024-09-10010 September 2024 Response to Request for Additional Information Related to the Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency NL-24-0259, License Amendment Request to Revise Technical Specification 3.4.14, Reactor Coolant System Pressure Isolation Valve Leakage, Surveillance Requirement 3.4.14.3 Acceptance Criteria and Miscellaneous Obsolete Changes2024-09-0404 September 2024 License Amendment Request to Revise Technical Specification 3.4.14, Reactor Coolant System Pressure Isolation Valve Leakage, Surveillance Requirement 3.4.14.3 Acceptance Criteria and Miscellaneous Obsolete Changes NL-24-0340, Unit 1 - Inservice Inspection Program Owners Activity Report (OAR-1) for Outage 1 R322024-09-0404 September 2024 Unit 1 - Inservice Inspection Program Owners Activity Report (OAR-1) for Outage 1 R32 NL-24-0321, License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions - Supplemental Information2024-08-16016 August 2024 License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions - Supplemental Information NL-24-0261, 10 CFR 50.46 ECCS Evaluation Model Annual Report for 20232024-07-19019 July 2024 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2023 NL-24-0281, License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions2024-07-18018 July 2024 License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions NL-24-0227, Proposed Inservice Inspection Alternative GEN-ISI-AL T-2024-03 for Pressurizer Welds in Accordance with 10 CFR 50.55a(z)(1)2024-07-0303 July 2024 Proposed Inservice Inspection Alternative GEN-ISI-AL T-2024-03 for Pressurizer Welds in Accordance with 10 CFR 50.55a(z)(1) NL-24-0234, Application to Revise Technical Specifications to Adopt TSTF-589, Eliminate Automatic Diesel Generator Start During Shutdown2024-06-28028 June 2024 Application to Revise Technical Specifications to Adopt TSTF-589, Eliminate Automatic Diesel Generator Start During Shutdown NL-24-0230, License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-500, Revision 2, DC Electrical Rewrite – Update to TSTF-3602024-06-28028 June 2024 License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-500, Revision 2, DC Electrical Rewrite – Update to TSTF-360 NL-24-0143, Proposed Alternative to Use ASME Code Case N-752, Risk-Informed Categorization and Treatment for Repair/ Replacement Activities in2024-06-27027 June 2024 Proposed Alternative to Use ASME Code Case N-752, Risk-Informed Categorization and Treatment for Repair/ Replacement Activities in NL-24-0201, Proposed Inservice Inspection Alternative GEN-ISI-ALT-2024-002 for Steam Generator Welds in Accordance with 10 CFR 50.55a(z)(1)2024-06-18018 June 2024 Proposed Inservice Inspection Alternative GEN-ISI-ALT-2024-002 for Steam Generator Welds in Accordance with 10 CFR 50.55a(z)(1) NL-24-0238, RIPE License Amendment Request to Change Containment Air Temperature Actions, Supplemental Information2024-06-14014 June 2024 RIPE License Amendment Request to Change Containment Air Temperature Actions, Supplemental Information NL-24-0229, Notice of Intent to Pursue Subsequent License Renewal2024-06-0707 June 2024 Notice of Intent to Pursue Subsequent License Renewal NL-24-0202, SNC Response to Regulatory Issue Summary 2024-01: Preparation and Scheduling of Operator Licensing Examinations2024-05-24024 May 2024 SNC Response to Regulatory Issue Summary 2024-01: Preparation and Scheduling of Operator Licensing Examinations NL-24-0191, Annual Radiological Environmental Operating Reports for 20232024-05-10010 May 2024 Annual Radiological Environmental Operating Reports for 2023 NL-24-0064, Units 1 & 2 and Hatch Nuclear Plant - Units 1 & 2 License Amendment Request to Revise Technical Specification 1.1 and Add Online Monitoring Program to Technical Specification 5.52024-05-0303 May 2024 Units 1 & 2 and Hatch Nuclear Plant - Units 1 & 2 License Amendment Request to Revise Technical Specification 1.1 and Add Online Monitoring Program to Technical Specification 5.5 NL-24-0188, Cycle 33 Core Operating Limits Report2024-05-0101 May 2024 Cycle 33 Core Operating Limits Report NL-24-0165, Annual Non-Radiological Environmental Operating Reports and Annual Radioactive Effluent Release Reports for 20232024-04-25025 April 2024 Annual Non-Radiological Environmental Operating Reports and Annual Radioactive Effluent Release Reports for 2023 NL-24-0137, RIPE License Amendment Request to Change Containment Air Temperature Actions2024-04-19019 April 2024 RIPE License Amendment Request to Change Containment Air Temperature Actions NL-24-0134, Renewed National Pollutant Discharge Elimination System (NPDES) Permit2024-04-12012 April 2024 Renewed National Pollutant Discharge Elimination System (NPDES) Permit NL-24-0088, Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency2024-04-0505 April 2024 Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency NL-24-0115, Response to Request for Additional Information Exemption Requests for Physical.2024-04-0404 April 2024 Response to Request for Additional Information Exemption Requests for Physical. NL-24-0116, Nuclear Property Insurance Coverage as of April 1, 2024 and Licensee Guarantees of Payment of Deferred.2024-03-29029 March 2024 Nuclear Property Insurance Coverage as of April 1, 2024 and Licensee Guarantees of Payment of Deferred. NL-24-0092, Inservice Inspection Program Owners Activity Report (OAR-1) for Outage 2R292024-03-15015 March 2024 Inservice Inspection Program Owners Activity Report (OAR-1) for Outage 2R29 NL-24-0003, Inservice Inspection Program Owners Activity Report (OAR) Supplement for Outages 1 R30 and 1 R312024-02-16016 February 2024 Inservice Inspection Program Owners Activity Report (OAR) Supplement for Outages 1 R30 and 1 R31 NL-24-0042, Response to Request for Additional Information Exemption Requests for Physical Barriers2024-02-13013 February 2024 Response to Request for Additional Information Exemption Requests for Physical Barriers NL-24-0033, Response to Question for Withholding Information from Public Disclosure Exemption Requests for Physical Barriers2024-02-0505 February 2024 Response to Question for Withholding Information from Public Disclosure Exemption Requests for Physical Barriers NL-24-0011, Report of Changes to Emergency Plan and Summary of 50.54(q) Analysis2024-01-11011 January 2024 Report of Changes to Emergency Plan and Summary of 50.54(q) Analysis NL-23-0901, 30-Day 10 CFR 21 Notification - Framatome Supplied Siemens Medium Voltage (Mv) Circuit Breakers2023-12-15015 December 2023 30-Day 10 CFR 21 Notification - Framatome Supplied Siemens Medium Voltage (Mv) Circuit Breakers NL-23-0908, Cycle 30 Core Operating Limits Report2023-12-13013 December 2023 Cycle 30 Core Operating Limits Report NL-23-0877, Request for Exemption from Security Event Notification Implementation2023-11-29029 November 2023 Request for Exemption from Security Event Notification Implementation NL-23-0825, Reply to Notice of Violation EA-23-080 and Readiness for 95001 Inspection2023-11-14014 November 2023 Reply to Notice of Violation EA-23-080 and Readiness for 95001 Inspection NL-23-0739, Response to NRC Inspection Report and Preliminary White Finding2023-09-0808 September 2023 Response to NRC Inspection Report and Preliminary White Finding NL-23-0716, Response to Request for Additional Information Regarding Emergency License Amendment Request: Technical Specification 3.6.5, Containment Air Temperature, One-Time Temporary Change to Limit2023-08-23023 August 2023 Response to Request for Additional Information Regarding Emergency License Amendment Request: Technical Specification 3.6.5, Containment Air Temperature, One-Time Temporary Change to Limit NL-23-0713, Response to Request for Additional Information Regarding Emergency License Amendment Request: Technical Specification 3.6.5, Containment Air Temperature, One-Time Temporary Change to Limit2023-08-23023 August 2023 Response to Request for Additional Information Regarding Emergency License Amendment Request: Technical Specification 3.6.5, Containment Air Temperature, One-Time Temporary Change to Limit NL-23-0704, Emergency License Amendment Request: Technical Specification 3.6.5, Containment Air Temperature, One-Time Temporary Change to Limit2023-08-22022 August 2023 Emergency License Amendment Request: Technical Specification 3.6.5, Containment Air Temperature, One-Time Temporary Change to Limit NL-23-0658, Southern Nuclear Operating Company - Response to Request for Additional Information Regarding Quality Assurance Topical Report Submittal2023-08-11011 August 2023 Southern Nuclear Operating Company - Response to Request for Additional Information Regarding Quality Assurance Topical Report Submittal NL-23-0542, CFR 50.46 ECCS Evaluation Model Annual Report for 20222023-08-0909 August 2023 CFR 50.46 ECCS Evaluation Model Annual Report for 2022 NL-23-0624, Report of Changes to Emergency Plan and Summary of 50.54(q) Analysis2023-08-0404 August 2023 Report of Changes to Emergency Plan and Summary of 50.54(q) Analysis NL-23-0628, Readiness for Supplemental Inspection EA-22-1012023-07-26026 July 2023 Readiness for Supplemental Inspection EA-22-101 NL-23-0566, ISFSI and Edwin I. Hatch Nuclear Plant ISFSI - Registration of Spent Fuel Cask Use2023-07-13013 July 2023 ISFSI and Edwin I. Hatch Nuclear Plant ISFSI - Registration of Spent Fuel Cask Use NL-23-0555, Request for Exemption from Physical Barrier Requirement2023-07-0707 July 2023 Request for Exemption from Physical Barrier Requirement NL-23-0506, To Non-Voluntary License Amendment Request: Technical Specification Revision to Adopt WCAP-17661-P-A, Improved RAOC and CAOC Fq Surveillance Technical Specifications2023-07-0505 July 2023 To Non-Voluntary License Amendment Request: Technical Specification Revision to Adopt WCAP-17661-P-A, Improved RAOC and CAOC Fq Surveillance Technical Specifications NL-23-0444, Quality Assurance Topical Report Submittal2023-06-15015 June 2023 Quality Assurance Topical Report Submittal 2024-09-04
[Table view] Category:License-Application for Facility Operating License (Amend/Renewal) DKT 50
MONTHYEARNL-24-0320, License Amendment Request Proposing a New Set of Fission Gas Gap Release Fractions for High Burnup Fuel Rods That Exceed the Linear Heat Generation Rate Limit Detailed in Regulatory Guide 1.183, Table 3,.2024-09-27027 September 2024 License Amendment Request Proposing a New Set of Fission Gas Gap Release Fractions for High Burnup Fuel Rods That Exceed the Linear Heat Generation Rate Limit Detailed in Regulatory Guide 1.183, Table 3,. NL-24-0259, License Amendment Request to Revise Technical Specification 3.4.14, Reactor Coolant System Pressure Isolation Valve Leakage, Surveillance Requirement 3.4.14.3 Acceptance Criteria and Miscellaneous Obsolete Changes2024-09-0404 September 2024 License Amendment Request to Revise Technical Specification 3.4.14, Reactor Coolant System Pressure Isolation Valve Leakage, Surveillance Requirement 3.4.14.3 Acceptance Criteria and Miscellaneous Obsolete Changes ML24240A0812024-08-27027 August 2024 License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions - Revised Completion Time NL-24-0321, License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions - Supplemental Information2024-08-16016 August 2024 License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions - Supplemental Information NL-24-0281, License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions2024-07-18018 July 2024 License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions NL-24-0234, Application to Revise Technical Specifications to Adopt TSTF-589, Eliminate Automatic Diesel Generator Start During Shutdown2024-06-28028 June 2024 Application to Revise Technical Specifications to Adopt TSTF-589, Eliminate Automatic Diesel Generator Start During Shutdown NL-24-0230, License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-500, Revision 2, DC Electrical Rewrite – Update to TSTF-3602024-06-28028 June 2024 License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-500, Revision 2, DC Electrical Rewrite – Update to TSTF-360 NL-24-0238, RIPE License Amendment Request to Change Containment Air Temperature Actions, Supplemental Information2024-06-14014 June 2024 RIPE License Amendment Request to Change Containment Air Temperature Actions, Supplemental Information NL-24-0064, Units 1 & 2 and Hatch Nuclear Plant - Units 1 & 2 License Amendment Request to Revise Technical Specification 1.1 and Add Online Monitoring Program to Technical Specification 5.52024-05-0303 May 2024 Units 1 & 2 and Hatch Nuclear Plant - Units 1 & 2 License Amendment Request to Revise Technical Specification 1.1 and Add Online Monitoring Program to Technical Specification 5.5 NL-24-0137, RIPE License Amendment Request to Change Containment Air Temperature Actions2024-04-19019 April 2024 RIPE License Amendment Request to Change Containment Air Temperature Actions NL-24-0088, Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency2024-04-0505 April 2024 Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency NL-23-0704, Emergency License Amendment Request: Technical Specification 3.6.5, Containment Air Temperature, One-Time Temporary Change to Limit2023-08-22022 August 2023 Emergency License Amendment Request: Technical Specification 3.6.5, Containment Air Temperature, One-Time Temporary Change to Limit NL-22-0799, License Amendment Request to Revise the Frequency of Surveillance Requirement 3.6.3.52022-12-20020 December 2022 License Amendment Request to Revise the Frequency of Surveillance Requirement 3.6.3.5 NL-22-0897, Supplement to Non-Voluntary License Amendment Request: Technical Specification Revision to Adopt WCAP-17661-P-A,2022-12-0909 December 2022 Supplement to Non-Voluntary License Amendment Request: Technical Specification Revision to Adopt WCAP-17661-P-A, NL-20-0170, Non-Voluntary License Amendment Request: Technical Specification Revision to Adopt WCAP-17661-P-A, Improved RAOC2022-10-14014 October 2022 Non-Voluntary License Amendment Request: Technical Specification Revision to Adopt WCAP-17661-P-A, Improved RAOC NL-22-0289, License Amendment Request to Revise Technical Specification 4.3 Fuel Storage to Correct Tabulated Values from the Associated Spent Fuel Pool (SFP) Criticality Analysis2022-09-21021 September 2022 License Amendment Request to Revise Technical Specification 4.3 Fuel Storage to Correct Tabulated Values from the Associated Spent Fuel Pool (SFP) Criticality Analysis NL-22-0223, License Amendment to Revise Technical Specification 3.4.10, Pressurizer Safety Valves to Decrease Low Side Setpoint Tolerance Limiting Condition for Operation (LCO) Value2022-06-30030 June 2022 License Amendment to Revise Technical Specification 3.4.10, Pressurizer Safety Valves to Decrease Low Side Setpoint Tolerance Limiting Condition for Operation (LCO) Value NL-21-0989, License Amendment Request to Relocate Augmented Piping Inspection Program Details2021-12-22022 December 2021 License Amendment Request to Relocate Augmented Piping Inspection Program Details NL-21-0925, Adoption of TSTF-269-A, Revision 2, Allow Administrative Means of Position Verification for Locked or Sealed Valves2021-12-22022 December 2021 Adoption of TSTF-269-A, Revision 2, Allow Administrative Means of Position Verification for Locked or Sealed Valves NL-21-1017, License Amendment Request to Revise Technical Specification 5.5.17, Containment Leakage Rate Testing Program to Increase Calculated Peak Containment Pressure2021-12-13013 December 2021 License Amendment Request to Revise Technical Specification 5.5.17, Containment Leakage Rate Testing Program to Increase Calculated Peak Containment Pressure NL-21-0930, Joseph F. Farley Nuclear Plant, Units 1 & 2 and Vogtle Electric Generating Plant, Units 1 and 2 - Supplement to Application to Revise Technical Specifications to Adopt TSTF 577, Revised Frequencies for Steam Generator Tube Inspections2021-10-21021 October 2021 Joseph F. Farley Nuclear Plant, Units 1 & 2 and Vogtle Electric Generating Plant, Units 1 and 2 - Supplement to Application to Revise Technical Specifications to Adopt TSTF 577, Revised Frequencies for Steam Generator Tube Inspections NL-21-0385, Application to Revise Technical Specifications to Adopt TSTF-554, Revise Reactor Coolant Leakage Requirements2021-09-29029 September 2021 Application to Revise Technical Specifications to Adopt TSTF-554, Revise Reactor Coolant Leakage Requirements NL-21-0658, Joseph Farley, Units 1 and 2, Vogtle, Units 1 and 2, Application to Revise Technical Specifications to Adopt TSTF 577, Revised Frequencies for for Steam Generator Tube Inspections2021-09-17017 September 2021 Joseph Farley, Units 1 and 2, Vogtle, Units 1 and 2, Application to Revise Technical Specifications to Adopt TSTF 577, Revised Frequencies for for Steam Generator Tube Inspections NL-21-0613, Supplement to License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, .2021-06-30030 June 2021 Supplement to License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, . NL-21-0160, License Amendment Request to Remove Table of Contents from Technical Specifications2021-06-22022 June 2021 License Amendment Request to Remove Table of Contents from Technical Specifications NL-21-0042, Units 1 and 2, Vogtle Electric Generating Plant - Units 1 and 2, Voluntary License Amendment Request to Use Beacon Power Distribution Monitoring System2021-06-0909 June 2021 Units 1 and 2, Vogtle Electric Generating Plant - Units 1 and 2, Voluntary License Amendment Request to Use Beacon Power Distribution Monitoring System NL-21-0065, License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, Administrative Controls2021-03-25025 March 2021 License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, Administrative Controls NL-20-0949, License Amendment Request to Revise, Technical Specifications to Adopt TSTF-541, Revision 22020-10-30030 October 2020 License Amendment Request to Revise, Technical Specifications to Adopt TSTF-541, Revision 2 ML20224A4642020-08-11011 August 2020 Southern Nuclear Operating Co, Inc - Supplement to License Amendment Request to Revise the Emergency Plan to Change Staffing and Extend Staff Augmentation Times for Emergency Response Organization Positions ML20192A1402020-06-30030 June 2020 Southern Nuclear Operating Co., Inc. - License Amendment Request to Revise the Emergency Plan to Change Staffing and Extend Staff Augmentation Times for Emergency Response Organization Positions NL-20-0275, Application to Revise Technical Specifications to Adopt TSTF-567, Add Containment Sump TS to Address GSI-191 Issues2020-05-29029 May 2020 Application to Revise Technical Specifications to Adopt TSTF-567, Add Containment Sump TS to Address GSI-191 Issues NL-19-0331, License Amendment Request: Revise Measurement Units Associated with Reactor Trip System Nuclear Instrument Comparison Surveillance and Trip Setpoint for Control Room Air Intake Radiation Monitors2019-12-12012 December 2019 License Amendment Request: Revise Measurement Units Associated with Reactor Trip System Nuclear Instrument Comparison Surveillance and Trip Setpoint for Control Room Air Intake Radiation Monitors NL-19-0963, Removal of the Main Steam and Main Feedwater Valve Isolation Times from Technical Specifications Using Consolidated Line Item Improvement Process2019-12-11011 December 2019 Removal of the Main Steam and Main Feedwater Valve Isolation Times from Technical Specifications Using Consolidated Line Item Improvement Process NL-19-1063, Units 1 and 2 and Vogtle Electric Generating Plant, Units 1 and 2 - Application to Revise Technical Specifications to Adopt TSTF-569, Revise Response Time Testing Definition2019-12-10010 December 2019 Units 1 and 2 and Vogtle Electric Generating Plant, Units 1 and 2 - Application to Revise Technical Specifications to Adopt TSTF-569, Revise Response Time Testing Definition NL-19-0006, Application to Revise Technical Specifications to Adopt TSTF-563, Revise Instrument Testing Definitions to Incorporate the Surveillance Frequency Control Program2019-07-15015 July 2019 Application to Revise Technical Specifications to Adopt TSTF-563, Revise Instrument Testing Definitions to Incorporate the Surveillance Frequency Control Program NL-19-0771, Risk Informed Technical Specification Information Only Bases Changes2019-06-27027 June 2019 Risk Informed Technical Specification Information Only Bases Changes NL-18-0668, Request for License Amendment for Performance-Based Fire Protection Alternative for Thermal Insulation Material2018-12-14014 December 2018 Request for License Amendment for Performance-Based Fire Protection Alternative for Thermal Insulation Material NL-18-1189, Revise Technical Specification Requirements During Handling Irradiated Fuel and Core Alterations- TSTF-51 and TSTF-4712018-11-29029 November 2018 Revise Technical Specification Requirements During Handling Irradiated Fuel and Core Alterations- TSTF-51 and TSTF-471 ML18226A0942018-08-0909 August 2018 Edwin I. Hatch, Units 1 and 2; and Vogtle, Units 1 and 2 - License Amendment Request to Revise Technical Specification 5.2.2.g and Update Emergency Plan Minimum On-shift Staff Tables NL-18-0039, License Amendment Request to Revise Technical Specifications to Implement NEI 06-09, Revision 0-A, Risk-Informed Technical Specifications Initiative 4b, Risk Managed Technical Specifications (Rmts) ...2018-07-27027 July 2018 License Amendment Request to Revise Technical Specifications to Implement NEI 06-09, Revision 0-A, Risk-Informed Technical Specifications Initiative 4b, Risk Managed Technical Specifications (Rmts) ... NL-18-0733, Supplement to License Amendment Request for Technical Specification 3.3.2 Regarding Steam Flow Isolation on High Steam Flow and Response to Request for Additional Information2018-06-0707 June 2018 Supplement to License Amendment Request for Technical Specification 3.3.2 Regarding Steam Flow Isolation on High Steam Flow and Response to Request for Additional Information ML18065A0222018-03-0606 March 2018 March 12, 2018, Public Meeting - Draft 4b Application ML18065A0252018-03-0606 March 2018 Joseph M Farley March 12, 2018, Public Meeting - Draft 4b Application Enclosures NL-17-0190, Revise Actions for One Steam Supply to Turbine Driven Auxiliary Feedwater Pump Inoperable Using the Consolidate Line Item Improvement Process2017-12-21021 December 2017 Revise Actions for One Steam Supply to Turbine Driven Auxiliary Feedwater Pump Inoperable Using the Consolidate Line Item Improvement Process NL-17-0611, Units 1 and 2, License Amendment Request for Technical Specification 3.3.2 Regarding Steam Flow Isolation on High Steam Flow2017-12-21021 December 2017 Units 1 and 2, License Amendment Request for Technical Specification 3.3.2 Regarding Steam Flow Isolation on High Steam Flow NL-17-1088, Submittal of License Amendment Request, Relocation of the Emergency Operations Facility2017-08-30030 August 2017 Submittal of License Amendment Request, Relocation of the Emergency Operations Facility NL-16-2384, Non-Voluntary License Amendment Request to Correct Non-Conservative Technical Specification 3.7.12017-03-22022 March 2017 Non-Voluntary License Amendment Request to Correct Non-Conservative Technical Specification 3.7.1 ML15329A0322017-01-23023 January 2017 Issuance of Amendment Related to Renewed Facility Operating License Condition 2.C.(23) Required Completion Date ML16340A0052016-12-0101 December 2016 License Amendment Request to Revise Technical Specifications to Adopt TSTF-529, Rev 4, Clarify Use and Application Rules. NL-16-1026, Units 1 & 2, Vogtle Electric Generating Plant- Units 1 & 2 - Application to Revise Technical Specifications to Adopt TSTF-547, Clarification of Rod Position Requirements2016-11-21021 November 2016 Units 1 & 2, Vogtle Electric Generating Plant- Units 1 & 2 - Application to Revise Technical Specifications to Adopt TSTF-547, Clarification of Rod Position Requirements 2024-09-04
[Table view] Category:Technical Specification
MONTHYEARNL-24-0321, License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions - Supplemental Information2024-08-16016 August 2024 License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions - Supplemental Information NL-24-0230, License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-500, Revision 2, DC Electrical Rewrite – Update to TSTF-3602024-06-28028 June 2024 License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-500, Revision 2, DC Electrical Rewrite – Update to TSTF-360 NL-24-0064, Units 1 & 2 and Hatch Nuclear Plant - Units 1 & 2 License Amendment Request to Revise Technical Specification 1.1 and Add Online Monitoring Program to Technical Specification 5.52024-05-0303 May 2024 Units 1 & 2 and Hatch Nuclear Plant - Units 1 & 2 License Amendment Request to Revise Technical Specification 1.1 and Add Online Monitoring Program to Technical Specification 5.5 NL-24-0088, Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency2024-04-0505 April 2024 Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency ML23318A0702023-10-31031 October 2023 Technical Specifications Bases ML23076A0502023-03-21021 March 2023 Correction of Amendment Nos. 244 and 241 Issuance of Amendments Regarding Revision to Technical Specifications to Relocate Augmented Piping Inspection Program Details to a License Controlled Document NL-20-0170, Non-Voluntary License Amendment Request: Technical Specification Revision to Adopt WCAP-17661-P-A, Improved RAOC2022-10-14014 October 2022 Non-Voluntary License Amendment Request: Technical Specification Revision to Adopt WCAP-17661-P-A, Improved RAOC NL-22-0289, License Amendment Request to Revise Technical Specification 4.3 Fuel Storage to Correct Tabulated Values from the Associated Spent Fuel Pool (SFP) Criticality Analysis2022-09-21021 September 2022 License Amendment Request to Revise Technical Specification 4.3 Fuel Storage to Correct Tabulated Values from the Associated Spent Fuel Pool (SFP) Criticality Analysis NL-21-0925, Adoption of TSTF-269-A, Revision 2, Allow Administrative Means of Position Verification for Locked or Sealed Valves2021-12-22022 December 2021 Adoption of TSTF-269-A, Revision 2, Allow Administrative Means of Position Verification for Locked or Sealed Valves NL-21-1017, License Amendment Request to Revise Technical Specification 5.5.17, Containment Leakage Rate Testing Program to Increase Calculated Peak Containment Pressure2021-12-13013 December 2021 License Amendment Request to Revise Technical Specification 5.5.17, Containment Leakage Rate Testing Program to Increase Calculated Peak Containment Pressure NL-21-0984, Southern Nuclear Operating Company - Second Supplement to License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, Administrative Controls2021-11-10010 November 2021 Southern Nuclear Operating Company - Second Supplement to License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, Administrative Controls ML21313A3272021-10-28028 October 2021 0, Technical Specification Bases ML21313A3262021-10-28028 October 2021 0 to Updated Final Safety Analysis Report, Chapter 16, Technical Specifications NL-21-0613, Supplement to License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, .2021-06-30030 June 2021 Supplement to License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, . NL-21-0160, License Amendment Request to Remove Table of Contents from Technical Specifications2021-06-22022 June 2021 License Amendment Request to Remove Table of Contents from Technical Specifications ML20125A2122020-04-28028 April 2020 Revisions to Technical Specification Bases Changes NL-19-0331, License Amendment Request: Revise Measurement Units Associated with Reactor Trip System Nuclear Instrument Comparison Surveillance and Trip Setpoint for Control Room Air Intake Radiation Monitors2019-12-12012 December 2019 License Amendment Request: Revise Measurement Units Associated with Reactor Trip System Nuclear Instrument Comparison Surveillance and Trip Setpoint for Control Room Air Intake Radiation Monitors NL-19-1063, Units 1 and 2 and Vogtle Electric Generating Plant, Units 1 and 2 - Application to Revise Technical Specifications to Adopt TSTF-569, Revise Response Time Testing Definition2019-12-10010 December 2019 Units 1 and 2 and Vogtle Electric Generating Plant, Units 1 and 2 - Application to Revise Technical Specifications to Adopt TSTF-569, Revise Response Time Testing Definition NL-19-0006, Application to Revise Technical Specifications to Adopt TSTF-563, Revise Instrument Testing Definitions to Incorporate the Surveillance Frequency Control Program2019-07-15015 July 2019 Application to Revise Technical Specifications to Adopt TSTF-563, Revise Instrument Testing Definitions to Incorporate the Surveillance Frequency Control Program NL-19-0771, Risk Informed Technical Specification Information Only Bases Changes2019-06-27027 June 2019 Risk Informed Technical Specification Information Only Bases Changes NL-19-0221, Risk-Informed Technical Specifications Initiative 4b, Risk-Managed Technical Specifications, SNC Response to NRC Request for Additional Information (RAI)2019-05-0303 May 2019 Risk-Informed Technical Specifications Initiative 4b, Risk-Managed Technical Specifications, SNC Response to NRC Request for Additional Information (RAI) ML18312A0772018-10-30030 October 2018 Technical Specifications Bases ML18226A0942018-08-0909 August 2018 Edwin I. Hatch, Units 1 and 2; and Vogtle, Units 1 and 2 - License Amendment Request to Revise Technical Specification 5.2.2.g and Update Emergency Plan Minimum On-shift Staff Tables NL-17-2095, Supplement Submittal of Corrected Technical Specification Definition of Iodine 1-131 for the Ast. TSTF-448 and TSTF-312 Amendment Package2017-12-18018 December 2017 Supplement Submittal of Corrected Technical Specification Definition of Iodine 1-131 for the Ast. TSTF-448 and TSTF-312 Amendment Package NL-17-0534, Joseph M. Farley Nuclear Plant, Technical Specifications Bases2017-04-20020 April 2017 Joseph M. Farley Nuclear Plant, Technical Specifications Bases ML17117A3742017-04-20020 April 2017 Technical Specifications Bases NL-16-1026, Units 1 & 2, Vogtle Electric Generating Plant- Units 1 & 2 - Application to Revise Technical Specifications to Adopt TSTF-547, Clarification of Rod Position Requirements2016-11-21021 November 2016 Units 1 & 2, Vogtle Electric Generating Plant- Units 1 & 2 - Application to Revise Technical Specifications to Adopt TSTF-547, Clarification of Rod Position Requirements NL-16-0091, License Amendment Request to Revise Technical Specifications to Adopt TSTF-545, Revision 3, TS Lnservice Testing Program Removal & Clarify SR Usage Rule Application.2016-07-28028 July 2016 License Amendment Request to Revise Technical Specifications to Adopt TSTF-545, Revision 3, TS Lnservice Testing Program Removal & Clarify SR Usage Rule Application. NL-15-1761, Response to Request for Additional Information Regarding Adoption of TSTF-432-A, Rev. 1, Change in Technical Specifications End States (WCAP-16294)2015-09-17017 September 2015 Response to Request for Additional Information Regarding Adoption of TSTF-432-A, Rev. 1, Change in Technical Specifications End States (WCAP-16294) NL-15-0421, J. M. Farley, Units 1 and 2 - License Amendment Request to Revise Technical Specifications Regarding Generic Letter 2008-01, Managing Gas Accumulation in Accordance with TSTF-523, Revision 2, Using the Consolidated Line Item Improvement P2015-05-12012 May 2015 J. M. Farley, Units 1 and 2 - License Amendment Request to Revise Technical Specifications Regarding Generic Letter 2008-01, Managing Gas Accumulation in Accordance with TSTF-523, Revision 2, Using the Consolidated Line Item Improvement Pro NL-14-1531, License Amendment Request for Adoption of TSTF-432-A, Rev. 1, Change in Technical Specifications End States (WCAP-16294), Using the Consolidated Line Item Improvement Process2015-04-13013 April 2015 License Amendment Request for Adoption of TSTF-432-A, Rev. 1, Change in Technical Specifications End States (WCAP-16294), Using the Consolidated Line Item Improvement Process ML14335A6292014-11-24024 November 2014 Basis for Proposed Changes. Part 2 of 2 NL-14-1385, Basis for Proposed Changes. Part 1 of 22014-11-24024 November 2014 Basis for Proposed Changes. Part 1 of 2 NL-14-0635, License Amendment Request to Revise Technical Specifications Reactor Trip System Instrumentation2014-06-0303 June 2014 License Amendment Request to Revise Technical Specifications Reactor Trip System Instrumentation NL-13-0081, Application to Revise Technical Specifications to Adopt TSTF-510, Revision to Steam Generator Program Inspection Frequencies and Tube Sample Selection,Using the Consolidated Line Item Improvement...2013-01-23023 January 2013 Application to Revise Technical Specifications to Adopt TSTF-510, Revision to Steam Generator Program Inspection Frequencies and Tube Sample Selection,Using the Consolidated Line Item Improvement... NL-12-0403, Exigent Technical Specification Revision Request for TS 3.5.4 Refueling Water Storage Tank (RWST)2012-02-28028 February 2012 Exigent Technical Specification Revision Request for TS 3.5.4 Refueling Water Storage Tank (RWST) NL-12-0346, Exigent Technical Specification Revision Request for TS 3.5.4 Refueling Water Storage Tank (RWST)2012-02-20020 February 2012 Exigent Technical Specification Revision Request for TS 3.5.4 Refueling Water Storage Tank (RWST) NL-11-0299, Application to Amend Surveillance Requirement 3.4.11.1 and 3.4.11.42012-01-18018 January 2012 Application to Amend Surveillance Requirement 3.4.11.1 and 3.4.11.4 NL-11-1057, License Amendment Request for Technical Specification Table 3.3.1-12011-09-0909 September 2011 License Amendment Request for Technical Specification Table 3.3.1-1 NL-10-0272, License Amendment Request for Adoption of TSTF-425-A, Revision 3, Risk-Informed Justification for the Relocation of Specific Surveillance Frequency Requirements to a Licensee Controlled Program Using the Consolidated..2010-10-29029 October 2010 License Amendment Request for Adoption of TSTF-425-A, Revision 3, Risk-Informed Justification for the Relocation of Specific Surveillance Frequency Requirements to a Licensee Controlled Program Using the Consolidated.. NL-09-1644, Emergency Technical Specification (TS) Revision Request Regarding TS 3.7.8, Service Water System (SWS)2009-10-0808 October 2009 Emergency Technical Specification (TS) Revision Request Regarding TS 3.7.8, Service Water System (SWS) NL-09-0154, Request to Revise Technical Specifications to Delete Reactor Trip System, Function 11, Reactor Coolant Pump Breaker Position2009-03-30030 March 2009 Request to Revise Technical Specifications to Delete Reactor Trip System, Function 11, Reactor Coolant Pump Breaker Position NL-08-0535, Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using Consolidated Line Item Improvement Process2008-10-0808 October 2008 Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using Consolidated Line Item Improvement Process NL-08-1519, Response to Request for Information Regarding Revision to Technical Specifications 3.3.1, 3.3.2, 3.3.6, 3.3.7, and 3.3.82008-10-0808 October 2008 Response to Request for Information Regarding Revision to Technical Specifications 3.3.1, 3.3.2, 3.3.6, 3.3.7, and 3.3.8 ML0611504462006-04-14014 April 2006 Technical Specifications, Revise TS Section 5.5.6, Pre-Stressed Concrete Containment Tendon Surveillance Program, for Consistency with the Requirements of 10 CFR 50.55a(g)(4) for Components Classified as Code Class CC NL-05-0856, Request to Revise Technical Specifications Regarding Mode Change Limitations Using the Consolidated Line Item Improvement Process2005-11-0202 November 2005 Request to Revise Technical Specifications Regarding Mode Change Limitations Using the Consolidated Line Item Improvement Process NL-05-0068, Technical Specification Amendment Request to Incorporate Best Estimate LOCA Analysis Using Astrum2005-10-0606 October 2005 Technical Specification Amendment Request to Incorporate Best Estimate LOCA Analysis Using Astrum NL-05-0740, Submittal of Joseph M. Farley Nuclear Plant, Technical Specifications Revision Spent Fuel Cask Loading Requirements2005-05-17017 May 2005 Submittal of Joseph M. Farley Nuclear Plant, Technical Specifications Revision Spent Fuel Cask Loading Requirements ML0512300672005-04-22022 April 2005 Enclosure, Correction Ltr. on Amendment Nos. 167 & 159 for Elimination of Hydrogen Recombiners and Monitors (Tac No. MC3224, MC3225) ML0507303042005-03-0808 March 2005 Enclosure, Amendment 168 & 160, TS Revision on 5.6 Reporting Requirements 2024-08-16
[Table view] Category:Amendment
MONTHYEARNL-24-0064, Units 1 & 2 and Hatch Nuclear Plant - Units 1 & 2 License Amendment Request to Revise Technical Specification 1.1 and Add Online Monitoring Program to Technical Specification 5.52024-05-0303 May 2024 Units 1 & 2 and Hatch Nuclear Plant - Units 1 & 2 License Amendment Request to Revise Technical Specification 1.1 and Add Online Monitoring Program to Technical Specification 5.5 NL-24-0088, Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency2024-04-0505 April 2024 Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency ML23076A0502023-03-21021 March 2023 Correction of Amendment Nos. 244 and 241 Issuance of Amendments Regarding Revision to Technical Specifications to Relocate Augmented Piping Inspection Program Details to a License Controlled Document NL-20-0170, Non-Voluntary License Amendment Request: Technical Specification Revision to Adopt WCAP-17661-P-A, Improved RAOC2022-10-14014 October 2022 Non-Voluntary License Amendment Request: Technical Specification Revision to Adopt WCAP-17661-P-A, Improved RAOC NL-22-0289, License Amendment Request to Revise Technical Specification 4.3 Fuel Storage to Correct Tabulated Values from the Associated Spent Fuel Pool (SFP) Criticality Analysis2022-09-21021 September 2022 License Amendment Request to Revise Technical Specification 4.3 Fuel Storage to Correct Tabulated Values from the Associated Spent Fuel Pool (SFP) Criticality Analysis NL-21-0925, Adoption of TSTF-269-A, Revision 2, Allow Administrative Means of Position Verification for Locked or Sealed Valves2021-12-22022 December 2021 Adoption of TSTF-269-A, Revision 2, Allow Administrative Means of Position Verification for Locked or Sealed Valves NL-21-1017, License Amendment Request to Revise Technical Specification 5.5.17, Containment Leakage Rate Testing Program to Increase Calculated Peak Containment Pressure2021-12-13013 December 2021 License Amendment Request to Revise Technical Specification 5.5.17, Containment Leakage Rate Testing Program to Increase Calculated Peak Containment Pressure NL-21-0984, Southern Nuclear Operating Company - Second Supplement to License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, Administrative Controls2021-11-10010 November 2021 Southern Nuclear Operating Company - Second Supplement to License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, Administrative Controls NL-21-0613, Supplement to License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, .2021-06-30030 June 2021 Supplement to License Amendment Request to Revise Technical Specification 5.7, High Radiation Area, . NL-21-0160, License Amendment Request to Remove Table of Contents from Technical Specifications2021-06-22022 June 2021 License Amendment Request to Remove Table of Contents from Technical Specifications NL-19-1063, Units 1 and 2 and Vogtle Electric Generating Plant, Units 1 and 2 - Application to Revise Technical Specifications to Adopt TSTF-569, Revise Response Time Testing Definition2019-12-10010 December 2019 Units 1 and 2 and Vogtle Electric Generating Plant, Units 1 and 2 - Application to Revise Technical Specifications to Adopt TSTF-569, Revise Response Time Testing Definition NL-19-0221, Risk-Informed Technical Specifications Initiative 4b, Risk-Managed Technical Specifications, SNC Response to NRC Request for Additional Information (RAI)2019-05-0303 May 2019 Risk-Informed Technical Specifications Initiative 4b, Risk-Managed Technical Specifications, SNC Response to NRC Request for Additional Information (RAI) ML18226A0942018-08-0909 August 2018 Edwin I. Hatch, Units 1 and 2; and Vogtle, Units 1 and 2 - License Amendment Request to Revise Technical Specification 5.2.2.g and Update Emergency Plan Minimum On-shift Staff Tables NL-17-2095, Supplement Submittal of Corrected Technical Specification Definition of Iodine 1-131 for the Ast. TSTF-448 and TSTF-312 Amendment Package2017-12-18018 December 2017 Supplement Submittal of Corrected Technical Specification Definition of Iodine 1-131 for the Ast. TSTF-448 and TSTF-312 Amendment Package NL-16-1026, Units 1 & 2, Vogtle Electric Generating Plant- Units 1 & 2 - Application to Revise Technical Specifications to Adopt TSTF-547, Clarification of Rod Position Requirements2016-11-21021 November 2016 Units 1 & 2, Vogtle Electric Generating Plant- Units 1 & 2 - Application to Revise Technical Specifications to Adopt TSTF-547, Clarification of Rod Position Requirements NL-15-0421, J. M. Farley, Units 1 and 2 - License Amendment Request to Revise Technical Specifications Regarding Generic Letter 2008-01, Managing Gas Accumulation in Accordance with TSTF-523, Revision 2, Using the Consolidated Line Item Improvement P2015-05-12012 May 2015 J. M. Farley, Units 1 and 2 - License Amendment Request to Revise Technical Specifications Regarding Generic Letter 2008-01, Managing Gas Accumulation in Accordance with TSTF-523, Revision 2, Using the Consolidated Line Item Improvement Pro NL-14-0635, License Amendment Request to Revise Technical Specifications Reactor Trip System Instrumentation2014-06-0303 June 2014 License Amendment Request to Revise Technical Specifications Reactor Trip System Instrumentation NL-12-0346, Exigent Technical Specification Revision Request for TS 3.5.4 Refueling Water Storage Tank (RWST)2012-02-20020 February 2012 Exigent Technical Specification Revision Request for TS 3.5.4 Refueling Water Storage Tank (RWST) NL-11-1057, License Amendment Request for Technical Specification Table 3.3.1-12011-09-0909 September 2011 License Amendment Request for Technical Specification Table 3.3.1-1 NL-09-1644, Emergency Technical Specification (TS) Revision Request Regarding TS 3.7.8, Service Water System (SWS)2009-10-0808 October 2009 Emergency Technical Specification (TS) Revision Request Regarding TS 3.7.8, Service Water System (SWS) NL-09-0154, Request to Revise Technical Specifications to Delete Reactor Trip System, Function 11, Reactor Coolant Pump Breaker Position2009-03-30030 March 2009 Request to Revise Technical Specifications to Delete Reactor Trip System, Function 11, Reactor Coolant Pump Breaker Position NL-08-0535, Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using Consolidated Line Item Improvement Process2008-10-0808 October 2008 Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using Consolidated Line Item Improvement Process NL-08-1519, Response to Request for Information Regarding Revision to Technical Specifications 3.3.1, 3.3.2, 3.3.6, 3.3.7, and 3.3.82008-10-0808 October 2008 Response to Request for Information Regarding Revision to Technical Specifications 3.3.1, 3.3.2, 3.3.6, 3.3.7, and 3.3.8 ML0611504462006-04-14014 April 2006 Technical Specifications, Revise TS Section 5.5.6, Pre-Stressed Concrete Containment Tendon Surveillance Program, for Consistency with the Requirements of 10 CFR 50.55a(g)(4) for Components Classified as Code Class CC NL-05-0856, Request to Revise Technical Specifications Regarding Mode Change Limitations Using the Consolidated Line Item Improvement Process2005-11-0202 November 2005 Request to Revise Technical Specifications Regarding Mode Change Limitations Using the Consolidated Line Item Improvement Process NL-05-0740, Submittal of Joseph M. Farley Nuclear Plant, Technical Specifications Revision Spent Fuel Cask Loading Requirements2005-05-17017 May 2005 Submittal of Joseph M. Farley Nuclear Plant, Technical Specifications Revision Spent Fuel Cask Loading Requirements ML0512300672005-04-22022 April 2005 Enclosure, Correction Ltr. on Amendment Nos. 167 & 159 for Elimination of Hydrogen Recombiners and Monitors (Tac No. MC3224, MC3225) ML0507303042005-03-0808 March 2005 Enclosure, Amendment 168 & 160, TS Revision on 5.6 Reporting Requirements NL-03-2454, Exigent Technical Specification Revision Request Regarding Electrical Power Systems AC Sources - Operating2003-12-0303 December 2003 Exigent Technical Specification Revision Request Regarding Electrical Power Systems AC Sources - Operating NL-03-1914, Request for Technical Specification Changes Regarding DC Sources - Operating2003-09-19019 September 2003 Request for Technical Specification Changes Regarding DC Sources - Operating NL-03-1470, Withdrawal of Request for Technical Specification Changes Deletion of LCO 3.6.1, Condition a and Addition of LCO 3.0.8, Inoperability of Non-Technical Specification Support Systems2003-08-18018 August 2003 Withdrawal of Request for Technical Specification Changes Deletion of LCO 3.6.1, Condition a and Addition of LCO 3.0.8, Inoperability of Non-Technical Specification Support Systems NL-03-0779, Request for Revise TS Control Room Emergency Filtration/Pressurization System & Penetration Room Filtration System - Revision 12003-05-20020 May 2003 Request for Revise TS Control Room Emergency Filtration/Pressurization System & Penetration Room Filtration System - Revision 1 ML0202402792002-01-0404 January 2002 Units 1 & 2, Technical Specifications 2024-05-03
[Table view] |
Text
J. Barnie Beasley, Jr, P.E. Southern Nuclear Vice President Operating Company. Inc.
40 Inverness Center Parkway Post Office Box 1295 Birmingham, Alabama 35201 Tel 205.992.7110 Fax 205.992.0341 SOUTHERNNI COMPANY September 19, 2003 Energy to Serve MAN o YoUTWoTUSU Docket No.: 50-348 NL-03-1914 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Joseph M. Farley Nuclear Plant - Unit I Request for Technical Specification Changes DC Sources - Operating Ladies and Gentlemen:
In accordance with the requirements of 10 CFR 50.90, Southern Nuclear Operating Company (SNC) proposes to amend the Farley Nuclear Plant (FNP) Unit 1 Technical Specifications (TS), Appendix A to Operating License NPF-2. The proposed changes would revise TS Limiting Conditions for Operation (LCO) 3.8.4, "DC Sources -
Operating," for Unit 1 for the remainder of operating cycle 19. Cycle 19 is presently scheduled to end on October 2, 2004.
The proposed changes would increase the Completion Time for the B Auxiliary Building DC electrical power subsystem inoperability due to an inoperable battery to allow for on-line replacement of individual cells. The B battery bank is reaching the end of its useful life and there are plans to replace it during the next Unit 1 refueling outage.
FNP has experienced a failure of a battery cell, and initial evaluation of the failure indicates that it is due to aging. Other cells within the battery bank have similar indications of aging. provides a basis for the proposed changes. Enclosure 2 provides the basis for a determination that the proposed changes do not involve a significant hazards consideration pursuant to 10 CFR 50.92. Marked-up TS and TS Bases pages are provided in Enclosure 3, and clean-typed pages are provided in Enclosure 4. The TS Bases changes are submitted for information only and will be approved in accordance with the Farley TS Bases Control Program.
SNC has reviewed the proposed amendment pursuant to 10 CFR 50.92 and determined that it does not involve a significant hazards consideration. In addition, there is no significant increase in the amounts of effluents that may be released offsite, and there is no significant increase in individual or cumulative occupational radiation exposure.
Consequently, the proposed amendment satisfies the criteria of 10 CFR 51.22 for categorical exclusion from the requirements for an environmental assessment, and the human environment is not affected by this amendment.
U. S. Nuclear Regulatory Commission NL-03-19 14 Page 2 SNC requests approval of the proposed changes by December 31, 2003. A copy of the proposed changes has been sent to Dr. D. E. Williamson, the Alabama State Designee, in accordance with 10 CFR 50.9 1(b)(1).
Mr. J. B. Beasley, Jr. states he is a Vice President of Southern Nuclear Operating Company, is authorized to execute this oath on behalf of Southern Nuclear Operating Company and to the best of his knowledge and belief, the facts set forth in this letter are true.
This letter contains no NRC commitments. If you have any questions, please advise.
Respectfully submitted, NUCLEAR OPERATING COMPANY Sworn to and subscribedbefore me this lday of +4~;4 , 2003.
- Notary Pub My commission expires:
JBB/WAS/sdl
Enclosures:
- 1. Basis for the TS Change
- 2. 10 CFR 50.92 Evaluation
- 3. Marked-Up Technical Specification and TS Bases Pages
- 4. Clean Typed Technical Specification and TS Bases Pages cc: Southern Nuclear Operating Com=anv Mr. J. D. Woodard, Executive Vice President w/o Enclosures Mr. L. M. Stinson, General Manager - Farley Mr. D. E. Grissette, General Manager - Plant Farley Document Services RTYPE: CFA04.054; LC# 13841 U. S. Nuclear Regulatory Commission Mr. L. A. Reyes, Regional Administrator Mr. F. Rinaldi, NRR Project Manager - Farley Mr. T. P. Johnson, Senior Resident Inspector - Farley Alabama Department of Public Health Dr. D. E. Williamson, State Health Officer
Enclosure 1 Joseph M. Farley Nuclear Plant - Unit 1 Request for Technical Specification Changes DC Sources - Operating Basis for the TS Change
Enclosure 1 Joseph M. Farley Nuclear Plant - Unit 1 Request for Technical Specification Changes DC Sources - Operating Basis for the TS Change Proposed Chances Southern Nuclear Operating Company (SNC) proposes to revise the Farley Nuclear Plant (FNP) Unit 1 Technical Specifications (TSs) for the remainder of operating cycle 19. The proposed changes would revise TS Limiting Condition for Operation (LCO) 3.8.4, "DC Sources - Operating," for Unit 1 only.
The Completion Time for the 1B Auxiliary Building DC electrical power subsystem inoperability due to an inoperable battery is proposed to be changed. Condition A of LCO 3.8.4 currently requires restoration of an inoperable Auxiliary Building DC electrical power subsystem to operable status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
The B battery bank is reaching the end of its useful life and there are plans to replace it during the next Unit 1 refueling outage. FNP has experienced a failure of a battery cell and initial evaluation of the failure indicates that it is due to aging. Other cells within the battery bank have similar indications of aging. The proposed change provides a new Completion Time for the 1B Auxiliary Building DC electrical power subsystem on Unit 1 which extends the Completion Time from 2 to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for the remainder of cycle 19 for inoperability due to an inoperable battery.
Background
The existing FNP Unit 1 TS LCO 3.8.4, "DC Sources - Operating," specifies DC source operability in terms of DC electrical power subsystems. The 125 VDC electrical power system consists of two main systems, the Auxiliary Building System and the Service Water Intake Structure (SWIS) System with 2 trains (subsystems) in each main system.
The Auxiliary Building 125 VDC system consists of two independent and redundant subsystems (A-Train and B-Train) which supply DC power to various Engineered Safety Features (ESF) systems throughout the plant. Each Auxiliary Building subsystem consists of a 125 VDC battery, an associated full capacity battery charger and all associated control equipment and interconnecting cabling. Each Auxiliary Building 125 VDC train is normally supplied by the associated battery charger (A or B). In the event of an A or B battery charger failure, battery charger C, the full capacity swing battery charger, may supply power to either train. Either train may be considered OPERABLE when supplied from battery charger C. Battery charger C input and output breakers are interlocked to prevent paralleling the redundant DC buses or the AC buses through the battery charger and to prevent cross-connecting trains.
During normal operation, the 125 VDC load is powered from the battery chargers with the batteries floating on the system. In case of loss of normal power to the battery charger, the DC load is automatically powered from the station batteries. In the unlikely event that a battery charger fails, the swing battery charger is manually placed in service.
Basis for TS Change Page 2 of 4 The A-Train and B-Train DC electrical power subsystems provide the control power for its associated Class E AC power load group, 4.16 kV switchgear, 600 V load centers, ESF controls, emergency lights, Emergency Diesel Generator (EDG) field flashing and control, DC solenoids for air-operated valves, miscellaneous controls and alarms, and reactor trip switchgear. The DC electrical power subsystems also provide DC electrical power to the inverters, which in turn power the AC vital buses. DC bus 1A supplies primary power for TS static inverters 1A and 1B, while DC bus B supplies primary power for TS inverters C and D.
The A-Train EDGs for FNP (lC and 1-2A) support both units and as such, the control panel for each Diesel Generator (DG) receives DC power from Unit 1 A-Train DC and Unit 2 A-Train DC through power seeking automatic transfer switches (ATSs). This ensures that an operable DC power supply is available for the A-Train DGs.
The B-train EDGs for FNP are unit specific (Unit 1- 1B, Unit 2 - 2B.) The control panel for each DG receives DC power from its respective Unit's B-Train DC system.
The Station Blackout (SBO) DG for FNP (2C) is B-Train and supports both units. As such, the control panel for the DG receives DC power from Unit 1 B-Train DC and Unit 2 B-Train DC through power seeking automatic transfer switches (ATSs). This ensures that an operable DC power supply is available at all times to the SBO D.
The Auxiliary Building batteries are stationary type consisting of 60 individual lead-calcium cells electrically connected in series to establish a nominal 125 VDC power supply. Initially, during a Loss of Offsite Power (LOSP) or LOSP with Safety Injection (S), the Auxiliary Building batteries supply safety-related loads without charger support.
The design is such that subsequent to LOSP, the battery chargers are re-energized by the EDGs.
Per the TS Bases, an operable Auxiliary Building DC electrical power subsystem must include a battery, a battery charger, and the corresponding control equipment and interconnecting cabling supplying power to the associated bus within the train.
Bases for Proposed Changes The B battery bank is reaching the end of its useful life and there are plans to replace it during the next Unit 1 refueling outage. FNP has experienced a failure of a battery cell and initial evaluation of the failure indicates that it is due to aging. Other cells within the battery bank have similar indications of aging.
The proposed change would increase the Completion Time for the 1B Auxiliary Building DC electrical power subsystem inoperability due to an inoperable battery. The Required Action is to restore the 1B Auxiliary Building DC electrical power subsystem to operable status and the Completion Time is 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. Presently, if the battery is inoperable, or if maintenance such as cell replacement is required, the 2-hour Completion Time is severely restrictive. Allowing 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for maintenance on the battery will facilitate a more orderly and effective work process. It will also minimize the potential for an additional shutdown/restart transient to comply with the TS in order to accomplish the required maintenance.
Basis for TS Change Page 3 of 4 At FNP, a failure of a single Auxiliary Building 125 VDC system will not result in conditions that will prevent the safe shutdown of the unit. Procedures are in place to respond to a complete loss of a train of DC power and maintain the capability to respond to design basis events, excluding a single failure due to the time-limited Condition.
For this condition, a dual unit LOSP with a SI on Unit 1 would be the most limiting accident condition. If this event occurred while a Unit I Auxiliary Building battery was unavailable, the opposite train of emergency power would start and sequence on the SILOSP loads. With the battery unavailable, field flashing to the B EDG is not assured.
In that circumstance, proceduralized operator action would allow emergency power to be supplied to Unit 1 from the SBO DG for LOSP loads. Field flashing for the SBO DG may be supplied by either unit.
Risk insights were also considered in this proposed TS amendment request. The Plant Farley-specific Level 1 and Level 2 Probabilistic Risk Assessment (PRA) Model, Revision 5, was used to evaluate the change in the Farley internal events Core Damage Frequency (CDF) and Large Early Release Frequency (LERF) resulting from the unavailability of the B Auxiliary Building battery for a period of 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. This model, when used in conjunction with deterministic evaluations, is of sufficient quality to support regulatory applications such as this submittal, as described below. The associated PRA calculations performed as part of the development of this submittal were originated, verified, approved and documented in accordance with SNC procedures for the preparation and control of calculations.
As an integral part of its initial development pursuant to NRC Generic Letter 88-20, "Individual Plant Examination for Severe Accident Vulnerabilities," the Farley PRA was reviewed by an Independent Review Group which included experts in plant design, plant operation, and probabilistic risk assessment. Further, each subsequent revision to the model has been internally reviewed and approved in accordance with applicable SNC procedures. In addition, an evaluation based upon Appendix B of the EPRI PSA Applications Guide was performed to confirm that the PRA conforms to the industry state-of-the-art practices with respect to the scope of potential plant scenarios.
In August 2001, the Revision 4 Farley PRA was extensively reviewed by an experienced five-man Peer Review Team coordinated by the Westinghouse Owners Group in a manner described in the Nuclear Energy Institute's document NEI 00-02, "Industry Peer Review Process." The peer review evaluated the eleven elements of the PRA and concluded that all elements were either a "Grade 3" or a "Contingency Grade 3." None of the items resulting in the assignment of a "Contingency Grade 3" rating to an element were judged to be of a level of significance to require prompt resolution to ensure the technical adequacy of the PRA.
The evaluation performed indicated that the incremental conditional core damage probability (CCDP) for a 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> battery outage is 3.424E-07 and the incremental conditional large early release probability (ICLERP) is 6.575E-1 1. These values are acceptable when compared to the acceptance criteria of ICCDP less than 5.0E-07 and ICLERP less than 5.0E-08 provided in NRC Regulatory Guide 1.177, An Approach for Plant-Specific. Risk-Informed Decisionmaking: Technical Specifications. This change would also be classified as "very small" when compared to the acceptance guidelines of Basis for TS Change Page 4 of 4 NRC Regulatory Guide 1.174, An Approach for Using Probabilistic Risk Assessments in Risk-Informed Decision-making.
There is reasonable assurance that risk-significant plant equipment configurations will not occur when the B battery is out of service (OOS) consistent with the proposed TS change. Increases in risk posed by potential combinations of equipment OOS will be managed under the site procedures.
FNP's configuration risk management program is governed by procedure FNP-0-ACP-52.1, "Guidelines for Scheduling of On-Line Maintenance," which ensures that on-line risk is appropriately evaluated prior to performing any maintenance activity. This program provides guidance for managing plant trip risk, probabilistic risk, and safety function degradation from on-line maintenance, external or internal conditions, as required by 10 CFR 50.65(a)(4) of the Maintenance Rule. The procedure addresses risk management practices in the maintenance planning and maintenance execution phases for Modes 1 through 3.
Therefore, the proposed extended Completion Time for an inoperable B battery is acceptable based on the available redundancy, defense-in-depth provided by the SBO DG, and the fact that the acceptance criteria of RGs 1.174 and 1.177 are met due to the very small impact on risk.
Conclusion The B battery bank is reaching the end of its useful life and there are plans to replace it during the next Unit 1 refueling outage. FNP has experienced a failure of a battery cell and initial evaluation of the failure indicates that it is due to aging. Other cells within the battery bank have similar indications of aging. Requiring a unit shutdown is not warranted when corrective maintenance such as replacement of a battery cell cannot be accomplished within a 2-hour window. The proposed TS change modifies the Completion Time for Condition A of LCO 3.8.4 such that a Unit 1 B Auxiliary Building DC electrical power subsystem may be inoperable for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> before beginning an orderly shutdown of the unit. This change is applicable to Unit 1 only for the remainder of operating cycle 19.
Enclosure 2 Joseph M. Farley Nuclear Plant - Unit 1 Request for Technical Specification Changes DC Sources - Operating 10 CFR 50.92 Evaluation
Enclosure 2 Joseph M. Farley Nuclear Plant - Unit 1 Request for Technical Specification Changes DC Sources - Operating 10 CFR 50.92 Evaluation Proposed Changes Southern Nuclear Operating Company (SNC) proposes to revise the Farley Nuclear Plant (FNP) Unit 1 Technical Specifications (TS) for the remainder of operating cycle 19. The proposed changes would revise TS Limiting Condition for Operation (LCO) 3.8.4, "DC Sources - Operating," for Unit 1 only.
These changes are needed to address required maintenance on aging battery cells. The Completion Time for the B Auxiliary Building DC electrical power subsystem inoperability due to an inoperable battery is proposed to be changed.
Evaluation Pursuant to 10 CFR 50.92, SNC has evaluated the proposed amendment and has determined that operation of the facility in accordance with the proposed amendment would not involve a significant hazards consideration. The basis for this determination is as follows:
- 1. The proposed changes do not involve a significant increase in the probability or consequences of an accident previously evaluated.
The proposed change to LCO 3.8.4 creates an extended Completion Time for an inoperable B Auxiliary Building DC electrical power subsystem due to an inoperable battery on Unit 1 only for the remainder of operating cycle 19. The Auxiliary Building battery is not a direct initiator of any analyzed accident sequence. The radiological consequences of any associated accidents are not impacted by the proposed amendment. Therefore, the proposed amendment does not involve a significant increase in the probability or consequences of an accident previously evaluated.
- 2. The proposed changes do not create the possibility of a new or different kind of accident from any accident previously evaluated.
The proposed change involves no change to the physical plant. It allows additional time for corrective maintenance on the B Auxiliary Building battery on Unit 1. The proposed amendment involves an extension of a previously determined acceptable mode of operation. The proposed amendment does not introduce any new equipment, create new failure modes for existing equipment, or create any new limiting single failures. Therefore, the proposed amendment does not create the possibility of a new or different kind of accident from any accident previously evaluated.
- 3. The proposed changes do not involve a significant reduction in a margin of safety.
The physical plant is unaffected by these changes. The proposed changes do not impact accident offsite dose, containment pressure or temperature, emergency core cooling system (ECCS) or reactor protection system (RPS) settings or any other parameter that could affect a margin of 10 CFR 50.92 Evaluation Page 2 of 2 safety. Under the proposed amendment, the unit will continue to be operated in a condition that will ensure that emergency power will be available as needed. The extended Completion Time for an inoperable battery has been shown to have a very small impact on plant risk using the criteria of Regulatory Guides 1.174, An Approach for Using Probabilistic Risk Assessments in Risk-Informed Decision-making and 1.177, An Approach for Plant-Specific. Risk-Informed Decisionmaking: Technical Specifications and is acceptable. Therefore, the proposed amendment does not involve a significant reduction in a margin to safety.
Conclusion Based on the preceding analysis, SNC has determined that the proposed changes to the Technical Specifications will not significantly increase the probability or consequences of an accident previously evaluated, create the possibility of a new or different kind of accident from any accident previously evaluated, or involve a significant reduction in a margin of safety. SNC therefore concludes that the proposed changes meet the requirements of 10 CFR 50.92(c) and do not involve a significant hazards consideration.
Enclosure 3 Joseph M. Farley Nuclear Plant - Unit 1 Request for Technical Specification Changes DC Sources - Operating Marked-UP Technical Specification and Bases Pages Affected Pages 3.8.4-1 B 3.8.4-5
DC Sources-Operating 3.8.4 3.8 ELECTRICAL POWER SYSTEMS 3.8.4 DC Sources -Operating LCO 3.8.4 The Train A and Train B Auxiliary Building and Service Water Intake Structure (SWIS) DC electrical power subsystems shall be OPERABLE.
APPLICABILITY: MODES 1, 2,3, and 4.
I[INERTA ACTIONS CONDITION REQUIRED ACTION COMPLETIO TIME A. One Auxiliary Building DC A.1 Restore the Auxiliary 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> electrical power subsystem Building DC electrical inoperable. power subsystem to OPERABLE status.
B. One Auxiliary Building DC B.1 Restore the battery 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> electrical power subsystem connection resistance to with battery connection within limit.
resistance not within limit.
C. Required Action and C.1 Be in MODE 3. 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition A or B AND not met.
C.2 Be in MODE 5. 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> D. One required SWIS DC D.1 Restore the battery 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> electrical power connection resistance to subsystem battery within the limit.
connection resistance not within limit.
E. One required SWIS DC E.1 Declare the associated Immediately electrical power subsystem Service Water System inoperable. train inoperable.
OR Required Action and associated Completion Time of Condition D not met.
Farley Units 1 and 2 3.8.4-1 Amendment No. 146 (Unit 1)
Amendment No. 137 (Unit 2)
INSERT A 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for B Auxiliary Building DC electrical power subsystem inoperable due to inoperable battery for cycle 19 only
DC Sources -Operating B 3.8.4 l INSERT B BASESII ACTIONS A.1 Condition A represents one train of Auxiliary Building DC electrical power with a loss of ability to completely respond to an event, and a potential loss of ability to remain energized during normal operation.
It is, therefore, imperative that the operators attention focus on stabilizing the unit, minimizing the potential for complete loss of DC power to the affected train. The 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> limit is consistent with the allowed time for an inoperable DC distribution system train.
If one of the required DC electrical power subsystems is inoperable (e.g., inoperable battery, inoperable battery charger(s), or inoperable battery charger and associated inoperable battery), the remaining DC electrical power subsystem has the capacity to support a safe shutdown and to mitigate an accident condition. Since a subsequent worst case single failure would, however, result in the complete loss of the remaining 125 VDC electrical power subsystems with attendant loss of ESF functions, in the case of the Auxiliary Building DC power subsystem, continued power operation should not exceed 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
The 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> Completion Time is based on Regulatory Guide 1.93 (Ref. 8) and reflects a reasonable time to assess unit status as a function of the inoperable DC electrical power subsystem and, if the Auxiliary Building DC electrical power subsystem is not restored to OPERABLE status, to prepare to effect an orderly and safe unit shutdown.
B.1 and D.1 Conditions B and D represent one Auxiliary Building or SWIS DC electrical power subsystem with connection resistance not within the specified limit. Consistent with the guidance in IEEE-450, connection resistance not within the limit is an indication that the affected battery requires attention to restore the resistance to within the limit but is not a basis on which to declare the battery inoperable. Therefore, the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Completion Time allowed to restore the battery connection resistance to within the required limit is a reasonable time considering that variations In connection resistance do not mean the battery is incapable of performing its required safety function, but is an indication that the battery requires maintenance.
(continued)
Farley Units 1 and 2 B 3.8.4-5 Revision 0
INSERT B
[For Unit 1 only for cycle 19] The second Completion time for Condition A represents the 1B train of Auxiliary Building DC electrical power subsystem due to an inoperable battery. With the 1B Auxiliary Building battery inoperable, the DC bus is being supplied by the OPERABLE battery charger. Any event that results in a loss of the AC bus supporting the battery charger will also result in the loss of DC to that train. Recovery of the AC bus, especially if it is due to a loss of offsite power, will be hampered by the fact that many of the components necessary for the recovery (e.g., diesel generator control and field flash, AC load shed and diesel generator output breakers, etc.) rely upon the battery. The 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> limit allows sufficient time to effect restoration of the inoperable battery given that the majority of the conditions that lead to battery inoperability (e.g., loss of battery charger, battery cell voltage less than 2.02 volts, etc.) are identified in Specifications 3.8.4, 3.8.5, and 3.8.6 together with additional specific completion times.
Enclosure 4 Joseph M. Farley Nuclear Plant - Unit 1 Request for Technical Specification Changes DC Sources - Operating Clean Typed Technical Specification and Bases Pages Affected Pages 3.8.4-1 B 3.8.4-5 B 3.8.4-6 B 3.8.4-7 B 3.8.4-8 B 3.8.4-9 B 3.8.4-10 B 3.8.4-11
DC Sources -Operating 3.8.4 3.8 ELECTRICAL POWER SYSTEMS 3.8.4 DC Sources -Operating LCO 3.8.4 The Train A and Train B Auxiliary Building and Service Water Intake Structure (SWIS) DC electrical power subsystems shall be OPERABLE.
APPLICABILITY: MODES 1, 2,3, and 4.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One Auxiliary Building DC A.1 Restore the Auxiliary 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> electrical power subsystem Building DC electrical 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for 1B inoperable. power subsystem to Auxiliary Building DC OPERABLE status. electrical power subsystem inoperable due to inoperable battery for cycle 19 only B. One Auxiliary Building DC B.1 Restore the battery 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> electrical power subsystem connection resistance to with battery connection within limit.
resistance not within limit.
C. Required Action and C.1 Be in MODE 3. 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition A or B AND not met.
C.2 Be in MODE 5. 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> D. One required SWIS DC D.1 Restore the battery 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> electrical power connection resistance to subsystem battery within the limit.
connection resistance not within limit.
E. One required SWIS DC E.1 Declare the associated Immediately electrical power subsystem Service Water System inoperable. train Inoperable.
OR Required Action and associated Completion Time of Condition D not met.
Farley Units 1 and 2 3.8.4-1 Amendment No. (Unit 1)
Amendment No. 137 (Unit 2)
DC Sources -Operating B 3.8.4 BASES ACTIONS A.1 Condition A represents one train of Auxiliary Building DC electrical power with a loss of ability to completely respond to an event, and a potential loss of ability to remain energized during normal operation.
It is, therefore, imperative that the operator's attention focus on stabilizing the unit, minimizing the potential for complete loss of DC power to the affected train. The 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> limit is consistent with the allowed time for an inoperable DC distribution system train.
[For Unit 1 only for cycle 19] The second Completion time for Condition A represents the 1B train of Auxiliary Building DC electrical power subsystem due to an inoperable battery. With the 1B Auxiliary Building battery inoperable, the DC bus is being supplied by the OPERABLE battery charger. Any event that results in a loss of the AC bus supporting the battery charger will also result in the loss of DC to that train. Recovery of the AC bus, especially if it is due to a loss of offsite power, will be hampered by the fact that many of the components necessary for the recovery (e.g., diesel generator control and field flash, AC load shed and diesel generator output breakers, etc.) rely upon the battery. The 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> limit allows sufficient time to effect restoration of the inoperable battery given that the majority of the conditions that lead to battery inoperability (e.g., loss of battery charger, battery cell voltage less than 2.02 volts, etc.) are identified in Specifications 3.8.4, 3.8.5, and 3.8.6 together with additional specific completion times.
If one of the required DC electrical power subsystems is inoperable (e.g., inoperable battery, inoperable battery charger(s), or inoperable battery charger and associated inoperable battery), the remaining DC electrical power subsystem has the capacity to support a safe shutdown and to mitigate an accident condition. Since a subsequent worst case single failure would, however, result in the complete loss of the remaining 125 VDC electrical power subsystems with attendant loss of ESF functions, in the case of the Auxiliary Building DC power subsystem, continued power operation should not exceed 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
The 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> Completion Time is based on Regulatory Guide 1.93 (Ref. 8) and reflects a reasonable time to assess unit status as a function of the inoperable DC electrical power subsystem and, if the Auxiliary Building DC electrical power subsystem is not restored to OPERABLE status, to prepare to effect an orderly and safe unit shutdown.
(continued)
Farley Units 1 and 2 B 3.8.4-5 Revision
DC Sources -Operating B 3.8.4 BASES ACTIONS B.1 and D.1 (continued)
Conditions B and D represent one Auxiliary Building or SWIS DC electrical power subsystem with connection resistance not within the specified limit. Consistent with the guidance in IEEE-450, connection resistance not within the limit is an ndication that the affected battery requires attention to restore the resistance to within the limit but is not a basis on which to declare the battery inoperable. Therefore, the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Completion Time allowed to restore the battery connection resistance to within the required limit is a reasonable time considering that variations in connection resistance do not mean the battery is incapable of performing its required safety function, but is an indication that the battery requires maintenance.
C.1 and C.2 If the inoperable Auxiliary Building DC electrical power subsystem cannot be restored to OPERABLE status or the connection resistance restored to within the limit within the required Completion Time, the unit must be brought to a MODE in which the LCO does not apply. To achieve this status, the unit must be brought to at least MODE 3 within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and to MODE 5 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. The allowed Completion Times are reasonable, based on operating experience, to reach the required unit conditions from full power conditions in an orderly manner and without challenging plant systems. The Completion Time to bring the unit to MODE 5 is consistent with the time required in Regulatory Guide 1.93 (Ref. 8).
E.1 If a required SWIS DC electrical power subsystem is inoperable or the connection resistance is not restored to within the limit and the associated Completion Time has expired, the Service Water System train supported by the affected SWIS DC electrical power subsystem must be declared inoperable. The capability of the affected SWIS DC electrical power subsystem to fully support the associated train of Service Water is not assured. Therefore, consistent with the definition of OPERABILITY, the associated train of Service Water must be declared inoperable immediately, thereby limiting operation in this condition to the Completion Time associated with the affected Service Water System train.
Farley Units 1 and 2 B 3.8.4-6 Revision
DC Sources -Operating B 3.8.4 BASES SURVEILLANCE SR 3.8.4.1 REQUIREMENTS Verifying battery terminal voltage while on float charge for the batteries helps to ensure the effectiveness of the charging system and the ability of the batteries to perform their intended function. Float charge is the condition in which the charger is applying a voltage to the battery to maintain it in a fully charged condition during normal operation. The float voltage of 2.2 V per cell or 132 V overall is higher than the nominal design voltage of 125 V and is consistent with the manufacturer's recommendations for maintaining a full charge.
Verifying that terminal voltage is 2 127.8 V provides assurance that the average of all cell voltages is maintained greater than 2.13 V.
Maintaining float voltage at the higher value of 2.2 V per cell prolongs cell life expectancy. The 7 day Frequency is consistent with IEEE-450 (Ref. 9).
SR 3.8.4.2 Visual inspection to detect excessive corrosion on the battery terminals or connectors, or measurement of the post to post resistance of these items provides an indication of the need for cleaning and/or retorqueing.
The Surveillance Frequency for these inspections, which can detect conditions that can cause power losses due to resistance heating, is 92 days. This Frequency is considered acceptable based on operating experience related to detecting corrosion trends.
SR 3.8.4.3 Visual inspection of the battery cells, cell plates, and battery racks provides an indication of physical damage or abnormal deterioration that could potentially degrade battery performance. The presence of physical damage or deterioration does not necessarily represent a failure of this SR, provided an evaluation determines that the physical damage or deterioration does not affect the OPERABILITY of the battery (its ability to perform its design function).
The 18 month frequency for this SR is sufficient to detect abnormal deterioration and has been shown to be adequate by operating experience.
(continued)
Farley Units 1 and 2 B 3.8.4-7 Revision
DC Sources -Operating B 3.8.4 BASES SURVEILLANCE SR 3.8.4.4 and SR 3.8.4.5 REQUIREMENTS (continued) Visual inspection and post to post resistance measurements of battery terminals or connectors provide an indication of the need for cleaning and/or retorqueing. The anticorrosion material is used to help ensure good electrical connections and to reduce terminal deterioration. The visual inspection for corrosion is not intended to require removal of and inspection under each terminal connection. The removal of visible corrosion is a preventive maintenance SR. The presence of visible corrosion does not necessarily represent a failure of this SR provided visible corrosion Is removed during performance of SR 3.8.4.4.
The 18 month frequency for this SR is sufficient to detect abnormal deterioration and has been shown to be adequate by operating experience.
SR 3.8.4.6 This SR requires that each required battery charger be capable of -
supplying 536 amps (Auxiliary Building chargers) and 3 amps (SWIS chargers) at 125 V for 2 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />. These requirements are based on the design capacity of the chargers (Ref. 4). According to Regulatory Guide 1.32 (Ref. 10), the battery charger supply is required to be based on the largest combined demands of the various steady state loads and the charging capacity to restore the battery from the design minimum charge state to the fully charged state, irrespective of the status of the unit during these demand occurrences. The minimum required amperes and duration ensures that these requirements can be satisfied.
The Surveillance Frequency is acceptable, given the unit conditions required to perform the test and the other administrative controls existing to ensure adequate charger performance during these 18 month intervals. In addition, this Frequency is intended to be consistent with expected fuel cycle lengths.
This surveillance is modified by a Note which clarifies that it may be performed in any mode of operation provided certain conditions are met. The design is such that any battery charger may be tested while a spare or redundant battery and/or charger is in service in its place.
The spare or redundant battery and/or charger must be within the 18 month surveillance frequency to maintain the DC subsystem(s) to which they are aligned OPERABLE. This operational flexibility maintains TS OPERABILITY of the applicable battery and DC train while testing the normally aligned charger.
(continued)
Farley Units 1 and 2 B 3.8.4-8 Revision I
DC Sources -Operating B 3.8.4 BASES SURVEILLANCE SR 3.8.4.7 REQUIREMENTS (continued) A battery service test is a special test of battery capability, as found, to satisfy the design requirements (design load profile) of the DC electrical power system. The discharge rate and test length should correspond to the design load profile requirements as specified in Reference 4.
The Surveillance Frequency of 18 months is consistent with the recommendations of Regulatory Guide 1.32 (Ref. 10), which states that the battery service test should be performed during refueling operations or at some other outage, (applicable to Auxiliary Building batteries only) with intervals between tests, not to exceed 18 months.
This SR is modified by three Notes. Note 1 allows the performance of a performance discharge test in lieu of a service test once per 60 months. Note 2 allows the performance of a modified performance discharge test in lieu of a service test at any time.
The modified performance discharge test is a simulated duty cycle consisting of just two rates: the one minute rate published for the battery or the largest current load of the duty cycle, followed by the test rate employed for the performance test, both of which envelop the duty cycle of the service test. Since the ampere-hours removed by a rated one minute discharge represents a very small portion of the battery capacity, the test rate can be changed to that for the performance test without compromising the results of the performance discharge test. The battery terminal voltage for the modified performance discharge test should remain above the minimum battery terminal voltage specified in the battery service test for the duration of time equal to that of the service test.
A modified discharge test is a test of the battery capacity and its ability to provide a high rate, short duration load (usually the highest rate of the duty cycle). This will often confirm the battery's ability to meet the critical period of the load duty cycle, in addition to determining its percentage of rated capacity. Initial conditions for the modified performance discharge test should be identical to those specified for a service test.
The reason for Note 3 is that performing the Surveillance for the Auxiliary Building batteries would perturb the electrical distribution system and challenge safety systems.
(continued)
Farley Units 1 and 2 B 3.8.4-9 Revision
DC Sources -Operating B 3.8.4 BASES SURVEILLANCE SR 3.8.4.8 REQUIREMENTS (continued) A battery performance discharge test is a test of constant current capacity of a battery, after having been in service, to detect any change in the capacity determined by the acceptance test. The test is intended to determine overall battery degradation due to age and usage.
A battery modified performance discharge test is described in the Bases for SR 3.8.4.7. Either the battery performance discharge test or the modified performance discharge test is acceptable for satisfying SR 3.8.4.8. The modified performance discharge test may be used to satisfy SR 3.8.4.8 while simultaneously satisfying the requirements of SR 3.8.4.7 at any time. The performance discharge test may be used to satisfy 3.8.4.8 while simultaneously satisfying the requirements of SR 3.8.4.7 once per 60 months.
The acceptance criteria for this Surveillance are consistent with IEEE-450 (Ref. 9). This reference recommends that the battery be replaced if its capacity is below 80% of the manufacturer's rating. A capacity of 80% shows that the battery rate of deterioration is increasing, even if there is ample capacity to meet the load requirements.
The Surveillance Frequency for this test is normally 60 months. If the battery shows degradation, or if the battery has reached 85% of its expected life or 17 years, whichever comes first, the Surveillance Frequency is reduced to 18 months. Degradation is indicated, according to IEEE-450 (Ref. 9), when the battery capacity drops by more than 10% relative to its capacity on the previous performance test or when it is > 10% below the manufacturer's rating. These Frequencies are consistent with the recommendations in IEEE-450 (Ref. 9).
This SR is modified by a Note. The reason for the Note is that performing the Surveillance for the Auxiliary Building batteries would perturb the electrical distribution system and challenge safety systems.
REFERENCES 1. 10 CFR 50, Appendix A, GDC 17.
- 2. Regulatory Guide 1.6, March 10, 1971.
(continued)
Farley Units 1 and 2 B 3.8.4-1 0 Revision I
DC Sources-Operating B 3.8.4 BASES REFERENCES 3. IEEE-308-1971.
(continued)
- 4. FSAR, Section 8.3.
- 5. None.
- 6. FSAR, Chapter 6.
- 7. FSAR, Chapter 15.
- 8. Regulatory Guide 1.93, December 1974.
- 9. IEEE-450-1980.
- 10. Regulatory Guide 1.32, February 1972.
Farley Units 1 and 2 B 3.8.4-11 Revision I