Text
-
.o Iowa Electric Light and Power Company January 14,1994 NG-944)l41 Mr. John Ik Martin Regional Administrator Region III U.S. Nuclear Regulatory Commission 80i Warrenville Road Lisle,IL 60532-135i Snbject: Duane Arnold Energy Center IbcLet No: 50-331 Operating 1 icense DPR-49 Ikcember 1993 Monthly Operating Report Dear Mr. Martin-Please find enclosed the Duane Amold Energy Center Monthly Operating Report for December 1993. The report has been preixued in accordance with the Fuidelines of NUREG4K)20 and distribution has been made in accordance with DAEC Technical Specifications, Section 6,11.1 c.
Very truly yours, dLLt
{0 Oh David Wilson Plant Superintendent, Nuclear DLW/RBW/cc Enclosures File A-118d ec:
Dir. of Nuclear Reactor Regulation Mr. Dennis Murdock U.S. Nuclear Regulatory Commission Central lov a Power Cooperative Mail Station PI-137 130x 2517 Washington, D.C. 20555 (Orig )
Cedar Rapids,IA 52406 Mr. Robert Pulsifer Mr. William Loveless Project Manager U.S. NRC 1 Whiteflint North I Whitellint North Mail Stop 13H21 Mail Stop 11C14 11555 Rockville Pike 11555 Rockville Pike Rockville, MD 20852 Rock +ille, MD 20852 (2)
Document Control Desk Dr, William A. Jacobs, Jr.
INPO Recordx Center GDS Associates, hic.
I100 Circle 75 Parkway Suite 720 Suite 1500 1850 Parkway Place Atlanta, GA 30339 30M Marietta, GA 30068-8237 Mr Stevellrown Mr. Dale Arends towa State Utilities lloard Corn Belt Power Cooperative Lucas State Office lluilding 130013th Street North Iks Moines,IA 50319 1hunboldt,IA 50548 250002
/gf Mr. Fred Yost DCRC Director, Research Services f
i Utility Data Institute NRC Resident In,spector 1700 K St. NW, Suite 400 9401250249 931231-G
\\
Washington, DC 20006 PDR ADOCK 05000331
!8
.R.
PDR s
Duane Arnoki Dwrgy Center
- 3277 DAEC fload
- Palo. Iowa 32324
- 319M17611
OPERATING DATA REPORT -
DOCKET NO.
30-0331 DATE:
1/14/94
. Unit:
Duane Arnold Engrev Center COMPLETED BY:
Bichard Woodward
- OPERATING STATUS 1.
Unit 'Name: Duane Amolafinergy Center
'2.
Reporting Period: December 1993 3.
Licensed Thermal Power (MWth): 1658 4.
Nameplate Rating (Gross MWe DER): 165.7 (Turbing) 5.
Design Electrical Rating (Net MWe DER): 13]
6.
Maximum Dependable Capacity (Gross MWe MDC): 54_5
-7.
Maximum Dependable Capacity (Net MWe MDC):
115 8.
If Changes Occur in Capacity Ratings (items Number 3 through 7) since the last report, Give Reasons: N/A
- 9.
- Power Level to Which Restricted, if Any (Net MWe): Not Applicablg 10.
Reasons for Restrictions, If Any: Not Applig;@k i
This Month Year-to-Date Cumulative 11.
Ilours in Reporting Period 744.0 8,760.0 165,816.0 12.
Number of flours Reactor Was Critical 744.0 6,963.4 122,944.6 13.
Reactor Reserve Shutdown Ilours -
0.0 0.0 192.8 14.
Ifours Generator On-Line 744.0 6,756.2 119,778.7 15.
Unit Reserve Shutdown flours 0.0 0.0 0.0 16.
Gross Thennal Energy Generated (MWII) 1,224,342.2 10,375,270.5
~ 164.458,564.2 17.
Gross Electrical Energy Generated (MWil) 4 t 5.938.0 3.455.476.0 55,080,385.5 18.
Net E!cetrical Energy Generated (MWil) 392,202.5 3,235,009.1 51,631,662.9 19.
Unit Sersice Factor 100.0 %
77.1 %
72.2 %
20.
Unit Availability Factor 100 0 %
77.1 %
72.2 %
21.
Unit Capacity Factor (Using MDC Net) 102.4 %
71.7 %
61.8 %
22.
Unit Capacity Factor (Using DER Net) 98.0 %
68.6 %
59.2%
23.
Unit Forced Outage Rate 0.0%
1.4%
i1.9%
24.
. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of each): NoneJLeheduled 25.
If Shutdown at End of Report Period, Est. Date of Startup: (Not Applicabic) 1
=
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO: }04)331 DATE: 1/14/94 Unit: panne ArnghlEngray Center COMPLETED 13Y: Riciqid Woodwmd TELEPilONE: (l[9L8517318
'MONTIl December 1993 Average Daily Average Daily Pow:r Level Power Level Da3 (M'Ne-Net)
Day (MWe-Net) 1 530.9 16 529.3 2
532.8 17 528.7 3
531.1 18 529.8 1
464.2 19 530.6 5
531.1 20 530.1 6
530.2 21 531.2 7
530.I 22 532.2 8
531.1 23 526.4 9
528.9 24 53 2.e.
10 530.4 25 531.0 11 532.2 26 532.6 12 530.3 27 531.1 13 528.1 28 529.8 14 494.5 29 529.7 15 528.1 30 528.7 31 531.2 1
1 e
l 1
IEFUELING INFORhiATION.
+
DOCKET NO: 504031 DATE: 1/14/94 Unit: Quane Arnold Enerf,y Center COMPLETED BY: Richard Woodward TELEPHONE: - (319) 851-7318 1.
Narne of facility.
Duane Arnold Energy Center 2.
Scheduled date for next refueling shutdown.
February 1995 3.
Scheduled date for restart following refueling.
Has not been determined 4.
Will refueling or resumption of operation thereafter require a technical specification change or other license amendment?
No 5.
Scheduled date(s) for submitting proposed licensing action and supporting information.'
Not applicable 6.
Important licensing considerations associated with refueling, e.g., new or different fuel design or supplier, unreviewed design or performance analysis methods, significant changes in fuel design, new operating procedures.
No 7.
The number of fuel assemblics (a) in the core,(b) in the spent fuel storage pool a.
368 b.
1280 8.
The present licensed spent fuel pool storage capacity and the size of any increase in licensed storage capacity that has been requested or is planned,in number of fuel assemblies, a.
2050 - Licensed Capacity or b.
1898 under the presently installed storage rack capacity.
c.
3152 requested by RTS#252, submitted March 26,1993 q
9.
The pro,lected date of the last refueling that can he discharged to the spent fuel pool nssuming the present licensed capacity.
a.
2000 Licensed Capacity or b.
1998 under the presently installed storage rack capacity.
1
-1
.x
DOCKETNO: 50-033I DATE: 1/14/94 Unit: Duane Arnold Encrev Center
~~
COMPLETED BY: Richard Woodward TELEPHONE: (319) 851-7318 UNIT SIRTIDOWNS AND POWER REDUCTIONS REPORT MONTH: December 1993 s
(There were no shutdowns or power reductions (greater than 20%) in Decemter.)
Date _
Type Duration Reason Method of Licensee System Comp.
Cause (1)
(Hours)
(2)
Shutting Event Report Code Code Down (4)
(5)
Reactor (3) 1 - F: Forced 2 - Reason:
3 -- Method; 4 - Exhibit G-5: Scheduled A-Equipment Failure (Explain) 1-Manual Instructions for Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee Estnt C-Refueling 3-Automatic Scram
- Report (LER) File (NUREG-0161)
D-Regulatory Restriction 4-Continued E-Ogrator Training & License 5-Reduced Load _
5 - Exhibit i Examination
_ 9-Other (Explain)
(Same Source)
F-Administratist G-Operational Error (Explain)
H-Other (Explain
. - - =
L.
DOCKET NO.: 50-033 t DATE: 1/14/94 Unit: Quane ArnoldEnerny Centqr COMPLETED DY: Richar.43V_ggd1v_ani TELEPilONE: (319) 851-7318 ~
Monthly Operational Overview for December 1993:
The only downpowers during December were to perform a control rod sequence exchange and turbine valve surveillance on December 4, and to perform maintenance on a Reactor Pressure.
l System liigh Drywell Pressure trip relay on December 14.
Production and Loss Statistics for the month:
Electric Capacity Clock i
Output Factor IIours
% of $65.7
- of 744-MWe h12Vg Hours.
Actual Electric Output 559.I 98.8 %
735.3 Weather (gains)/ losses
-4.2
-0.7%
-5.5 Control Rod Movements 2.2 0.4%
2.9 Planned Maintenance 1.2 0.2%
1.6 -
Other Capacity Losses (Avg MWth < 1658) 0.8 0.1% -
1.0 Efficiency Losses (Weather Nonnalized. full power MWe < 565.7)
(2f6
.12%
H7
'l Design Electric Output 565.7
' 100.0% '
744.0:
At 2109 December 14, the plant entered a 30 day Limiting Condition of Operation (LCO) for the "C" Residual llcat Removal system pump due to the pump not' meeting required discharge pressure at rated -
flow during ASME surveillance tests. Maintenance was performed, including replacement of the entire j
~
rotating element, wear rings, and readadjustment of the motor rotor position.- The pump was retested j
and found to be within specification. It was declared operable at 1549 January 10,1994, which was day.
27 of the LCO.
Lksush!aAclign.S.mnma!I Plant Availability:
100.0 %
Unplanned Auto Scrams (w/ Critical) this month:
0-Number of reportable events O Unplanned Auto Scrams (w/ Critical)last 12 months:
1 l
,