57484-EN 57484 - Final Report Notification Pursuant to 10 CFR 21.21 Regarding Limitorque SMB-00 Torque Switch Assemblies
ML25050A042
Person / Time
Site: Beaver Valley, Calvert Cliffs, Mcguire, Catawba, Point Beach, Watts Bar, Sequoyah, River Bend, McGuire  
Issue date: 02/14/2025
From: Van Eyk A
Flowserve US
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LIMDOC-2025-002
Download: ML25050A042 (1)


Text

FLOWSERVE February 14, 2025 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001 Limitorque Actuation LIMDOC-2025-002

Subject:

Final Report Notification Pursuant to 10 CFR 21.21 Regarding Limitorque SMB-00 Torque Switch Assemblies

Reference:

Interim Notification Accession No. ML25006A165 Flowserve hereby submits the enclosed written final notification of the identification of a defect in accordance with the requirements of 1 OCFR 21.21. This report pertains to SMB-00 torque switch assemblies supplied for use in safety related applications. The affected switches were supplied either as replacement parts under Limitorque part# 11501-010 or as original equipment switches contained in new SMB/SB-00 actuators.

The extent of condition investigation of the issue has been completed. Enclosure 1 has been updated to reflect additional information not contained in the interim notification (reference NRC Accession No. ML25006A165).

Should you have any questions regarding this submittal, please contact Chris Shaffer, Global Quality Manager at (434) 258-5074.

~~

~or, Plant Manager Flowserve US Inc.

Enclosures:

1) Final Report Notification Information Page 1 of 5 Final Report Notification Information
1. Reporting Individual Arie van Eyk, Director, Plant Manager Flowserve US Inc.

5114 Woodall Road Lynchburg VA 24502

2. Identification of Basic Components that Contains a Defect The basic components that contain a defect are torque switch assemblies identified by Limitorque part # 11501-010 used exclusively in Limitorque actuator model number and size SMB/SB/SBD-00
3. Identification of the Supplier The torque switch assemblies are manufactured and supplied by Flowserve US Inc.
4. Nature of Defect Description of the Defect During installation of a replacement torque switch into a SMB-00 actuator at Beaver Valley nuclear power station, technicians reported that the roller subassembly which connects the torque switch to the actuator drive train was loose and was easily removed from the torque switch. The condition was identified on a quantity of two torque switches at Beaver Valley NPS. The torque switches were shipped to Beaver Valley NPS from Framatome nuclear parts center.

Investigations by Flowserve indicate that the torque switch assemblies contain a manufacturing error resulting in the torque switch roller pin to be improperly secured in the tripper arm. This condition can potentially result in the roller subassembly becoming detached from the torque switch rendering the torque switch assembly non-functional.

Page 2of s

Safety Hazard Created by the Defect The Limitorque SMB torque switch assembly is certified as a safety related component which is typically wired into the electrical control circuit of the actuator. For valve applications that are torque seated, the primary function of the torque switch is to interrupt control power to the motor control center at the end of valve travel when seating the valve. If the torque switch becomes non-functional, electric power to the motor may be maintained resulting in a motor stall event.

5. Date the Information was Obtained Flowserve was informed of the issue found at Beaver Valley NPS on 11/12/2024.

The affected torque switches were received for inspection on 12/13/2024.

6. Number and Location of the Basic Component Supplied Flowserve's extent of condition investigation has identified a quantity of 75 torque switches supplied to domestic U.S. nuclear power plant customers that are affected.

The torque switches were manufactured between September 29, 2022 and December 3, 2024. Enclosure I details the Flowserve order number, customer name, customer purchase order, end user location and actuator serial number (when applicable) of the affected components.

7. Corrective Action Plan Flowserve is notifying all customers identified in Enclosure I by separate correspondence containing guidance for return of the components for replacement.

Flowserve is also notifying international customers who received torque switches containing the defect.

8. Advice Given to Purchasers or Licensees For affected torque switch assemblies which have been installed and are in-service, either as a replacement part or in a new SMB/SB/SBD-00 actuator assembly, plants are advised to evaluate the potential impact of the reported defect on plant operation and safety related systems. To date, there have been no occurrences of a loss of torque switch function reported to Flowserve on in-service SMB/SB/SBD-00 actuators attributable to this issue.
9. In the case of an early site permit, the entities to whom the early site permit was transferred. Not applicable.

Page 3 of 5

ENCLOSURE 1 Flowserve Order Part Identifier QTY Customer Name Customer PO End User I Location Ship Date Serial Numbers 193798.001 SMB-00/HBC-3 2

Trillium Valves, USA 2046513 Entergy River Bend NGS 7/20/2023 1310618-1310619 193798.001 SMB-00/HBC-3 2

Trillium Valves, USA 2046513 Entergy River Bend NGS 7/25/2023 1310617 & 1310620 193798.003 SMB-00/HBC-3 2

Trillium Valves, USA 2046513 Entergy River Bend NGS 2/17/2023 1310629-1310630 193798.003 SMB-00/HBC-3 2

Trillium Valves, USA 2046513 Entergy River Bend NGS 3/15/2023 1310631-1310632 Constellation Energy 195531.001 SMB-00 1

Framatome Nuclear Parts Center 1022035137 Calvert Cliffs NPP 11/30/2022 1316993 Constellation Energy 195531.002 SMB-00 1

Framatome Nuclear Parts Center 1022035137 Calvert Cliffs NPP 11/30/2022 1316994 Constellation Energy 195682.001 SMB-00 1

Framatome Nuclear Parts Center 1022036273 Calvert Cliffs NPP 8/2/2023 1318552 Constellation Energy 195682.002 SMB-00 1

Framatome Nuclear Parts Center 1022036273 Calvert Cliffs NPP 11/3/2023 1318553 Constellation Energy 195682.003 SMB-00 1

Framatome Nuclear Parts Center 1022036273 Calvert Cliffs NPP 8/2/2023 1318554 196076.001 SMB-00 1

Framatome Nuclear Parts Center 1022038905 Exelon Limerick NGS 10/13/2023 1319236 198666.001 SMB-00 1

Framatome Nuclear Parts Center 1023006495 TVA 6/6/2024 1331847 205552.001 SMB-00 1

Framatome Nuclear Parts Center 1024026973 OPG 10/4/2024 1364731 198483.006 11501-010 10 Framatome Nuclear Parts Center 1023012379 4/3/2023 NIA 201205.001 11501-010 11 Framatome Nuclear Parts Center 1023041178 10/2/2023 NIA 204636.001 11501-010 9

Framatome Nuclear Parts Center 1024025352 7/17/2024 N/A 197749.001 SB-00 1

IMI Critical Engineering LLC 5100479027 Florida Power & Light 1/29/2024 1329043 Page4of5

ENCLOSURE 1 (continued)

Flowserve Order Part Identifier QTY Customer Name Customer PO End User/ Location Ship Date Serial Numbers 192796.001 SMB-00 2

Velan Valve Corp. Williston VT P30006052 OPG Darlington NGS 7/3/2023 1309056-1309057 198089.001 SMB-00 1

Velan Valve Corp. Williston VT P30006936 OPG Darlington NGS 2/1/2024 1330063 198209.001 SMB-00 4

Velan Inc. Montreal P40010642 Bruce Power 2/6/2024 1330480-1330483 Energy Harbor 198314.001 SMB-00/HBC-3 1

Velan Inc. Montreal P10011876 Beaver Valley NPS 4/4/2024 1331530 195668.001 SMB-00 1

Tennessee Valley Authority 7325136 Watts Bar NP 9/11/2023 1318987 195668.002 SMB-00/HBC-2 1

Tennessee Valley Authority 7325136 Watts Bar NP 9/11/2023 1318988 195668.003 SMB-00 1

Tennessee Valley Authority 7325136 Watts Bar NP 9/20/2024 1340908 198617.001 SMB-00 1

Tennessee Valley Authority 7442790 Sequoyah NP 4/12/2024 1331741 200416.001 SMB-00 1

Tennessee Valley Authority 7494583 Sequoyah NP 2/13/2024 1341213 200416.002 SMB-00 1

Tennessee Valley Authority 7494583 Sequoyah NP 2/26/2024 1341214 200416.004 SMB-00 1

Tennessee Valley Authority 7494583 Sequoyah NP 8/14/2024 1341216 200416.005 SMB-00 1

Tennessee Valley Authority 7494583 Sequoyah NP 10/15/2024 1360617 200968.001 SMB-00 1

Tennessee Valley Authority 7509327 Sequoyah NP 10/15/2024 1341888 200968.002 SMB-00 1

Tennessee Valley Authority 7509327 Sequoyah NP 10/15/2024 1341889 201369.001 SMB-00 1

Tennessee Valley Authority 7529807 Sequoyah NP 11/18/2024 1343965 200978.001 SMB-00/H BC-3 1

Duke Energy Corp.

3166623 McGuire NPS 10/29/2024 1343348 200986.001 SMB-00 1

Duke Energy Corp.

3167332 McGuire NPS 8/14/2024 1341850 196898.001 SMB-00 2

Duke Energy Corp.

3153951 Catawba NS 10/16/2023 1322784-1322785 202290.001 11501-010 1

Florida Power & Light 2462421 Point Beach NPP 1/23/2024 N/A 199300.001 SMB-00 2

Flowserve Edward Valve 296127 Bruce Power 11/13/2023 1334418-1334419 199300.002 SMB-00 2

Flowserve Edward Valve 296127 Bruce Power 5/29/2024 1341622-1341623 Pages ofs