MEMORANDUM TO:

Jill Shepherd, Chief Materials Rulemaking and Project Management Branch Division of Rulemaking, Environmental, and Financial Support Office of Nuclear Material Safety and Safeguards FROM:

Yoira K. Diaz Sanabria, Chief Storage and Transportation Licensing Branch Division of Fuel Management Office of Nuclear Material Safety and Safeguards

SUBJECT:

USER NEED FOR RULEMAKING FOR AMENDMENT NO. 13, TO THE NAC INTERNATIONAL, INC. MAGNASTOR STORAGE SYSTEM The following information is being provided to request rulemaking support for the following Division of Fuel Management certification activity to amend Title 10, Code of Federal Regulations (10 CFR) Part 72:

1.

Changes to 10 CFR 72.214 rule text (changes appear in bold):

Certificate Number: 1031.

Initial Certificate Effective Date: February 4, 2009, superseded by Initial Certificate, Revision 1, on February 1, 2016, superseded by Initial Certificate, Revision 2 on October 16, 2023.

Amendment Number 1 Effective Date: August 30, 2010, superseded by Amendment Number 1, Revision 1, on February 1, 2016, superseded by Amendment Number 1, Revision 2, on October 16, 2023.

Amendment Number 2 Effective Date: January 30, 2012, superseded by Amendment Number 2, Revision 1, on February 1, 2016, superseded by Amendment Number 2, Revision 2 on October 16, 2023.

Amendment Number 3 Effective Date: July 25, 2013, superseded by Amendment Number 3, Revision 1, on February 1, 2016, superseded by Amendment Number 3, Revision 2 on October 16, 2023.

Amendment Number 4 Effective Date: April 14, 2015, superseded by Amendment Number 4, Revision 1, on October 16, 2023.

CONTACT:

Nishka Devaser, NMSS/DFM (301) 415-5196 June 18, 2024 Signed by Diaz-Sanabria, Yoira on 06/18/24

J. Shepherd Amendment Number 5 Effective Date: June 29, 2015, superseded by Amendment Number 5, Revision 1, on October 16, 2023.

Amendment Number 6 Effective Date: December 21, 2016, superseded by Amendment Number 6, Revision 1, on October 16, 2023.

Amendment Number 7 Effective Date: August 21, 2017, as corrected (ADAMS Accession No. ML19045A346), superseded by Amendment Number 7, Revision 1, on October 16, 2023.

Amendment Number 8, Effective Date: March 24, 2020, superseded by Amendment Number 8, Revision 1, on October 16, 2023.

Amendment Number 9, Effective Date: December 7, 2020, superseded by Amendment Number 9, Revision 1, on October 16, 2023.

Amendment Number 10, Effective Date: January 18, 2023 Amendment Number 11, Effective Date: October 16, 2023 Amendment Number 12, Effective Date: October 16, 2023 Amendment Number 13, Effective Date: TBD SAR Submitted by: NAC International, Inc.

SAR

Title:

Final Safety Analysis Report for the MAGNASTOR System.

Docket Number: 72-1031.

Certificate Expiration Date: February 4, 2029.

Model Number: MAGNASTOR.

2.

Use the following text for the purpose and scope of the amendment:

By letter dated July 13, 2022 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML22194A908), as supplemented on October 13, 2022, November 30, 2022, June 27, 2023, August 17, 2023, and September 15, 2023 (ADAMS Accession Nos. ML22287A038, ML22321A269, ML23178A225, ML23229A481, and ML23258A233, respectively), NAC International (NAC) submitted an application for Amendment No. 13 to the Model No. MAGNASTOR storage cask. The applicant proposes to:

add a new type of radioactive contents, fuel bearing material (FBM) from the damaged Three Mile Island Unit 2 (TMI-2) reactor to be stored inside the MAGNASTOR transportable storage canister (TSC);

add a new design configuration of the TSC (the FBM TSC) to accommodate the FBM and the new TSC internal components which includes:

reducing closure lid assembly thickness of the FBM TSC and removing the hydrostatic pressure test, adding a new waste basket liner (WBL) (based on the Greater Than Class C Waste WBL) made from stainless steel in lieu of the fuel basket, for the storage of FBM inside the FBM TSC, adding a new debris material container to be used as an operational device to handle and house finer debris; and adding a new segmented tube assembly to define cells for loading, and include concrete with a compressive strength of 6,000 psi for concrete cask number 6 as an alternate to the previously approved 8,000 psi compressive strength.

3.

The proposed certificate of compliance (CoC), technical specifications (TS), and preliminary safety evaluation report (SER) have been placed in ADAMS (see references below) and are available for your use in the rulemaking package. The Division of Fuel Management will designate these documents as Official Agency Records after the Executive Director for Operations has approved the rulemaking package (ML24075A113).

J. Shepherd The Office of the General Counsel has reviewed this memorandum with its referenced documents and has no legal objection to its contents.

Docket No. 72-1031 ADAMS

References:

1. Proposed CoC No. 1031, Amendment No. 13 (ML24075A115)
2. Proposed TS Appendix A (ML24075A116)
3. Proposed TS Appendix B (ML24075A117)
4. Preliminary SER (ML24075A118)

ML24075A113 (pkg), ML24075A114 (Memo), ML24075A115 (CoC), ML24075A116 (TS App A), ML24075A117 (TS App B), ML24075A118 (SER)

OFFICE NMSS/DFM NMSS/DFM NMSS/DFM NMSS/DFM NMSS/DFM NAME NDevaser WWheatley SSamaddar CSydnor JChang DATE 3/15/2024 3/20/2024 3/19/2024 3/22/2024 3/18/2024 OFFICE NMSS/DFM NMSS/DFM NMSS/DFM NMSS/DFM NMSS/DFM NAME JTapp EGoldfeiz JSmith TBoyce DMarcano DATE 3/18/2024 3/15/2024 3/18/2024 3/25/2024 3/24/2024 OFFICE NMSS/DFM NMSS/DFM OGC NLO NMSS/DFM NAME HRodriguez DJohnson GMostaghimi YDiaz-Sanabria DATE 3/25/2024 3/27/2024 6/14/2024 6/18/2024