A I R SID E SEA L OJ L -~~----,------~-------
PRESSURE GAUGE RANGE O TO 160 PSIG P I - 2 MA I N BEAR!NG------ 1 OIL FEED
<I[QIID MA I N BEARING---~----_
HYDROG EN SEAL COMB INED BEARING OIL AND AIR SIDE SEAL OIL DRAIN --
" DEFOAM I NG TANK LE VE L HI GH" ALARM LS - 2 __________....-
<KfilD COMB I NED OEFOAM I NG TANK----
DRA I N AND GAS PRESSURE SENS I NG L I NE 43 HYDROG EN INNE R-COOLED TURBINE GENERATOR 44 45 46 47 48 49 NO TE S:
LEGEND I. ~x~R~~~~ n~~Llr~6~ si~~ ~~A~og1~s6t 1NG -{><}-
VA L VE (NORMALLY OPEN J PRESSURE GAUGE THERMOMETER
- 2.
145 " THICK
-MA I N OIL FEED BEARING
~
--- SEE NOTE I AIR SIDE~
01 L IN LET \
<KillD VA L VE (NORMALLY CLOSED J
~
VA L VE (NORMALLY THROTTLED)
~::--
CHECK VAL VE
[Q]
REL IEF VAL VE ORIFICE OIL ALARMS IT2J DEFOAM I NG TANK LEVE L-HIGH
[ill AIR S I DE SEAL OIL PUMP-OFF
@]
SEAL OI L PRESSURE-LOW
[!]
HYDROGEN SI DE LE VEL-L OW ELECTRICAL CONNECT I ON PRESSURE SWITCH SOLENOID VALVE
[8J SEAL OI L TURBINE BACKUP PRESSURE-LOW
[fil HY DROG EN S I DE SEAL OI L PUMP - OFF
[ill A I R S I DE SEAL OIL BACKUP PUMP-RUNN I NG CON DE NSED OP ERAT I NG INS TRUCTI ONS SEE INSTRUCTION BOOK FOR COMPLETE OPERATING INSTRUCT I ONS GENERA L -SEA L OI L PRESSURE MUST BE MAINT A INED AT THE HYDROG EN SEALS WHEN HYDROGEN I S I N TH E GENERATOR OR WHEN THE SHA FT IS TURNING.
THE HYDROGEN PRESSURE MAY BE VARIED UP TO 75 PS I G.
SEAL OIL PRESSURE IS NORMAL L Y MA I NTAINED AT 12 PSI ABOVE THE HYDROGEN PRESSURE. 3 PS]
I S REQUI RED TO MAINTAIN A SEAL WHEN RUNNING.
THE VAPOR EXTRACTORS SHOULD BE OPERATED CONTINUOUSLY WHEN THE GENERATOR IS FILLED WI TH HYDROGEN.
HYDROGEN SHOUL D BE PURGED FROM THE GENERATOR BEFORE MA I N OIL RESERVOIR rs DRAINED.
THE GENERATOR CAN BE OPERATED WI TH THE HYDROGEN S I DE SEAL OIL PUMP OFF.
DUPLEX FI LTERS PROV I DE FOR ON-LINE FI LTER ELEMENT REPLACEMENT.
REF ER TO INSTRUCTION MANUAL DC -663 280 - 41 SEA L OIL SUPPLY-EMERGENCY SOURCES MAIN OI L PUMP ON TURBIN E SE AL OIL BACK UP PUMP ON MAIN OIL RESERVIOR AIR SIDE SEAL OI L BACKUP SHAFT~ WIL L MA I NTA I N 75 PSlG HYDROGEN PRESSURE PUMP TURNING GEAR BEAR I NG OIL PUMPS WI LL MA I NTA I N 2 PS IG HYDROGEN PRESSURE THE TURBINE BACKUP REGULATOR VALVE 264 OPENS WHEN THE DIFFEREN-T I AL PR ESSURE AT THE SEALS DECR EASES TO 8 PSI. THEN I F TH E SEAL DIF FERENTIA L PRESSURE DECREAS ES TO 5 PS!, PRESSURE SW I TCH [TI)
ACTIVATES THE AIR S I DE SEAL OIL BACKUP PUMP ON THE SEAL OI L UNIT AND THE DIFFERENTIAL PRESSURE IS RESTORED TO 12 PSI.
TH E NEXT SOURC ES OF EMERGENCY OI L AFTER THE A I R SID E SE AL OI L PUMP AR E THE TURNING GEAR BEAR I NG OI L PUMP S ON THE MAIN OIL RESERV I OR.
THESE CAN MAINTAIN A PRESSURE OF 2 PSIG ONLY.
WHEN THE A I R SIDE SEAL OI L IS RUN-HYDROGEN PRESSURE SHOULD BE REDUCED TO 2 PS I G I F THE SEAL PUMP ON THE RESERVIOR IS NOT AVA I LA BLE.
TO PLACE EQUIPMENT I N OPERA T ION-SET VALVES AS IND I CA TED.
START AIR SIDE SEAL OIL PUMP AND FILL OEFOAMJNG TANKS AND HYDROGEN SIDE DRAIN REGULATOR. STAR T HYDROGEN SIDE SEAL OI L PUMP.
EQUIP-MENT IS THEN IN NORMAL OPERATION.
UN I T DIABLO CA NYO N POWER PLANT - PG& E CO.
TURBI NE AND GENERA TOR ASSOCIATED SYSTEMS E