ML23241A182

From kanterella
Jump to navigation Jump to search
7 to Updated Final Safety Analysis Report, Chapter 3, Figure 3.8-83, Drawing 515213, Revision 6, Sheet 1, Architectural Safety Related Masonry Walls Turbine Building
ML23241A182
Person / Time
Site: Diablo Canyon  
Issue date: 05/25/2023
From:
Pacific Gas & Electric Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML23241A052 List: ... further results
References
DCL-23-044
Download: ML23241A182 (1)


Text

i 6

SEISMICALLY QUALIF I ED CE 1 LI NG STRUCTURE ISEE NOTE 7) i T - 268 DETA IL I I. CONCRETE MASONRY WA L L DIMENSIONS AND DETAIL RE FERENCES ARE SHOWN ON ARCH ITECTURAL DRAWINGS 59532, 59533, 59534, 59535,

59536, 59541, 59544, 59545. 59554, 59557, 59558 AND 5957 1.

2. FOR UNI T ONE CONC RETE MASONRY WA L L STRUCTURA L MODIFICATI ONS, KEY PLAN ANO SCHEDULE OF RECORD DRAWINGS,

SE E DRAW I NGS 5 15 194, 40 I 0616 ANO 40 I 061 7.

3. FOR DESIGN BASIS OF SA FETY REL ATED MASONRY WAL LS ANO SEISMICALLY QUAL I FIED NON-SA FETY RELATED MA SONRY WALLS. REFER TO DCM T-3 1.
4. ANY MODIFICATION OF SAFETY RE LATED MASONRY WAL LS ANO SEISMICALLY QUALIFIED NON-SAFETY RELATED MA SONRY WALLS, REFER TO DCM T -3 1.
5.

SAFETY RELATED EQUIPMENT ANO SYSTEMS SHALL NOT BE LOCATED IN THE VICINITY ( WI TH IN A DISTANCE EQUAL TO THE WALL HEIGHT ) OF' EXI STING NON-SAF'ETY RELA TED MASONRY \.IALLS UNL ESS APPROVED BY CI VI L ENGI NEER ING.

6. SEISMICALLY QUALIFIED NON-SAFETY RELATED MASONRY WALLS ARE RELIED UPON TO SUPPORT SAFETY RELA TED MASONRY WALLS.

QUALITY REQUIREMENTS FOR MOD I F I CATION OF THESE WA LL S.

INC LUDI NG STEEL SUPPORTING MEMBERS, SHALL BE THE SAME AS FOR DESIGN CL ASS I

STRUCTUR ES.

7. SEISMICALLY QUAL I F I ED CEILI NG STRUC TURES,

I NCL UDING CONCRETE SLABS, META L DECKS ANO SUPPORTI NG FRAM I NG ARE RELIED UPON TO LA TERALLY SUPPORT SAFETY RELATED MASONRY WA LLS AND ARE SEISMICALLY QUALI F IED TO THE REQU I REMENTS OF DC M T - 31.

QUALITY REQUIREMENTS FOR MOD I FICA T ION OF THESE STRUCTURES SHALL BE THE SA ME AS FOR DESIGN CLASS I STRUCT URES.