ND-23-0391, ITAAC Closure Notification on Completion of ITAAC 2.3.01.03.ii (Index Number 281)

From kanterella
(Redirected from ML23139A185)
Jump to navigation Jump to search

ITAAC Closure Notification on Completion of ITAAC 2.3.01.03.ii (Index Number 281)
ML23139A185
Person / Time
Site: Vogtle Southern Nuclear icon.png
Issue date: 05/19/2023
From: Coleman J
Southern Nuclear Operating Co
To:
Office of Nuclear Reactor Regulation, Document Control Desk
References
ND-23-0391
Download: ML23139A185 (1)


Text

Jamie M. Coleman Regulatory Affairs Director Vogtle 3 & 4 7825 River Road Waynesboro, GA 30830 706-848-6926 tel May 19, 2023 Docket No.:

52-026 ND-23-0391 10 CFR 52.99(c)(1)

U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Southern Nuclear Operating Company Vogtle Electric Generating Plant Unit 4 ITAAC Closure Notification on Completion of ITAAC 2.3.01.03.ii [Index Number 281]

Ladies and Gentlemen:

In accordance with 10 CFR 52.99(c)(1), the purpose of this letter is to notify the Nuclear Regulatory Commission (NRC) of the completion of Vogtle Electric Generating Plant (VEGP)

Unit 4 Inspections, Tests, Analyses, and Acceptance Criteria (ITAAC) Item 2.3.01.03.ii [Index Number 281], for verifying the following:

The Component Cooling Water System (CCS) provides the nonsafety-related functions of transferring heat from the Normal Residual Heat Removal System (RNS) during shutdown and the Spent Fuel Pool Cooling System (SFS) during all modes of operation to the Service Water System (SWS).

Controls exist in the Main Control Room (MCR) to cause the pumps identified in Table 2.3.1-1 to perform the listed function.

Displays of parameters identified in Table 2.3.1-1 can be retrieved in the MCR.

The closure process for this ITAAC is based on the guidance described in NEI 08-01, Industry Guideline for the ITAAC Closure Process under 10 CFR Part 52, which is endorsed by the NRC in Regulatory Guide 1.215.

This letter contains no new NRC regulatory commitments. Southern Nuclear Operating Company (SNC) requests NRC staff confirmation of this determination and publication of the required notice in the Federal Register per 10 CFR 52.99.

If there are any questions, please contact Kelli Roberts at 706-848-6991.

Respectfully submitted, Jamie M. Coleman Regulatory Affairs Director Vogtle 3 & 4

Enclosure:

Vogtle Electric Generating Plant (VEGP) Unit 4 Completion of ITAAC 2.3.01.03.ii [Index Number 281]

JMC/TL/sfr

U.S. Nuclear Regulatory Commission ND-23-0391 Page 2 of 2 cc:

Regional Administrator, Region ll Director, Office of Nuclear Reactor Regulation (NRR)

Director, Vogtle Project Office NRR Senior Resident Inspector - Vogtle 3 & 4

U.S. Nuclear Regulatory Commission ND-23-0391 Enclosure Page 1 of 5 Southern Nuclear Operating Company ND-23-0391 Enclosure Vogtle Electric Generating Plant (VEGP) Unit 4 Completion of ITAAC 2.3.01.03.ii [Index Number 281]

U.S. Nuclear Regulatory Commission ND-23-0391 Enclosure Page 2 of 5 ITAAC Statement Design Commitment

3. The CCS provides the nonsafety-related functions of transferring heat from the RNS during shutdown and the spent fuel pool cooling system during all modes of operation to the SWS.
4. Controls exist in the MCR to cause the pumps identified in Table 2.3.1-1 to perform the listed functions.
5. Displays of the parameters identified in Table 2.3.1-1 can be retrieved in the MCR.

Inspections/Tests/Analyses ii) Testing will be performed to confirm that the CCS can provide cooling water to the RNS HXs while providing cooling water to the SFS HXs.

Testing will be performed to actuate the pumps identified in Table 2.3.1-1 using controls in the MCR.

Inspection will be performed for retrievability of the parameters in the MCR.

Acceptance Criteria ii) Each pump of the CCS can provide at least 2685 gpm of cooling water to one RNS HX and at least 1200 gpm of cooling water to one SFS HX while providing at least 4415 gpm to other users of cooling water.

Controls in the MCR operate to cause pumps listed in Table 2.3.1-1 to perform the listed functions.

Displays identified in Table 2.3.1-1 can be retrieved in the MCR.

ITAAC Determination Basis Multiple ITAAC are performed to demonstrate that the Component Cooling Water System (CCS) provides the nonsafety-related functions of transferring heat from the Normal Residual Heat Removal System (RNS) during shutdown and the Spent Fuel Pool Cooling System (SFS) during all modes of operation to the Service Water System (SWS), that controls exist in the Main Control Room (MCR) to cause the pumps identified in VEGP Combined License (COL)

Appendix C Table 2.3.1-1 to perform the listed function, and displays of the parameters identified in COL Appendix C Table 2.3.1-1 can be retrieved in the Main Control Room (MCR).

This ITAAC requires testing and inspections to be performed to confirm that the CCS can provide cooling water to the RNS Heat Exchangers (HXs) while providing cooling water to the SFS HXs, that controls in the MCR operate to actuate the pumps in COL Appendix C Table 2.3.1-1, and displays listed in COL Attachment C Table 2.3.1-1 can be retrieved in the MCR.

U.S. Nuclear Regulatory Commission ND-23-0391 Enclosure Page 3 of 5 ii) Each pump of the CCS can provide at least 2685 gpm of cooling water to one RNS HX and at least 1200 gpm of cooling water to one SFS HX while providing at least 4415 gpm to other users of cooling water.

Testing was performed in accordance with preoperational test identified in Reference 1 to verify that each CCS pump can provide at least 2685 gpm (gallons per minute) of cooling water to one RNS HX and at least 1200 gpm of cooling water to one SFS HX while providing at least 4415 gpm to other users of cooling water.

The test was conducted by running each CCS pump, individually, to supply one RNS HX, one SFS HX and other users of CCS in the Auxiliary, Containment, and Turbine Buildings. CCS pump A was place into service and when steady flow was established to SFS HX A, RNS HX A, and other users of cooling water, flow was measured using a combination of permanently installed and temporarily installed flow instrumentation. The flow values were recorded and verified to meet the acceptance criteria. This testing was repeated using CCS Pump B with the SFS HX B, RNS HX B and the other users of CCS in service. The results of the testing were documented in ITAAC Technical Report SV4-CCS-ITR-800281 (Reference 1). The component flows measured during testing are summarized in Attachment A.

The completed preoperational test confirmed that each CCS pump for Unit 4 provides at least 2685 gpm of cooling water to one RNS HX and at least 1200 gpm of cooling water to one SFS HX while providing at least 4415 gpm to other users of cooling water and provided evidence that the ITAAC Acceptance Criteria were met.

Controls in the MCR operate to cause pumps listed in Table 2.3.1-1 to perform the listed functions.

Testing was performed to verify controls in the MCR cause pumps identified in COL Appendix C Table 2.3.1-1 (Attachment B) to perform the listed functions.

Testing was performed by ensuring CCS B Train was filled and vented and then CCS Pump B was started per the operating procedure in the MCR. The test then ensured the CCS A Train was filled and vented and then CCC Pump A was started per the operating procedure in the MCR. Both pump starts were verified locally and documented in ITAAC Technical Report SV4-CCS-ITR-801281 (Reference 2).

This confirmed that controls in the MCR cause pumps identified in Table 2.3.1-1 to perform the listed functions.

U.S. Nuclear Regulatory Commission ND-23-0391 Enclosure Page 4 of 5 Displays identified in Table 2.3.1-1 can be retrieved in the MCR.

An inspection was performed to confirm that displays identified in COL Appendix C Table 2.3.1-1 (Attachment C) can be retrieved in the MCR.

The inspection visually confirmed that when each of the displays of parameters identified in Attachment C was summoned at a MCR workstation, the summoned plant parameters appeared on a display monitor at that MCR workstation. This was documented in ITAAC Technical Report SV4-CCS-ITR-801281 (Reference 2).

The inspection results confirmed that the displays identified in Table 2.3.1-1 could be retrieved in the Unit 4 MCR and provided evidence that the ITAAC Acceptance Criteria were met.

References 1 and 2 are available for NRC inspection as well as Unit 4 ITAAC Completion Package (Reference 3).

ITAAC Finding Review In accordance with plant procedures for ITAAC completion, Southern Nuclear Operating Company (SNC) performed a review of all findings pertaining to the subject ITAAC and associated corrective actions. This review found there are no relevant ITAAC findings associated with this ITAAC. The ITAAC completion review is documented in the ITAAC Completion Package for ITAAC 2.3.01.03.ii (Reference 3) and is available for NRC review.

ITAAC Completion Statement Based on the above information, SNC hereby notifies the NRC that ITAAC 2.3.01.03.ii was performed for VEGP Unit 4 and that the prescribed acceptance criteria were met.

Systems, structures, and components verified as part of this ITAAC are being maintained in their as-designed, ITAAC compliant condition in accordance with approved plant programs and procedures.

References (available for NRC inspection)

1. SV4-CCS-ITR-800281, Rev. 0, Unit 4 Recorded Results of CCS Pump Flow Through RNS HX, SFS HX, & Other Users of CCS Cooling: ITAAC 2.3.01.03.ii Item 3.ii
2. SV4-CCS-ITR-801281, Rev. 0, Unit 4 Recorded Results of CCS Controls and Displays in MCR associated with Table 2.3.1-1: ITAAC 2.3.01.03.ii Items 4 and 5
3. 2.3.01.03.ii-U4-CP-Rev0, ITAAC Completion Package

U.S. Nuclear Regulatory Commission ND-23-0391 Enclosure Page 5 of 5 Attachment A CCS Component Flow Values CCS Pump RNS HX Flow (gpm)

SFS HX Flow (gpm)

Other System Flows (gpm)

Unit 4 A HX A - 3071 HX A - 1270 Train A HXs - 6785 Unit 4 B HX B - 3029 HX B - 1308 Train B HXs - 6894 Attachment B

  • Excerpt from COL Appendix C Table 2.3.1-1 Equipment Name*

Tag No.*

Control Function*

CCS Pump A CCS-MP-01A Start CCS Pump B CCS-MP-01B Start Attachment C

  • Excerpt from COL Appendix C Table 2.3.1-1 Equipment Name*

Tag No.*

Display*

CCS Pump A CCS-MP-01A Yes (Run Status)

CCS Pump B CCS-MP-01B Yes (Run Status)

CCS Discharge Header Flow Sensor CCS-101 Yes CCS to Normal Residual Heat Removal System Heat Exchanger (RNS HX) A Flow Sensor CCS-301 Yes CCS to RNS HX B Flow Sensor CCS-302 Yes CCS to Spent Fuel Pool Cooling System (SFS) HX A Flow Sensor CCS-341 Yes CCS to SFS HX B Flow Sensor CCS-342 Yes CCS Surge Tank Level Sensor A CCS-130 Yes CCS Surge Tank Level Sensor B CCS-131 Yes CCS Heat Exchanger Inlet Temperature Sensor CCS-121 Yes CCS Heat Exchanger Outlet Temperature Sensor CCS-122 Yes CCS Flow to Reactor Coolant Pump (RCP) 1A Valve (Position Indicator)

CCS-PL-V256A Yes CCS Flow to RCP 1B Valve (Position Indicator)

CCS-PL-V256B Yes CCS Flow to RCP 2A Valve (Position Indicator)

CCS-PL-V256C Yes CCS Flow to RCP 2B Valve (Position Indicator)

CCS-PL-V256D Yes