1CAN102104, Steam Generator Tube Inspection Report - 1R29
| ML21295A720 | |
| Person / Time | |
|---|---|
| Site: | Arkansas Nuclear |
| Issue date: | 10/22/2021 |
| From: | Keele R Entergy Operations |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| 1CAN102104 | |
| Download: ML21295A720 (161) | |
Text
1CAN102104 October 22, 2021 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555
SUBJECT:
Steam Generator Tube Inspection Report - 1R29 Arkansas Nuclear One, Unit 1 NRC Docket No. 50-313 Renewed Facility Operating License No. DPR-51 Entergy Operations, Inc. (Entergy) inspected the Arkansas Nuclear One, Unit 1 (ANO-1) steam generator (SG) tubes during the Spring 2021 refueling outage (1R29) in accordance with ANO-1 Technical Specification (TS) 5.5.9, Steam Generator (SG) Program. ANO-1 TS 5.6.7 requires that the results of inspections performed during the report period be submitted to the NRC within 180 days after the initial entry into Mode 4. The initial entry into Mode 4 post-1R29 was made on May 9, 2021.
Enclosed is the subject inspection report.
The 1R29 inspection performed on both SGs involved an initial full-length bobbin coil inspection, as well as utilizing the X-probe for diagnostic testing.
Four damage mechanisms were identified, three of which have been previously identified: tube support plate (TSP) wear at broached support plates, TSP wear at drilled support plates, and tube-to-tube wear.
The fourth, tube-to-tie rod wear, was a new mechanism for the 1R29 inspection but was previously classified as a potential damage mechanism in the Degradation Assessment. No identified damage mechanism challenged the performance criteria for leakage or burst.
This submittal completes the reporting requirements of the ANO-1 TSs for this inspection.
This letter contains no new regulatory commitments.
Entergy Operations, Inc.
1448 S.R. 333 Russellville, AR 72802 Tel 479-858-7826 Riley D. Keele, Jr.
Manager, Regulatory Assurance Arkansas Nuclear One
1CAN102104 Page 2 of 2 If you need any additional information, please contact me.
Respectfully, ORIGINAL SIGNED BY RILEY D. KEELE, JR.
Riley Keele RDK/rwc
Enclosure:
Results of ANO-1 SG Tube Inspections During 1R29 Attachments: Location of Service Induced Indications SG A TSP Wear (Broached) SG B TSP Wear (Broached) SG A TSP Wear (Drilled) SG A TTW SG B TTW SG A TRW SG B TRW cc:
NRC Region IV Regional Administrator NRC Senior Resident Inspector - Arkansas Nuclear One NRC Project Manager - Arkansas Nuclear One
ENCLOSURE TO 1CAN102104 Results of ANO-1 SG Tube Inspections During 1R29
Enclosure 1CAN102104 Page 1 of 11 RESULTS OF ANO-1 SG TUBE INSPECTIONS DURING 1R29
1.0 INTRODUCTION
Arkansas Nuclear One, Unit 1 (ANO-1) Technical Specification (TS) 5.6.7, Steam Generator Tube Inspection Reports, requires Entergy Operations, Inc. (Entergy) to submit a 180-day report to the NRC that outlines the details of the steam generator (SG) tubing inspections that were performed during the reporting period. The report shall include:
- 1.
The scope of inspections performed on each SG.
- 2.
Active degradation mechanisms found.
- 3.
Nondestructive examination (NDE) techniques utilized for each degradation mechanism.
- 4.
Location, orientation (if linear), and measured sizes (if available) of service induced indications.
- 5.
Number of tubes plugged during the inspection outage for each active degradation mechanism.
- 6.
Total number and percentage of tubes plugged to date.
- 7.
The results of condition monitoring, including the results of tube pulls and in-situ testing.
The operating period for this report includes one refueling inspection outage (1R29) in April 2021. The previous inspection in 1R26 was a 100% scope bobbin inspection, the results of which permitted skipping inspections in 1R27 and 1R28.
This report details the result of the 1R29 inspection. The inspection was a 100% full-length bobbin inspection, as well as utilizing the X-probe for diagnostic testing. Four damage mechanisms were identified, three of which have been previously identified: tube support plate (TSP) wear at broached support plates, TSP wear at drilled support plates, and tube-to-tube wear (TTW). The fourth, tube-to-tie rod wear (TRW), was a new mechanism for the 1R29 inspection but was previously classified as a potential damage mechanism in the Degradation Assessment. No identified damage mechanism challenged the performance criteria for leakage or burst.
2.0 DESIGN The replacement SGs for ANO-1 are Enhanced Once-Through Steam Generators (EOTSGs) manufactured by AREVA and installed in 2005 during refueling outage 1R19. The EOTSG is a straight shell-and-tube type heat exchanger installed in a vertical position with bottom supports and emergency supports as required to accommodate normal and accident loads. The tubing consists of Inconel 690 thermally treated tubing that is 5/8" in diameter with a 0.037" wall thickness. The tubes are expanded full depth hydraulically in the tubesheet. There are 15 TSPs that are constructed of stainless steel (SA 240 Type 410) and are a broached trefoil-hole design.
Enclosure 1CAN102104 Page 2 of 11 3.0 REPORT REQUIREMENTS 3.1 The scope of inspections performed on each SG The 1R29 work scope included eddy current (ECT) inspections and primary side visual inspections in each of the SGs. Bobbin examination was performed on all in-service tubes, full length upper tube-end (UTE) to lower tube-end (LTE). Array examination was performed on the periphery tubes (2 deep) from the LTE to the first TSP (01S) to facilitate identification of potential loose parts. Array examination was also used on bobbin indication codes, manufacturing related indications, TSP wear indications, TTW indications, and other indications.
Table 3.1.1 1R29 Inspection Scope Examination Type
- Inspections
% Scope Extent Tested SG A Bobbin 15554 100 UTE to LTE Array (periphery) 902 6
LTE to 01S SG B Bobbin 15560 100 UTE to LTE Array (periphery) 881 6
LTE to 01S 3.2 Active degradation mechanisms found The 1R29 inspection was the seventh inspection following replacement of the SGs.
There were four active degradation mechanisms identified: TSP wear at broached support plates, TSP wear at drilled support plates, TTW, and TRW. These are listed in Table 3.2.1.
Table 3.2.1 All Indication List for 1R29 SG TSP Wear (Broached)
TSP Wear (Drilled)
TTW TRW A
2574 2
109 1
B 2591 0
154 1
Enclosure 1CAN102104 Page 3 of 11 3.3 NDE techniques utilized for each degradation mechanism.
Table 3.3.1 1R29 NDE Techniques This note is applicable to the last column of the table above:
ETSS Examination Technical Specification Sheet
[13.e] Framatome Document 51-9094580-004, Measuring the Gap between Tubes and Tie Rods with the Bobbin Coil Eddy Current Method
Enclosure 1CAN102104 Page 4 of 11 3.4 Location, orientation (if linear), and measured sizes (if available) of service induced indications.
The service induced mechanisms were mechanical wear at TSPs (broached and drilled),
TTW, and TRW. Due to the large number of indications, these are listed in the following attachments:
SG A TSP Wear (Broached) SG B TSP Wear (Broached) SG A TSP Wear (Drilled) SG A TTW SG B TTW SG A TRW SG B TRW 3.5 Number of tubes plugged during the inspection outage for each active degradation mechanism.
There were 27 tubes plugged in 1R29, all of which were stabilized. Listed below in Tables 3.5.1 and 3.5.2 is a summary of the plugged tubes in each SG.
Table 3.5.1 SG A Repaired Tubes in 1R29 Row Tube Repair Type Reason 81 126 Plug & Stabilizer Preventative 39% @ 11S 85 123 Plug & Stabilizer Preventative 34% @ 10S 114 3
Plug & Stabilizer Preventative 33% @ 13S 134 9
Plug & Stabilizer Preventative 30% @ 10S Table 3.5.2 SG B Repaired Tubes in 1R29 Row Tube Repair Type Reason 10 3
Plug & Stabilizer Preventative 26% @ 11S 11 61 Plug & Stabilizer Preventative 21% @ 11S 22 2
Plug & Stabilizer Preventative 28% @ 12S 26 97 Plug & Stabilizer Preventative - Loose Part 26 98 Plug & Stabilizer Preventative - Loose Part 27 98 Plug & Stabilizer Preventative - Loose Part 27 99 Plug & Stabilizer Preventative - Loose Part 73 131 Plug & Stabilizer Preventative 30% @ 13S
Enclosure 1CAN102104 Page 5 of 11 106 2
Plug & Stabilizer Preventative 27% @ 12S 114 1
Plug & Stabilizer Preventative 35% @ 12S 115 1
Plug & Stabilizer 42% @ 12S 117 2
Plug & Stabilizer 41% @ 12S 118 2
Plug & Stabilizer 44% @ 12S 124 2
Plug & Stabilizer Preventative 34% @ 12S 127 1
Plug & Stabilizer Preventative 39% @ 12S 129 1
Plug & Stabilizer Preventative 37% @ 12S 130 2
Plug & Stabilizer Preventative 27% @ 12S 131 1
Plug & Stabilizer Preventative 32% @ 11S 137 69 Plug & Stabilizer Preventative 32% @ 11S 138 75 Plug & Stabilizer Preventative 29% @ 12S 145 47 Plug & Stabilizer Preventative 33% @ 14S 148 3
Plug & Stabilizer Preventative 30% @ 13S 148 4
Plug & Stabilizer 44% @ 12S 3.6 Total number and percentage of tubes plugged to date.
There were no sleeves installed in either SG. The aggregate plugging information is listed in Table 3.6.1 below.
Table 3.6.1 Cumulative Plugs in Service SG A Year Outage Installed Cumulative
% Plugged 2004 Fabrication 2 (welded) 2 0.013 2005 Baseline (1R19) 0 2
0.013 2007 First ISI 1R20 0
2 0.013 2008 1R21 8
10 0.064 2010 1R22 0
10 0.064 2011 1R23 7
17 0.109 2013 1R24 7
24 0.154 2016 1R26 19 43 0.276 2021 1R29 4
47 0.301
Enclosure 1CAN102104 Page 6 of 11 SG B Year Outage Installed Cumulative
% Plugged 2005 Fabrication 0
0 0
2005 Baseline (1R19) 0 0
0 2007 First ISI 1R20 1
1 0.006 2008 1R21 5
6 0.038 2010 1R22 0
6 0.038 2011 1R23 9
15 0.096 2013 1R24 9
24 0.154 2016 1R26 13 37 0.237 2021 1R29 23 60 0.385 Note: 15597 total tubes per SG 3.7 The results of condition monitoring, including the results of tube pulls and in-situ testing.
All condition monitoring requirements for the tubing performance criteria were met.
There were no indications that exceeded performance criteria or in-situ screening limits. There was no tube pulls required.
The Condition Monitoring Operational Assessment (CMOA) for 1R26 evaluated an Operational Assessment (OA) of three operating cycles totaling 4.65 Effective Full Power Years (EFPY) to 1R29 (EOC29). At the conclusion of Cycle 29, 3.82 EFPY had passed therefore the 1R26 CMOA is still applicable.
The previous OA included deterministic and probabilistic analyses for all detected mechanisms (TSP wear and TTW), and the findings of the 1R29 SG examinations are bounded by the behavior projected in the 1R26 OA. The first, and strongest, point is noted by none of the TSP wear (broached and drilled) or TTW meeting or exceeding the Condition Monitoring (CM) limits. The second point is demonstrated by the growth rate behavior associated with TSP wear and TTW. The 1R26 OA assumed no attenuation in growth rates and used a bounding Kunin growth rate for broached TSP wear in the full bundle probabilistic model, and the maximum growth rate for TTW deterministically. It is noted that in 1R29 growth rate attenuation for both TSP wear and TTW seemed to stagnate where 1R29 growth rate distribution is almost identical to 1R26. Additionally, while the upper 95th growth rate from the 1R26 SG B inner bundle is slightly less than the observed upper 95th at 1R29, it is still bounded by the periphery in both growth rates as well as depths of indications.
3.7.1 Tie Rod Bowing There were no new bowed tie rods detected at 1R29 in either SG. Some tie rods which experienced bow in prior outages but did not have proximity indications detected in adjacent tubes, had a maximum bow calculated based on proximity detection thresholds
Enclosure 1CAN102104 Page 7 of 11 on in-service tubes. Each tie rods bow is plotted as a function of time (in cooldown cycles) in Figure 3.7.1 through Figure 3.7.4. For SG A, which has the longest history of tie rod bowing, a pattern is developing that shows the tie rods bowing to a point and then stagnating with a majority of tie rods showing no change or even a decrease in calculated bow. This is most evident in the first span tie rods where even the preventative tube plugging proximity signals are still detected for each tie rod to accurately calculate the magnitude and direction of the tie rod bow. It is believed the same relationship is true for the upper span tie rods with the majority experiencing a similar pattern; however, due to the lack of information for some tie rods (affected tubes plugged in prior outages) a conservative maximum possible bow is calculated which shows a jump in tie rod bow. This is assumed to be conservative for plugging projections, as some of these tie rods still show stagnation after multiple outages with no change in affected tubes.
Enclosure 1CAN102104 Page 8 of 11 Figure 3.7.1 SG A First Span Bowing with Allowable Limits
Enclosure 1CAN102104 Page 9 of 11 Figure 3.7.2 SG A Upper Span Bowing with Allowable Limits
Enclosure 1CAN102104 Page 10 of 11 Figure 3.7.3 SG B First Span Bowing with Allowable Limits
Enclosure 1CAN102104 Page 11 of 11 Figure 3.7.4 SG B Upper Span Bowing with Allowable Limits
Enclosure to 1CAN102104 Location of Service Induced Indications SG A TSP Wear (Broached)
1CAN102104 Page 1 of 65 Location of Service Induced Indications SG A TSP Wear (Broached)
SG Row Col
%TW Elev Offset SG A 1
5 18 13S
-0.8 SG A 1
6 18 13S
-0.73 SG A 1
16 7
10S 0.39 SG A 1
17 7
10S 0.36 SG A 1
19 9
10S 0.41 SG A 1
19 13 13S
-0.88 SG A 1
20 13 13S
-0.78 SG A 1
20 15 14S
-0.84 SG A 1
23 8
10S 0.41 SG A 2
4 9
13S
-0.73 SG A 2
18 14 14S 0.3 SG A 2
22 10 10S 0.42 SG A 2
24 18 13S
-0.72 SG A 2
26 13 10S 0.45 SG A 2
26 15 13S
-0.76 SG A 2
27 10 10S 0.39 SG A 2
28 11 13S
-0.74 SG A 3
5 11 13S
-0.7 SG A 3
11 5
10S 0.49 SG A 3
23 9
10S 0.04 SG A 3
27 11 13S
-0.76 SG A 4
6 11 13S
-0.75 SG A 4
15 12 10S
-0.77 SG A 4
19 16 13S 0.34 SG A 4
22 15 14S 0.32 SG A 4
23 10 14S 0.26 SG A 4
24 7
10S 0.02 SG A 4
25 15 10S 0.04 SG A 5
1 11 12S
-0.68 SG A 5
3 10 13S
-0.73 SG A 5
18 17 12S
-0.75 SG A 5
19 8
10S
-0.73 SG A 5
19 9
12S
-0.84 SG A 5
20 18 10S
-0.75 SG A 5
22 6
10S
-0.68 SG A 5
22 16 13S 0.36 SG A 5
22 10 14S 0.28 SG A 5
23 11 10S
-0.77
1CAN102104 Page 2 of 65 SG Row Col
%TW Elev Offset SG A 5
24 8
12S
-0.74 SG A 5
25 12 12S
-0.84 SG A 5
25 13 13S
-0.75 SG A 5
25 11 13S 0.21 SG A 5
25 11 14S 0.22 SG A 5
26 10 10S
-0.65 SG A 5
26 15 12S
-0.76 SG A 5
26 20 13S 0.28 SG A 5
27 12 10S
-0.68 SG A 5
27 16 12S
-0.8 SG A 5
27 13 13S
-0.78 SG A 5
28 7
10S
-0.75 SG A 5
28 18 10S 0.09 SG A 5
29 19 10S 0.11 SG A 6
2 11 13S
-0.73 SG A 6
6 19 10S
-0.68 SG A 6
7 11 10S
-0.66 SG A 6
9 21 10S
-0.68 SG A 6
13 11 10S
-0.68 SG A 6
14 10 13S
-0.77 SG A 6
15 17 10S
-0.68 SG A 6
15 13 13S 0.32 SG A 6
16 14 10S
-0.75 SG A 6
17 11 10S
-0.72 SG A 6
18 7
10S
-0.66 SG A 6
19 16 10S
-0.68 SG A 6
19 11 12S
-0.78 SG A 6
19 13 13S 0.38 SG A 6
20 9
09S
-0.73 SG A 6
20 9
15S 0.37 SG A 6
21 8
12S
-0.82 SG A 6
24 16 13S 0.26 SG A 6
25 10 12S
-0.83 SG A 6
26 9
12S
-0.72 SG A 6
26 23 13S 0.26 SG A 6
26 12 14S
-0.72 SG A 6
26 14 14S 0.28 SG A 6
29 9
09S
-0.77 SG A 6
30 10 09S
-0.7 SG A 6
30 8
12S
-0.79
1CAN102104 Page 3 of 65 SG Row Col
%TW Elev Offset SG A 6
30 9
13S
-0.79 SG A 6
31 16 09S
-0.72 SG A 6
31 12 12S
-0.76 SG A 6
32 8
10S
-0.64 SG A 6
32 9
10S 0.02 SG A 6
32 14 12S
-0.84 SG A 6
33 10 10S 0.02 SG A 6
35 10 15S 0.21 SG A 6
37 10 13S 0.32 SG A 6
38 18 13S 0.28 SG A 6
39 13 13S 0.26 SG A 6
39 10 14S 0.24 SG A 6
41 10 09S 0.38 SG A 7
1 25 13S
-0.65 SG A 7
1 11 13S 0.47 SG A 7
2 14 13S
-0.7 SG A 7
3 11 13S
-0.73 SG A 7
6 14 10S
-0.73 SG A 7
6 17 13S
-0.72 SG A 7
6 11 13S 0.55 SG A 7
7 10 10S
-0.73 SG A 7
9 17 10S
-0.73 SG A 7
10 25 10S
-0.68 SG A 7
12 7
10S
-0.75 SG A 7
13 11 10S
-0.7 SG A 7
14 9
10S
-0.77 SG A 7
15 16 10S
-0.7 SG A 7
16 11 13S 0.3 SG A 7
17 14 09S
-0.7 SG A 7
17 25 10S
-0.7 SG A 7
17 12 12S
-0.7 SG A 7
17 13 13S 0.34 SG A 7
21 13 09S
-0.72 SG A 7
28 11 10S 0.28 SG A 7
28 11 12S
-0.83 SG A 7
32 18 09S
-0.72 SG A 7
32 12 12S 0.36 SG A 7
33 12 09S
-0.72 SG A 7
33 15 13S 0.32 SG A 7
34 15 12S
-0.74
1CAN102104 Page 4 of 65 SG Row Col
%TW Elev Offset SG A 7
35 9
10S 0.04 SG A 7
35 10 12S
-0.79 SG A 7
37 11 10S 0.15 SG A 7
38 6
10S 0
SG A 7
38 11 12S
-0.86 SG A 7
41 19 13S 0.34 SG A 7
42 13 13S
-0.77 SG A 7
42 12 13S 0.3 SG A 8
1 23 13S
-0.66 SG A 8
1 13 13S 0.53 SG A 8
9 16 10S
-0.7 SG A 8
11 12 10S
-0.68 SG A 8
14 13 10S
-0.73 SG A 8
14 10 12S
-0.82 SG A 8
16 15 09S
-0.71 SG A 8
17 20 09S
-0.73 SG A 8
19 15 09S
-0.75 SG A 8
19 17 10S
-0.77 SG A 8
20 15 09S
-0.59 SG A 8
29 10 12S
-0.81 SG A 8
29 10 12S 0.34 SG A 8
30 13 12S
-0.71 SG A 8
31 13 12S
-0.81 SG A 8
33 14 15S 0.21 SG A 8
34 19 09S
-0.7 SG A 8
34 15 12S
-0.81 SG A 8
34 18 13S 0.26 SG A 8
35 12 09S 0.4 SG A 8
35 16 13S 0.25 SG A 8
36 18 12S
-0.79 SG A 8
36 10 15S 0.2 SG A 8
37 13 12S
-0.85 SG A 8
38 11 12S
-0.83 SG A 8
38 11 14S 0.19 SG A 8
39 12 09S
-0.7 SG A 8
39 17 12S
-0.87 SG A 8
39 15 13S 0.34 SG A 8
39 13 14S 0.26 SG A 8
39 9
15S
-0.9 SG A 8
40 26 12S
-0.74
1CAN102104 Page 5 of 65 SG Row Col
%TW Elev Offset SG A 8
40 10 15S 0.2 SG A 8
41 14 09S
-0.66 SG A 8
45 12 14S 0.26 SG A 8
47 10 14S 0.28 SG A 8
48 12 14S
-0.75 SG A 8
49 17 14S
-0.79 SG A 8
50 11 14S 0.28 SG A 8
51 8
14S 0.26 SG A 9
1 12 13S
-0.64 SG A 9
2 10 13S 0.43 SG A 9
3 12 13S
-0.7 SG A 9
3 10 13S 0.55 SG A 9
4 10 13S 0.41 SG A 9
7 11 10S
-0.66 SG A 9
8 7
10S
-0.73 SG A 9
9 24 10S
-0.68 SG A 9
10 6
10S 0.53 SG A 9
11 13 13S
-0.75 SG A 9
11 12 13S 0.34 SG A 9
12 7
09S 0.47 SG A 9
12 21 10S
-0.68 SG A 9
17 8
09S 0.39 SG A 9
17 13 10S
-0.73 SG A 9
31 10 05S 0.39 SG A 9
31 13 12S
-0.81 SG A 9
32 14 12S 0.24 SG A 9
34 13 05S
-0.66 SG A 9
34 11 05S 0.4 SG A 9
40 17 12S
-0.76 SG A 9
40 10 14S
-0.81 SG A 9
42 14 12S
-0.81 SG A 9
42 16 13S 0.3 SG A 9
43 19 09S
-0.68 SG A 9
43 17 12S
-0.72 SG A 9
45 11 15S 0.24 SG A 9
48 11 15S 0.22 SG A 9
50 10 14S 0.19 SG A 9
52 14 10S 0
SG A 9
53 10 14S 0.21 SG A 9
54 10 14S 0.24
1CAN102104 Page 6 of 65 SG Row Col
%TW Elev Offset SG A 9
56 13 13S
-0.79 SG A 9
57 13 13S
-0.85 SG A 10 1
11 13S
-0.6 SG A 10 1
14 13S 0.51 SG A 10 2
11 13S 0.45 SG A 10 3
23 13S 0.51 SG A 10 9
25 10S
-0.68 SG A 10 10 19 10S
-0.68 SG A 10 13 7
10S
-0.64 SG A 10 14 11 10S
-0.75 SG A 10 15 15 10S
-0.7 SG A 10 17 10 10S
-0.73 SG A 10 19 10 06S
-0.7 SG A 10 19 12 10S
-0.74 SG A 10 36 11 15S 0.25 SG A 10 38 10 12S
-0.83 SG A 10 40 18 12S
-0.81 SG A 10 42 14 12S
-0.81 SG A 10 44 12 12S
-0.79 SG A 10 49 10 15S 0.22 SG A 10 52 14 15S 0.19 SG A 10 53 12 13S 0.28 SG A 10 53 13 14S 0.21 SG A 10 54 12 14S 0.21 SG A 10 56 8
14S 0.24 SG A 10 57 10 14S 0.21 SG A 10 58 11 14S 0.19 SG A 10 59 10 14S
-0.79 SG A 10 60 8
10S
-0.13 SG A 10 61 13 13S 0.3 SG A 10 61 7
14S 0.21 SG A 10 62 13 14S 0.21 SG A 10 63 15 14S 0.23 SG A 10 65 18 13S
-0.71 SG A 11 1
16 13S
-0.62 SG A 11 1
22 13S 0.53 SG A 11 2
12 13S 0.49 SG A 11 2
11 14S
-0.73 SG A 11 2
13 14S 0.46 SG A 11 5
14 10S
-0.69
1CAN102104 Page 7 of 65 SG Row Col
%TW Elev Offset SG A 11 6
8 10S 0.55 SG A 11 6
10 13S 0.51 SG A 11 7
13 13S 0.41 SG A 11 8
19 10S
-0.64 SG A 11 8
14 12S
-0.76 SG A 11 10 13 10S
-0.68 SG A 11 11 14 10S
-0.69 SG A 11 11 16 13S 0.37 SG A 11 12 29 10S
-0.68 SG A 11 14 20 10S
-0.54 SG A 11 14 8
12S
-0.65 SG A 11 15 11 10S
-0.66 SG A 11 16 14 10S
-0.68 SG A 11 27 14 15S 0.27 SG A 11 41 11 12S
-0.81 SG A 11 43 25 12S
-0.68 SG A 11 48 9
15S 0.18 SG A 11 49 15 15S
-0.96 SG A 11 50 14 15S 0.2 SG A 11 51 16 12S
-0.81 SG A 11 51 12 15S 0.18 SG A 11 52 10 10S
-0.72 SG A 11 54 16 13S 0.3 SG A 11 54 14 14S
-0.7 SG A 11 55 10 09S 0.36 SG A 11 58 11 14S
-0.81 SG A 11 59 9
14S 0.23 SG A 11 62 10 14S
-0.81 SG A 11 64 14 10S 0.04 SG A 11 65 7
10S
-0.11 SG A 11 68 17 13S
-0.77 SG A 12 1
16 13S 0.49 SG A 12 2
11 13S 0.47 SG A 12 3
13 13S
-0.64 SG A 12 7
19 10S
-0.62 SG A 12 8
12 10S
-0.73 SG A 12 8
13 12S
-0.63 SG A 12 8
13 13S 0.43 SG A 12 9
21 10S
-0.68 SG A 12 11 23 10S
-0.7
1CAN102104 Page 8 of 65 SG Row Col
%TW Elev Offset SG A 12 12 12 10S
-0.72 SG A 12 13 12 10S
-0.69 SG A 12 14 15 10S
-0.74 SG A 12 15 11 10S
-0.68 SG A 12 15 5
10S 0.38 SG A 12 22 8
09S
-0.66 SG A 12 37 12 15S 0.18 SG A 12 42 18 12S
-0.77 SG A 12 42 13 12S 0.26 SG A 12 45 14 15S 0.16 SG A 12 48 16 15S
-0.92 SG A 12 55 14 13S 0.3 SG A 12 57 8
15S
-0.79 SG A 12 57 10 15S 0.21 SG A 12 63 11 14S
-0.79 SG A 12 65 10 06S
-0.7 SG A 13 1
16 13S 0.49 SG A 13 2
12 13S 0.41 SG A 13 10 18 10S
-0.69 SG A 13 11 23 10S
-0.72 SG A 13 12 15 10S
-0.71 SG A 13 13 21 10S
-0.68 SG A 13 14 13 10S
-0.6 SG A 13 16 21 10S
-0.71 SG A 13 38 14 15S 0.22 SG A 13 51 12 15S 0.19 SG A 13 57 8
09S
-0.68 SG A 13 59 9
12S
-0.83 SG A 13 60 8
09S 0.4 SG A 13 60 11 10S 0.04 SG A 13 61 12 12S
-0.81 SG A 13 61 13 13S
-0.74 SG A 13 61 10 14S 0.24 SG A 13 67 11 14S 0.24 SG A 13 74 17 13S
-0.87 SG A 14 11 7
10S
-0.68 SG A 14 12 6
12S
-0.75 SG A 14 15 11 10S
-0.7 SG A 14 15 7
11S
-0.75 SG A 14 16 14 10S
-0.73
1CAN102104 Page 9 of 65 SG Row Col
%TW Elev Offset SG A 14 16 14 14S
-0.77 SG A 14 17 7
07S
-0.68 SG A 14 18 12 10S
-0.75 SG A 14 19 17 10S
-0.7 SG A 14 37 11 15S
-0.98 SG A 14 42 9
15S 0.22 SG A 14 52 10 15S 0.22 SG A 14 63 11 13S 0.3 SG A 14 74 8
10S
-0.06 SG A 14 77 13 13S
-0.85 SG A 15 5
8 12S
-0.68 SG A 15 7
7 10S
-0.7 SG A 15 10 11 10S
-0.73 SG A 15 15 11 11S
-0.72 SG A 15 16 13 10S
-0.75 SG A 15 16 15 11S
-0.77 SG A 15 19 14 10S
-0.73 SG A 15 49 5
09S
-0.7 SG A 15 55 10 15S
-0.81 SG A 15 63 12 09S
-0.75 SG A 15 72 10 09S
-0.72 SG A 15 80 21 13S
-0.83 SG A 16 4
6 10S 0.21 SG A 16 6
14 13S
-0.73 SG A 16 53 11 15S 0.17 SG A 16 60 11 15S
-0.94 SG A 16 61 10 15S
-0.82 SG A 16 66 12 09S
-0.76 SG A 16 68 11 14S 0.21 SG A 16 69 10 09S
-0.75 SG A 16 73 10 09S
-0.75 SG A 16 74 12 09S 0.42 SG A 16 76 6
10S 0.09 SG A 16 76 10 13S
-0.81 SG A 16 76 11 14S 0.21 SG A 17 2
14 11S
-0.72 SG A 17 5
22 10S
-0.56 SG A 17 57 11 15S 0.19 SG A 17 62 16 15S 0.19 SG A 17 64 10 15S 0.17
1CAN102104 Page 10 of 65 SG Row Col
%TW Elev Offset SG A 17 67 11 15S
-0.82 SG A 17 68 6
10S
-0.81 SG A 17 68 10 15S
-0.96 SG A 17 74 18 13S 0.25 SG A 17 76 11 09S
-0.68 SG A 17 76 12 12S
-0.81 SG A 17 76 12 15S
-0.99 SG A 17 77 12 14S 0.22 SG A 17 79 10 13S
-0.81 SG A 17 83 13 13S
-0.83 SG A 18 7
10 12S
-0.72 SG A 18 21 8
09S
-0.68 SG A 18 60 11 15S
-0.99 SG A 18 76 12 09S
-0.72 SG A 18 77 12 09S 0.39 SG A 18 78 15 09S
-0.74 SG A 18 80 12 10S 0.11 SG A 19 7
15 10S
-0.68 SG A 19 48 10 15S 0.17 SG A 19 51 11 15S
-0.95 SG A 19 54 11 15S
-0.92 SG A 19 66 7
09S
-0.73 SG A 19 71 11 12S 0.34 SG A 19 72 17 10S
-0.79 SG A 19 75 13 12S 0.3 SG A 19 78 11 09S 0.36 SG A 19 80 23 09S
-0.72 SG A 19 81 12 13S 0.28 SG A 19 81 10 14S 0.26 SG A 19 82 10 10S 0.17 SG A 19 87 20 13S
-0.78 SG A 20 43 14 15S 0.22 SG A 20 65 11 15S
-0.9 SG A 20 80 19 09S
-0.72 SG A 20 81 12 09S
-0.7 SG A 20 81 12 09S 0.36 SG A 20 82 16 12S 0.3 SG A 20 85 11 14S 0.26 SG A 20 89 13 12S
-0.83 SG A 21 45 6
08S 0.37
1CAN102104 Page 11 of 65 SG Row Col
%TW Elev Offset SG A 21 82 14 09S 0.36 SG A 21 82 11 10S
-0.73 SG A 21 84 11 10S 0.14 SG A 21 84 13 12S
-0.87 SG A 21 85 11 14S 0.21 SG A 21 87 16 12S
-0.83 SG A 21 90 23 12S
-0.79 SG A 22 83 15 10S
-0.75 SG A 22 83 12 15S
-0.9 SG A 22 84 13 10S
-0.84 SG A 22 85 17 09S
-0.73 SG A 22 85 11 09S 0.36 SG A 22 85 24 10S
-0.75 SG A 22 85 11 10S 0.3 SG A 22 85 11 11S 0.28 SG A 22 85 21 12S
-0.85 SG A 22 86 15 12S
-0.89 SG A 22 88 12 12S
-0.87 SG A 22 92 15 12S
-0.83 SG A 22 92 29 13S
-0.87 SG A 23 33 6
08S 0.43 SG A 23 40 10 08S
-0.68 SG A 23 44 11 08S
-0.72 SG A 23 66 12 11S
-0.9 SG A 23 72 11 12S
-0.91 SG A 23 72 15 15S
-0.79 SG A 23 85 21 10S
-0.81 SG A 23 86 28 10S
-0.8 SG A 23 87 21 12S
-0.82 SG A 23 88 10 12S
-0.89 SG A 23 88 12 12S 0.3 SG A 23 89 12 12S 0.3 SG A 23 93 13 12S
-0.83 SG A 23 94 18 12S
-0.85 SG A 24 30 10 08S
-0.72 SG A 24 31 7
08S
-0.69 SG A 24 38 9
08S 0.4 SG A 24 48 9
08S
-0.72 SG A 24 53 7
08S 0.39 SG A 24 82 22 15S
-0.82
1CAN102104 Page 12 of 65 SG Row Col
%TW Elev Offset SG A 24 83 19 10S
-0.82 SG A 24 83 12 12S 0.28 SG A 24 84 9
10S
-0.74 SG A 24 84 18 12S
-0.84 SG A 24 85 13 12S
-0.85 SG A 24 86 13 10S 0.08 SG A 24 90 18 12S
-0.8 SG A 24 91 15 12S
-0.85 SG A 25 30 15 08S 0.4 SG A 25 31 5
08S 0.45 SG A 25 34 10 08S
-0.76 SG A 25 40 8
08S 0.4 SG A 25 42 9
08S
-0.75 SG A 25 47 8
08S 0.39 SG A 25 50 11 08S
-0.7 SG A 25 52 10 08S
-0.77 SG A 25 54 9
08S 0.36 SG A 25 56 12 08S
-0.71 SG A 25 59 9
08S
-0.7 SG A 25 62 10 08S 0.38 SG A 25 64 12 08S 0.36 SG A 25 82 16 15S
-0.93 SG A 25 85 14 12S
-0.84 SG A 25 86 11 14S 0.19 SG A 25 92 13 14S 0.19 SG A 25 96 14 12S
-0.81 SG A 26 29 11 08S
-0.76 SG A 26 33 11 08S
-0.72 SG A 26 42 7
08S 0.45 SG A 26 43 7
08S
-0.74 SG A 26 47 10 08S
-0.78 SG A 26 49 13 08S
-0.76 SG A 26 51 9
08S
-0.74 SG A 26 52 8
08S 0.41 SG A 26 54 13 08S
-0.74 SG A 26 54 7
08S 0.38 SG A 26 55 8
08S 0.41 SG A 26 56 9
08S
-0.71 SG A 26 65 12 08S
-0.72 SG A 26 65 8
08S 0.34
1CAN102104 Page 13 of 65 SG Row Col
%TW Elev Offset SG A 26 67 10 08S
-0.7 SG A 26 71 8
08S
-0.71 SG A 26 91 14 12S
-0.85 SG A 26 92 17 10S
-0.73 SG A 26 92 16 12S
-0.87 SG A 26 93 19 12S
-0.79 SG A 26 94 11 10S 0.13 SG A 26 94 12 12S
-0.83 SG A 26 95 6
10S 0.06 SG A 26 96 15 14S 0.19 SG A 26 99 12 12S
-0.85 SG A 27 15 13 10S
-0.64 SG A 27 27 7
08S
-0.68 SG A 27 28 9
08S 0.42 SG A 27 29 7
08S 0.43 SG A 27 30 10 08S
-0.7 SG A 27 31 6
08S
-0.71 SG A 27 32 10 08S
-0.72 SG A 27 34 10 08S
-0.74 SG A 27 36 11 08S
-0.72 SG A 27 36 15 08S 0.45 SG A 27 38 12 08S
-0.62 SG A 27 39 9
08S
-0.75 SG A 27 39 9
08S 0.39 SG A 27 40 9
08S
-0.75 SG A 27 41 8
08S
-0.77 SG A 27 42 8
09S
-0.72 SG A 27 43 7
08S
-0.71 SG A 27 45 7
07S 0.45 SG A 27 46 11 08S
-0.74 SG A 27 46 12 08S 0.4 SG A 27 49 10 08S
-0.82 SG A 27 51 13 08S
-0.84 SG A 27 51 7
08S 0.37 SG A 27 54 5
08S
-0.76 SG A 27 55 7
08S
-0.7 SG A 27 58 7
08S
-0.75 SG A 27 63 7
08S
-0.77 SG A 27 64 6
08S 0.41 SG A 27 69 8
08S 0.4
1CAN102104 Page 14 of 65 SG Row Col
%TW Elev Offset SG A 27 71 7
08S 0.42 SG A 27 92 14 15S 0.17 SG A 27 93 17 12S
-0.85 SG A 27 94 19 12S
-0.9 SG A 27 94 11 12S 0.28 SG A 27 95 21 12S
-0.86 SG A 27 97 8
10S 0.06 SG A 27 102 11 10S
-0.83 SG A 28 6
10 12S
-0.68 SG A 28 8
11 11S
-0.73 SG A 28 12 16 10S
-0.66 SG A 28 15 21 10S
-0.64 SG A 28 16 6
10S 0.47 SG A 28 27 8
08S
-0.71 SG A 28 28 10 08S 0.43 SG A 28 31 8
08S
-0.77 SG A 28 31 9
08S 0.45 SG A 28 32 10 08S
-0.72 SG A 28 35 9
08S
-0.73 SG A 28 38 13 08S
-0.68 SG A 28 40 13 08S
-0.75 SG A 28 41 12 08S
-0.73 SG A 28 41 8
08S 0.4 SG A 28 41 8
09S
-0.72 SG A 28 42 11 08S
-0.79 SG A 28 43 11 08S
-0.81 SG A 28 43 8
08S 0.38 SG A 28 46 13 08S
-0.83 SG A 28 54 7
08S 0.42 SG A 28 55 5
08S
-0.75 SG A 28 56 8
08S
-0.74 SG A 28 57 8
08S
-0.72 SG A 28 57 5
08S 0.38 SG A 28 80 13 15S 0.19 SG A 28 96 15 12S
-0.83 SG A 28 96 18 12S 0.21 SG A 28 97 9
12S
-0.89 SG A 28 98 13 12S
-0.83 SG A 29 9
16 10S 0.45 SG A 29 30 7
08S 0.43
1CAN102104 Page 15 of 65 SG Row Col
%TW Elev Offset SG A 29 31 13 08S
-0.66 SG A 29 32 10 08S
-0.75 SG A 29 33 16 08S
-0.68 SG A 29 33 12 08S 0.43 SG A 29 34 13 08S
-0.75 SG A 29 34 7
08S 0.43 SG A 29 41 8
08S
-0.76 SG A 29 42 12 08S
-0.79 SG A 29 44 10 08S
-0.79 SG A 29 49 11 08S
-0.79 SG A 29 51 15 08S
-0.81 SG A 29 51 15 08S 0.42 SG A 29 52 10 08S
-0.81 SG A 29 56 10 08S
-0.75 SG A 29 56 5
08S 0.36 SG A 29 57 9
08S 0.4 SG A 29 58 15 08S
-0.75 SG A 29 58 11 08S 0.43 SG A 29 60 5
08S 0.43 SG A 29 61 12 08S
-0.77 SG A 29 61 14 08S 0.4 SG A 29 62 6
08S
-0.72 SG A 29 63 13 08S
-0.74 SG A 29 63 11 08S 0.4 SG A 29 64 5
08S 0.45 SG A 29 66 6
08S 0.43 SG A 29 71 15 08S 0.34 SG A 29 72 7
08S 0.38 SG A 29 73 8
08S 0.4 SG A 29 96 12 12S
-0.88 SG A 29 97 30 12S 0.28 SG A 29 98 9
12S
-0.89 SG A 29 98 16 12S 0.28 SG A 29 99 12 12S
-0.87 SG A 30 31 12 08S
-0.72 SG A 30 32 11 08S
-0.73 SG A 30 33 17 08S
-0.79 SG A 30 34 11 08S
-0.75 SG A 30 36 14 08S
-0.74 SG A 30 37 12 08S
-0.74
1CAN102104 Page 16 of 65 SG Row Col
%TW Elev Offset SG A 30 38 12 08S
-0.76 SG A 30 39 12 08S
-0.76 SG A 30 40 11 08S
-0.78 SG A 30 41 7
08S
-0.72 SG A 30 42 11 08S
-0.79 SG A 30 47 15 08S 0.42 SG A 30 48 12 08S
-0.79 SG A 30 49 17 08S
-0.78 SG A 30 51 13 08S
-0.78 SG A 30 53 14 08S
-0.8 SG A 30 56 5
08S
-0.75 SG A 30 67 9
08S 0.4 SG A 30 68 9
08S
-0.77 SG A 30 70 4
08S 0.43 SG A 30 72 5
08S 0.38 SG A 30 73 9
08S 0.38 SG A 30 96 12 10S
-0.81 SG A 30 98 18 12S
-0.87 SG A 30 98 13 14S 0.17 SG A 30 99 10 10S 0.08 SG A 30 99 12 12S
-0.83 SG A 30 99 8
12S 0.27 SG A 30 99 13 14S 0.19 SG A 30 100 11 12S
-0.83 SG A 31 30 10 08S
-0.7 SG A 31 32 12 08S
-0.74 SG A 31 32 8
08S 0.43 SG A 31 33 7
08S 0.41 SG A 31 34 16 08S
-0.72 SG A 31 37 15 08S
-0.75 SG A 31 38 13 08S
-0.75 SG A 31 41 13 08S
-0.77 SG A 31 45 11 08S
-0.79 SG A 31 50 10 08S
-0.74 SG A 31 57 9
08S
-0.75 SG A 31 58 10 08S
-0.77 SG A 31 67 10 08S 0.41 SG A 31 70 10 08S 0.4 SG A 31 75 8
08S 0.36 SG A 31 79 10 08S 0.36
1CAN102104 Page 17 of 65 SG Row Col
%TW Elev Offset SG A 31 98 18 10S
-0.81 SG A 31 98 15 12S
-0.83 SG A 31 98 18 12S 0.23 SG A 31 100 13 10S 0.06 SG A 31 100 11 12S 0.25 SG A 31 101 16 10S 0.09 SG A 32 20 14 10S 0.32 SG A 32 23 7
08S
-0.68 SG A 32 25 17 08S
-0.7 SG A 32 25 10 08S 0.45 SG A 32 29 10 08S
-0.6 SG A 32 29 8
08S 0.42 SG A 32 31 7
08S 0.43 SG A 32 32 12 08S
-0.74 SG A 32 32 6
08S 0.49 SG A 32 33 10 08S
-0.75 SG A 32 34 11 08S
-0.74 SG A 32 34 10 08S 0.47 SG A 32 36 9
08S
-0.64 SG A 32 45 10 08S
-0.77 SG A 32 47 11 08S
-0.75 SG A 32 48 12 08S
-0.76 SG A 32 49 16 08S
-0.79 SG A 32 50 13 08S
-0.76 SG A 32 51 12 08S
-0.79 SG A 32 52 10 08S
-0.79 SG A 32 52 10 08S 0.42 SG A 32 53 13 08S
-0.78 SG A 32 54 15 08S
-0.76 SG A 32 65 10 08S 0.4 SG A 32 67 7
08S 0.42 SG A 32 70 4
08S 0.43 SG A 32 73 6
08S 0.4 SG A 32 81 12 08S
-0.81 SG A 32 97 21 10S
-0.83 SG A 32 98 12 12S
-0.85 SG A 32 98 17 12S 0.28 SG A 32 99 11 10S 0.15 SG A 32 99 12 12S 0.21 SG A 32 100 9
10S 0.08
1CAN102104 Page 18 of 65 SG Row Col
%TW Elev Offset SG A 32 100 6
14S 0.17 SG A 32 102 6
14S 0.21 SG A 33 18 11 08S
-0.69 SG A 33 21 9
08S
-0.59 SG A 33 21 6
09S
-0.66 SG A 33 21 15 10S 0.4 SG A 33 22 8
08S
-0.71 SG A 33 23 6
08S 0.45 SG A 33 24 13 09S
-0.73 SG A 33 25 10 08S
-0.74 SG A 33 29 11 08S
-0.7 SG A 33 30 7
08S 0.4 SG A 33 31 11 08S
-0.73 SG A 33 32 11 08S
-0.77 SG A 33 34 11 08S
-0.77 SG A 33 34 11 08S 0.41 SG A 33 36 15 08S
-0.75 SG A 33 37 11 08S
-0.76 SG A 33 37 11 09S
-0.72 SG A 33 37 11 09S 0.38 SG A 33 38 14 08S
-0.74 SG A 33 38 11 08S 0.41 SG A 33 38 13 09S
-0.77 SG A 33 40 11 08S
-0.78 SG A 33 43 10 08S
-0.74 SG A 33 44 12 08S
-0.75 SG A 33 45 17 08S
-0.74 SG A 33 45 12 08S 0.4 SG A 33 51 11 08S
-0.76 SG A 33 57 11 08S
-0.72 SG A 33 58 12 08S
-0.74 SG A 33 59 10 08S
-0.77 SG A 33 60 9
08S
-0.76 SG A 33 61 11 08S
-0.78 SG A 33 66 12 08S
-0.74 SG A 33 67 14 08S
-0.72 SG A 33 71 17 08S 0.38 SG A 33 72 6
08S 0.4 SG A 33 73 12 08S
-0.77 SG A 33 75 9
08S 0.4
1CAN102104 Page 19 of 65 SG Row Col
%TW Elev Offset SG A 33 76 9
08S 0.38 SG A 33 77 9
08S
-0.72 SG A 33 77 9
08S 0.36 SG A 33 78 7
08S 0.38 SG A 33 79 11 11S
-0.91 SG A 33 80 8
08S
-0.75 SG A 33 103 15 12S
-0.78 SG A 34 6
11 09S
-0.67 SG A 34 6
9 12S
-0.73 SG A 34 26 11 08S
-0.71 SG A 34 27 12 08S
-0.64 SG A 34 34 13 08S
-0.76 SG A 34 36 6
08S
-0.7 SG A 34 48 10 08S
-0.78 SG A 34 51 11 08S
-0.79 SG A 34 56 11 08S
-0.76 SG A 34 57 14 08S
-0.81 SG A 34 69 5
08S 0.45 SG A 34 75 9
08S
-0.77 SG A 34 76 10 09S
-0.78 SG A 34 78 8
08S
-0.77 SG A 34 79 6
08S 0.4 SG A 34 82 5
08S 0.43 SG A 34 103 16 10S
-0.85 SG A 34 104 15 12S
-0.82 SG A 34 105 13 12S
-0.87 SG A 35 21 13 08S
-0.64 SG A 35 23 8
08S 0.41 SG A 35 24 12 08S
-0.7 SG A 35 35 12 08S
-0.72 SG A 35 38 13 08S
-0.75 SG A 35 45 12 08S 0.38 SG A 35 48 12 08S
-0.79 SG A 35 62 14 08S
-0.7 SG A 35 62 15 09S
-0.81 SG A 35 63 13 08S
-0.72 SG A 35 66 10 08S
-0.76 SG A 35 76 6
08S 0.36 SG A 35 77 9
08S 0.45 SG A 35 80 6
08S 0.4
1CAN102104 Page 20 of 65 SG Row Col
%TW Elev Offset SG A 35 82 6
08S
-0.78 SG A 35 82 9
08S 0.34 SG A 35 83 8
08S 0.43 SG A 35 84 7
08S 0.36 SG A 35 86 9
08S 0.38 SG A 35 87 7
08S 0.4 SG A 35 90 7
08S 0.38 SG A 35 106 6
11S 0.28 SG A 35 107 14 10S 0.26 SG A 35 107 9
14S 0.23 SG A 35 110 13 13S
-0.87 SG A 36 19 7
08S 0.49 SG A 36 21 7
08S 0.51 SG A 36 22 9
08S 0.45 SG A 36 24 9
08S
-0.68 SG A 36 25 9
08S
-0.73 SG A 36 27 10 08S
-0.69 SG A 36 30 9
08S
-0.68 SG A 36 32 8
10S
-0.71 SG A 36 69 11 08S
-0.78 SG A 36 69 22 08S 0.4 SG A 36 72 11 08S
-0.76 SG A 36 78 7
08S 0.49 SG A 36 82 7
08S 0.4 SG A 36 84 9
08S 0.38 SG A 36 87 6
08S 0.3 SG A 36 89 13 08S 0.3 SG A 36 107 9
11S 0.3 SG A 36 107 14 12S
-0.85 SG A 36 108 10 10S 0.13 SG A 36 109 10 10S 0.13 SG A 37 7
8 10S 0.51 SG A 37 16 15 14S
-0.77 SG A 37 24 8
08S 0.43 SG A 37 34 11 08S
-0.69 SG A 37 38 11 08S
-0.75 SG A 37 39 15 08S
-0.72 SG A 37 69 13 09S
-0.76 SG A 37 77 11 08S
-0.77 SG A 37 77 15 08S 0.38
1CAN102104 Page 21 of 65 SG Row Col
%TW Elev Offset SG A 37 85 10 08S 0.38 SG A 37 86 10 08S 0.38 SG A 37 87 13 08S 0.38 SG A 37 88 5
08S 0.34 SG A 37 108 9
12S 0.19 SG A 37 110 11 10S 0.06 SG A 37 111 10 10S 0.11 SG A 38 9
12 09S
-0.69 SG A 38 18 9
08S
-0.68 SG A 38 20 11 08S 0.51 SG A 38 23 11 08S
-0.73 SG A 38 24 9
08S 0.45 SG A 38 25 12 08S
-0.73 SG A 38 26 15 08S
-0.7 SG A 38 27 12 08S
-0.73 SG A 38 29 9
08S
-0.73 SG A 38 31 10 09S 0.36 SG A 38 80 10 08S 0.34 SG A 38 85 5
08S 0.38 SG A 38 86 6
08S
-0.81 SG A 38 89 8
08S 0.36 SG A 38 109 7
10S
-0.83 SG A 38 110 9
11S 0.32 SG A 38 110 12 12S
-0.91 SG A 38 111 7
10S
-0.74 SG A 39 23 7
08S 0.49 SG A 39 25 10 08S
-0.6 SG A 39 25 8
08S 0.53 SG A 39 27 8
08S
-0.66 SG A 39 27 11 08S 0.51 SG A 39 32 7
08S 0.45 SG A 39 35 11 08S
-0.76 SG A 39 89 17 08S 0.36 SG A 39 89 13 09S
-0.76 SG A 39 111 6
12S
-0.89 SG A 39 113 6
14S 0.21 SG A 40 8
16 11S
-0.73 SG A 40 9
13 11S 0.42 SG A 40 19 12 08S
-0.55 SG A 40 19 9
08S 0.49
1CAN102104 Page 22 of 65 SG Row Col
%TW Elev Offset SG A 40 23 14 08S
-0.68 SG A 40 24 12 08S
-0.73 SG A 40 25 16 08S
-0.7 SG A 40 27 15 08S
-0.59 SG A 40 28 13 08S
-0.66 SG A 40 31 10 08S 0.51 SG A 40 33 9
08S
-0.68 SG A 40 34 11 08S
-0.75 SG A 40 87 7
08S
-0.8 SG A 40 89 9
08S
-0.78 SG A 40 89 6
08S 0.4 SG A 40 92 16 08S 0.34 SG A 40 101 11 11S
-0.89 SG A 41 20 10 08S
-0.57 SG A 41 21 9
08S
-0.73 SG A 41 22 11 08S
-0.66 SG A 41 23 16 08S
-0.73 SG A 41 24 11 08S
-0.66 SG A 41 26 11 08S
-0.64 SG A 41 26 10 09S 0.42 SG A 41 27 11 08S
-0.73 SG A 41 28 11 08S
-0.62 SG A 41 29 15 08S
-0.62 SG A 41 31 10 08S
-0.73 SG A 41 32 13 09S
-0.72 SG A 41 93 7
08S 0.38 SG A 41 94 6
08S 0.4 SG A 41 109 13 14S 0.17 SG A 42 1
11 13S
-0.62 SG A 42 5
9 10S 0.49 SG A 42 17 9
08S
-0.62 SG A 42 17 10 09S 0.47 SG A 42 20 10 08S
-0.68 SG A 42 22 11 08S
-0.7 SG A 42 24 10 08S
-0.68 SG A 42 25 12 08S
-0.6 SG A 42 26 11 08S
-0.68 SG A 42 30 9
08S
-0.74 SG A 42 87 8
08S 0.4 SG A 43 2
13 13S
-0.66
1CAN102104 Page 23 of 65 SG Row Col
%TW Elev Offset SG A 43 14 5
08S 0.53 SG A 43 19 14 08S
-0.57 SG A 43 20 14 08S
-0.69 SG A 43 21 12 08S
-0.68 SG A 43 24 12 08S
-0.73 SG A 43 25 12 08S
-0.61 SG A 43 26 14 08S
-0.71 SG A 43 26 16 09S
-0.75 SG A 43 27 13 08S
-0.67 SG A 43 32 12 08S
-0.73 SG A 43 34 10 08S
-0.77 SG A 43 115 12 12S
-0.8 SG A 44 15 5
08S 0.54 SG A 44 22 11 08S
-0.62 SG A 44 23 12 08S
-0.66 SG A 44 24 15 08S
-0.59 SG A 44 25 12 09S
-0.77 SG A 44 29 11 08S
-0.74 SG A 44 95 9
08S 0.38 SG A 44 96 7
08S 0.36 SG A 44 97 10 08S 0.38 SG A 45 1
15 13S
-0.62 SG A 45 1
12 13S 0.47 SG A 45 1
11 14S 0.49 SG A 45 5
10 14S 0.41 SG A 45 15 9
08S
-0.62 SG A 45 20 17 08S
-0.57 SG A 45 20 10 09S
-0.66 SG A 45 22 10 08S
-0.67 SG A 45 23 10 08S
-0.54 SG A 45 24 14 08S
-0.7 SG A 45 24 12 09S
-0.7 SG A 45 25 11 08S
-0.73 SG A 45 32 12 08S
-0.66 SG A 45 35 11 08S
-0.71 SG A 45 91 7
08S 0.36 SG A 45 96 7
08S 0.38 SG A 45 97 9
08S 0.4 SG A 45 115 8
12S
-0.87 SG A 46 1
13 13S
-0.66
1CAN102104 Page 24 of 65 SG Row Col
%TW Elev Offset SG A 46 1
14 13S 0.47 SG A 46 11 9
11S
-0.68 SG A 46 20 8
08S
-0.65 SG A 46 22 8
08S 0.47 SG A 46 23 15 08S
-0.63 SG A 46 23 6
08S 0.54 SG A 46 24 10 08S
-0.68 SG A 46 24 12 09S
-0.68 SG A 46 25 11 08S
-0.64 SG A 46 26 13 08S
-0.72 SG A 46 92 6
08S 0.4 SG A 46 94 6
08S 0.4 SG A 46 96 9
08S 0.4 SG A 46 112 10 11S 0.28 SG A 46 117 11 12S
-0.79 SG A 46 118 10 12S
-0.89 SG A 47 7
7 10S 0.51 SG A 47 17 8
08S
-0.62 SG A 47 21 10 08S
-0.63 SG A 47 23 12 08S
-0.65 SG A 47 27 11 08S
-0.71 SG A 47 28 11 08S
-0.68 SG A 47 82 9
08S 0.4 SG A 47 88 9
08S
-0.76 SG A 47 94 6
08S
-0.78 SG A 47 113 9
10S
-0.81 SG A 47 118 7
14S 0.21 SG A 48 4
10 11S
-0.64 SG A 48 5
14 10S 0.3 SG A 48 22 9
08S
-0.58 SG A 48 25 11 08S
-0.7 SG A 48 27 9
08S
-0.58 SG A 48 28 10 08S
-0.72 SG A 48 98 5
08S 0.38 SG A 48 112 9
14S 0.17 SG A 49 8
9 09S 0.56 SG A 49 17 9
08S
-0.64 SG A 49 25 11 08S
-0.61 SG A 49 29 13 08S
-0.71 SG A 49 91 11 08S 0.38
1CAN102104 Page 25 of 65 SG Row Col
%TW Elev Offset SG A 49 93 15 08S 0.36 SG A 49 100 7
08S 0.4 SG A 49 102 9
07S 0.38 SG A 49 102 8
10S
-0.87 SG A 49 115 8
10S
-0.8 SG A 50 17 11 09S 0.49 SG A 50 31 11 08S
-0.71 SG A 50 92 9
08S 0.38 SG A 50 94 8
08S 0.36 SG A 50 95 11 08S 0.4 SG A 50 96 10 08S
-0.77 SG A 51 1
18 13S
-0.62 SG A 51 7
18 10S 0.17 SG A 51 8
14 10S 0.42 SG A 51 18 15 08S
-0.62 SG A 51 22 14 08S
-0.66 SG A 51 99 8
09S
-0.78 SG A 51 100 11 08S 0.36 SG A 51 101 11 08S 0.4 SG A 51 104 8
08S 0.38 SG A 51 111 12 10S
-0.81 SG A 51 111 21 12S
-0.9 SG A 51 112 10 10S
-0.81 SG A 51 112 9
14S 0.19 SG A 52 16 14 08S
-0.6 SG A 52 18 12 08S
-0.54 SG A 52 27 11 09S 0.42 SG A 52 104 12 08S 0.38 SG A 52 107 7
08S 0.38 SG A 52 113 13 09S 0.34 SG A 52 114 22 10S
-0.8 SG A 52 118 11 10S
-0.82 SG A 53 1
17 13S
-0.62 SG A 53 2
21 13S 0.47 SG A 53 8
14 10S 0.19 SG A 53 11 11 09S 0.47 SG A 53 19 13 08S
-0.62 SG A 53 20 12 08S
-0.64 SG A 53 20 8
08S 0.52 SG A 53 22 18 08S
-0.69
1CAN102104 Page 26 of 65 SG Row Col
%TW Elev Offset SG A 53 23 13 08S
-0.68 SG A 53 24 14 08S
-0.6 SG A 53 26 12 08S
-0.62 SG A 53 95 11 08S 0.38 SG A 53 97 12 08S 0.38 SG A 53 98 9
08S 0.38 SG A 53 116 10 14S 0.13 SG A 53 121 13 12S 0.25 SG A 53 122 4
14S 0.17 SG A 53 123 10 12S
-0.84 SG A 53 123 11 14S 0.21 SG A 54 3
10 13S
-0.66 SG A 54 9
10 09S 0.52 SG A 54 11 10 09S 0.49 SG A 54 19 11 08S 0.54 SG A 54 20 15 08S
-0.66 SG A 54 21 10 08S
-0.6 SG A 54 21 10 08S 0.54 SG A 54 22 12 08S
-0.7 SG A 54 23 13 08S
-0.71 SG A 54 24 16 08S
-0.63 SG A 54 25 12 08S
-0.75 SG A 54 26 14 08S
-0.7 SG A 54 27 10 08S
-0.7 SG A 54 28 13 08S
-0.72 SG A 54 31 9
08S
-0.71 SG A 54 95 9
06S
-0.74 SG A 54 96 11 08S 0.38 SG A 54 106 7
08S 0.38 SG A 54 109 9
08S
-0.72 SG A 54 109 12 08S 0.36 SG A 54 114 15 09S 0.34 SG A 54 115 12 12S
-0.89 SG A 54 116 15 10S
-0.79 SG A 54 119 18 10S
-0.78 SG A 54 121 10 10S 0
SG A 54 121 8
11S 0.3 SG A 54 123 8
12S
-0.85 SG A 54 124 12 12S
-0.79 SG A 55 8
9 09S 0.55
1CAN102104 Page 27 of 65 SG Row Col
%TW Elev Offset SG A 55 9
15 09S 0.55 SG A 55 12 12 09S 0.45 SG A 55 19 12 08S
-0.66 SG A 55 22 11 08S
-0.66 SG A 55 23 19 08S
-0.68 SG A 55 24 13 08S
-0.72 SG A 55 26 14 08S
-0.72 SG A 55 27 11 08S
-0.66 SG A 55 28 13 08S
-0.72 SG A 55 28 10 08S 0.49 SG A 55 30 12 08S
-0.74 SG A 55 31 11 08S 0.47 SG A 55 31 11 09S 0.41 SG A 55 32 12 08S
-0.74 SG A 55 93 11 08S 0.38 SG A 55 94 11 08S 0.41 SG A 55 95 12 08S 0.38 SG A 55 99 10 08S 0.34 SG A 55 101 14 08S
-0.78 SG A 55 101 12 08S 0.4 SG A 55 102 10 08S 0.36 SG A 55 103 11 08S 0.38 SG A 55 116 11 11S 0.23 SG A 55 118 10 11S 0.23 SG A 55 119 17 11S 0.25 SG A 55 119 10 12S
-0.89 SG A 55 121 12 09S
-0.83 SG A 55 121 19 10S
-0.78 SG A 55 121 13 10S 0.11 SG A 55 121 13 11S 0.27 SG A 55 121 18 12S 0.25 SG A 55 122 20 09S
-0.75 SG A 55 122 11 09S 0.36 SG A 55 122 12 11S 0.28 SG A 55 123 11 12S
-0.88 SG A 56 7
7 09S
-0.66 SG A 56 7
10 10S 0.58 SG A 56 8
18 09S 0.5 SG A 56 19 10 08S
-0.6 SG A 56 19 8
08S 0.45
1CAN102104 Page 28 of 65 SG Row Col
%TW Elev Offset SG A 56 20 12 08S
-0.64 SG A 56 20 10 08S 0.52 SG A 56 21 14 08S
-0.62 SG A 56 23 16 08S
-0.66 SG A 56 24 17 08S
-0.64 SG A 56 26 12 08S
-0.66 SG A 56 27 11 08S
-0.72 SG A 56 28 10 08S
-0.67 SG A 56 28 11 08S 0.49 SG A 56 29 12 08S
-0.7 SG A 56 102 15 08S 0.36 SG A 56 118 10 09S 0.32 SG A 56 118 13 11S
-0.89 SG A 56 119 13 10S
-0.77 SG A 56 120 23 12S 0.19 SG A 56 120 11 14S 0.15 SG A 56 121 15 09S
-0.77 SG A 56 122 23 09S
-0.74 SG A 56 122 12 11S 0.21 SG A 56 122 10 12S
-0.93 SG A 56 123 10 09S
-0.77 SG A 56 123 11 10S
-0.83 SG A 56 123 11 12S 0.23 SG A 56 127 11 12S
-0.87 SG A 57 20 14 08S 0.45 SG A 57 21 17 08S
-0.7 SG A 57 21 7
08S 0.45 SG A 57 22 13 08S
-0.62 SG A 57 23 14 08S
-0.64 SG A 57 25 12 08S
-0.7 SG A 57 27 13 08S
-0.76 SG A 57 27 10 09S
-0.74 SG A 57 30 11 08S
-0.71 SG A 57 105 16 08S
-0.72 SG A 57 107 11 07S
-0.68 SG A 57 107 7
09S
-0.78 SG A 57 107 10 10S
-0.82 SG A 57 124 12 12S
-0.83 SG A 57 125 13 12S
-0.91 SG A 58 3
12 13S
-0.59
1CAN102104 Page 29 of 65 SG Row Col
%TW Elev Offset SG A 58 4
15 13S
-0.69 SG A 58 20 9
08S 0.4 SG A 58 21 12 08S
-0.56 SG A 58 21 7
08S 0.54 SG A 58 22 12 08S
-0.64 SG A 58 23 13 08S
-0.6 SG A 58 24 11 08S
-0.68 SG A 58 24 7
08S 0.51 SG A 58 25 11 08S
-0.69 SG A 58 25 10 08S 0.52 SG A 58 29 9
08S
-0.71 SG A 58 33 11 08S
-0.73 SG A 58 104 10 07S 0.38 SG A 58 125 16 12S
-0.87 SG A 59 20 12 08S
-0.51 SG A 59 21 8
08S 0.49 SG A 59 29 14 08S
-0.72 SG A 59 95 10 08S 0.36 SG A 59 105 10 08S
-0.82 SG A 59 124 12 10S
-0.79 SG A 59 124 13 11S 0.21 SG A 59 125 15 12S
-0.62 SG A 60 7
12 10S
-0.54 SG A 60 9
12 11S
-0.64 SG A 60 21 12 08S
-0.69 SG A 60 21 6
08S 0.54 SG A 60 22 12 08S
-0.7 SG A 60 23 16 08S
-0.58 SG A 60 24 15 08S
-0.61 SG A 60 103 12 08S 0.38 SG A 60 108 14 08S 0.38 SG A 60 124 16 11S 0.31 SG A 60 125 12 10S
-0.8 SG A 60 125 12 12S
-0.85 SG A 61 21 14 08S
-0.6 SG A 61 21 6
08S 0.47 SG A 61 22 15 08S
-0.64 SG A 61 22 9
08S 0.51 SG A 61 23 12 08S
-0.64 SG A 61 100 10 08S 0.36
1CAN102104 Page 30 of 65 SG Row Col
%TW Elev Offset SG A 61 101 19 08S 0.36 SG A 61 103 10 08S
-0.78 SG A 61 103 11 08S 0.32 SG A 61 124 14 12S
-0.89 SG A 61 125 18 10S
-0.74 SG A 61 125 6
10S 0.21 SG A 61 125 19 11S 0.27 SG A 61 125 13 12S
-0.91 SG A 62 19 11 08S
-0.62 SG A 62 22 9
08S
-0.68 SG A 62 26 12 08S
-0.72 SG A 62 26 9
08S 0.42 SG A 62 98 11 08S
-0.81 SG A 62 98 14 08S 0.38 SG A 62 99 13 08S 0.36 SG A 62 100 8
08S
-0.77 SG A 62 107 11 08S 0.38 SG A 62 122 11 09S 0.36 SG A 62 122 9
14S 0.17 SG A 63 19 10 08S
-0.62 SG A 63 20 13 08S
-0.53 SG A 63 21 15 08S
-0.62 SG A 63 22 16 08S
-0.64 SG A 63 22 6
08S 0.53 SG A 63 23 13 08S
-0.59 SG A 63 25 8
08S
-0.68 SG A 63 26 10 08S
-0.7 SG A 63 27 10 08S
-0.71 SG A 63 101 10 08S 0.36 SG A 63 111 10 08S 0.42 SG A 63 124 13 12S
-0.96 SG A 63 125 16 06S
-0.72 SG A 63 125 18 10S
-0.74 SG A 63 125 13 11S
-0.82 SG A 63 125 13 12S
-0.95 SG A 64 12 13 11S
-0.68 SG A 64 20 13 08S
-0.61 SG A 64 22 12 08S
-0.59 SG A 64 24 12 08S
-0.66 SG A 64 25 18 08S
-0.72
1CAN102104 Page 31 of 65 SG Row Col
%TW Elev Offset SG A 64 25 11 08S 0.44 SG A 64 27 9
08S
-0.7 SG A 64 31 10 08S
-0.74 SG A 64 103 14 06S
-0.72 SG A 64 103 12 08S 0.32 SG A 64 103 14 10S
-0.87 SG A 64 104 15 08S 0.38 SG A 64 105 14 08S
-0.76 SG A 64 106 10 06S 0.4 SG A 64 124 10 14S 0.15 SG A 64 126 10 14S 0.17 SG A 65 20 11 08S
-0.63 SG A 65 21 15 08S
-0.61 SG A 65 23 11 08S
-0.7 SG A 65 24 12 08S
-0.65 SG A 65 26 18 08S
-0.73 SG A 65 27 8
08S 0.44 SG A 65 28 13 08S
-0.66 SG A 65 30 10 08S
-0.73 SG A 65 31 10 08S 0.42 SG A 65 32 14 08S
-0.71 SG A 65 103 11 06S
-0.7 SG A 65 104 12 05S
-0.68 SG A 65 104 11 10S
-0.87 SG A 65 106 12 08S 0.38 SG A 65 107 10 08S 0.38 SG A 65 107 19 10S
-0.83 SG A 65 107 19 10S 0.19 SG A 65 110 11 07S 0.37 SG A 65 110 10 09S
-0.67 SG A 65 110 11 10S 0.25 SG A 65 125 13 10S
-0.74 SG A 65 125 14 10S 0.28 SG A 65 125 14 11S
-0.85 SG A 65 126 10 06S
-0.66 SG A 66 17 10 09S 0.49 SG A 66 20 11 08S
-0.61 SG A 66 21 8
08S
-0.54 SG A 66 22 14 08S
-0.65 SG A 66 23 10 08S
-0.63
1CAN102104 Page 32 of 65 SG Row Col
%TW Elev Offset SG A 66 24 13 08S
-0.64 SG A 66 26 27 08S
-0.7 SG A 66 27 13 08S
-0.69 SG A 66 28 13 08S
-0.72 SG A 66 101 14 08S
-0.78 SG A 66 106 11 08S
-0.79 SG A 66 108 10 08S 0.38 SG A 66 123 11 10S 0.27 SG A 66 124 12 10S
-0.79 SG A 66 124 10 11S 0.24 SG A 66 124 11 12S 0.23 SG A 66 124 11 14S 0.17 SG A 66 125 16 06S
-0.74 SG A 67 2
16 13S 0.53 SG A 67 4
10 13S 0.47 SG A 67 20 14 08S
-0.61 SG A 67 21 9
08S
-0.65 SG A 67 22 12 08S
-0.61 SG A 67 23 15 08S
-0.63 SG A 67 24 12 08S
-0.7 SG A 67 25 12 08S
-0.67 SG A 67 26 14 08S
-0.66 SG A 67 27 15 08S
-0.72 SG A 67 28 13 08S
-0.68 SG A 67 29 19 08S
-0.72 SG A 67 30 14 08S
-0.7 SG A 67 102 9
07S
-0.72 SG A 67 105 12 07S 0.38 SG A 67 105 15 09S
-0.8 SG A 67 105 11 10S 0.32 SG A 67 111 15 09S
-0.78 SG A 67 111 12 10S
-0.85 SG A 67 124 12 09S 0.32 SG A 67 124 9
11S 0.28 SG A 67 125 10 09S 0.36 SG A 67 125 13 12S
-0.88 SG A 68 2
14 13S 0.51 SG A 68 18 11 08S
-0.56 SG A 68 22 10 08S
-0.66 SG A 68 24 16 08S
-0.66
1CAN102104 Page 33 of 65 SG Row Col
%TW Elev Offset SG A 68 24 8
08S 0.49 SG A 68 25 12 08S
-0.72 SG A 68 26 13 08S
-0.68 SG A 68 27 9
08S
-0.68 SG A 68 28 23 08S
-0.72 SG A 68 29 12 08S
-0.73 SG A 68 31 15 08S
-0.71 SG A 68 32 12 08S
-0.74 SG A 68 109 11 09S
-0.83 SG A 68 113 12 10S
-0.82 SG A 68 126 10 09S 0.34 SG A 69 2
12 11S
-0.66 SG A 69 2
10 13S 0.51 SG A 69 4
11 10S 0.26 SG A 69 4
11 13S
-0.64 SG A 69 24 12 08S
-0.73 SG A 69 25 7
08S 0.53 SG A 69 26 13 08S
-0.73 SG A 69 26 11 09S
-0.73 SG A 69 27 23 08S
-0.7 SG A 69 28 13 08S
-0.66 SG A 69 29 11 08S
-0.72 SG A 69 102 11 08S
-0.8 SG A 69 110 13 10S
-0.74 SG A 69 110 10 10S 0.34 SG A 69 126 9
09S 0.3 SG A 69 126 17 11S 0.28 SG A 69 127 12 10S
-0.82 SG A 70 1
8 11S 0.54 SG A 70 3
9 13S
-0.64 SG A 70 4
11 10S 0.25 SG A 70 4
17 13S 0.47 SG A 70 6
10 13S
-0.66 SG A 70 19 9
08S
-0.64 SG A 70 20 11 08S
-0.68 SG A 70 21 9
08S
-0.71 SG A 70 22 11 09S
-0.66 SG A 70 23 10 08S
-0.53 SG A 70 25 11 08S
-0.71 SG A 70 26 14 08S
-0.68
1CAN102104 Page 34 of 65 SG Row Col
%TW Elev Offset SG A 70 28 15 08S
-0.7 SG A 70 103 13 08S 0.38 SG A 70 104 12 06S
-0.63 SG A 70 104 9
07S 0.42 SG A 70 104 18 09S
-0.76 SG A 70 105 12 08S
-0.76 SG A 70 106 10 08S 0.38 SG A 70 109 12 08S 0.4 SG A 70 119 12 14S 0.17 SG A 70 125 17 12S
-0.86 SG A 71 1
12 11S
-0.6 SG A 71 4
22 13S
-0.63 SG A 71 4
14 13S 0.47 SG A 71 5
12 09S
-0.49 SG A 71 5
11 13S
-0.67 SG A 71 21 8
08S 0.49 SG A 71 23 16 08S
-0.68 SG A 71 23 8
08S 0.45 SG A 71 24 17 08S
-0.63 SG A 71 25 18 08S
-0.7 SG A 71 26 14 08S
-0.72 SG A 71 27 18 08S
-0.72 SG A 71 27 12 08S 0.38 SG A 71 27 15 09S 0.47 SG A 71 30 10 08S
-0.71 SG A 71 31 19 08S
-0.7 SG A 71 32 13 08S
-0.71 SG A 71 102 14 08S 0.4 SG A 71 103 10 08S
-0.78 SG A 71 104 12 08S
-0.81 SG A 71 105 20 06S
-0.7 SG A 71 105 6
07S 0.42 SG A 71 105 11 08S 0.36 SG A 71 105 17 09S
-0.76 SG A 71 105 10 10S
-0.85 SG A 71 107 11 08S
-0.82 SG A 71 107 11 08S 0.36 SG A 71 110 12 08S 0.38 SG A 71 112 10 08S 0.4 SG A 71 112 6
10S
-0.81
1CAN102104 Page 35 of 65 SG Row Col
%TW Elev Offset SG A 72 1
13 13S
-0.58 SG A 72 4
13 13S
-0.66 SG A 72 22 13 08S
-0.57 SG A 72 24 12 08S
-0.59 SG A 72 25 18 08S
-0.66 SG A 72 26 12 08S
-0.71 SG A 72 27 12 08S
-0.68 SG A 72 28 10 08S
-0.73 SG A 72 29 18 08S
-0.7 SG A 72 31 11 08S
-0.72 SG A 72 103 7
08S 0.42 SG A 72 106 13 08S
-0.77 SG A 72 106 10 08S 0.35 SG A 72 107 10 08S
-0.78 SG A 72 109 14 08S 0.38 SG A 72 109 9
10S
-0.84 SG A 72 110 12 08S 0.4 SG A 72 111 15 08S 0.4 SG A 72 111 10 10S
-0.82 SG A 72 124 10 10S 0.32 SG A 72 125 14 11S 0.23 SG A 73 2
6 11S 0.61 SG A 73 10 7
09S 0.53 SG A 73 17 12 08S
-0.66 SG A 73 18 10 08S
-0.51 SG A 73 19 10 08S
-0.64 SG A 73 20 11 08S
-0.61 SG A 73 25 20 08S
-0.63 SG A 73 26 13 08S
-0.63 SG A 73 27 17 08S
-0.66 SG A 73 28 12 08S
-0.68 SG A 73 29 16 08S 0.4 SG A 73 31 11 08S 0.47 SG A 73 104 12 06S
-0.74 SG A 73 104 9
09S
-0.82 SG A 73 105 9
08S 0.38 SG A 73 107 11 10S
-0.84 SG A 73 108 13 09S
-0.79 SG A 73 109 11 07S 0.36 SG A 73 109 11 08S
-0.74
1CAN102104 Page 36 of 65 SG Row Col
%TW Elev Offset SG A 73 110 15 09S
-0.79 SG A 73 111 11 08S 0.38 SG A 73 113 10 08S 0.4 SG A 73 115 12 07S 0.55 SG A 73 131 24 12S 0.23 SG A 74 2
23 13S 0.49 SG A 74 6
8 09S 0.57 SG A 74 24 11 08S
-0.7 SG A 74 25 11 08S
-0.71 SG A 74 26 14 08S
-0.72 SG A 74 27 11 08S
-0.73 SG A 74 28 9
08S
-0.74 SG A 74 30 12 08S
-0.72 SG A 74 39 13 08S
-0.73 SG A 74 104 9
08S
-0.78 SG A 74 107 12 08S
-0.66 SG A 74 108 12 08S 0.36 SG A 74 108 10 09S
-0.8 SG A 74 109 11 07S 0.4 SG A 74 109 8
08S
-0.76 SG A 74 109 11 08S 0.38 SG A 74 109 14 09S
-0.81 SG A 74 110 10 05S
-0.7 SG A 74 110 16 06S
-0.61 SG A 74 110 12 06S 0.4 SG A 74 110 9
07S 0.42 SG A 74 110 13 08S 0.36 SG A 74 110 15 10S
-0.82 SG A 74 110 13 10S 0.3 SG A 74 116 9
09S
-0.76 SG A 74 124 12 11S 0.27 SG A 75 6
7 09S
-0.62 SG A 75 15 11 11S
-0.68 SG A 75 16 10 09S 0.49 SG A 75 18 9
08S
-0.64 SG A 75 20 9
08S
-0.64 SG A 75 21 13 08S
-0.61 SG A 75 22 8
08S
-0.64 SG A 75 26 12 08S
-0.73 SG A 75 27 11 08S
-0.68
1CAN102104 Page 37 of 65 SG Row Col
%TW Elev Offset SG A 75 28 12 08S
-0.75 SG A 75 30 9
08S
-0.73 SG A 75 105 11 07S 0.38 SG A 75 105 8
08S
-0.7 SG A 75 105 11 09S
-0.78 SG A 75 107 14 08S 0.36 SG A 75 107 10 09S
-0.74 SG A 75 108 16 06S
-0.69 SG A 75 108 8
08S
-0.7 SG A 75 108 12 08S 0.26 SG A 75 108 12 09S
-0.81 SG A 75 108 11 09S 0.35 SG A 75 109 22 06S 0.4 SG A 75 109 9
07S 0.4 SG A 75 109 13 08S 0.38 SG A 75 111 13 08S 0.34 SG A 75 113 12 06S
-0.67 SG A 76 5
5 09S 0.55 SG A 76 15 8
09S 0.51 SG A 76 17 5
08S 0.55 SG A 76 19 5
08S 0.53 SG A 76 20 14 08S
-0.61 SG A 76 22 17 08S
-0.66 SG A 76 23 12 08S
-0.65 SG A 76 23 7
08S 0.51 SG A 76 23 6
09S
-0.7 SG A 76 26 11 08S
-0.65 SG A 76 27 11 08S
-0.69 SG A 76 28 14 08S
-0.71 SG A 76 89 7
05S 0.51 SG A 76 101 8
08S 0.34 SG A 76 102 22 06S
-0.78 SG A 76 102 18 10S
-0.85 SG A 76 105 7
08S
-0.7 SG A 76 105 9
09S
-0.78 SG A 76 106 12 06S
-0.74 SG A 76 106 13 08S 0.36 SG A 76 107 7
06S 0.44 SG A 76 107 8
08S 0.32 SG A 76 108 10 08S 0.38
1CAN102104 Page 38 of 65 SG Row Col
%TW Elev Offset SG A 76 110 11 08S 0.38 SG A 76 111 11 08S 0.38 SG A 76 120 16 10S 0.26 SG A 76 122 13 11S 0.26 SG A 76 122 7
12S
-0.85 SG A 76 123 16 11S 0.28 SG A 76 124 11 06S
-0.68 SG A 76 124 11 12S 0.23 SG A 77 2
19 11S 0.53 SG A 77 4
10 13S 0.44 SG A 77 19 7
08S 0.51 SG A 77 22 10 08S 0.53 SG A 77 23 14 08S
-0.65 SG A 77 23 7
08S 0.55 SG A 77 27 11 08S 0.45 SG A 77 28 11 08S
-0.7 SG A 77 104 8
08S 0.36 SG A 77 109 10 06S 0.38 SG A 77 109 13 08S
-0.76 SG A 77 109 14 08S 0.36 SG A 77 109 11 09S
-0.78 SG A 77 110 11 08S 0.36 SG A 77 110 10 10S 0.3 SG A 77 112 13 08S 0.43 SG A 77 117 6
09S
-0.77 SG A 77 118 15 10S
-0.83 SG A 77 132 26 10S 0
SG A 78 8
11 11S
-0.66 SG A 78 17 9
08S
-0.49 SG A 78 19 10 08S
-0.61 SG A 78 23 11 08S
-0.65 SG A 78 25 12 09S 0.44 SG A 78 103 10 08S 0.38 SG A 78 105 11 08S 0.36 SG A 78 107 13 08S
-0.76 SG A 78 111 12 08S
-0.79 SG A 78 115 11 07S
-0.6 SG A 78 124 12 10S 0.3 SG A 78 125 11 11S 0.21 SG A 78 125 12 12S
-0.81
1CAN102104 Page 39 of 65 SG Row Col
%TW Elev Offset SG A 78 131 10 10S
-0.81 SG A 79 3
6 13S 0.51 SG A 79 17 11 09S 0.51 SG A 79 19 7
08S 0.53 SG A 79 20 11 08S
-0.63 SG A 79 21 8
08S 0.53 SG A 79 24 13 08S
-0.69 SG A 79 27 7
08S 0.51 SG A 79 28 15 08S
-0.72 SG A 79 29 14 08S
-0.69 SG A 79 30 6
08S 0.46 SG A 79 110 8
08S 0.34 SG A 79 111 13 08S 0.38 SG A 79 113 11 08S 0.4 SG A 79 123 12 10S 0.28 SG A 79 126 11 14S 0.15 SG A 80 5
11 09S 0.57 SG A 80 5
11 12S 0.49 SG A 80 25 11 08S
-0.67 SG A 80 28 10 08S
-0.69 SG A 80 107 12 08S 0.36 SG A 80 109 6
08S 0.38 SG A 80 110 13 10S
-0.89 SG A 80 113 7
08S 0.37 SG A 80 125 21 11S 0.3 SG A 81 13 10 09S 0.51 SG A 81 15 12 08S
-0.53 SG A 81 17 12 08S
-0.62 SG A 81 17 7
08S 0.53 SG A 81 18 10 08S
-0.64 SG A 81 23 11 08S 0.47 SG A 81 24 11 08S
-0.66 SG A 81 25 7
08S 0.45 SG A 81 26 13 08S
-0.72 SG A 81 111 8
05S
-0.7 SG A 81 111 19 06S
-0.71 SG A 81 114 6
08S 0.41 SG A 81 115 13 08S 0.4 SG A 81 124 10 09S
-0.7 SG A 81 126 10 10S
-0.83
1CAN102104 Page 40 of 65 SG Row Col
%TW Elev Offset SG A 81 126 39 11S 0.3 SG A 81 128 12 12S 0.28 SG A 82 9
10 11S
-0.66 SG A 82 11 11 09S 0.53 SG A 82 14 11 11S
-0.66 SG A 82 18 11 08S
-0.59 SG A 82 19 12 08S
-0.59 SG A 82 20 8
08S
-0.66 SG A 82 22 10 08S
-0.64 SG A 82 22 8
08S 0.51 SG A 82 23 7
08S 0.51 SG A 82 24 13 08S
-0.68 SG A 82 24 7
08S 0.51 SG A 82 26 12 08S
-0.72 SG A 82 76 8
09S 0.49 SG A 82 111 11 06S
-0.72 SG A 82 111 11 08S 0.38 SG A 82 113 10 08S 0.38 SG A 82 115 7
08S 0.42 SG A 82 115 5
09S
-0.76 SG A 82 117 10 08S 0.38 SG A 83 6
8 10S 0.53 SG A 83 10 13 11S
-0.68 SG A 83 15 10 08S
-0.57 SG A 83 18 8
08S
-0.64 SG A 83 19 6
08S 0.45 SG A 83 20 15 08S
-0.59 SG A 83 21 9
08S
-0.61 SG A 83 21 8
08S 0.53 SG A 83 23 18 08S
-0.67 SG A 83 23 7
08S 0.45 SG A 83 24 11 08S
-0.66 SG A 83 25 11 08S
-0.72 SG A 83 25 8
08S 0.44 SG A 83 26 11 08S
-0.7 SG A 83 28 9
08S
-0.72 SG A 83 29 9
08S
-0.74 SG A 83 29 7
08S 0.47 SG A 83 32 10 08S
-0.7 SG A 83 112 11 10S
-0.77
1CAN102104 Page 41 of 65 SG Row Col
%TW Elev Offset SG A 83 114 14 08S 0.41 SG A 83 126 10 10S
-0.83 SG A 84 6
10 09S 0.53 SG A 84 8
14 10S
-0.62 SG A 84 9
15 11S
-0.66 SG A 84 15 5
08S 0.55 SG A 84 17 9
08S
-0.61 SG A 84 17 7
08S 0.51 SG A 84 18 12 08S
-0.61 SG A 84 18 6
08S 0.53 SG A 84 20 10 08S
-0.55 SG A 84 21 12 08S
-0.61 SG A 84 21 7
08S 0.46 SG A 84 22 16 08S
-0.63 SG A 84 22 8
08S 0.52 SG A 84 23 15 08S
-0.66 SG A 84 24 12 08S
-0.66 SG A 84 26 15 08S
-0.68 SG A 84 27 16 08S
-0.7 SG A 84 29 11 08S
-0.7 SG A 84 30 12 08S
-0.7 SG A 84 107 5
08S
-0.72 SG A 84 110 11 08S 0.4 SG A 84 111 14 08S 0.38 SG A 84 113 10 08S 0.4 SG A 84 116 11 08S 0.38 SG A 84 116 8
09S
-0.79 SG A 84 124 17 10S 0.26 SG A 84 125 14 09S 0.34 SG A 84 125 12 10S
-0.78 SG A 84 126 11 10S
-0.77 SG A 85 6
8 09S
-0.55 SG A 85 6
9 09S 0.53 SG A 85 11 12 11S
-0.68 SG A 85 17 11 08S
-0.55 SG A 85 17 5
08S 0.53 SG A 85 19 6
08S 0.49 SG A 85 19 11 09S 0.44 SG A 85 21 11 08S
-0.68 SG A 85 23 9
08S
-0.56
1CAN102104 Page 42 of 65 SG Row Col
%TW Elev Offset SG A 85 23 6
08S 0.52 SG A 85 24 9
08S
-0.68 SG A 85 25 10 08S
-0.7 SG A 85 27 11 08S 0.45 SG A 85 29 13 08S
-0.7 SG A 85 30 10 08S
-0.7 SG A 85 30 10 08S 0.45 SG A 85 97 8
07S 0.51 SG A 85 109 12 08S
-0.74 SG A 85 112 7
08S 0.36 SG A 85 123 34 10S 0
SG A 85 123 11 11S 0.42 SG A 85 124 20 11S 0.3 SG A 86 6
7 09S 0.53 SG A 86 18 6
08S 0.55 SG A 86 22 7
08S 0.49 SG A 86 23 12 08S
-0.7 SG A 86 24 9
08S
-0.7 SG A 86 27 11 08S 0.4 SG A 86 78 11 09S 0.44 SG A 86 97 11 08S
-0.76 SG A 86 112 8
08S 0.38 SG A 86 114 8
08S 0.41 SG A 86 123 12 10S 0.23 SG A 86 124 12 11S 0.32 SG A 86 124 17 13S
-0.9 SG A 87 5
7 09S 0.53 SG A 87 20 11 08S
-0.64 SG A 87 21 10 08S
-0.63 SG A 87 22 9
08S
-0.68 SG A 87 26 10 08S 0.45 SG A 87 27 5
08S 0.49 SG A 87 97 11 08S
-0.76 SG A 87 113 10 08S 0.4 SG A 87 129 12 14S
-0.89 SG A 88 5
8 09S 0.55 SG A 88 21 5
08S 0.53 SG A 88 22 9
08S
-0.68 SG A 88 23 11 08S
-0.68 SG A 88 23 8
08S 0.49
1CAN102104 Page 43 of 65 SG Row Col
%TW Elev Offset SG A 88 28 11 08S
-0.7 SG A 88 55 11 08S 0.47 SG A 88 111 10 08S 0.38 SG A 88 115 7
08S 0.38 SG A 88 125 14 12S
-0.83 SG A 88 127 12 13S
-0.89 SG A 89 3
6 10S 0.08 SG A 89 20 9
08S
-0.64 SG A 89 21 11 08S
-0.68 SG A 89 22 13 08S
-0.72 SG A 89 22 9
08S 0.45 SG A 89 22 11 09S 0.42 SG A 89 23 10 08S
-0.68 SG A 89 23 9
08S 0.49 SG A 89 24 12 08S 0.51 SG A 89 25 11 08S
-0.7 SG A 89 106 13 08S 0.38 SG A 89 107 8
09S
-0.81 SG A 90 3
6 10S 0.17 SG A 90 4
8 09S 0.55 SG A 90 5
9 09S 0.49 SG A 90 14 10 09S 0.51 SG A 90 19 10 08S
-0.63 SG A 90 22 8
08S
-0.68 SG A 90 22 6
08S 0.53 SG A 90 24 11 08S
-0.7 SG A 90 24 7
08S 0.51 SG A 90 26 9
08S 0.45 SG A 90 27 11 08S
-0.72 SG A 90 28 14 08S
-0.72 SG A 90 30 10 08S
-0.7 SG A 91 19 9
08S
-0.63 SG A 91 21 11 08S
-0.66 SG A 91 22 12 08S
-0.59 SG A 91 23 11 08S
-0.68 SG A 91 24 14 08S
-0.66 SG A 91 25 16 08S
-0.68 SG A 91 106 10 08S 0.38 SG A 91 108 9
08S 0.4 SG A 91 127 13 10S 0.09
1CAN102104 Page 44 of 65 SG Row Col
%TW Elev Offset SG A 92 4
9 09S 0.55 SG A 92 6
11 10S 0.49 SG A 92 11 12 11S
-0.65 SG A 92 21 13 08S
-0.68 SG A 92 22 11 08S
-0.72 SG A 92 23 13 08S
-0.68 SG A 92 24 13 08S
-0.66 SG A 92 25 15 08S
-0.7 SG A 92 26 14 08S
-0.68 SG A 92 109 6
08S 0.45 SG A 93 1
8 13S 0.53 SG A 93 4
10 12S 0.49 SG A 93 20 10 08S
-0.61 SG A 93 20 10 09S 0.44 SG A 93 22 18 08S
-0.68 SG A 93 23 14 08S
-0.68 SG A 93 24 14 08S
-0.68 SG A 93 24 8
08S 0.51 SG A 93 25 10 08S
-0.68 SG A 93 27 12 08S
-0.72 SG A 93 27 11 08S 0.47 SG A 93 107 7
08S 0.4 SG A 94 1
7 13S 0.53 SG A 94 2
7 13S 0.51 SG A 94 24 15 08S
-0.68 SG A 94 25 13 08S
-0.65 SG A 94 26 14 08S
-0.7 SG A 94 28 8
08S
-0.8 SG A 94 109 11 08S 0.4 SG A 94 111 14 07S
-0.7 SG A 94 111 12 08S 0.42 SG A 95 3
10 10S
-0.64 SG A 95 21 10 08S
-0.68 SG A 95 23 9
08S
-0.68 SG A 95 24 11 08S
-0.66 SG A 95 25 13 08S
-0.68 SG A 95 27 11 08S
-0.74 SG A 95 28 14 08S
-0.68 SG A 95 106 10 07S
-0.74 SG A 95 109 5
08S 0.42
1CAN102104 Page 45 of 65 SG Row Col
%TW Elev Offset SG A 95 111 9
08S 0.4 SG A 95 124 13 10S
-0.79 SG A 96 19 11 08S
-0.65 SG A 96 23 12 08S
-0.63 SG A 96 24 13 08S
-0.72 SG A 96 26 14 08S
-0.72 SG A 96 29 14 08S
-0.68 SG A 96 107 12 08S 0.36 SG A 97 18 13 09S 0.44 SG A 97 21 11 08S
-0.7 SG A 97 23 12 08S
-0.72 SG A 97 24 11 08S
-0.72 SG A 97 25 11 08S
-0.68 SG A 97 25 10 08S 0.42 SG A 97 26 12 08S
-0.72 SG A 97 26 13 08S 0.42 SG A 97 28 12 08S
-0.72 SG A 97 28 11 08S 0.45 SG A 97 118 6
10S 0.31 SG A 97 119 20 11S 0.34 SG A 98 2
16 13S 0.45 SG A 98 4
17 09S 0.51 SG A 98 5
10 10S
-0.55 SG A 98 5
11 11S
-0.55 SG A 98 8
20 09S 0.47 SG A 98 9
11 09S 0.53 SG A 98 18 14 09S 0.46 SG A 98 22 13 08S
-0.68 SG A 98 23 10 08S
-0.66 SG A 98 24 14 08S
-0.7 SG A 98 24 7
08S 0.45 SG A 98 25 9
08S
-0.72 SG A 98 25 11 08S 0.47 SG A 98 26 16 08S
-0.72 SG A 98 28 10 08S
-0.68 SG A 98 30 11 08S
-0.74 SG A 98 89 11 08S
-0.73 SG A 98 105 8
08S 0.46 SG A 98 116 12 11S 0.34 SG A 99 8
13 09S 0.49
1CAN102104 Page 46 of 65 SG Row Col
%TW Elev Offset SG A 99 8
10 12S
-0.68 SG A 99 9
12 09S 0.49 SG A 99 9
10 11S
-0.68 SG A 99 12 12 11S
-0.68 SG A 99 19 8
08S
-0.74 SG A 99 20 9
08S
-0.74 SG A 99 22 10 08S
-0.72 SG A 99 23 9
08S
-0.66 SG A 99 23 10 08S 0.45 SG A 99 24 16 08S
-0.7 SG A 99 25 8
08S
-0.72 SG A 99 25 8
08S 0.47 SG A 99 26 15 08S
-0.7 SG A 99 29 12 08S
-0.72 SG A 99 107 6
08S
-0.73 SG A 99 107 10 08S 0.4 SG A 99 114 8
09S
-0.66 SG A 99 115 10 10S
-0.69 SG A 99 115 11 11S 0.42 SG A 99 117 11 09S 0.4 SG A 99 118 11 09S 0.4 SG A 99 119 10 07S
-0.69 SG A 99 119 13 09S 0.4 SG A 100 1
7 13S
-0.65 SG A 100 2
16 13S 0.42 SG A 100 8
6 10S
-0.59 SG A 100 9
10 11S
-0.69 SG A 100 18 10 09S 0.47 SG A 100 19 10 09S 0.45 SG A 100 24 9
08S
-0.7 SG A 100 25 11 08S
-0.7 SG A 100 114 10 10S
-0.75 SG A 101 1
9 13S
-0.64 SG A 101 1
16 13S 0.4 SG A 101 7
5 10S
-0.63 SG A 101 10 11 09S 0.49 SG A 101 23 15 08S
-0.68 SG A 101 102 8
08S
-0.64 SG A 101 102 9
08S 0.43 SG A 101 111 12 09S 0.43
1CAN102104 Page 47 of 65 SG Row Col
%TW Elev Offset SG A 101 112 5
10S
-0.04 SG A 102 5
6 10S
-0.61 SG A 102 8
15 11S
-0.59 SG A 102 9
11 09S 0.49 SG A 103 1
15 12S 0.51 SG A 103 5
9 10S
-0.68 SG A 103 9
12 09S
-0.59 SG A 103 9
15 09S 0.51 SG A 103 9
19 11S
-0.57 SG A 103 16 12 09S 0.47 SG A 103 19 8
08S
-0.64 SG A 103 19 11 09S 0.45 SG A 103 29 21 08S
-0.72 SG A 103 103 8
08S 0.43 SG A 103 113 10 12S
-0.83 SG A 104 8
7 09S
-0.55 SG A 104 8
11 09S 0.47 SG A 104 9
9 09S
-0.62 SG A 104 23 7
08S
-0.65 SG A 104 25 9
08S
-0.72 SG A 104 27 9
08S
-0.7 SG A 104 29 11 08S
-0.72 SG A 104 30 12 08S
-0.72 SG A 104 31 10 08S
-0.74 SG A 104 34 15 08S
-0.7 SG A 104 35 12 08S
-0.74 SG A 105 7
7 09S 0.49 SG A 105 8
8 09S
-0.55 SG A 105 8
10 09S 0.47 SG A 105 18 10 09S 0.45 SG A 105 24 9
08S
-0.66 SG A 105 25 9
08S
-0.7 SG A 105 28 7
08S
-0.7 SG A 105 29 10 08S
-0.72 SG A 105 32 13 08S 0.4 SG A 105 34 13 08S 0.38 SG A 105 35 12 08S
-0.72 SG A 106 5
13 10S 0.45 SG A 106 17 6
08S
-0.62 SG A 106 20 13 09S 0.45
1CAN102104 Page 48 of 65 SG Row Col
%TW Elev Offset SG A 106 23 10 08S
-0.7 SG A 106 23 10 08S 0.47 SG A 106 24 7
08S
-0.67 SG A 106 25 12 08S
-0.7 SG A 106 27 12 08S
-0.7 SG A 106 27 5
08S 0.49 SG A 106 29 15 08S
-0.72 SG A 106 31 20 08S
-0.7 SG A 106 32 9
08S
-0.69 SG A 106 33 14 08S
-0.74 SG A 106 87 8
08S
-0.75 SG A 106 98 11 08S
-0.76 SG A 106 111 10 12S
-0.76 SG A 106 112 6
10S
-0.7 SG A 106 119 23 10S
-0.76 SG A 107 3
8 10S 0.23 SG A 107 5
9 09S 0.47 SG A 107 6
17 09S
-0.68 SG A 107 17 6
08S
-0.63 SG A 107 18 12 09S 0.43 SG A 107 22 11 08S
-0.64 SG A 107 26 14 08S
-0.71 SG A 107 27 7
08S
-0.64 SG A 107 29 11 08S
-0.7 SG A 107 29 10 08S 0.42 SG A 107 30 15 08S
-0.68 SG A 107 30 11 08S 0.4 SG A 107 81 10 08S
-0.74 SG A 107 82 8
08S
-0.72 SG A 107 88 15 08S 0.36 SG A 107 93 10 08S
-0.72 SG A 107 112 13 10S
-0.74 SG A 107 113 9
10S
-0.7 SG A 107 114 12 10S
-0.74 SG A 107 115 10 10S
-0.7 SG A 108 5
10 09S
-0.62 SG A 108 18 10 09S 0.45 SG A 108 21 7
08S
-0.7 SG A 108 25 7
08S
-0.72 SG A 108 26 16 08S
-0.7
1CAN102104 Page 49 of 65 SG Row Col
%TW Elev Offset SG A 108 28 27 08S
-0.68 SG A 108 28 13 08S 0.34 SG A 108 30 19 08S
-0.72 SG A 108 31 11 08S
-0.72 SG A 108 31 11 08S 0.42 SG A 108 91 10 08S 0.38 SG A 108 109 15 10S
-0.74 SG A 108 113 11 10S
-0.74 SG A 108 114 11 10S
-0.72 SG A 109 2
11 13S 0.45 SG A 109 4
6 09S
-0.6 SG A 109 18 9
10S
-0.72 SG A 109 20 9
08S
-0.7 SG A 109 24 11 08S
-0.75 SG A 109 25 9
08S
-0.7 SG A 109 27 11 08S
-0.72 SG A 109 27 13 08S 0.45 SG A 109 29 15 08S
-0.74 SG A 109 29 10 08S 0.38 SG A 109 32 11 08S
-0.72 SG A 109 90 8
08S
-0.74 SG A 110 15 13 09S 0.42 SG A 110 21 10 08S
-0.7 SG A 110 25 10 08S
-0.7 SG A 110 26 7
08S
-0.68 SG A 110 27 8
08S 0.49 SG A 110 28 7
08S
-0.72 SG A 110 29 9
08S
-0.74 SG A 110 29 12 08S 0.45 SG A 110 30 7
08S
-0.71 SG A 110 31 12 08S
-0.72 SG A 110 80 9
08S 0.43 SG A 110 83 10 08S
-0.74 SG A 110 86 14 06S
-0.7 SG A 110 86 5
06S 0.43 SG A 111 15 11 09S 0.44 SG A 111 20 9
08S
-0.7 SG A 111 24 10 08S 0.42 SG A 111 24 12 10S
-0.76 SG A 111 25 10 08S
-0.7
1CAN102104 Page 50 of 65 SG Row Col
%TW Elev Offset SG A 111 25 10 08S 0.44 SG A 111 25 11 09S 0.42 SG A 111 26 6
08S
-0.66 SG A 111 27 11 08S
-0.74 SG A 111 27 8
09S
-0.74 SG A 111 29 22 08S
-0.7 SG A 111 29 11 08S 0.43 SG A 111 30 10 08S
-0.68 SG A 111 31 9
08S
-0.74 SG A 111 32 6
08S
-0.7 SG A 111 34 10 08S
-0.72 SG A 111 35 10 08S
-0.74 SG A 111 82 8
08S
-0.74 SG A 111 89 8
08S 0.38 SG A 112 2
10 11S
-0.7 SG A 112 23 6
08S 0.43 SG A 112 27 11 08S
-0.74 SG A 112 27 10 08S 0.44 SG A 112 29 11 08S
-0.7 SG A 112 30 8
08S
-0.7 SG A 112 30 8
08S 0.42 SG A 112 31 12 08S
-0.72 SG A 112 32 8
08S
-0.76 SG A 112 33 10 08S
-0.74 SG A 112 34 9
08S
-0.72 SG A 112 35 11 08S
-0.74 SG A 112 69 10 08S
-0.76 SG A 112 88 9
08S 0.38 SG A 112 95 13 08S 0.45 SG A 112 98 7
08S 0.4 SG A 112 110 11 10S
-0.72 SG A 113 3
14 10S
-0.66 SG A 113 5
9 09S 0.51 SG A 113 24 9
08S
-0.68 SG A 113 26 9
08S
-0.72 SG A 113 26 10 08S 0.45 SG A 113 26 12 09S 0.4 SG A 113 27 6
08S 0.49 SG A 113 28 10 08S
-0.72 SG A 113 28 11 08S 0.42
1CAN102104 Page 51 of 65 SG Row Col
%TW Elev Offset SG A 113 30 16 08S
-0.75 SG A 113 30 14 08S 0.4 SG A 113 31 7
08S 0.42 SG A 113 37 8
08S
-0.72 SG A 113 72 11 08S
-0.74 SG A 113 83 8
08S
-0.72 SG A 113 88 9
08S
-0.74 SG A 113 110 11 10S
-0.74 SG A 113 111 11 10S
-0.7 SG A 113 111 13 12S
-0.72 SG A 113 113 15 13S
-0.76 SG A 114 3
11 13S
-0.65 SG A 114 3
33 13S 0.42 SG A 114 4
9 10S
-0.6 SG A 114 30 5
08S
-0.67 SG A 114 31 12 08S
-0.74 SG A 114 35 13 08S
-0.74 SG A 114 35 11 08S 0.4 SG A 114 36 11 08S
-0.71 SG A 114 108 13 10S
-0.72 SG A 114 109 13 10S
-0.7 SG A 115 4
17 10S
-0.66 SG A 115 21 13 09S 0.43 SG A 115 27 13 08S
-0.7 SG A 115 27 10 08S 0.4 SG A 115 29 19 08S
-0.74 SG A 115 29 10 08S 0.42 SG A 115 38 10 08S 0.42 SG A 115 61 10 08S
-0.76 SG A 115 70 13 08S
-0.72 SG A 115 71 14 08S
-0.76 SG A 115 107 13 10S
-0.72 SG A 115 107 10 12S
-0.74 SG A 115 108 9
10S
-0.7 SG A 115 108 12 13S
-0.7 SG A 115 109 11 10S 0.17 SG A 115 110 15 10S 0.17 SG A 115 113 12 07S
-0.68 SG A 116 5
25 09S 0.41 SG A 116 6
8 09S 0.42
1CAN102104 Page 52 of 65 SG Row Col
%TW Elev Offset SG A 116 26 7
08S
-0.7 SG A 116 26 9
08S 0.45 SG A 116 28 13 08S
-0.72 SG A 116 33 7
08S
-0.72 SG A 116 40 20 08S
-0.74 SG A 116 61 11 08S
-0.72 SG A 116 71 13 08S
-0.76 SG A 116 77 14 08S
-0.74 SG A 116 79 11 08S
-0.72 SG A 116 86 10 08S 0.44 SG A 116 87 4
08S 0.45 SG A 116 107 7
10S
-0.08 SG A 116 109 7
10S 0.11 SG A 117 6
9 09S 0.44 SG A 117 7
7 09S 0.49 SG A 117 22 5
08S 0.47 SG A 117 28 8
08S
-0.7 SG A 117 29 7
08S
-0.68 SG A 117 37 10 08S 0.42 SG A 117 59 13 08S
-0.76 SG A 117 62 14 08S
-0.76 SG A 117 66 10 08S
-0.76 SG A 117 67 18 08S
-0.76 SG A 117 68 8
08S
-0.76 SG A 117 107 15 10S 0.15 SG A 118 7
13 10S
-0.63 SG A 118 30 11 09S 0.36 SG A 118 33 10 08S
-0.76 SG A 118 36 12 08S
-0.78 SG A 118 42 10 07S
-0.66 SG A 118 58 11 08S
-0.74 SG A 118 62 12 08S
-0.74 SG A 118 68 18 08S
-0.76 SG A 118 76 7
09S
-0.74 SG A 118 83 6
08S 0.42 SG A 118 105 5
14S 0.38 SG A 118 106 4
10S 0.08 SG A 119 6
13 09S 0.49 SG A 119 25 8
08S
-0.72 SG A 119 26 12 09S 0.32
1CAN102104 Page 53 of 65 SG Row Col
%TW Elev Offset SG A 119 27 6
08S
-0.74 SG A 119 30 14 08S
-0.77 SG A 119 30 8
09S
-0.72 SG A 119 31 12 08S
-0.76 SG A 119 34 7
08S
-0.7 SG A 119 44 11 07S 0.36 SG A 119 44 6
08S
-0.68 SG A 119 44 10 09S
-0.78 SG A 119 56 13 08S
-0.85 SG A 119 57 12 08S
-0.77 SG A 119 58 13 08S
-0.76 SG A 119 59 11 08S
-0.74 SG A 119 60 15 08S
-0.76 SG A 119 62 10 08S
-0.76 SG A 119 67 14 08S
-0.75 SG A 119 69 14 08S
-0.74 SG A 119 70 8
08S 0.42 SG A 119 101 8
10S
-0.7 SG A 119 104 5
10S 0.3 SG A 120 4
23 10S
-0.66 SG A 120 5
11 10S
-0.69 SG A 120 7
8 09S 0.45 SG A 120 16 11 09S 0.36 SG A 120 22 14 09S 0.34 SG A 120 24 7
08S
-0.63 SG A 120 40 9
08S
-0.83 SG A 120 58 13 08S
-0.76 SG A 120 60 7
08S
-0.74 SG A 120 62 8
08S
-0.76 SG A 120 64 11 08S
-0.74 SG A 120 66 9
08S
-0.76 SG A 120 76 7
08S
-0.72 SG A 120 78 8
08S
-0.72 SG A 120 78 11 08S 0.4 SG A 120 80 10 08S 0.4 SG A 120 98 9
10S
-0.72 SG A 120 99 11 12S
-0.76 SG A 120 101 11 10S 0.23 SG A 120 102 8
10S 0.15 SG A 120 105 12 10S 0.42
1CAN102104 Page 54 of 65 SG Row Col
%TW Elev Offset SG A 121 2
11 14S
-0.63 SG A 121 8
14 09S 0.4 SG A 121 16 13 10S
-0.66 SG A 121 26 4
08S
-0.74 SG A 121 30 8
08S 0.38 SG A 121 31 11 08S
-0.72 SG A 121 33 9
08S
-0.68 SG A 121 54 9
08S
-0.8 SG A 121 55 10 08S
-0.8 SG A 121 56 15 08S
-0.77 SG A 121 59 8
08S
-0.76 SG A 121 65 9
08S
-0.76 SG A 121 76 10 08S
-0.7 SG A 121 76 7
08S 0.4 SG A 121 76 13 09S 0.38 SG A 121 80 7
08S 0.43 SG A 121 100 9
10S
-0.74 SG A 121 101 6
10S 0.17 SG A 121 102 8
10S 0.17 SG A 122 1
12 10S 0.42 SG A 122 2
18 14S
-0.59 SG A 122 7
17 10S
-0.7 SG A 122 8
11 09S 0.49 SG A 122 8
14 13S
-0.73 SG A 122 34 6
07S 0.43 SG A 122 34 10 08S
-0.7 SG A 122 34 9
08S 0.38 SG A 122 35 9
08S
-0.74 SG A 122 39 6
08S
-0.72 SG A 122 40 17 09S
-0.68 SG A 122 50 13 08S
-0.74 SG A 122 52 13 08S
-0.81 SG A 122 56 11 08S
-0.77 SG A 122 61 12 08S
-0.78 SG A 122 62 10 08S
-0.79 SG A 122 63 7
08S
-0.8 SG A 122 63 7
08S 0.42 SG A 122 72 10 07S
-0.7 SG A 122 89 10 14S 0.3 SG A 122 97 12 14S 0.38
1CAN102104 Page 55 of 65 SG Row Col
%TW Elev Offset SG A 122 98 10 12S
-0.72 SG A 122 99 12 14S 0.38 SG A 123 7
7 10S
-0.72 SG A 123 8
8 09S 0.42 SG A 123 8
11 10S
-0.7 SG A 123 18 11 09S 0.38 SG A 123 28 11 08S
-0.7 SG A 123 29 4
08S
-0.78 SG A 123 35 10 09S
-0.78 SG A 123 36 15 09S
-0.72 SG A 123 37 17 09S
-0.78 SG A 123 38 10 08S 0.4 SG A 123 40 14 09S
-0.72 SG A 123 41 6
08S
-0.81 SG A 123 41 11 09S
-0.78 SG A 123 51 6
08S
-0.74 SG A 123 54 14 08S
-0.76 SG A 123 60 9
08S
-0.76 SG A 123 65 8
08S 0.43 SG A 123 71 8
08S 0.38 SG A 123 74 9
08S 0.42 SG A 123 99 7
10S 0.21 SG A 124 4
14 13S 0.36 SG A 124 8
10 09S 0.42 SG A 124 9
14 09S 0.38 SG A 124 14 11 10S
-0.66 SG A 124 28 10 08S
-0.74 SG A 124 30 9
08S
-0.74 SG A 124 31 9
08S
-0.68 SG A 124 32 8
08S
-0.78 SG A 124 35 10 09S
-0.74 SG A 124 36 12 08S
-0.74 SG A 124 37 11 09S
-0.78 SG A 124 38 10 08S
-0.74 SG A 124 38 11 08S 0.36 SG A 124 39 10 09S
-0.76 SG A 124 42 9
08S
-0.74 SG A 124 44 10 08S 0.36 SG A 124 48 9
08S
-0.78 SG A 124 49 15 08S
-0.76
1CAN102104 Page 56 of 65 SG Row Col
%TW Elev Offset SG A 124 55 12 08S 0.38 SG A 124 55 11 09S
-0.72 SG A 124 76 8
08S
-0.7 SG A 125 1
13 13S 0.38 SG A 125 7
7 10S
-0.72 SG A 125 8
7 09S 0.4 SG A 125 8
26 10S
-0.67 SG A 125 9
11 09S 0.38 SG A 125 13 13 10S
-0.64 SG A 125 17 17 10S
-0.74 SG A 125 27 18 10S
-0.78 SG A 125 28 14 08S 0.38 SG A 125 39 13 09S
-0.74 SG A 125 44 10 08S
-0.76 SG A 125 45 7
08S
-0.74 SG A 125 46 7
08S
-0.82 SG A 125 48 8
08S
-0.76 SG A 125 51 12 09S
-0.72 SG A 125 53 9
08S
-0.74 SG A 125 54 5
06S 0.47 SG A 125 54 9
08S
-0.68 SG A 125 54 12 08S 0.38 SG A 125 54 10 09S
-0.75 SG A 125 56 7
08S 0.41 SG A 125 58 8
08S
-0.75 SG A 125 64 10 08S 0.41 SG A 125 65 14 08S 0.4 SG A 125 73 8
08S 0.44 SG A 125 93 16 10S
-0.68 SG A 126 1
11 07S 0.42 SG A 126 7
13 10S
-0.7 SG A 126 9
11 09S 0.45 SG A 126 21 11 10S
-0.76 SG A 126 24 20 10S
-0.82 SG A 126 32 8
08S
-0.74 SG A 126 32 10 08S 0.42 SG A 126 32 14 09S
-0.76 SG A 126 37 10 09S 0.32 SG A 126 40 7
08S
-0.76 SG A 126 42 11 08S
-0.71
1CAN102104 Page 57 of 65 SG Row Col
%TW Elev Offset SG A 126 42 12 08S 0.36 SG A 126 42 12 09S
-0.78 SG A 126 46 11 08S 0.36 SG A 126 47 11 08S
-0.76 SG A 126 48 12 09S
-0.78 SG A 126 50 7
08S
-0.8 SG A 126 54 5
08S
-0.74 SG A 126 55 9
08S
-0.71 SG A 126 57 8
08S
-0.72 SG A 126 59 11 09S
-0.77 SG A 126 92 18 14S 0.34 SG A 126 97 10 13S
-0.72 SG A 127 40 12 09S
-0.7 SG A 127 41 13 08S 0.36 SG A 127 47 12 08S 0.36 SG A 127 47 14 09S 0.34 SG A 127 50 6
08S
-0.78 SG A 127 58 12 09S
-0.68 SG A 127 60 11 08S 0.41 SG A 127 64 10 08S 0.43 SG A 127 88 10 09S 0.44 SG A 127 89 10 10S
-0.7 SG A 127 91 7
10S
-0.66 SG A 127 95 13 14S
-0.66 SG A 127 98 19 13S
-0.7 SG A 128 1
16 13S 0.4 SG A 128 1
10 14S
-0.59 SG A 128 2
12 12S
-0.7 SG A 128 2
10 14S 0.43 SG A 128 36 16 10S
-0.83 SG A 128 42 10 09S
-0.78 SG A 128 42 10 10S
-0.83 SG A 128 48 7
08S
-0.72 SG A 128 83 13 09S 0.42 SG A 128 84 8
09S 0.45 SG A 128 88 9
10S 0.13 SG A 129 9
20 09S 0.38 SG A 129 15 10 10S 0.38 SG A 129 20 16 10S
-0.7 SG A 129 21 14 10S
-0.7
1CAN102104 Page 58 of 65 SG Row Col
%TW Elev Offset SG A 129 22 11 10S
-0.72 SG A 129 26 13 10S
-0.72 SG A 129 33 14 10S
-0.81 SG A 129 40 5
08S
-0.76 SG A 130 2
12 13S 0.43 SG A 130 8
10 10S
-0.7 SG A 130 9
11 09S 0.4 SG A 130 10 12 09S 0.45 SG A 130 33 5
08S
-0.66 SG A 130 34 6
08S
-0.72 SG A 130 37 7
08S
-0.61 SG A 130 39 5
08S
-0.76 SG A 130 45 9
08S
-0.74 SG A 130 48 10 09S 0.34 SG A 130 49 8
08S
-0.75 SG A 130 51 7
08S
-0.66 SG A 130 85 18 11S 0.4 SG A 131 1
7 14S
-0.66 SG A 131 7
9 10S
-0.7 SG A 131 8
13 09S 0.4 SG A 131 9
5 09S 0.44 SG A 131 17 10 10S
-0.7 SG A 131 36 6
08S
-0.72 SG A 131 38 11 09S
-0.7 SG A 131 83 9
11S 0.36 SG A 131 84 15 10S 0.15 SG A 131 85 6
10S 0.13 SG A 132 7
10 10S
-0.69 SG A 132 8
19 09S 0.42 SG A 132 9
11 09S 0.4 SG A 132 10 12 09S 0.42 SG A 132 19 14 10S
-0.72 SG A 132 30 5
08S
-0.74 SG A 132 38 6
08S
-0.74 SG A 132 46 8
08S 0.43 SG A 132 46 10 09S 0.4 SG A 133 1
7 13S 0.43 SG A 133 2
10 13S 0.43 SG A 133 2
8 14S
-0.62 SG A 133 9
7 09S 0.42
1CAN102104 Page 59 of 65 SG Row Col
%TW Elev Offset SG A 133 10 14 09S 0.43 SG A 133 13 11 10S
-0.71 SG A 133 37 4
08S
-0.76 SG A 133 81 12 11S 0.46 SG A 133 81 12 13S
-0.8 SG A 133 83 12 13S
-0.72 SG A 133 87 12 13S
-0.72 SG A 134 1
13 14S
-0.7 SG A 134 2
12 10S
-0.7 SG A 134 6
11 10S
-0.7 SG A 134 7
18 10S
-0.68 SG A 134 8
13 10S
-0.7 SG A 134 9
18 09S 0.45 SG A 134 9
30 10S
-0.68 SG A 134 10 22 10S
-0.67 SG A 134 11 17 09S 0.36 SG A 134 79 20 11S 0.45 SG A 135 1
11 13S 0.43 SG A 135 1
6 14S
-0.64 SG A 135 8
9 10S
-0.68 SG A 135 9
10 09S
-0.74 SG A 135 9
11 09S 0.38 SG A 135 9
25 10S
-0.72 SG A 135 9
11 12S 0.38 SG A 135 10 23 10S
-0.66 SG A 135 11 14 09S 0.38 SG A 135 11 11 10S
-0.74 SG A 135 65 12 10S
-0.74 SG A 135 78 13 11S
-0.72 SG A 135 78 11 11S 0.42 SG A 135 78 12 13S
-0.75 SG A 136 1
12 11S
-0.74 SG A 136 6
14 10S
-0.68 SG A 136 7
13 10S
-0.67 SG A 136 7
9 13S
-0.79 SG A 136 8
8 09S 0.43 SG A 136 8
11 10S
-0.68 SG A 136 9
14 09S 0.44 SG A 136 9
30 10S
-0.68 SG A 136 19 15 10S
-0.7
1CAN102104 Page 60 of 65 SG Row Col
%TW Elev Offset SG A 136 67 15 09S 0.36 SG A 136 76 10 11S
-0.69 SG A 136 76 13 11S 0.46 SG A 136 77 10 11S 0.42 SG A 137 8
10 09S 0.4 SG A 137 9
18 10S
-0.7 SG A 137 11 10 10S
-0.74 SG A 137 12 7
09S 0.4 SG A 137 19 10 10S
-0.72 SG A 137 64 11 11S 0.32 SG A 137 75 9
10S 0.4 SG A 138 7
10 10S
-0.68 SG A 138 9
14 11S
-0.7 SG A 138 11 18 11S
-0.7 SG A 138 13 7
09S 0.42 SG A 138 15 16 10S
-0.72 SG A 138 17 22 10S
-0.72 SG A 138 17 10 14S 0.32 SG A 138 18 20 09S 0.36 SG A 138 19 16 10S
-0.68 SG A 138 60 13 11S 0.38 SG A 138 61 11 11S
-0.76 SG A 138 62 13 11S 0.36 SG A 138 64 13 11S 0.42 SG A 138 65 21 11S 0.42 SG A 138 65 13 14S
-0.76 SG A 138 74 10 12S
-0.69 SG A 139 5
12 11S
-0.72 SG A 139 7
13 10S
-0.7 SG A 139 10 10 10S
-0.81 SG A 139 11 18 10S
-0.74 SG A 139 12 22 10S
-0.81 SG A 139 13 17 10S
-0.74 SG A 139 14 26 10S
-0.81 SG A 139 15 16 10S
-0.72 SG A 139 16 27 10S
-0.83 SG A 139 17 19 10S
-0.72 SG A 139 19 10 09S 0.38 SG A 139 54 13 10S
-0.72 SG A 139 57 8
09S
-0.66
1CAN102104 Page 61 of 65 SG Row Col
%TW Elev Offset SG A 139 59 28 11S 0.35 SG A 139 60 23 11S 0.43 SG A 139 61 12 11S 0.42 SG A 139 62 14 11S 0.45 SG A 139 63 13 11S 0.44 SG A 139 65 11 11S
-0.74 SG A 139 65 11 11S 0.4 SG A 139 69 13 14S
-0.7 SG A 140 1
5 13S
-0.74 SG A 140 4
13 10S
-0.68 SG A 140 4
13 13S 0.38 SG A 140 7
21 10S
-0.7 SG A 140 8
12 10S
-0.7 SG A 140 9
28 10S
-0.69 SG A 140 10 11 10S
-0.7 SG A 140 11 14 10S
-0.7 SG A 140 13 14 10S
-0.72 SG A 140 13 7
14S
-0.79 SG A 140 14 31 10S
-0.67 SG A 140 15 21 10S
-0.78 SG A 140 16 6
09S
-0.69 SG A 140 16 28 09S 0.37 SG A 140 16 14 10S
-0.7 SG A 140 17 12 09S 0.36 SG A 140 57 11 11S
-0.74 SG A 140 57 10 11S 0.38 SG A 140 57 14 13S
-0.79 SG A 140 58 10 11S 0.48 SG A 140 60 15 11S 0.44 SG A 140 61 15 11S 0.42 SG A 140 61 12 13S
-0.68 SG A 140 62 14 11S
-0.75 SG A 140 63 18 10S 0.36 SG A 140 66 9
10S 0.43 SG A 141 9
10 10S
-0.68 SG A 141 10 8
10S
-0.72 SG A 141 11 26 10S
-0.72 SG A 141 14 14 09S 0.36 SG A 141 14 17 10S
-0.59 SG A 141 15 13 09S 0.35
1CAN102104 Page 62 of 65 SG Row Col
%TW Elev Offset SG A 141 16 10 09S 0.38 SG A 141 16 12 10S
-0.68 SG A 141 17 18 09S 0.32 SG A 141 53 10 10S 0.38 SG A 141 56 17 11S 0.42 SG A 141 59 17 11S
-0.76 SG A 141 59 13 11S 0.4 SG A 141 62 14 11S
-0.76 SG A 142 2
12 10S
-0.7 SG A 142 2
11 11S
-0.7 SG A 142 4
10 11S
-0.68 SG A 142 11 8
10S
-0.7 SG A 142 12 23 10S
-0.7 SG A 142 12 12 11S
-0.74 SG A 142 14 13 10S
-0.7 SG A 142 15 10 10S
-0.77 SG A 142 15 11 11S
-0.74 SG A 142 52 11 11S
-0.81 SG A 142 53 10 11S
-0.76 SG A 142 53 21 11S 0.42 SG A 142 54 11 11S 0.47 SG A 142 57 13 11S 0.47 SG A 142 58 12 11S
-0.7 SG A 142 60 10 11S
-0.68 SG A 142 60 9
11S 0.51 SG A 142 62 7
11S 0.55 SG A 142 63 13 11S
-0.67 SG A 143 1
11 11S
-0.7 SG A 143 1
16 14S
-0.68 SG A 143 2
13 14S
-0.7 SG A 143 10 15 10S
-0.68 SG A 143 10 16 11S
-0.77 SG A 143 12 18 10S
-0.7 SG A 143 12 14 11S
-0.72 SG A 143 41 10 09S 0.4 SG A 143 49 11 11S
-0.71 SG A 143 52 10 11S
-0.74 SG A 143 52 17 11S 0.37 SG A 143 53 10 11S
-0.74 SG A 143 53 18 11S 0.47
1CAN102104 Page 63 of 65 SG Row Col
%TW Elev Offset SG A 143 55 8
10S 0.46 SG A 143 56 10 11S
-0.66 SG A 143 58 16 11S
-0.68 SG A 143 60 12 11S
-0.66 SG A 144 5
10 13S 0.36 SG A 144 7
14 10S
-0.69 SG A 144 8
8 10S
-0.7 SG A 144 9
30 10S
-0.62 SG A 144 10 14 10S
-0.72 SG A 144 10 12 11S
-0.74 SG A 144 13 11 10S 0.38 SG A 144 14 15 11S
-0.74 SG A 144 14 10 11S 0.4 SG A 144 14 11 13S
-0.74 SG A 144 15 10 11S
-0.74 SG A 144 17 10 11S
-0.71 SG A 144 17 11 13S
-0.77 SG A 144 18 14 09S 0.38 SG A 144 18 10 12S 0.3 SG A 144 18 12 13S
-0.77 SG A 144 20 13 09S 0.42 SG A 144 21 11 09S 0.4 SG A 144 35 13 09S 0.36 SG A 144 36 13 09S 0.4 SG A 144 41 11 09S 0.4 SG A 144 45 20 11S
-0.72 SG A 144 46 19 11S 0.45 SG A 144 47 16 11S
-0.7 SG A 144 47 13 11S 0.47 SG A 145 3
14 11S
-0.7 SG A 145 3
12 13S
-0.74 SG A 145 3
18 13S 0.36 SG A 145 4
12 10S
-0.72 SG A 145 5
10 11S
-0.69 SG A 145 5
10 14S
-0.75 SG A 145 7
15 10S
-0.72 SG A 145 9
10 10S
-0.71 SG A 145 9
12 11S
-0.7 SG A 145 11 24 10S
-0.72 SG A 145 19 12 09S 0.44
1CAN102104 Page 64 of 65 SG Row Col
%TW Elev Offset SG A 145 20 11 05S
-0.68 SG A 145 32 8
09S 0.41 SG A 145 36 12 11S 0.41 SG A 145 37 18 11S 0.4 SG A 145 44 11 11S
-0.7 SG A 145 44 9
11S 0.49 SG A 145 45 16 11S
-0.7 SG A 145 46 5
10S 0.04 SG A 145 47 8
11S 0.53 SG A 146 5
8 13S
-0.85 SG A 146 6
13 10S
-0.69 SG A 146 7
11 10S
-0.72 SG A 146 8
16 10S
-0.69 SG A 146 9
10 11S
-0.75 SG A 146 10 21 10S
-0.69 SG A 146 15 20 10S
-0.72 SG A 146 16 13 10S
-0.75 SG A 146 34 8
10S 0.06 SG A 146 36 11 11S 0.41 SG A 146 36 12 13S
-0.81 SG A 146 39 10 11S
-0.76 SG A 146 41 10 11S
-0.74 SG A 146 42 10 11S
-0.75 SG A 146 43 10 10S
-0.72 SG A 146 44 10 11S
-0.7 SG A 146 46 11 13S
-0.75 SG A 146 47 11 10S
-0.78 SG A 147 5
16 10S
-0.7 SG A 147 6
16 10S
-0.68 SG A 147 7
22 10S
-0.69 SG A 147 8
30 10S
-0.72 SG A 147 10 9
10S
-0.7 SG A 147 13 14 10S
-0.72 SG A 147 15 13 10S
-0.75 SG A 147 16 9
10S
-0.71 SG A 147 28 11 11S 0.41 SG A 147 29 5
10S 0.08 SG A 147 29 11 11S 0.38 SG A 147 30 9
11S 0.41 SG A 148 4
11 10S
-0.68
1CAN102104 Page 65 of 65 SG Row Col
%TW Elev Offset SG A 148 11 13 10S
-0.72 SG A 148 13 19 10S
-0.71 SG A 148 14 10 10S
-0.7 SG A 148 22 12 10S 0.38 SG A 148 23 8
10S 0.38 SG A 148 25 8
10S 0.11 SG A 149 2
11 11S
-0.72 SG A 149 4
12 11S
-0.66 SG A 149 32 11 10S 0.4 SG A 150 2
10 11S
-0.71 SG A 150 4
18 11S
-0.72 SG A 150 5
12 11S
-0.73 SG A 150 14 11 10S
-0.76 SG A 151 5
11 11S
-0.77 SG A 151 19 12 10S
-0.7 SG A 151 23 10 13S 0.32
Enclosure to 1CAN102104 Location of Service Induced Indications SG B TSP Wear (Broached)
1CAN102104 Page 1 of 65 Location of Service Induced Indications SG B TSP Wear (Broached)
SG Row Col
%TW Elev Offset SG B 1
1 9
11S
-0.75 SG B 1
4 29 11S
-0.65 SG B 1
8 21 11S
-0.61 SG B 1
10 12 11S
-0.77 SG B 1
14 19 11S
-0.72 SG B 1
15 15 11S
-0.75 SG B 1
16 26 11S
-0.65 SG B 1
16 12 12S
-0.75 SG B 1
17 13 11S
-0.72 SG B 1
18 19 11S
-0.72 SG B 1
19 9
11S
-0.75 SG B 1
20 19 11S
-0.65 SG B 1
24 14 11S
-0.74 SG B 2
1 11 11S
-0.75 SG B 2
2 17 10S 0.41 SG B 2
2 18 11S 0.43 SG B 2
2 11 14S
-0.91 SG B 2
4 22 11S
-0.77 SG B 2
5 28 11S
-0.63 SG B 2
6 9
10S
-0.75 SG B 2
6 18 11S
-0.77 SG B 2
7 30 11S
-0.68 SG B 2
8 19 11S
-0.75 SG B 2
9 20 11S
-0.7 SG B 2
10 20 11S
-0.68 SG B 2
15 10 11S
-0.77 SG B 2
16 9
11S
-0.79 SG B 2
17 16 11S
-0.77 SG B 2
18 11 11S
-0.74 SG B 2
19 12 11S
-0.64 SG B 2
20 20 11S
-0.7 SG B 2
21 34 11S
-0.7 SG B 2
23 22 11S
-0.72 SG B 2
24 16 11S
-0.81 SG B 2
25 11 11S
-0.75 SG B 2
26 12 11S
-0.77 SG B 2
27 13 11S
-0.73 SG B 2
28 12 11S
-0.7
1CAN102104 Page 2 of 65 SG Row Col
%TW Elev Offset SG B 3
1 20 11S
-0.7 SG B 3
1 8
11S 0.42 SG B 3
2 12 10S
-0.75 SG B 3
2 6
10S 0.47 SG B 3
2 29 11S
-0.7 SG B 3
3 8
10S 0.43 SG B 3
3 18 11S
-0.77 SG B 3
4 13 10S 0.45 SG B 3
4 16 11S
-0.75 SG B 3
5 14 10S
-0.72 SG B 3
5 8
10S 0.44 SG B 3
5 15 11S
-0.77 SG B 3
6 23 11S
-0.77 SG B 3
6 10 11S 0.42 SG B 3
7 17 11S
-0.75 SG B 3
8 5
08S
-0.65 SG B 3
8 14 10S
-0.7 SG B 3
8 14 11S
-0.72 SG B 3
9 10 10S 0.41 SG B 3
9 10 11S
-0.79 SG B 3
9 11 11S 0.36 SG B 3
9 12 12S 0.28 SG B 3
9 12 14S
-0.84 SG B 3
9 10 14S 0.32 SG B 3
10 11 10S
-0.75 SG B 3
10 10 11S
-0.77 SG B 3
10 13 11S 0.41 SG B 3
11 7
08S 0.43 SG B 3
11 7
12S
-0.79 SG B 3
12 4
10S
-0.73 SG B 3
12 12 12S
-0.66 SG B 3
12 12 12S 0.28 SG B 3
20 11 11S
-0.77 SG B 3
21 12 11S
-0.7 SG B 3
21 13 12S 0.3 SG B 3
22 11 11S
-0.79 SG B 3
24 10 11S
-0.74 SG B 3
32 11 11S
-0.8 SG B 3
34 10 10S 0.45 SG B 3
35 9
10S 0.45
1CAN102104 Page 3 of 65 SG Row Col
%TW Elev Offset SG B 4
1 5
10S 0.45 SG B 4
1 13 11S
-0.75 SG B 4
2 13 10S
-0.7 SG B 4
2 10 10S 0.45 SG B 4
2 26 11S
-0.77 SG B 4
3 14 11S
-0.75 SG B 4
4 12 10S 0.43 SG B 4
4 13 11S
-0.75 SG B 4
5 20 11S
-0.68 SG B 4
6 23 11S
-0.7 SG B 4
7 18 11S
-0.77 SG B 4
7 7
12S 0.3 SG B 4
8 10 11S
-0.75 SG B 4
8 12 11S 0.36 SG B 4
8 20 12S 0
SG B 4
9 11 11S
-0.77 SG B 4
10 11 10S
-0.68 SG B 4
10 14 11S 0.28 SG B 4
10 16 12S
-0.68 SG B 4
10 16 12S 0.21 SG B 4
12 9
10S
-0.71 SG B 4
12 8
12S 0.28 SG B 4
13 14 11S 0.38 SG B 4
24 12 12S 0.32 SG B 4
26 13 11S
-0.72 SG B 4
27 10 12S 0.3 SG B 4
28 12 12S 0.32 SG B 4
34 13 11S
-0.75 SG B 4
35 17 11S
-0.69 SG B 4
36 14 11S
-0.71 SG B 4
37 19 10S 0.35 SG B 4
37 12 11S
-0.63 SG B 4
37 12 11S 0.4 SG B 5
2 18 11S
-0.79 SG B 5
3 12 10S
-0.73 SG B 5
3 8
10S 0.43 SG B 5
4 15 11S
-0.72 SG B 5
5 13 11S
-0.75 SG B 5
7 14 11S
-0.73 SG B 5
8 14 12S
-0.76
1CAN102104 Page 4 of 65 SG Row Col
%TW Elev Offset SG B 5
8 15 12S 0.32 SG B 5
9 8
10S
-0.73 SG B 5
9 10 11S 0.42 SG B 5
10 16 11S 0.41 SG B 5
11 18 10S
-0.68 SG B 5
11 13 11S 0.37 SG B 5
11 14 12S
-0.21 SG B 5
12 14 10S
-0.65 SG B 5
12 11 11S 0.3 SG B 5
12 11 12S
-0.72 SG B 5
12 15 12S 0.19 SG B 5
12 10 14S
-0.82 SG B 5
13 11 11S 0.41 SG B 5
13 12 14S
-0.83 SG B 5
14 12 11S 0.38 SG B 5
18 11 10S
-0.77 SG B 5
23 12 10S
-0.79 SG B 5
23 11 12S 0.36 SG B 5
24 7
12S 0.32 SG B 5
26 7
10S 0.04 SG B 5
27 14 10S 0.06 SG B 5
27 10 11S 0.36 SG B 5
29 13 11S 0.38 SG B 5
31 15 11S 0.38 SG B 5
34 12 11S 0.34 SG B 5
36 11 12S 0.34 SG B 5
37 11 11S 0.43 SG B 5
39 14 11S
-0.62 SG B 5
39 14 11S 0.43 SG B 5
39 16 12S 0.34 SG B 5
39 10 13S
-0.79 SG B 5
40 13 11S
-0.68 SG B 5
41 17 11S
-0.75 SG B 5
41 20 11S 0.41 SG B 5
42 11 10S 0.49 SG B 5
42 13 11S
-0.73 SG B 5
42 14 11S 0.49 SG B 6
1 18 11S
-0.73 SG B 6
3 5
10S 0.45 SG B 6
3 13 11S
-0.75
1CAN102104 Page 5 of 65 SG Row Col
%TW Elev Offset SG B 6
4 18 10S
-0.75 SG B 6
4 13 10S 0.43 SG B 6
5 10 10S
-0.75 SG B 6
5 15 11S
-0.75 SG B 6
6 8
10S
-0.75 SG B 6
7 14 10S
-0.7 SG B 6
7 11 11S
-0.73 SG B 6
8 13 10S
-0.72 SG B 6
11 9
11S 0.4 SG B 6
16 13 11S 0.36 SG B 6
21 23 10S
-0.77 SG B 6
23 17 10S
-0.75 SG B 6
24 15 10S
-0.62 SG B 6
24 11 11S 0.36 SG B 6
25 16 10S
-0.73 SG B 6
25 11 12S
-0.83 SG B 6
26 13 10S
-0.75 SG B 6
30 12 10S 0.06 SG B 6
30 10 11S 0.38 SG B 6
30 10 12S 0.32 SG B 6
32 12 11S 0.38 SG B 6
34 14 11S 0.36 SG B 6
37 22 11S 0.34 SG B 6
37 11 12S 0.3 SG B 6
38 24 11S 0.38 SG B 6
39 12 11S
-0.67 SG B 6
39 22 11S 0.35 SG B 6
40 14 11S 0.41 SG B 6
43 9
10S 0.47 SG B 6
43 19 11S
-0.7 SG B 6
44 8
10S 0.44 SG B 6
44 18 11S
-0.74 SG B 6
44 11 11S 0.47 SG B 6
45 10 11S
-0.75 SG B 6
45 12 12S 0.3 SG B 6
46 11 11S
-0.74 SG B 6
46 15 11S 0.43 SG B 6
47 18 10S 0.47 SG B 7
1 17 11S
-0.75 SG B 7
2 26 11S
-0.75
1CAN102104 Page 6 of 65 SG Row Col
%TW Elev Offset SG B 7
6 14 11S
-0.77 SG B 7
7 21 11S
-0.81 SG B 7
8 17 10S
-0.68 SG B 7
9 26 10S
-0.7 SG B 7
10 23 10S
-0.7 SG B 7
11 21 10S
-0.68 SG B 7
12 17 10S
-0.75 SG B 7
15 17 10S
-0.75 SG B 7
26 11 10S 0.34 SG B 7
26 13 11S 0.24 SG B 7
27 10 10S
-0.75 SG B 7
27 18 11S 0.38 SG B 7
30 10 11S 0.36 SG B 7
36 12 11S 0.36 SG B 7
37 14 11S 0.38 SG B 7
38 13 11S 0.32 SG B 7
38 13 12S 0.3 SG B 7
39 31 11S 0.35 SG B 7
40 6
10S 0.45 SG B 7
40 13 11S 0.32 SG B 7
41 11 11S 0.41 SG B 7
46 10 11S
-0.7 SG B 7
46 11 11S 0.36 SG B 7
47 14 10S 0.49 SG B 7
47 10 11S
-0.75 SG B 7
47 11 11S 0.45 SG B 7
47 11 12S 0.32 SG B 7
48 12 10S 0.42 SG B 7
48 13 11S
-0.67 SG B 7
49 9
10S 0.45 SG B 7
49 14 11S 0.41 SG B 7
49 8
12S 0.35 SG B 7
50 11 10S 0.47 SG B 8
1 9
10S 0.47 SG B 8
1 22 11S
-0.77 SG B 8
2 14 11S
-0.77 SG B 8
4 10 10S 0.45 SG B 8
4 17 11S
-0.77 SG B 8
5 20 10S
-0.74 SG B 8
5 11 11S
-0.7
1CAN102104 Page 7 of 65 SG Row Col
%TW Elev Offset SG B 8
6 19 10S
-0.7 SG B 8
6 14 11S
-0.75 SG B 8
7 16 10S
-0.67 SG B 8
7 16 11S
-0.7 SG B 8
7 12 11S 0.38 SG B 8
8 10 11S
-0.77 SG B 8
8 19 11S 0.42 SG B 8
12 20 10S
-0.73 SG B 8
12 7
10S 0.38 SG B 8
13 13 10S
-0.75 SG B 8
13 12 10S 0.41 SG B 8
14 15 10S
-0.77 SG B 8
15 13 10S
-0.72 SG B 8
16 16 10S
-0.73 SG B 8
18 15 10S
-0.74 SG B 8
19 12 10S
-0.76 SG B 8
38 13 10S 0.32 SG B 8
39 10 09S
-0.73 SG B 8
39 12 10S 0.34 SG B 8
39 8
13S 0.26 SG B 8
40 9
09S
-0.68 SG B 8
43 5
13S
-0.92 SG B 8
47 10 11S 0.39 SG B 8
50 11 10S 0.45 SG B 8
50 20 11S 0.45 SG B 8
51 17 10S 0.47 SG B 8
51 10 11S
-0.7 SG B 8
52 16 11S
-0.72 SG B 8
53 6
10S 0.49 SG B 8
53 7
11S
-0.6 SG B 8
54 9
10S 0.49 SG B 8
54 11 11S
-0.73 SG B 8
54 13 12S
-0.83 SG B 9
1 8
10S 0.43 SG B 9
3 15 11S
-0.77 SG B 9
4 16 10S
-0.68 SG B 9
4 10 11S
-0.79 SG B 9
5 17 10S
-0.72 SG B 9
7 12 10S
-0.7 SG B 9
7 13 11S
-0.75
1CAN102104 Page 8 of 65 SG Row Col
%TW Elev Offset SG B 9
8 11 11S
-0.88 SG B 9
9 13 10S
-0.73 SG B 9
9 15 11S
-0.77 SG B 9
11 18 11S
-0.77 SG B 9
11 14 11S 0.38 SG B 9
12 12 10S
-0.72 SG B 9
13 13 10S
-0.73 SG B 9
14 10 10S
-0.74 SG B 9
14 13 10S 0.4 SG B 9
15 8
10S 0.41 SG B 9
16 10 10S
-0.7 SG B 9
16 12 10S 0.38 SG B 9
17 18 10S
-0.75 SG B 9
18 21 10S
-0.72 SG B 9
20 13 10S
-0.7 SG B 9
28 14 10S 0.36 SG B 9
34 15 10S 0.3 SG B 9
37 10 10S 0.34 SG B 9
41 19 14S
-0.83 SG B 9
47 11 14S
-0.81 SG B 9
52 11 13S
-0.73 SG B 9
53 9
13S
-0.84 SG B 9
54 10 10S 0.49 SG B 9
54 32 11S 0.43 SG B 9
55 10 10S 0.47 SG B 9
55 10 11S
-0.7 SG B 9
55 21 11S 0.41 SG B 9
55 11 12S
-0.77 SG B 9
56 9
10S 0.51 SG B 9
56 12 11S
-0.68 SG B 9
56 14 12S
-0.75 SG B 9
56 10 12S 0.34 SG B 9
57 16 11S 0.41 SG B 9
58 24 10S 0.47 SG B 9
59 8
10S 0.49 SG B 9
59 18 11S
-0.62 SG B 9
59 8
11S 0.39 SG B 9
60 20 10S 0.47 SG B 9
60 17 12S
-0.75 SG B 10 2
13 10S 0.45
1CAN102104 Page 9 of 65 SG Row Col
%TW Elev Offset SG B 10 2
13 11S
-0.79 SG B 10 3
26 11S
-0.75 SG B 10 4
14 10S 0.43 SG B 10 4
19 11S
-0.75 SG B 10 7
7 10S
-0.71 SG B 10 9
17 10S
-0.73 SG B 10 11 16 11S
-0.79 SG B 10 11 10 11S 0.4 SG B 10 13 14 11S
-0.79 SG B 10 15 7
14S
-0.86 SG B 10 16 14 10S
-0.73 SG B 10 17 8
10S 0.36 SG B 10 29 11 08S
-0.7 SG B 10 32 11 10S 0.34 SG B 10 33 14 10S 0.38 SG B 10 44 17 14S 0.24 SG B 10 45 6
14S 0.26 SG B 10 53 10 11S 0.37 SG B 10 54 19 11S 0.38 SG B 10 56 10 10S 0.45 SG B 10 56 11 11S
-0.72 SG B 10 57 8
10S 0.42 SG B 10 58 7
11S
-0.75 SG B 10 58 16 11S 0.41 SG B 10 59 8
10S 0.49 SG B 10 59 16 11S 0.41 SG B 10 59 11 13S
-0.88 SG B 10 60 11 11S
-0.73 SG B 10 60 12 13S 0.28 SG B 10 61 12 11S
-0.71 SG B 10 61 7
12S 0.35 SG B 10 62 15 11S 0.46 SG B 10 64 9
11S
-0.77 SG B 10 65 15 10S 0.45 SG B 11 2
12 11S
-0.77 SG B 11 2
9 11S 0.41 SG B 11 3
9 11S
-0.76 SG B 11 6
10 11S
-0.73 SG B 11 7
12 10S
-0.71 SG B 11 8
20 10S
-0.7
1CAN102104 Page 10 of 65 SG Row Col
%TW Elev Offset SG B 11 9
19 10S
-0.7 SG B 11 10 11 10S
-0.7 SG B 11 12 14 11S
-0.75 SG B 11 13 10 10S
-0.75 SG B 11 14 29 10S
-0.61 SG B 11 17 20 10S
-0.72 SG B 11 18 15 10S
-0.75 SG B 11 31 7
14S
-0.94 SG B 11 34 11 10S 0.36 SG B 11 35 11 10S 0.36 SG B 11 36 11 10S 0.34 SG B 11 46 8
13S
-0.79 SG B 11 49 6
14S
-0.84 SG B 11 55 5
13S
-0.8 SG B 11 58 8
10S 0.43 SG B 11 59 13 11S 0.43 SG B 11 60 7
10S 0.45 SG B 11 60 13 11S 0.43 SG B 11 61 11 10S 0.47 SG B 11 61 12 11S
-0.75 SG B 11 61 21 11S 0.42 SG B 11 61 10 13S
-0.75 SG B 11 61 11 13S 0.3 SG B 11 62 8
10S 0.47 SG B 11 63 13 11S
-0.73 SG B 11 64 7
08S
-0.73 SG B 11 64 7
11S 0.45 SG B 11 65 12 11S
-0.7 SG B 11 66 10 11S
-0.7 SG B 12 1
7 10S 0.38 SG B 12 1
9 11S
-0.77 SG B 12 2
10 10S 0.41 SG B 12 2
16 11S
-0.79 SG B 12 6
7 10S
-0.73 SG B 12 7
18 10S
-0.73 SG B 12 8
12 10S
-0.73 SG B 12 9
16 10S
-0.73 SG B 12 10 16 10S
-0.72 SG B 12 11 20 10S
-0.73 SG B 12 12 21 10S
-0.7
1CAN102104 Page 11 of 65 SG Row Col
%TW Elev Offset SG B 12 13 19 10S
-0.75 SG B 12 18 10 10S 0.38 SG B 12 24 11 14S
-0.92 SG B 12 24 11 14S 0.24 SG B 12 35 13 10S 0.36 SG B 12 38 9
14S 0.22 SG B 12 40 8
14S 0.22 SG B 12 57 11 10S 0.41 SG B 12 59 13 11S 0.43 SG B 12 63 10 11S
-0.7 SG B 12 63 13 12S
-0.73 SG B 12 64 8
10S 0.47 SG B 12 65 9
10S 0.45 SG B 12 66 12 11S
-0.68 SG B 12 66 10 12S 0.35 SG B 12 67 22 11S
-0.72 SG B 12 67 13 11S 0.41 SG B 12 68 12 11S
-0.68 SG B 12 69 12 10S 0.45 SG B 13 3
11 11S
-0.77 SG B 13 6
16 10S
-0.75 SG B 13 7
17 10S
-0.73 SG B 13 8
16 10S
-0.75 SG B 13 9
33 10S
-0.66 SG B 13 10 28 10S
-0.77 SG B 13 10 7
14S
-0.85 SG B 13 11 17 10S
-0.68 SG B 13 13 17 10S
-0.75 SG B 13 13 8
10S 0.36 SG B 13 17 9
11S
-0.83 SG B 13 18 9
10S
-0.79 SG B 13 56 7
14S 0.28 SG B 13 60 13 10S 0.43 SG B 13 60 11 11S 0.41 SG B 13 62 9
10S 0.38 SG B 13 64 13 11S 0.47 SG B 13 68 8
10S 0.49 SG B 13 69 6
13S 0.32 SG B 13 72 21 11S
-0.62 SG B 13 73 12 11S
-0.72
1CAN102104 Page 12 of 65 SG Row Col
%TW Elev Offset SG B 13 74 21 10S
-0.65 SG B 13 74 8
10S 0.37 SG B 14 4
12 11S
-0.79 SG B 14 7
18 10S
-0.68 SG B 14 8
23 10S
-0.75 SG B 14 12 21 10S
-0.73 SG B 14 13 28 10S
-0.75 SG B 14 13 11 10S 0.36 SG B 14 14 16 10S
-0.73 SG B 14 14 10 11S 0.34 SG B 14 15 14 11S 0.35 SG B 14 19 10 10S
-0.75 SG B 14 20 10 10S
-0.75 SG B 14 24 12 14S 0.21 SG B 14 25 11 14S 0.17 SG B 14 28 12 14S 0.24 SG B 14 38 8
14S 0.17 SG B 14 42 9
14S 0.19 SG B 14 61 10 13S
-0.81 SG B 14 62 16 10S 0.39 SG B 14 68 11 10S 0.41 SG B 14 69 6
10S 0.51 SG B 14 70 9
11S
-0.72 SG B 14 70 24 11S 0.43 SG B 14 74 17 11S
-0.7 SG B 14 75 18 11S
-0.64 SG B 14 75 21 11S 0.4 SG B 14 76 24 11S
-0.6 SG B 14 77 11 10S 0.45 SG B 15 3
10 11S
-0.75 SG B 15 5
6 10S 0.39 SG B 15 7
32 10S
-0.75 SG B 15 8
15 10S
-0.72 SG B 15 9
16 10S
-0.75 SG B 15 12 15 10S 0.41 SG B 15 14 11 10S 0.38 SG B 15 17 13 10S
-0.72 SG B 15 18 12 10S
-0.73 SG B 15 19 13 10S
-0.72 SG B 15 24 11 10S 0.36
1CAN102104 Page 13 of 65 SG Row Col
%TW Elev Offset SG B 15 25 6
10S 0.32 SG B 15 25 10 14S 0.17 SG B 15 30 9
14S
-0.92 SG B 15 32 11 14S
-0.88 SG B 15 36 16 14S 0.17 SG B 15 40 11 14S 0.19 SG B 15 63 13 10S 0.36 SG B 15 65 11 10S 0.39 SG B 15 66 12 10S 0.41 SG B 15 67 10 10S 0.41 SG B 15 67 7
13S
-0.77 SG B 15 69 10 10S 0.41 SG B 15 72 6
14S
-0.73 SG B 15 72 12 14S 0.34 SG B 15 73 12 09S
-0.7 SG B 15 74 10 11S 0.43 SG B 15 76 11 12S 0.34 SG B 15 77 20 11S
-0.71 SG B 15 77 13 11S 0.41 SG B 15 78 10 08S
-0.7 SG B 15 78 15 11S
-0.71 SG B 15 79 14 10S 0.45 SG B 15 79 19 11S
-0.69 SG B 15 80 19 10S
-0.68 SG B 15 80 17 11S
-0.7 SG B 16 1
12 11S
-0.79 SG B 16 2
9 11S
-0.79 SG B 16 7
13 10S
-0.73 SG B 16 8
15 10S
-0.73 SG B 16 9
10 10S
-0.73 SG B 16 20 10 10S
-0.79 SG B 16 28 13 14S 0.17 SG B 16 64 13 10S 0.36 SG B 16 66 13 10S 0.41 SG B 16 67 12 09S
-0.72 SG B 16 68 7
10S 0.43 SG B 16 70 9
09S
-0.73 SG B 16 70 7
13S
-0.83 SG B 16 72 10 09S
-0.68 SG B 16 72 15 14S
-0.78
1CAN102104 Page 14 of 65 SG Row Col
%TW Elev Offset SG B 16 75 17 10S 0.45 SG B 16 78 14 11S
-0.7 SG B 16 78 14 11S 0.36 SG B 16 78 11 12S
-0.75 SG B 16 79 27 11S
-0.7 SG B 16 79 11 11S 0.4 SG B 16 80 12 11S
-0.64 SG B 16 80 10 13S
-0.79 SG B 16 81 14 09S 0.34 SG B 16 81 23 10S 0.44 SG B 16 81 13 11S
-0.74 SG B 17 1
19 11S
-0.79 SG B 17 4
10 11S
-0.77 SG B 17 8
14 11S 0.39 SG B 17 13 14 10S
-0.75 SG B 17 28 12 14S
-0.83 SG B 17 68 12 09S
-0.72 SG B 17 68 14 10S 0.41 SG B 17 69 8
09S
-0.73 SG B 17 71 8
09S
-0.71 SG B 17 78 12 11S 0.45 SG B 17 79 9
13S
-0.8 SG B 17 80 12 12S
-0.74 SG B 17 82 24 10S 0.4 SG B 17 82 17 11S
-0.72 SG B 17 82 10 13S 0.35 SG B 17 84 13 10S
-0.72 SG B 17 84 18 11S
-0.7 SG B 18 1
24 11S
-0.74 SG B 18 3
13 11S
-0.75 SG B 18 8
10 10S 0.3 SG B 18 12 9
14S 0.19 SG B 18 19 7
14S 0.23 SG B 18 54 7
08S
-0.68 SG B 18 54 6
08S 0.41 SG B 18 73 16 14S 0.3 SG B 18 78 7
09S
-0.73 SG B 18 78 8
09S 0.4 SG B 18 78 19 10S 0.45 SG B 18 78 8
13S
-0.78
1CAN102104 Page 15 of 65 SG Row Col
%TW Elev Offset SG B 18 81 11 13S
-0.79 SG B 18 81 12 13S 0.28 SG B 18 82 11 11S
-0.82 SG B 18 83 10 10S
-0.75 SG B 18 83 21 10S 0.4 SG B 18 83 16 11S
-0.72 SG B 18 83 10 11S 0.44 SG B 18 83 11 12S 0.38 SG B 18 83 11 13S
-0.74 SG B 18 84 15 11S
-0.72 SG B 18 85 20 10S
-0.72 SG B 19 1
31 11S
-0.77 SG B 19 9
18 10S
-0.71 SG B 19 9
15 14S
-0.79 SG B 19 9
12 14S 0.21 SG B 19 10 8
10S 0.34 SG B 19 42 12 08S 0.4 SG B 19 49 6
08S
-0.66 SG B 19 80 20 10S 0.43 SG B 19 83 11 11S
-0.73 SG B 19 83 14 11S 0.28 SG B 19 85 10 12S 0.37 SG B 19 86 11 11S
-0.72 SG B 19 86 11 12S 0.37 SG B 19 87 13 10S 0.43 SG B 20 2
27 11S
-0.88 SG B 20 7
13 10S
-0.75 SG B 20 9
8 14S
-0.9 SG B 20 11 8
10S 0.39 SG B 20 15 10 10S 0.38 SG B 20 18 15 14S 0.24 SG B 20 19 11 10S 0.32 SG B 20 29 11 08S 0.38 SG B 20 50 12 07S
-0.69 SG B 20 51 10 07S
-0.68 SG B 20 51 9
08S
-0.68 SG B 20 51 14 08S 0.38 SG B 20 51 8
09S
-0.75 SG B 20 54 8
08S 0.41 SG B 20 55 11 08S 0.39
1CAN102104 Page 16 of 65 SG Row Col
%TW Elev Offset SG B 20 80 7
14S 0.3 SG B 20 81 11 10S 0.43 SG B 20 81 11 11S 0.38 SG B 20 81 7
13S
-0.8 SG B 20 81 10 14S
-0.7 SG B 20 82 9
10S 0.4 SG B 20 83 18 11S 0.33 SG B 20 84 8
13S
-0.82 SG B 20 84 10 13S 0.32 SG B 20 85 10 04S
-0.7 SG B 20 85 10 08S
-0.72 SG B 20 86 12 12S 0.34 SG B 20 87 13 12S 0.38 SG B 21 2
15 11S
-0.8 SG B 21 3
11 11S
-0.78 SG B 21 7
30 10S
-0.77 SG B 21 8
10 10S
-0.75 SG B 21 21 16 14S 0.21 SG B 21 33 8
08S 0.41 SG B 21 42 6
08S 0.42 SG B 21 47 9
08S 0.43 SG B 21 47 10 09S
-0.71 SG B 21 47 11 09S 0.36 SG B 21 48 7
08S 0.4 SG B 21 57 8
08S 0.43 SG B 21 58 13 08S 0.39 SG B 21 60 6
07S 0.45 SG B 21 82 14 10S 0.41 SG B 21 83 9
10S 0.43 SG B 21 84 10 04S
-0.64 SG B 21 86 11 12S
-0.72 SG B 21 89 8
10S
-0.73 SG B 22 2
28 12S 0
SG B 22 3
20 11S
-0.77 SG B 22 4
11 11S
-0.81 SG B 22 8
11 10S
-0.74 SG B 22 10 16 10S
-0.79 SG B 22 11 6
10S 0.34 SG B 22 12 11 10S 0.36 SG B 22 26 10 14S 0.19
1CAN102104 Page 17 of 65 SG Row Col
%TW Elev Offset SG B 22 36 11 08S
-0.68 SG B 22 36 10 08S 0.38 SG B 22 38 7
07S 0.43 SG B 22 38 8
08S 0.4 SG B 22 41 9
06S
-0.68 SG B 22 41 6
08S
-0.77 SG B 22 41 12 08S 0.38 SG B 22 56 7
07S 0.4 SG B 22 57 10 08S 0.41 SG B 22 58 7
08S 0.42 SG B 22 59 11 08S 0.43 SG B 22 60 7
08S 0.43 SG B 22 62 7
08S 0.36 SG B 22 63 9
08S 0.41 SG B 22 66 11 08S 0.4 SG B 22 86 11 11S 0.38 SG B 22 89 14 12S
-0.77 SG B 22 89 16 13S
-0.75 SG B 22 89 13 13S 0.26 SG B 22 92 13 13S
-0.8 SG B 22 93 13 10S
-0.73 SG B 22 93 14 11S
-0.73 SG B 23 2
18 11S
-0.77 SG B 23 4
11 11S
-0.75 SG B 23 5
8 10S
-0.77 SG B 23 8
30 10S
-0.75 SG B 23 14 11 10S 0.34 SG B 23 19 13 14S
-0.88 SG B 23 24 10 14S 0.19 SG B 23 38 7
08S 0.34 SG B 23 45 18 08S 0.39 SG B 23 51 10 08S 0.41 SG B 23 56 8
08S 0.38 SG B 23 59 12 08S 0.38 SG B 23 80 11 13S
-0.83 SG B 23 85 8
09S
-0.64 SG B 23 88 16 11S 0.38 SG B 23 92 22 12S 0.38 SG B 24 1
15 11S
-0.79 SG B 24 2
15 11S
-0.79
1CAN102104 Page 18 of 65 SG Row Col
%TW Elev Offset SG B 24 5
14 10S
-0.77 SG B 24 10 12 10S
-0.75 SG B 24 11 6
10S 0.36 SG B 24 15 15 14S 0.19 SG B 24 19 10 14S
-0.89 SG B 24 41 11 08S 0.43 SG B 24 43 12 08S 0.4 SG B 24 44 13 08S 0.4 SG B 24 45 10 08S
-0.68 SG B 24 45 18 08S 0.36 SG B 24 49 5
08S
-0.77 SG B 24 49 10 08S 0.36 SG B 24 51 9
08S 0.43 SG B 24 84 14 11S 0.36 SG B 24 84 11 13S
-0.76 SG B 24 85 11 10S 0.4 SG B 25 1
21 10S
-0.8 SG B 25 2
14 10S
-0.79 SG B 25 3
15 11S
-0.75 SG B 25 4
16 11S
-0.83 SG B 25 5
11 11S
-0.78 SG B 25 7
23 10S
-0.75 SG B 25 15 18 14S 0.21 SG B 25 16 10 10S 0.34 SG B 25 22 10 10S 0.34 SG B 25 31 8
08S 0.36 SG B 25 33 9
08S 0.39 SG B 25 34 11 08S 0.4 SG B 25 35 6
08S 0.41 SG B 25 36 13 08S 0.4 SG B 25 41 7
08S
-0.79 SG B 25 44 7
07S 0.55 SG B 25 52 14 08S 0.36 SG B 25 53 7
07S 0.43 SG B 25 53 11 08S 0.41 SG B 25 55 6
08S 0.43 SG B 25 72 7
08S 0.4 SG B 25 84 8
13S
-0.85 SG B 25 96 12 10S 0.43 SG B 25 96 14 12S 0.38
1CAN102104 Page 19 of 65 SG Row Col
%TW Elev Offset SG B 26 3
10 11S
-0.83 SG B 26 4
15 11S
-0.83 SG B 26 5
17 11S
-0.81 SG B 26 7
13 10S
-0.75 SG B 26 8
12 10S
-0.77 SG B 26 13 11 10S 0.34 SG B 26 15 16 14S 0.19 SG B 26 24 9
10S 0.32 SG B 26 28 7
08S 0.38 SG B 26 31 8
08S 0.41 SG B 26 33 8
08S 0.36 SG B 26 34 5
08S 0.43 SG B 26 36 6
08S 0.38 SG B 26 39 11 06S 0.38 SG B 26 45 8
07S 0.58 SG B 26 45 9
08S 0.41 SG B 26 46 6
07S 0.4 SG B 26 46 9
08S 0.43 SG B 26 91 12 10S 0.36 SG B 26 92 10 10S 0.41 SG B 27 2
32 11S
-0.75 SG B 27 4
12 11S
-0.74 SG B 27 4
11 12S 0.21 SG B 27 5
21 11S
-0.81 SG B 27 13 15 14S
-0.79 SG B 27 19 9
10S 0.34 SG B 27 27 10 08S 0.38 SG B 27 30 10 08S 0.38 SG B 27 34 6
07S 0.4 SG B 27 47 10 08S 0.41 SG B 27 48 6
07S 0.45 SG B 27 48 9
08S 0.41 SG B 27 56 12 08S 0.39 SG B 27 67 13 08S 0.43 SG B 27 68 4
08S 0.41 SG B 28 2
15 11S
-0.81 SG B 28 3
19 11S
-0.83 SG B 28 4
11 11S
-0.81 SG B 28 5
12 11S
-0.81 SG B 28 42 9
08S 0.41
1CAN102104 Page 20 of 65 SG Row Col
%TW Elev Offset SG B 28 49 8
08S 0.4 SG B 28 61 13 08S 0.43 SG B 28 62 7
08S 0.41 SG B 28 66 7
08S 0.41 SG B 28 67 8
08S 0.43 SG B 28 68 5
08S 0.39 SG B 28 78 7
08S 0.41 SG B 28 82 6
08S 0.45 SG B 28 97 10 04S
-0.68 SG B 29 2
11 10S
-0.81 SG B 29 2
15 11S
-0.75 SG B 29 3
14 11S
-0.83 SG B 29 3
10 11S 0.41 SG B 29 14 16 14S 0.15 SG B 29 31 8
08S 0.36 SG B 29 33 8
08S 0.38 SG B 30 2
12 11S
-0.77 SG B 30 3
10 11S
-0.83 SG B 30 14 11 14S
-0.9 SG B 30 32 7
08S 0.34 SG B 30 33 9
08S 0.41 SG B 30 34 5
08S 0.45 SG B 30 36 8
08S 0.39 SG B 30 37 11 08S 0.41 SG B 30 76 10 08S 0.43 SG B 30 77 5
07S 0.43 SG B 30 77 7
08S 0.43 SG B 30 79 5
08S 0.45 SG B 30 82 10 08S 0.41 SG B 30 99 11 13S
-0.75 SG B 30 102 11 04S
-0.66 SG B 30 102 8
13S
-0.79 SG B 30 103 19 12S
-0.68 SG B 31 2
8 10S
-0.75 SG B 31 2
16 11S
-0.77 SG B 31 2
10 11S 0.37 SG B 31 3
19 11S
-0.79 SG B 31 23 8
08S 0.36 SG B 31 33 19 08S 0.41 SG B 31 33 8
10S
-0.71
1CAN102104 Page 21 of 65 SG Row Col
%TW Elev Offset SG B 31 34 12 08S 0.41 SG B 31 36 12 08S 0.41 SG B 31 36 6
10S
-0.73 SG B 31 37 10 06S
-0.64 SG B 31 37 16 08S 0.35 SG B 31 73 10 08S 0.43 SG B 31 77 7
07S 0.47 SG B 31 77 11 08S
-0.75 SG B 31 77 12 08S 0.41 SG B 31 78 10 08S 0.39 SG B 31 79 9
08S 0.36 SG B 31 98 6
08S
-0.66 SG B 31 100 8
10S 0.43 SG B 32 1
20 11S
-0.77 SG B 32 3
12 11S
-0.79 SG B 32 13 14 14S
-0.94 SG B 32 30 13 08S 0.39 SG B 32 32 7
08S
-0.75 SG B 32 32 8
08S 0.36 SG B 32 32 8
09S 0.36 SG B 32 34 9
10S 0.32 SG B 32 36 9
08S 0.39 SG B 32 77 11 08S 0.43 SG B 32 100 11 10S 0.41 SG B 32 103 10 12S 0.38 SG B 33 1
23 11S
-0.79 SG B 33 2
19 11S
-0.81 SG B 33 28 6
08S 0.36 SG B 33 52 10 08S 0.45 SG B 33 79 11 08S 0.41 SG B 33 87 9
08S 0.47 SG B 33 88 6
07S 0.45 SG B 33 89 8
08S 0.38 SG B 33 103 12 13S
-0.75 SG B 33 106 11 12S
-0.72 SG B 33 106 10 12S 0.38 SG B 34 1
14 11S
-0.77 SG B 34 2
28 11S
-0.84 SG B 34 3
16 11S
-0.76 SG B 34 4
11 12S 0.26
1CAN102104 Page 22 of 65 SG Row Col
%TW Elev Offset SG B 34 6
10 14S
-0.96 SG B 34 85 7
08S 0.36 SG B 34 90 9
08S 0.45 SG B 34 107 11 13S
-0.68 SG B 35 1
17 11S
-0.75 SG B 35 2
21 11S
-0.79 SG B 35 2
10 12S 0.19 SG B 35 3
13 11S
-0.77 SG B 35 89 8
08S 0.47 SG B 35 107 15 13S
-0.7 SG B 35 109 10 12S
-0.7 SG B 36 2
13 11S
-0.81 SG B 36 3
11 11S
-0.78 SG B 36 37 4
07S 0.57 SG B 36 38 5
08S 0.38 SG B 36 40 5
08S 0.41 SG B 36 90 12 08S
-0.68 SG B 36 97 5
08S 0.43 SG B 36 108 12 09S
-0.71 SG B 36 110 22 12S 0.34 SG B 36 111 11 12S
-0.68 SG B 36 111 10 13S
-0.72 SG B 36 111 12 13S 0.34 SG B 37 2
15 11S
-0.74 SG B 37 10 14 14S 0.19 SG B 37 24 7
08S 0.4 SG B 37 27 6
08S 0.4 SG B 37 31 10 08S 0.4 SG B 37 31 8
09S 0.38 SG B 37 83 6
08S 0.41 SG B 37 91 7
08S 0.47 SG B 37 93 11 08S
-0.66 SG B 37 110 8
10S 0.51 SG B 37 111 14 13S
-0.7 SG B 37 112 10 12S
-0.68 SG B 37 112 12 12S 0.39 SG B 37 112 12 13S
-0.71 SG B 37 112 13 13S 0.36 SG B 37 114 6
11S
-0.64 SG B 38 1
9 10S 0.38
1CAN102104 Page 23 of 65 SG Row Col
%TW Elev Offset SG B 38 2
13 11S
-0.85 SG B 38 38 7
08S 0.42 SG B 38 39 5
08S 0.45 SG B 38 69 8
04S 0.53 SG B 38 110 12 13S
-0.73 SG B 38 111 13 10S 0.38 SG B 38 113 12 13S
-0.71 SG B 38 115 5
10S
-0.53 SG B 39 25 7
08S 0.42 SG B 39 27 7
08S 0.4 SG B 39 28 4
07S 0.51 SG B 39 28 4
08S 0.45 SG B 39 113 14 12S 0.44 SG B 39 114 12 12S 0.42 SG B 39 114 14 13S
-0.72 SG B 40 1
12 11S
-0.73 SG B 40 3
11 11S 0.38 SG B 40 31 5
08S 0.38 SG B 40 93 8
08S
-0.67 SG B 40 112 10 10S
-0.66 SG B 40 113 10 10S
-0.66 SG B 40 113 11 12S 0.42 SG B 40 113 12 13S
-0.72 SG B 41 22 6
08S 0.36 SG B 41 22 10 09S
-0.83 SG B 41 25 6
08S
-0.75 SG B 41 97 10 08S 0.46 SG B 41 111 16 13S
-0.72 SG B 41 113 8
10S 0.5 SG B 41 114 9
11S
-0.68 SG B 41 114 8
14S
-0.65 SG B 41 115 12 12S
-0.74 SG B 41 115 22 13S
-0.72 SG B 41 116 13 12S 0.38 SG B 42 2
17 11S
-0.79 SG B 42 24 8
08S 0.34 SG B 42 25 4
08S 0.41 SG B 42 112 15 13S
-0.72 SG B 43 100 10 08S 0.44 SG B 43 114 7
09S 0.5
1CAN102104 Page 24 of 65 SG Row Col
%TW Elev Offset SG B 43 114 13 13S
-0.74 SG B 43 115 10 13S
-0.7 SG B 44 1
6 10S 0.36 SG B 44 2
11 11S
-0.76 SG B 44 3
8 10S 0.09 SG B 44 4
10 10S 0.17 SG B 44 25 4
08S 0.45 SG B 44 98 10 09S 0.48 SG B 44 100 8
08S 0.46 SG B 44 113 12 09S
-0.7 SG B 44 114 15 13S
-0.7 SG B 44 115 13 12S 0.4 SG B 44 116 22 13S
-0.68 SG B 44 117 14 11S
-0.68 SG B 45 3
11 11S 0.38 SG B 45 5
9 10S 0.04 SG B 45 29 4
08S 0.47 SG B 45 113 18 09S
-0.56 SG B 45 113 7
09S 0.5 SG B 45 114 14 09S
-0.67 SG B 45 114 11 13S
-0.69 SG B 45 115 9
10S 0.54 SG B 45 115 10 13S
-0.61 SG B 45 116 8
10S 0.54 SG B 45 116 16 13S
-0.69 SG B 45 118 17 13S
-0.72 SG B 46 2
8 10S 0.4 SG B 46 6
8 10S 0.06 SG B 46 103 8
07S 0.53 SG B 46 103 5
08S 0.49 SG B 46 114 14 13S
-0.7 SG B 46 115 7
10S 0.51 SG B 46 117 13 13S
-0.66 SG B 46 118 12 13S
-0.66 SG B 46 119 11 11S
-0.66 SG B 46 119 17 13S
-0.68 SG B 46 119 14 13S 0.38 SG B 47 1
13 11S 0.45 SG B 47 2
7 10S 0.38 SG B 47 7
12 10S 0.11
1CAN102104 Page 25 of 65 SG Row Col
%TW Elev Offset SG B 47 111 19 09S
-0.64 SG B 47 114 10 10S 0.53 SG B 47 117 11 13S
-0.68 SG B 48 1
13 11S 0.43 SG B 48 20 4
09S
-0.72 SG B 48 38 4
08S 0.43 SG B 48 113 14 09S
-0.64 SG B 48 114 14 09S
-0.64 SG B 48 116 12 13S
-0.66 SG B 48 121 10 11S 0.56 SG B 48 121 13 12S
-0.66 SG B 48 121 24 13S
-0.69 SG B 49 1
12 11S
-0.79 SG B 49 1
10 12S 0.26 SG B 49 2
13 11S
-0.77 SG B 49 2
12 11S 0.43 SG B 49 7
5 13S 0.24 SG B 49 8
9 10S 0.11 SG B 49 20 4
08S 0.39 SG B 49 84 12 04S
-0.69 SG B 49 85 7
06S 0.47 SG B 49 102 5
08S 0.49 SG B 49 113 13 09S
-0.66 SG B 49 113 8
09S 0.45 SG B 49 115 11 13S
-0.7 SG B 49 122 16 13S
-0.66 SG B 50 1
10 10S
-0.75 SG B 50 1
15 11S
-0.79 SG B 50 8
5 13S 0.2 SG B 50 20 4
08S 0.36 SG B 50 105 7
08S 0.49 SG B 50 113 13 09S
-0.66 SG B 50 114 9
10S 0.49 SG B 50 116 8
10S 0.51 SG B 51 6
10 13S 0.21 SG B 51 118 11 12S 0.43 SG B 52 4
11 10S
-0.75 SG B 52 4
9 13S 0.24 SG B 52 76 11 07S 0.51 SG B 52 83 13 04S
-0.66
1CAN102104 Page 26 of 65 SG Row Col
%TW Elev Offset SG B 52 93 12 08S 0.49 SG B 52 114 10 09S 0.51 SG B 52 116 11 10S 0.45 SG B 52 120 9
13S
-0.64 SG B 52 121 10 10S 0.63 SG B 52 121 18 13S
-0.67 SG B 53 1
5 06S 0.47 SG B 53 1
10 11S
-0.72 SG B 53 3
14 14S
-0.92 SG B 53 104 7
08S 0.49 SG B 53 116 16 13S
-0.66 SG B 53 117 10 10S 0.49 SG B 53 117 17 13S
-0.7 SG B 53 118 14 10S 0.51 SG B 53 118 13 13S
-0.68 SG B 53 119 14 10S 0.51 SG B 53 120 11 10S 0.56 SG B 53 121 18 10S 0.57 SG B 53 122 12 10S 0.66 SG B 53 122 10 12S 0.43 SG B 53 124 12 13S
-0.64 SG B 54 1
12 12S 0.21 SG B 54 1
15 14S
-0.79 SG B 54 22 5
08S 0.36 SG B 54 23 12 08S
-0.68 SG B 54 23 10 08S 0.38 SG B 54 23 10 09S
-0.74 SG B 54 92 14 03S
-0.66 SG B 54 118 16 13S
-0.7 SG B 54 119 12 09S
-0.68 SG B 54 119 8
10S 0.49 SG B 54 120 11 09S
-0.66 SG B 54 120 7
10S 0.53 SG B 54 121 11 09S
-0.66 SG B 54 122 11 09S
-0.66 SG B 54 122 7
10S 0.53 SG B 54 123 9
10S 0.6 SG B 54 123 9
11S 0.51 SG B 54 123 23 13S
-0.64 SG B 54 124 17 12S
-0.68
1CAN102104 Page 27 of 65 SG Row Col
%TW Elev Offset SG B 54 124 11 12S 0.49 SG B 54 124 24 13S
-0.64 SG B 54 125 8
12S 0.45 SG B 55 4
6 13S
-0.76 SG B 55 26 8
08S 0.34 SG B 55 124 9
09S 0.51 SG B 55 125 13 10S 0.65 SG B 55 125 10 12S
-0.7 SG B 55 125 16 12S 0.43 SG B 56 25 5
08S 0.39 SG B 56 112 7
08S 0.53 SG B 56 125 10 10S 0.6 SG B 56 125 15 12S
-0.66 SG B 56 126 10 10S 0.7 SG B 56 126 12 12S
-0.68 SG B 56 127 12 12S
-0.66 SG B 57 1
10 11S
-0.81 SG B 57 17 7
08S 0.36 SG B 57 20 8
08S 0.38 SG B 57 22 8
08S 0.36 SG B 57 124 11 09S
-0.64 SG B 57 126 19 12S 0.43 SG B 57 126 15 13S
-0.64 SG B 57 127 12 10S 0.68 SG B 58 18 5
09S
-0.77 SG B 58 99 16 03S
-0.64 SG B 58 108 6
09S 0.49 SG B 58 126 9
11S 0.55 SG B 58 126 13 12S
-0.64 SG B 58 126 15 13S
-0.64 SG B 58 127 12 12S
-0.66 SG B 58 127 12 13S
-0.71 SG B 59 110 10 09S
-0.66 SG B 59 124 12 09S 0.53 SG B 59 125 9
11S 0.64 SG B 59 127 11 10S 0.66 SG B 59 128 10 13S
-0.64 SG B 60 1
10 11S
-0.77 SG B 60 4
16 11S 0.3 SG B 60 19 8
08S 0.34
1CAN102104 Page 28 of 65 SG Row Col
%TW Elev Offset SG B 60 124 12 09S
-0.64 SG B 60 125 10 09S
-0.56 SG B 60 125 10 09S 0.51 SG B 60 125 9
10S 0.49 SG B 60 125 7
11S 0.6 SG B 60 125 14 14S 0.54 SG B 60 127 9
10S 0.63 SG B 61 1
14 11S
-0.79 SG B 61 6
12 11S 0.34 SG B 61 125 10 09S 0.55 SG B 61 126 7
10S 0.53 SG B 61 127 8
10S 0.64 SG B 61 128 12 13S
-0.66 SG B 61 129 7
12S
-0.6 SG B 61 130 9
10S 0.66 SG B 62 5
8 14S
-0.89 SG B 62 110 6
08S 0.58 SG B 62 122 13 09S
-0.51 SG B 62 124 7
10S 0.59 SG B 62 124 10 12S 0.43 SG B 63 3
13 11S 0.32 SG B 63 4
26 11S 0.31 SG B 63 125 9
09S
-0.62 SG B 63 125 13 09S 0.53 SG B 63 126 8
10S 0.62 SG B 63 128 13 12S 0.49 SG B 63 128 14 13S
-0.62 SG B 63 129 10 12S 0.49 SG B 64 5
10 12S 0.23 SG B 64 111 10 09S
-0.7 SG B 64 123 9
10S
-0.66 SG B 64 124 6
09S 0.57 SG B 64 125 11 10S 0.6 SG B 64 129 12 10S 0.64 SG B 65 110 9
09S
-0.59 SG B 65 110 11 09S 0.47 SG B 65 110 8
10S 0.42 SG B 65 114 11 08S 0.51 SG B 65 118 10 09S 0.53 SG B 65 128 6
12S 0.51
1CAN102104 Page 29 of 65 SG Row Col
%TW Elev Offset SG B 66 37 6
08S 0.49 SG B 66 109 7
08S 0.57 SG B 66 119 6
09S 0.51 SG B 66 124 14 12S 0.45 SG B 67 5
8 10S 0.21 SG B 67 6
6 13S
-0.83 SG B 67 121 10 11S 0.51 SG B 67 125 6
09S
-0.58 SG B 67 126 10 13S
-0.62 SG B 67 129 7
10S 0.61 SG B 67 130 10 12S 0.51 SG B 67 130 9
13S
-0.64 SG B 67 130 12 13S 0.51 SG B 68 5
11 12S 0.23 SG B 68 7
13 14S 0.19 SG B 68 110 10 08S 0.53 SG B 68 111 6
08S 0.53 SG B 68 113 7
08S 0.53 SG B 68 114 6
08S 0.55 SG B 68 117 7
09S 0.49 SG B 68 124 7
09S 0.58 SG B 68 126 8
09S
-0.56 SG B 68 126 7
09S 0.53 SG B 68 129 10 12S 0.45 SG B 68 130 6
12S 0.53 SG B 68 131 12 10S
-0.55 SG B 68 131 12 10S 0.6 SG B 68 131 17 13S 0.49 SG B 69 4
13 11S 0.36 SG B 69 4
11 12S 0.25 SG B 69 6
11 14S 0.15 SG B 69 8
16 14S
-0.91 SG B 69 13 16 14S
-0.36 SG B 69 16 14 14S
-0.46 SG B 69 112 11 09S
-0.64 SG B 69 113 11 09S
-0.64 SG B 69 114 7
08S 0.55 SG B 69 128 9
13S
-0.64 SG B 69 130 10 12S 0.47 SG B 69 131 14 12S 0.48
1CAN102104 Page 30 of 65 SG Row Col
%TW Elev Offset SG B 69 131 19 13S 0.47 SG B 70 5
10 12S 0.25 SG B 70 5
12 14S
-0.93 SG B 70 6
8 13S 0.24 SG B 70 20 5
08S 0.38 SG B 70 116 11 09S 0.49 SG B 70 118 11 09S 0.51 SG B 70 124 10 09S
-0.6 SG B 70 124 7
09S 0.51 SG B 70 128 16 12S 0.44 SG B 70 130 6
12S 0.51 SG B 71 1
8 12S
-0.87 SG B 71 5
9 10S 0.06 SG B 71 116 5
08S 0.55 SG B 71 121 7
09S 0.53 SG B 71 132 11 10S
-0.62 SG B 72 67 10 13S
-0.71 SG B 72 67 10 13S 0.43 SG B 72 125 25 11S 0.45 SG B 72 128 7
12S 0.55 SG B 72 129 12 12S
-0.64 SG B 72 129 14 12S 0.49 SG B 72 130 7
11S 0.55 SG B 72 130 16 12S 0.44 SG B 72 131 10 10S
-0.6 SG B 72 131 11 11S 0.56 SG B 72 131 12 12S 0.6 SG B 73 7
12 14S
-0.92 SG B 73 108 9
08S 0.45 SG B 73 120 9
09S 0.53 SG B 73 125 10 09S
-0.55 SG B 73 126 13 09S
-0.55 SG B 73 131 12 09S
-0.53 SG B 73 131 9
12S 0.55 SG B 73 131 30 13S 0.45 SG B 73 132 9
08S
-0.64 SG B 73 132 7
08S 0.64 SG B 73 132 25 10S
-0.59 SG B 73 132 8
12S 0.66 SG B 74 114 8
08S 0.57
1CAN102104 Page 31 of 65 SG Row Col
%TW Elev Offset SG B 74 117 12 09S
-0.64 SG B 74 124 7
13S
-0.6 SG B 74 125 11 09S
-0.64 SG B 74 127 10 12S 0.48 SG B 74 127 10 13S
-0.63 SG B 74 128 8
09S
-0.51 SG B 74 130 11 10S 0.53 SG B 74 131 13 11S
-0.58 SG B 74 131 10 12S 0.64 SG B 74 131 13 13S 0.51 SG B 75 2
10 11S
-0.9 SG B 75 5
9 10S
-0.09 SG B 75 125 20 14S 0.47 SG B 75 126 9
09S
-0.57 SG B 75 126 6
09S 0.51 SG B 75 127 17 13S
-0.63 SG B 75 128 13 13S
-0.64 SG B 75 129 8
12S 0.55 SG B 75 131 5
11S 0.64 SG B 75 131 8
12S 0.51 SG B 75 132 12 11S
-0.58 SG B 75 132 9
12S 0.58 SG B 75 132 14 13S 0.53 SG B 76 1
11 11S
-0.77 SG B 76 1
13 12S
-0.79 SG B 76 4
4 10S
-0.04 SG B 76 110 12 09S 0.51 SG B 76 123 11 09S
-0.57 SG B 76 123 10 09S 0.59 SG B 76 123 22 14S 0.45 SG B 76 124 11 09S
-0.62 SG B 76 124 9
14S 0.53 SG B 76 127 17 11S 0.6 SG B 77 1
18 11S
-0.79 SG B 77 2
12 12S
-0.83 SG B 77 4
11 12S 0.26 SG B 77 18 5
08S 0.4 SG B 77 108 15 08S 0.49 SG B 77 116 17 09S 0.49 SG B 77 118 20 09S 0.51
1CAN102104 Page 32 of 65 SG Row Col
%TW Elev Offset SG B 77 120 12 09S 0.6 SG B 77 126 18 09S
-0.6 SG B 77 126 15 09S 0.6 SG B 77 127 10 09S
-0.47 SG B 77 130 17 11S 0.53 SG B 77 130 16 12S 0.49 SG B 77 131 8
10S 0.49 SG B 77 132 14 09S
-0.55 SG B 77 132 14 12S 0.55 SG B 78 1
13 12S
-0.82 SG B 78 2
12 12S
-0.73 SG B 78 3
11 12S 0.24 SG B 78 4
9 10S 0.06 SG B 78 4
14 12S 0.28 SG B 78 4
10 13S
-0.79 SG B 78 114 9
08S 0.53 SG B 78 116 10 09S 0.53 SG B 78 118 13 08S 0.53 SG B 78 125 8
09S
-0.53 SG B 78 125 7
09S 0.53 SG B 78 126 15 09S
-0.57 SG B 78 128 13 12S 0.47 SG B 78 129 6
06S 0.55 SG B 78 129 14 13S 0.47 SG B 79 1
17 12S
-0.81 SG B 79 2
19 12S
-0.83 SG B 79 3
16 12S 0.28 SG B 79 4
11 12S 0.28 SG B 79 123 11 09S 0.51 SG B 79 126 10 09S
-0.58 SG B 79 126 11 14S
-0.66 SG B 79 126 12 14S 0.45 SG B 79 130 16 11S 0.5 SG B 79 131 12 12S 0.51 SG B 79 132 13 08S 0.57 SG B 79 132 11 10S 0.53 SG B 80 1
14 11S
-0.82 SG B 80 1
17 12S
-0.77 SG B 80 2
10 12S
-0.7 SG B 80 4
11 10S 0.02
1CAN102104 Page 33 of 65 SG Row Col
%TW Elev Offset SG B 80 5
10 06S 0.41 SG B 80 25 11 09S
-0.77 SG B 80 26 10 09S
-0.72 SG B 80 114 10 08S 0.59 SG B 80 115 7
08S 0.57 SG B 80 126 23 09S
-0.59 SG B 80 130 10 11S 0.51 SG B 81 2
17 12S
-0.78 SG B 81 3
14 12S 0.3 SG B 81 5
14 10S 0.09 SG B 81 6
5 14S 0.19 SG B 81 112 18 08S 0.55 SG B 81 113 12 07S
-0.55 SG B 81 113 9
08S 0.55 SG B 81 114 12 09S 0.51 SG B 81 118 18 11S
-0.7 SG B 81 120 11 09S 0.51 SG B 81 125 16 11S 0.45 SG B 81 126 14 09S
-0.57 SG B 81 126 17 09S 0.57 SG B 81 127 11 13S
-0.62 SG B 81 130 12 13S
-0.53 SG B 81 131 17 12S 0.49 SG B 81 132 16 09S
-0.64 SG B 82 1
16 12S
-0.74 SG B 82 2
15 12S
-0.82 SG B 82 4
12 10S 0.02 SG B 82 22 6
08S 0.51 SG B 82 112 13 08S 0.57 SG B 82 112 20 09S
-0.62 SG B 82 112 15 09S 0.53 SG B 82 114 19 09S
-0.62 SG B 82 114 11 09S 0.49 SG B 82 115 7
08S 0.53 SG B 82 115 8
09S
-0.64 SG B 82 115 10 09S 0.45 SG B 82 116 16 08S 0.55 SG B 82 116 13 09S 0.51 SG B 82 119 9
09S 0.53 SG B 82 120 9
08S 0.55
1CAN102104 Page 34 of 65 SG Row Col
%TW Elev Offset SG B 82 122 14 09S 0.55 SG B 82 126 15 09S 0.51 SG B 82 126 15 11S 0.49 SG B 82 126 15 12S 0.4 SG B 83 1
11 12S
-0.81 SG B 83 2
19 12S
-0.71 SG B 83 4
5 10S 0.02 SG B 83 4
13 12S 0.28 SG B 83 5
12 10S 0.09 SG B 83 23 9
08S 0.4 SG B 83 25 7
08S 0.4 SG B 83 112 13 09S 0.49 SG B 83 116 11 08S 0.59 SG B 83 116 16 09S 0.51 SG B 83 117 14 09S 0.47 SG B 83 127 6
09S
-0.53 SG B 83 128 18 13S
-0.64 SG B 84 1
20 12S
-0.75 SG B 84 2
17 12S
-0.75 SG B 84 2
15 12S 0.3 SG B 84 4
13 10S 0.06 SG B 84 4
11 12S 0.26 SG B 84 18 11 08S
-0.74 SG B 84 112 7
08S 0.61 SG B 84 115 5
08S 0.56 SG B 84 116 12 09S 0.51 SG B 84 117 10 09S 0.47 SG B 84 120 14 09S 0.53 SG B 84 126 16 09S 0.53 SG B 84 130 12 12S 0.47 SG B 85 1
11 08S
-0.73 SG B 85 2
12 11S
-0.73 SG B 85 2
14 12S
-0.77 SG B 85 29 7
08S 0.4 SG B 85 111 7
08S 0.59 SG B 85 112 13 09S 0.51 SG B 85 114 17 09S 0.49 SG B 85 116 15 09S 0.51 SG B 85 118 13 09S 0.51 SG B 85 124 11 12S 0.47
1CAN102104 Page 35 of 65 SG Row Col
%TW Elev Offset SG B 85 125 7
09S
-0.52 SG B 85 125 6
09S 0.53 SG B 85 125 8
14S 0.55 SG B 85 129 10 07S
-0.55 SG B 85 129 7
09S
-0.53 SG B 86 1
13 12S
-0.8 SG B 86 1
14 12S 0.28 SG B 86 4
14 10S 0.11 SG B 86 20 6
08S
-0.79 SG B 86 20 6
08S 0.36 SG B 86 25 12 08S 0.4 SG B 86 114 12 09S 0.51 SG B 86 115 12 09S 0.55 SG B 87 1
12 12S
-0.84 SG B 87 3
12 06S
-0.7 SG B 87 3
15 10S 0.11 SG B 87 3
19 12S 0.3 SG B 87 25 7
08S 0.41 SG B 87 119 11 09S 0.53 SG B 88 1
11 12S
-0.76 SG B 88 2
12 05S
-0.71 SG B 88 2
13 12S
-0.75 SG B 88 2
12 12S 0.34 SG B 88 4
11 10S 0.13 SG B 88 110 6
08S 0.58 SG B 88 110 10 09S 0.49 SG B 88 112 6
08S 0.53 SG B 88 113 12 09S 0.55 SG B 88 114 11 09S 0.47 SG B 88 115 17 09S 0.53 SG B 88 116 8
09S 0.51 SG B 89 4
8 10S 0.11 SG B 89 111 11 08S 0.59 SG B 89 111 21 14S 0.36 SG B 89 119 29 14S
-0.66 SG B 89 122 11 09S 0.57 SG B 89 125 11 11S 0.51 SG B 89 126 12 10S 0.51 SG B 89 126 9
14S 0.53 SG B 90 5
10 10S 0.02
1CAN102104 Page 36 of 65 SG Row Col
%TW Elev Offset SG B 90 6
11 12S 0.32 SG B 90 105 10 08S 0.55 SG B 90 107 11 09S 0.49 SG B 90 109 11 08S 0.59 SG B 90 112 10 09S 0.51 SG B 90 113 14 09S 0.47 SG B 90 116 10 09S 0.51 SG B 90 123 11 14S 0.47 SG B 90 124 7
14S 0.55 SG B 91 5
12 11S
-0.77 SG B 91 5
10 12S
-0.81 SG B 91 110 11 08S 0.59 SG B 91 111 9
08S 0.53 SG B 91 112 14 08S 0.57 SG B 91 112 11 09S 0.53 SG B 91 114 14 09S 0.49 SG B 91 116 21 09S 0.53 SG B 91 118 20 09S 0.53 SG B 91 126 7
14S 0.51 SG B 92 24 8
08S
-0.81 SG B 92 109 13 08S 0.57 SG B 92 111 12 09S 0.49 SG B 92 112 11 08S 0.56 SG B 92 112 10 09S 0.51 SG B 92 113 13 09S 0.51 SG B 92 115 15 09S 0.51 SG B 92 116 12 09S 0.49 SG B 92 117 12 09S 0.51 SG B 92 118 8
09S 0.49 SG B 93 4
13 11S
-0.75 SG B 93 4
17 12S
-0.76 SG B 93 4
16 12S 0.32 SG B 93 23 5
08S 0.49 SG B 93 107 5
08S 0.51 SG B 93 108 13 08S 0.59 SG B 93 111 7
08S 0.56 SG B 93 111 10 15S 0.36 SG B 93 112 18 09S 0.51 SG B 93 116 13 09S 0.51 SG B 93 125 13 09S 0.55
1CAN102104 Page 37 of 65 SG Row Col
%TW Elev Offset SG B 93 125 6
14S 0.62 SG B 93 128 20 12S
-0.59 SG B 94 11 12 14S 0.21 SG B 94 107 10 08S 0.57 SG B 94 109 17 08S 0.53 SG B 94 111 14 08S 0.57 SG B 94 112 6
08S 0.55 SG B 94 114 11 09S 0.49 SG B 94 115 13 09S 0.51 SG B 94 116 11 09S 0.53 SG B 94 117 12 09S 0.51 SG B 94 121 13 09S 0.53 SG B 94 125 18 09S
-0.59 SG B 94 126 11 12S 0.49 SG B 94 127 17 12S 0.49 SG B 95 4
18 14S
-0.89 SG B 95 5
15 10S
-0.71 SG B 95 104 14 08S 0.59 SG B 95 106 13 08S 0.53 SG B 95 107 9
08S 0.55 SG B 95 108 9
08S 0.53 SG B 95 108 11 09S 0.49 SG B 95 109 6
08S 0.53 SG B 95 109 8
09S 0.51 SG B 95 111 6
08S 0.59 SG B 95 112 11 08S 0.57 SG B 95 112 12 09S 0.51 SG B 95 113 10 09S 0.49 SG B 95 114 15 09S 0.53 SG B 95 115 10 09S 0.49 SG B 95 116 11 09S 0.55 SG B 95 117 10 09S 0.54 SG B 95 118 15 09S 0.57 SG B 95 119 10 09S 0.53 SG B 95 120 12 09S 0.51 SG B 95 121 10 09S 0.53 SG B 95 126 14 12S 0.49 SG B 96 1
22 12S
-0.79 SG B 96 108 10 09S 0.53 SG B 96 109 7
08S 0.58
1CAN102104 Page 38 of 65 SG Row Col
%TW Elev Offset SG B 96 110 10 09S 0.49 SG B 96 111 6
08S 0.56 SG B 96 112 11 09S 0.51 SG B 96 114 15 09S 0.51 SG B 96 116 14 09S 0.53 SG B 96 118 17 09S 0.53 SG B 96 119 12 11S
-0.64 SG B 96 120 7
09S 0.55 SG B 96 124 12 12S 0.45 SG B 96 124 9
14S 0.53 SG B 96 126 12 12S 0.51 SG B 97 8
10 14S
-0.9 SG B 97 9
15 14S
-0.85 SG B 97 22 5
08S 0.38 SG B 97 23 11 08S 0.36 SG B 97 26 7
08S 0.44 SG B 97 96 5
08S 0.51 SG B 97 109 7
08S 0.58 SG B 97 112 11 09S 0.53 SG B 97 114 11 09S 0.49 SG B 97 116 11 09S
-0.64 SG B 97 116 20 09S 0.53 SG B 97 117 9
09S
-0.56 SG B 97 117 11 09S 0.56 SG B 97 119 9
09S 0.62 SG B 97 122 17 12S 0.43 SG B 97 123 11 11S
-0.64 SG B 97 123 16 12S 0.47 SG B 97 124 12 12S 0.47 SG B 97 124 9
14S 0.57 SG B 97 126 10 11S 0.55 SG B 98 1
14 12S 0.32 SG B 98 6
7 10S 0.24 SG B 98 107 13 08S 0.55 SG B 98 107 11 09S
-0.66 SG B 98 108 7
08S
-0.53 SG B 98 108 8
08S 0.51 SG B 98 109 11 08S
-0.55 SG B 98 109 12 08S 0.55 SG B 98 109 11 09S 0.53
1CAN102104 Page 39 of 65 SG Row Col
%TW Elev Offset SG B 98 110 6
08S 0.53 SG B 98 113 11 09S 0.53 SG B 98 115 18 09S
-0.63 SG B 98 116 9
09S 0.53 SG B 98 117 8
09S 0.53 SG B 98 117 13 11S
-0.66 SG B 98 118 7
11S
-0.67 SG B 98 120 6
11S
-0.69 SG B 98 122 9
11S
-0.64 SG B 98 122 10 14S 0.57 SG B 98 125 12 12S
-0.61 SG B 99 1
12 12S 0.28 SG B 99 1
12 14S 0.19 SG B 99 2
13 12S
-0.74 SG B 99 4
6 10S 0.11 SG B 99 4
10 14S
-0.83 SG B 99 6
9 10S 0
SG B 99 7
11 10S
-0.02 SG B 99 105 9
08S 0.53 SG B 99 106 11 09S 0.49 SG B 99 107 9
08S
-0.53 SG B 99 107 7
08S 0.53 SG B 99 108 10 09S 0.51 SG B 99 110 13 09S 0.45 SG B 99 112 10 09S 0.51 SG B 99 113 9
09S 0.49 SG B 99 114 11 09S
-0.62 SG B 99 114 10 09S 0.51 SG B 99 115 10 09S
-0.6 SG B 99 115 9
09S 0.56 SG B 99 115 14 11S
-0.66 SG B 99 116 13 11S
-0.57 SG B 99 116 13 13S
-0.68 SG B 99 118 10 11S 0.55 SG B 99 119 18 14S 0.45 SG B 99 121 15 12S 0.49 SG B 99 124 8
12S 0.55 SG B 99 124 12 13S 0.51 SG B 100 1
11 12S 0.41 SG B 100 3
12 10S 0.23
1CAN102104 Page 40 of 65 SG Row Col
%TW Elev Offset SG B 100 3
10 12S 0.28 SG B 100 4
13 14S
-0.76 SG B 100 5
8 10S 0.02 SG B 100 7
14 10S 0.06 SG B 100 8
10 10S 0.06 SG B 100 8
25 14S 0
SG B 100 21 11 08S 0.38 SG B 100 99 12 08S 0.57 SG B 100 105 11 08S 0.53 SG B 100 108 6
08S 0.55 SG B 100 109 11 09S 0.47 SG B 100 114 9
09S
-0.6 SG B 100 114 12 09S 0.54 SG B 100 114 13 11S
-0.66 SG B 100 115 13 09S 0.59 SG B 100 115 14 11S
-0.62 SG B 100 118 6
14S 0.55 SG B 101 7
9 10S 0.02 SG B 101 20 8
08S 0.4 SG B 101 22 6
08S 0.4 SG B 101 23 11 08S 0.38 SG B 101 104 7
08S 0.68 SG B 101 106 7
08S 0.55 SG B 101 107 12 09S 0.53 SG B 101 108 11 09S 0.53 SG B 101 109 11 09S 0.5 SG B 101 111 10 09S
-0.62 SG B 101 111 10 09S 0.54 SG B 101 112 18 11S
-0.62 SG B 101 117 7
14S 0.63 SG B 101 120 14 12S 0.56 SG B 101 120 8
13S 0.64 SG B 102 5
12 14S
-0.87 SG B 102 7
15 10S 0.02 SG B 102 29 11 09S
-0.74 SG B 102 104 11 09S 0.57 SG B 102 108 10 09S 0.57 SG B 102 112 10 09S 0.47 SG B 102 113 18 11S
-0.61 SG B 102 114 12 11S
-0.66
1CAN102104 Page 41 of 65 SG Row Col
%TW Elev Offset SG B 103 7
9 10S 0.11 SG B 103 8
11 10S 0
SG B 103 107 10 09S 0.51 SG B 103 110 9
08S 0.62 SG B 103 113 8
09S
-0.55 SG B 103 113 12 09S 0.47 SG B 103 121 11 07S
-0.72 SG B 104 1
10 12S
-0.7 SG B 104 1
29 12S 0.4 SG B 104 6
15 04S
-0.7 SG B 104 6
14 10S 0.04 SG B 104 7
11 10S 0.04 SG B 104 99 11 09S 0.49 SG B 104 99 7
10S 0.47 SG B 104 104 10 08S 0.6 SG B 104 105 8
08S 0.62 SG B 104 105 9
09S 0.48 SG B 104 106 7
08S 0.58 SG B 104 107 12 09S 0.51 SG B 104 108 7
08S 0.53 SG B 104 112 8
09S 0.57 SG B 104 113 17 11S
-0.64 SG B 104 114 9
11S
-0.68 SG B 104 118 15 12S 0.45 SG B 104 118 8
14S 0.7 SG B 104 119 11 11S 0.49 SG B 104 121 9
12S 0.54 SG B 105 1
16 12S 0.32 SG B 105 5
11 10S 0.11 SG B 105 29 7
08S 0.42 SG B 105 104 7
08S 0.52 SG B 105 104 10 09S 0.53 SG B 105 105 10 09S 0.51 SG B 105 106 7
08S 0.59 SG B 105 110 12 09S 0.53 SG B 105 114 8
12S 0.56 SG B 105 115 11 10S 0.43 SG B 105 116 12 11S 0.51 SG B 105 117 13 12S
-0.64 SG B 106 2
27 12S
-0.72
1CAN102104 Page 42 of 65 SG Row Col
%TW Elev Offset SG B 106 2
25 12S 0.38 SG B 106 2
10 13S
-0.75 SG B 106 2
18 13S 0.23 SG B 106 3
12 14S
-0.75 SG B 106 4
11 10S 0.13 SG B 106 102 8
08S 0.59 SG B 106 106 11 08S 0.57 SG B 106 112 9
09S 0.55 SG B 106 114 8
14S 0.59 SG B 106 116 12 12S 0.49 SG B 107 3
11 10S 0.08 SG B 107 4
15 14S
-0.75 SG B 107 100 6
08S 0.55 SG B 107 101 8
08S 0.52 SG B 107 102 7
08S 0.55 SG B 107 104 7
08S 0.55 SG B 107 113 17 11S 0.51 SG B 107 114 12 14S 0.4 SG B 107 115 14 12S 0.47 SG B 107 116 16 12S 0.49 SG B 107 117 8
11S
-0.66 SG B 107 117 17 11S 0.56 SG B 107 117 13 12S
-0.6 SG B 107 117 9
12S 0.53 SG B 108 2
5 10S 0
SG B 108 5
17 14S
-0.83 SG B 108 101 10 09S 0.51 SG B 109 3
15 14S
-0.83 SG B 109 23 9
08S 0.4 SG B 109 26 6
08S 0.43 SG B 109 97 10 09S 0.49 SG B 109 98 4
08S 0.54 SG B 109 99 8
08S 0.56 SG B 109 101 12 09S 0.43 SG B 109 115 8
12S 0.49 SG B 110 1
19 12S
-0.74 SG B 110 6
12 14S
-0.79 SG B 110 22 10 08S
-0.7 SG B 110 22 10 08S 0.38 SG B 110 24 9
08S 0.38
1CAN102104 Page 43 of 65 SG Row Col
%TW Elev Offset SG B 110 25 8
08S 0.41 SG B 110 98 12 09S 0.51 SG B 110 100 13 09S 0.49 SG B 110 109 6
14S 0.59 SG B 111 1
19 12S
-0.74 SG B 111 19 6
08S 0.38 SG B 111 98 6
08S 0.53 SG B 111 111 12 11S
-0.61 SG B 111 114 12 12S 0.45 SG B 111 116 11 11S 0.49 SG B 112 28 7
08S 0.38 SG B 112 98 6
08S 0.54 SG B 112 111 13 10S 0.47 SG B 112 113 13 11S 0.51 SG B 113 1
17 12S
-0.72 SG B 113 7
14 14S
-0.79 SG B 113 7
10 14S 0.23 SG B 113 9
14 14S
-0.89 SG B 113 11 11 14S
-0.89 SG B 113 24 8
08S 0.36 SG B 113 95 5
08S 0.51 SG B 113 96 9
08S 0.45 SG B 113 98 10 09S
-0.64 SG B 113 99 10 09S 0.45 SG B 114 1
35 12S
-0.68 SG B 114 1
16 12S 0.36 SG B 114 22 6
08S 0.38 SG B 114 97 14 11S
-0.74 SG B 114 99 11 09S 0.51 SG B 114 110 9
11S
-0.64 SG B 114 115 8
13S 0.51 SG B 115 1
42 12S
-0.7 SG B 115 2
11 05S
-0.7 SG B 115 6
10 14S
-0.85 SG B 115 7
17 14S
-0.77 SG B 115 23 15 08S
-0.74 SG B 115 83 10 08S 0.51 SG B 115 88 15 06S
-0.64 SG B 115 93 5
08S 0.58 SG B 115 95 7
08S 0.6
1CAN102104 Page 44 of 65 SG Row Col
%TW Elev Offset SG B 115 97 5
08S 0.51 SG B 116 2
10 12S
-0.75 SG B 116 6
15 14S
-0.85 SG B 116 7
11 14S
-0.83 SG B 116 9
10 14S
-0.89 SG B 116 27 9
08S 0.38 SG B 116 86 11 08S 0.51 SG B 116 87 6
08S 0.51 SG B 116 91 11 09S 0.45 SG B 116 113 20 10S 0.54 SG B 116 113 13 11S 0.59 SG B 117 2
41 12S
-0.72 SG B 117 3
10 12S
-0.79 SG B 117 91 8
08S 0.53 SG B 117 112 18 10S
-0.53 SG B 117 112 5
11S
-0.55 SG B 117 112 13 11S 0.59 SG B 118 1
17 12S
-0.74 SG B 118 2
44 12S
-0.72 SG B 118 3
15 12S
-0.75 SG B 118 9
13 14S
-0.79 SG B 118 28 5
08S 0.38 SG B 118 31 10 08S 0.41 SG B 118 86 7
08S 0.49 SG B 118 87 13 08S
-0.61 SG B 118 93 6
08S 0.51 SG B 118 97 11 09S
-0.6 SG B 118 97 14 15S
-0.64 SG B 118 106 10 09S 0.51 SG B 118 106 12 11S
-0.58 SG B 118 109 18 11S
-0.7 SG B 118 109 10 11S 0.66 SG B 118 111 11 10S
-0.62 SG B 118 111 10 11S 0.59 SG B 118 111 5
13S
-0.43 SG B 118 111 16 13S 0.62 SG B 119 6
12 14S
-0.77 SG B 119 7
13 14S
-0.85 SG B 119 10 10 14S
-0.95 SG B 119 26 10 08S
-0.77
1CAN102104 Page 45 of 65 SG Row Col
%TW Elev Offset SG B 119 26 7
08S 0.36 SG B 119 78 10 08S 0.45 SG B 119 79 8
08S 0.52 SG B 119 79 13 09S
-0.63 SG B 119 86 25 08S
-0.57 SG B 119 86 18 08S 0.57 SG B 119 87 10 08S
-0.53 SG B 119 87 10 08S 0.51 SG B 119 88 8
08S 0.57 SG B 119 107 9
11S 0.58 SG B 120 1
30 12S
-0.77 SG B 120 2
15 12S
-0.74 SG B 120 9
12 14S 0.19 SG B 120 22 8
08S 0.38 SG B 120 30 8
08S 0.38 SG B 120 32 10 08S 0.41 SG B 120 50 6
08S 0.47 SG B 120 80 17 06S
-0.61 SG B 120 80 10 08S 0.53 SG B 120 82 10 08S
-0.64 SG B 120 82 10 08S 0.53 SG B 120 89 7
08S 0.54 SG B 120 100 15 11S
-0.66 SG B 120 104 10 11S 0.58 SG B 121 1
10 11S
-0.79 SG B 121 1
18 12S
-0.77 SG B 121 2
20 12S
-0.73 SG B 121 7
11 14S
-0.79 SG B 121 9
13 14S 0.22 SG B 121 83 7
08S 0.55 SG B 121 101 11 10S 0.21 SG B 121 105 7
11S 0.53 SG B 121 105 12 12S
-0.7 SG B 121 106 9
11S 0.62 SG B 122 1
25 12S
-0.81 SG B 122 2
28 12S
-0.72 SG B 122 6
10 06S 0.36 SG B 122 69 11 10S
-0.73 SG B 122 78 13 10S
-0.72 SG B 122 79 7
08S 0.51
1CAN102104 Page 46 of 65 SG Row Col
%TW Elev Offset SG B 122 89 7
08S 0.56 SG B 122 99 7
09S
-0.49 SG B 122 99 26 11S
-0.66 SG B 122 104 25 11S 0.54 SG B 122 104 9
12S
-0.57 SG B 122 104 7
12S 0.47 SG B 122 105 14 10S
-0.66 SG B 122 105 25 11S 0.54 SG B 122 105 27 12S
-0.61 SG B 123 1
31 12S
-0.81 SG B 123 2
31 12S
-0.77 SG B 123 10 16 14S
-0.89 SG B 123 21 5
08S 0.39 SG B 123 31 8
08S
-0.68 SG B 123 31 10 08S 0.36 SG B 123 54 12 08S 0.44 SG B 123 78 5
08S 0.53 SG B 123 88 9
09S 0.49 SG B 123 98 6
09S
-0.51 SG B 123 103 19 11S 0.53 SG B 123 103 13 12S
-0.68 SG B 124 1
29 12S
-0.77 SG B 124 2
34 12S
-0.79 SG B 124 3
13 12S
-0.75 SG B 124 8
12 14S 0.21 SG B 124 9
11 14S
-0.87 SG B 124 9
10 15S 0.16 SG B 124 10 13 14S
-0.81 SG B 124 11 16 14S
-0.8 SG B 124 11 11 14S 0.19 SG B 124 30 9
08S 0.36 SG B 124 32 7
08S 0.43 SG B 124 40 10 08S 0.41 SG B 124 71 19 09S
-0.66 SG B 124 77 7
08S 0.56 SG B 124 98 12 11S
-0.66 SG B 124 101 10 11S
-0.68 SG B 124 101 8
11S 0.51 SG B 124 101 11 12S
-0.66 SG B 124 102 21 11S 0.63
1CAN102104 Page 47 of 65 SG Row Col
%TW Elev Offset SG B 124 102 14 12S
-0.65 SG B 124 102 9
12S 0.58 SG B 124 103 11 09S
-0.68 SG B 124 103 20 10S
-0.64 SG B 125 1
9 11S
-0.84 SG B 125 1
24 12S
-0.76 SG B 125 1
8 12S 0.35 SG B 125 2
23 12S
-0.76 SG B 125 3
10 10S
-0.79 SG B 125 3
24 12S
-0.79 SG B 125 31 10 08S 0.38 SG B 125 39 9
08S 0.36 SG B 125 68 10 08S 0.49 SG B 125 70 17 08S
-0.67 SG B 125 70 18 08S 0.51 SG B 125 71 9
08S 0.45 SG B 125 73 7
08S 0.49 SG B 125 86 15 08S
-0.53 SG B 125 86 11 08S 0.51 SG B 125 86 13 09S
-0.62 SG B 125 96 7
09S
-0.57 SG B 125 96 16 11S
-0.64 SG B 125 97 9
11S
-0.64 SG B 125 98 10 10S 0.32 SG B 125 100 16 11S
-0.7 SG B 125 100 14 12S
-0.7 SG B 125 101 13 12S
-0.57 SG B 125 101 14 12S 0.55 SG B 126 7
19 12S
-0.81 SG B 126 7
15 12S 0.3 SG B 126 11 13 14S
-0.91 SG B 126 15 11 14S
-0.93 SG B 126 40 5
08S 0.41 SG B 126 62 11 08S 0.47 SG B 126 73 7
08S 0.53 SG B 126 76 11 08S
-0.62 SG B 126 76 10 08S 0.51 SG B 126 93 16 11S
-0.66 SG B 126 94 14 11S
-0.7 SG B 126 95 10 11S
-0.66
1CAN102104 Page 48 of 65 SG Row Col
%TW Elev Offset SG B 126 96 11 10S 0.38 SG B 126 98 17 12S
-0.7 SG B 126 99 8
11S 0.62 SG B 126 99 8
12S 0.6 SG B 127 1
39 12S
-0.74 SG B 127 2
13 11S
-0.83 SG B 127 2
10 12S
-0.81 SG B 127 3
12 12S
-0.83 SG B 127 4
11 12S
-0.85 SG B 127 7
18 12S 0.3 SG B 127 10 14 14S
-0.91 SG B 127 12 14 14S
-0.91 SG B 127 63 8
08S 0.49 SG B 127 65 11 08S 0.45 SG B 127 69 7
08S 0.51 SG B 127 74 7
08S 0.51 SG B 127 75 7
08S 0.51 SG B 127 80 12 08S
-0.64 SG B 127 93 17 11S
-0.66 SG B 127 96 13 11S
-0.6 SG B 127 96 6
11S 0.53 SG B 127 96 22 12S
-0.68 SG B 127 97 19 11S
-0.75 SG B 127 97 22 12S
-0.68 SG B 127 98 7
07S 0.47 SG B 127 98 19 11S 0.49 SG B 127 98 14 12S
-0.61 SG B 127 98 12 12S 0.59 SG B 128 1
34 12S
-0.79 SG B 128 6
17 10S
-0.72 SG B 128 28 4
07S 0.47 SG B 128 28 6
08S 0.43 SG B 128 53 5
08S 0.38 SG B 128 58 8
08S 0.43 SG B 128 60 9
08S 0.51 SG B 128 64 8
08S 0.45 SG B 128 66 6
08S 0.43 SG B 128 68 8
08S 0.47 SG B 128 70 9
08S 0.47 SG B 128 81 8
11S
-0.64
1CAN102104 Page 49 of 65 SG Row Col
%TW Elev Offset SG B 128 86 14 11S
-0.7 SG B 128 87 14 11S
-0.75 SG B 128 88 9
10S 0.28 SG B 128 90 11 11S
-0.7 SG B 128 91 15 12S
-0.7 SG B 128 91 8
12S 0.49 SG B 129 1
37 12S
-0.76 SG B 129 4
10 12S
-0.79 SG B 129 28 7
08S 0.41 SG B 129 29 8
08S 0.38 SG B 129 38 6
08S 0.38 SG B 129 83 6
09S 0.52 SG B 129 84 8
09S 0.52 SG B 129 86 11 14S 0.42 SG B 129 87 16 11S
-0.66 SG B 129 89 11 11S
-0.68 SG B 129 90 5
14S 0.43 SG B 129 93 12 12S
-0.7 SG B 129 93 8
12S 0.6 SG B 129 94 16 12S 0.53 SG B 130 1
17 12S
-0.81 SG B 130 2
22 11S
-0.26 SG B 130 2
27 12S
-0.77 SG B 130 2
15 14S
-0.82 SG B 130 3
13 12S
-0.85 SG B 130 9
17 14S 0.19 SG B 130 32 6
08S 0.36 SG B 130 34 6
10S
-0.79 SG B 130 38 7
06S 0.47 SG B 130 38 12 08S 0.36 SG B 130 41 9
08S 0.38 SG B 130 48 8
08S 0.41 SG B 130 49 14 08S 0.38 SG B 130 49 10 10S
-0.79 SG B 130 63 8
08S 0.39 SG B 130 69 7
08S
-0.68 SG B 130 69 6
08S 0.47 SG B 130 85 12 12S
-0.68 SG B 130 86 7
11S 0.57 SG B 130 86 14 12S
-0.68
1CAN102104 Page 50 of 65 SG Row Col
%TW Elev Offset SG B 130 86 12 12S 0.53 SG B 130 88 9
10S 0.23 SG B 130 93 11 11S 0.53 SG B 131 1
32 12S
-0.77 SG B 131 7
14 12S 0.3 SG B 131 7
12 15S 0.21 SG B 131 8
12 10S
-0.82 SG B 131 13 13 14S 0.19 SG B 131 15 12 14S 0.21 SG B 131 59 8
08S 0.39 SG B 131 82 9
09S
-0.66 SG B 131 83 6
09S 0.52 SG B 131 83 14 11S
-0.64 SG B 131 84 13 11S
-0.64 SG B 131 86 12 12S
-0.65 SG B 131 86 13 12S 0.53 SG B 131 87 11 12S 0.53 SG B 131 88 15 11S
-0.68 SG B 131 88 12 12S
-0.65 SG B 131 89 10 11S
-0.7 SG B 131 89 11 12S
-0.73 SG B 131 90 16 12S
-0.68 SG B 131 90 10 14S
-0.66 SG B 132 1
27 12S
-0.79 SG B 132 2
14 12S
-0.79 SG B 132 3
11 12S
-0.81 SG B 132 7
9 06S
-0.73 SG B 132 7
15 14S
-0.94 SG B 132 38 5
08S 0.42 SG B 132 82 12 09S 0.51 SG B 132 82 20 11S
-0.64 SG B 132 83 11 14S 0.37 SG B 132 86 11 13S 0.62 SG B 132 87 11 11S
-0.66 SG B 132 87 13 12S
-0.73 SG B 132 88 5
09S 0.47 SG B 132 88 15 11S
-0.63 SG B 132 88 21 12S
-0.59 SG B 132 88 8
12S 0.52 SG B 132 88 11 13S
-0.45
1CAN102104 Page 51 of 65 SG Row Col
%TW Elev Offset SG B 132 88 9
13S 0.62 SG B 132 89 22 10S
-0.54 SG B 132 89 16 11S 0.54 SG B 132 89 12 12S
-0.63 SG B 133 8
17 13S 0.17 SG B 133 9
10 06S 0.36 SG B 133 9
9 07S
-0.77 SG B 133 9
10 13S 0.19 SG B 133 14 13 14S
-0.89 SG B 133 50 11 06S
-0.7 SG B 133 80 9
14S 0.39 SG B 133 81 17 12S
-0.65 SG B 133 82 16 12S
-0.7 SG B 133 84 8
10S
-0.66 SG B 133 84 12 12S
-0.68 SG B 133 85 13 12S
-0.64 SG B 133 86 10 11S 0.47 SG B 133 86 21 12S
-0.73 SG B 133 86 10 13S
-0.66 SG B 133 87 13 11S 0.53 SG B 133 87 24 12S
-0.57 SG B 133 87 14 13S 0.64 SG B 133 88 7
11S 0.51 SG B 133 88 20 12S
-0.62 SG B 134 1
19 12S
-0.85 SG B 134 1
7 12S 0.24 SG B 134 4
24 12S
-0.76 SG B 134 4
14 12S 0.32 SG B 134 78 7
09S 0.54 SG B 134 78 13 11S
-0.7 SG B 134 79 11 11S
-0.71 SG B 134 79 13 13S 0.49 SG B 134 82 13 12S
-0.68 SG B 134 83 21 12S
-0.7 SG B 134 84 7
08S 0.51 SG B 134 84 5
09S 0.54 SG B 134 84 12 10S
-0.59 SG B 134 84 21 11S
-0.64 SG B 134 84 9
11S 0.54 SG B 134 84 30 12S
-0.59
1CAN102104 Page 52 of 65 SG Row Col
%TW Elev Offset SG B 134 85 12 10S
-0.73 SG B 134 85 21 12S
-0.66 SG B 134 85 6
13S 0.6 SG B 135 7
10 12S 0.32 SG B 135 9
12 10S
-0.79 SG B 135 9
10 13S
-0.79 SG B 135 15 17 14S
-0.85 SG B 135 32 15 14S 0.15 SG B 135 51 10 15S 0.29 SG B 135 70 11 11S
-0.68 SG B 135 77 8
09S 0.53 SG B 135 78 14 11S
-0.62 SG B 135 78 9
14S 0.41 SG B 135 81 12 11S
-0.66 SG B 135 81 20 12S
-0.63 SG B 135 82 11 11S
-0.61 SG B 135 82 14 12S
-0.61 SG B 135 82 17 12S 0.54 SG B 135 83 14 11S
-0.66 SG B 135 83 11 11S 0.55 SG B 135 83 24 12S
-0.67 SG B 135 83 16 13S
-0.6 SG B 135 83 17 13S 0.67 SG B 135 84 16 12S
-0.66 SG B 135 84 14 13S
-0.58 SG B 136 7
14 13S 0.23 SG B 136 7
10 14S 0.23 SG B 136 8
15 12S
-0.81 SG B 136 8
16 12S 0.27 SG B 136 17 21 14S
-0.79 SG B 136 65 11 09S
-0.71 SG B 136 66 13 11S 0.44 SG B 136 67 9
11S
-0.73 SG B 136 68 16 11S
-0.72 SG B 136 69 11 14S
-0.71 SG B 136 71 20 14S
-0.7 SG B 136 73 10 14S 0.41 SG B 136 76 15 11S
-0.68 SG B 136 76 9
14S 0.5 SG B 136 77 14 12S 0.58
1CAN102104 Page 53 of 65 SG Row Col
%TW Elev Offset SG B 136 77 7
13S 0.55 SG B 136 78 13 12S
-0.68 SG B 136 79 21 12S
-0.64 SG B 136 79 10 13S
-0.64 SG B 136 80 5
07S 0.49 SG B 136 80 10 11S 0.54 SG B 136 80 24 12S
-0.59 SG B 136 80 13 13S
-0.45 SG B 136 80 10 13S 0.62 SG B 136 81 13 10S
-0.73 SG B 136 81 9
11S
-0.69 SG B 136 81 15 11S 0.45 SG B 136 81 18 12S
-0.64 SG B 136 81 12 13S
-0.55 SG B 136 81 16 13S 0.58 SG B 137 1
7 12S 0.3 SG B 137 3
15 12S
-0.78 SG B 137 7
18 14S
-0.34 SG B 137 8
6 11S
-0.81 SG B 137 8
10 12S 0.3 SG B 137 9
15 13S 0.28 SG B 137 10 11 12S 0.28 SG B 137 10 19 14S 0.17 SG B 137 63 11 11S
-0.7 SG B 137 65 13 09S
-0.68 SG B 137 65 17 11S
-0.7 SG B 137 66 10 10S 0.24 SG B 137 66 13 11S
-0.77 SG B 137 67 14 11S
-0.7 SG B 137 69 32 11S
-0.11 SG B 137 70 35 11S
-0.14 SG B 137 70 13 12S 0.43 SG B 137 71 15 11S
-0.68 SG B 137 73 11 11S
-0.7 SG B 137 75 10 11S
-0.68 SG B 137 75 12 12S
-0.68 SG B 137 75 10 12S 0.52 SG B 137 77 18 10S
-0.66 SG B 137 77 12 11S
-0.7 SG B 137 77 11 13S
-0.67
1CAN102104 Page 54 of 65 SG Row Col
%TW Elev Offset SG B 137 77 13 13S 0.47 SG B 137 78 29 12S
-0.72 SG B 137 79 14 11S
-0.65 SG B 137 79 22 12S
-0.64 SG B 137 79 26 13S
-0.54 SG B 137 80 5
11S 0.49 SG B 137 80 10 12S
-0.66 SG B 138 7
13 13S 0.21 SG B 138 7
14 14S 0.17 SG B 138 8
11 12S 0.32 SG B 138 9
12 13S 0.24 SG B 138 9
12 14S
-0.86 SG B 138 9
13 14S 0.15 SG B 138 12 14 13S
-0.74 SG B 138 13 12 13S
-0.8 SG B 138 14 13 13S
-0.73 SG B 138 60 11 09S
-0.68 SG B 138 61 15 11S
-0.75 SG B 138 62 23 11S
-0.7 SG B 138 63 21 11S
-0.75 SG B 138 64 11 10S 0.15 SG B 138 64 15 11S
-0.7 SG B 138 66 13 11S
-0.7 SG B 138 67 6
13S 0.47 SG B 138 68 12 10S 0.17 SG B 138 69 14 11S
-0.64 SG B 138 70 14 11S
-0.7 SG B 138 72 12 11S
-0.7 SG B 138 74 18 11S
-0.68 SG B 138 75 14 11S
-0.62 SG B 138 75 29 12S
-0.66 SG B 138 75 15 13S
-0.71 SG B 138 76 14 11S
-0.7 SG B 138 76 22 12S
-0.68 SG B 138 76 21 13S
-0.58 SG B 138 77 6
11S 0.47 SG B 139 7
6 10S
-0.71 SG B 139 10 17 12S 0.34 SG B 139 10 10 15S 0.21 SG B 139 11 10 11S
-0.82
1CAN102104 Page 55 of 65 SG Row Col
%TW Elev Offset SG B 139 11 11 14S 0.17 SG B 139 15 11 10S
-0.77 SG B 139 57 8
09S 0
SG B 139 58 11 11S
-0.76 SG B 139 59 26 11S
-0.68 SG B 139 59 10 11S 0.42 SG B 139 60 14 11S
-0.77 SG B 139 64 12 11S
-0.75 SG B 139 64 10 12S
-0.62 SG B 139 64 8
12S 0.49 SG B 139 67 13 10S 0.23 SG B 139 68 12 11S
-0.75 SG B 139 71 14 12S
-0.64 SG B 139 72 14 12S
-0.62 SG B 139 72 13 12S 0.52 SG B 139 73 15 11S
-0.7 SG B 139 73 20 12S
-0.68 SG B 139 73 13 13S
-0.66 SG B 139 74 25 12S
-0.57 SG B 139 74 11 12S 0.61 SG B 139 74 11 13S
-0.57 SG B 140 3
11 13S
-0.78 SG B 140 7
18 13S
-0.81 SG B 140 9
11 14S 0.19 SG B 140 10 11 13S 0.26 SG B 140 10 11 14S 0.23 SG B 140 10 15 15S 0.21 SG B 140 11 12 13S 0.24 SG B 140 11 10 14S 0.24 SG B 140 12 10 14S 0.23 SG B 140 12 8
15S 0.21 SG B 140 15 15 13S 0.17 SG B 140 18 13 14S
-0.82 SG B 140 55 9
11S
-0.73 SG B 140 55 12 13S 0.43 SG B 140 56 13 10S 0.16 SG B 140 56 28 11S
-0.07 SG B 140 56 11 12S 0.4 SG B 140 59 12 13S
-0.61 SG B 140 59 20 14S 0.43
1CAN102104 Page 56 of 65 SG Row Col
%TW Elev Offset SG B 140 60 14 14S
-0.77 SG B 140 61 11 11S
-0.7 SG B 140 61 11 12S 0.42 SG B 140 61 10 14S 0.45 SG B 140 62 13 14S 0.41 SG B 140 65 10 11S
-0.68 SG B 140 65 15 14S
-0.66 SG B 140 65 8
14S 0.49 SG B 140 67 23 12S
-0.68 SG B 140 69 14 11S
-0.7 SG B 140 69 23 12S
-0.64 SG B 140 69 12 13S
-0.57 SG B 141 2
17 12S
-0.74 SG B 141 4
22 12S
-0.72 SG B 141 6
10 11S
-0.81 SG B 141 6
11 13S
-0.72 SG B 141 9
16 15S 0.16 SG B 141 10 10 12S 0.36 SG B 141 10 11 13S 0.25 SG B 141 10 10 15S 0.23 SG B 141 12 10 15S
-0.87 SG B 141 13 9
10S
-0.83 SG B 141 14 8
12S 0.3 SG B 141 16 15 10S
-0.72 SG B 141 16 13 12S 0.33 SG B 141 16 10 14S
-0.78 SG B 141 17 18 14S
-0.83 SG B 141 27 16 14S 0.15 SG B 141 54 9
11S
-0.66 SG B 141 55 10 11S
-0.66 SG B 141 56 16 10S 0.25 SG B 141 56 13 14S
-0.71 SG B 141 58 8
13S
-0.62 SG B 141 59 12 13S
-0.58 SG B 141 60 9
14S 0.45 SG B 141 61 12 12S 0.45 SG B 141 61 7
13S
-0.57 SG B 141 61 10 14S 0.45 SG B 141 62 10 12S 0.49 SG B 141 62 6
13S
-0.56
1CAN102104 Page 57 of 65 SG Row Col
%TW Elev Offset SG B 141 62 6
14S 0.58 SG B 141 63 10 12S
-0.66 SG B 141 63 11 12S 0.49 SG B 141 63 13 13S
-0.57 SG B 141 63 8
14S 0.51 SG B 141 64 7
12S 0.54 SG B 141 66 10 12S
-0.64 SG B 141 67 17 11S
-0.68 SG B 141 67 13 12S
-0.66 SG B 141 67 16 13S
-0.66 SG B 141 68 14 12S
-0.58 SG B 141 68 15 13S
-0.64 SG B 142 2
10 12S
-0.76 SG B 142 3
15 12S
-0.79 SG B 142 4
13 11S
-0.79 SG B 142 14 13 13S
-0.75 SG B 142 16 16 12S 0.31 SG B 142 16 14 14S 0.19 SG B 142 17 12 14S 0.2 SG B 142 23 13 14S
-0.88 SG B 142 52 10 11S
-0.66 SG B 142 53 18 11S
-0.7 SG B 142 54 7
10S 0.33 SG B 142 54 14 14S 0.38 SG B 142 56 11 12S
-0.64 SG B 142 56 12 12S 0.4 SG B 142 56 21 14S 0.43 SG B 142 60 11 12S
-0.68 SG B 142 62 14 11S
-0.7 SG B 142 63 10 12S
-0.65 SG B 142 64 10 11S
-0.02 SG B 142 64 15 12S
-0.59 SG B 142 64 20 12S 0.59 SG B 142 65 8
10S
-0.62 SG B 142 65 7
11S
-0.6 SG B 142 65 11 12S
-0.62 SG B 142 65 10 13S
-0.7 SG B 143 2
11 11S
-0.81 SG B 143 2
32 12S
-0.74 SG B 143 3
12 11S
-0.83
1CAN102104 Page 58 of 65 SG Row Col
%TW Elev Offset SG B 143 3
15 14S 0.17 SG B 143 4
18 12S
-0.72 SG B 143 4
14 12S 0.38 SG B 143 7
8 13S
-0.81 SG B 143 12 10 13S 0.32 SG B 143 12 18 14S
-0.79 SG B 143 13 14 13S 0.24 SG B 143 13 13 14S 0.22 SG B 143 15 10 10S
-0.76 SG B 143 21 11 11S
-0.79 SG B 143 21 12 14S
-0.84 SG B 143 50 12 11S 0.45 SG B 143 51 15 14S 0.41 SG B 143 55 15 12S
-0.64 SG B 143 55 12 12S 0.43 SG B 143 56 5
13S
-0.58 SG B 143 56 10 13S 0.49 SG B 143 57 13 11S
-0.66 SG B 143 57 13 12S
-0.66 SG B 143 59 14 11S
-0.68 SG B 143 60 11 12S
-0.62 SG B 143 60 15 13S
-0.67 SG B 144 3
10 11S
-0.83 SG B 144 9
11 15S
-0.92 SG B 144 11 10 12S 0.32 SG B 144 11 12 13S
-0.77 SG B 144 11 10 14S
-0.81 SG B 144 11 14 14S 0.11 SG B 144 12 10 10S
-0.72 SG B 144 13 18 10S
-0.72 SG B 144 13 15 12S 0.34 SG B 144 14 12 10S
-0.75 SG B 144 16 11 12S
-0.83 SG B 144 38 11 09S
-0.7 SG B 144 40 20 09S
-0.68 SG B 144 47 11 11S
-0.73 SG B 144 48 9
13S
-0.52 SG B 144 48 13 13S 0.43 SG B 144 51 13 11S
-0.66 SG B 144 51 22 13S
-0.64
1CAN102104 Page 59 of 65 SG Row Col
%TW Elev Offset SG B 144 51 14 13S 0.45 SG B 144 51 14 14S
-0.68 SG B 144 51 19 14S 0.36 SG B 144 52 11 12S
-0.68 SG B 144 52 11 13S
-0.49 SG B 144 52 9
13S 0.45 SG B 144 53 13 13S 0.47 SG B 144 54 12 12S
-0.64 SG B 145 2
13 08S
-0.7 SG B 145 2
12 11S
-0.83 SG B 145 9
10 10S
-0.75 SG B 145 10 15 10S
-0.72 SG B 145 11 16 11S
-0.81 SG B 145 11 11 14S
-0.79 SG B 145 13 17 12S
-0.81 SG B 145 13 11 12S 0.3 SG B 145 13 11 14S
-0.88 SG B 145 15 22 10S
-0.76 SG B 145 16 12 11S
-0.81 SG B 145 18 14 14S 0.23 SG B 145 28 12 12S 0.36 SG B 145 28 13 14S 0.32 SG B 145 28 10 15S 0.34 SG B 145 30 11 13S 0.36 SG B 145 30 12 14S
-0.8 SG B 145 33 10 13S 0.3 SG B 145 34 12 11S
-0.7 SG B 145 34 10 12S 0.34 SG B 145 35 7
10S 0.3 SG B 145 36 14 11S
-0.72 SG B 145 37 11 11S
-0.72 SG B 145 46 10 10S 0.11 SG B 145 46 10 14S 0.38 SG B 145 47 9
13S
-0.52 SG B 145 47 33 14S 0
SG B 145 48 14 12S 0.45 SG B 145 48 18 13S 0.5 SG B 145 48 10 14S 0.43 SG B 145 49 15 14S 0.36 SG B 145 50 13 12S
-0.66
1CAN102104 Page 60 of 65 SG Row Col
%TW Elev Offset SG B 145 50 10 13S 0.56 SG B 146 1
14 11S
-0.85 SG B 146 6
10 13S
-0.75 SG B 146 7
15 12S
-0.72 SG B 146 9
14 14S
-0.75 SG B 146 10 10 10S
-0.79 SG B 146 12 13 10S
-0.71 SG B 146 12 9
12S 0.38 SG B 146 13 12 12S
-0.72 SG B 146 13 11 12S 0.34 SG B 146 14 10 10S
-0.77 SG B 146 16 11 14S 0.21 SG B 146 18 10 11S
-0.75 SG B 146 20 5
10S
-0.09 SG B 146 20 17 14S
-0.85 SG B 146 22 10 11S
-0.79 SG B 146 24 12 11S
-0.77 SG B 146 25 18 11S
-0.72 SG B 146 30 11 13S
-0.68 SG B 146 32 10 10S 0.11 SG B 146 33 10 10S 0.21 SG B 146 36 13 10S 0.17 SG B 146 37 10 10S 0.17 SG B 146 40 12 11S
-0.7 SG B 146 44 10 10S 0.13 SG B 146 44 11 14S
-0.72 SG B 146 44 16 14S 0.41 SG B 146 46 17 12S
-0.63 SG B 146 46 10 14S 0.48 SG B 146 47 11 12S
-0.66 SG B 146 47 13 12S 0.49 SG B 146 47 17 13S 0.43 SG B 147 1
20 13S
-0.77 SG B 147 1
12 13S 0.28 SG B 147 4
16 12S
-0.68 SG B 147 5
18 12S
-0.75 SG B 147 6
13 10S
-0.72 SG B 147 6
18 12S
-0.72 SG B 147 7
14 13S
-0.78 SG B 147 7
10 13S 0.26
1CAN102104 Page 61 of 65 SG Row Col
%TW Elev Offset SG B 147 8
17 10S
-0.68 SG B 147 9
11 10S
-0.77 SG B 147 12 11 14S 0.28 SG B 147 13 13 14S
-0.83 SG B 147 15 14 14S 0.22 SG B 147 17 14 14S
-0.81 SG B 147 18 11 14S 0.27 SG B 147 21 17 14S
-0.86 SG B 147 22 12 10S
-0.72 SG B 147 26 10 11S
-0.72 SG B 147 26 15 13S
-0.72 SG B 147 27 5
10S 0.11 SG B 147 28 9
10S 0.13 SG B 147 28 11 14S
-0.68 SG B 147 29 13 10S 0.19 SG B 147 40 14 13S
-0.66 SG B 147 40 17 13S 0.4 SG B 147 40 20 14S
-0.74 SG B 147 40 17 14S 0.44 SG B 147 41 10 13S 0.45 SG B 147 41 11 14S 0.34 SG B 147 42 11 11S
-0.66 SG B 147 42 11 12S
-0.64 SG B 147 42 10 13S 0.52 SG B 147 42 11 14S
-0.73 SG B 147 42 14 14S 0.38 SG B 148 1
12 13S
-0.77 SG B 148 3
11 11S
-0.74 SG B 148 3
30 13S
-0.68 SG B 148 4
17 10S
-0.79 SG B 148 4
13 11S
-0.83 SG B 148 4
44 12S
-0.73 SG B 148 4
18 13S
-0.77 SG B 148 5
22 12S
-0.7 SG B 148 5
17 13S
-0.68 SG B 148 6
14 11S
-0.79 SG B 148 6
28 12S
-0.77 SG B 148 6
10 13S
-0.79 SG B 148 7
30 12S
-0.7 SG B 148 8
17 12S
-0.79
1CAN102104 Page 62 of 65 SG Row Col
%TW Elev Offset SG B 148 8
10 13S
-0.75 SG B 148 9
15 13S
-0.7 SG B 148 23 12 12S 0.4 SG B 148 25 12 10S 0.11 SG B 148 26 7
10S 0.15 SG B 148 26 9
12S 0.39 SG B 148 32 6
13S 0.49 SG B 148 37 13 13S
-0.66 SG B 148 38 13 14S
-0.66 SG B 148 38 15 14S 0.34 SG B 148 39 22 14S 0.38 SG B 149 2
12 13S
-0.77 SG B 149 5
13 11S
-0.71 SG B 149 5
28 12S
-0.71 SG B 149 5
19 13S
-0.69 SG B 149 7
24 12S
-0.71 SG B 149 8
25 12S
-0.7 SG B 149 9
17 12S
-0.77 SG B 149 14 7
10S 0.42 SG B 149 17 7
13S 0.32 SG B 149 21 12 13S
-0.7 SG B 149 24 11 11S
-0.72 SG B 149 27 14 11S
-0.7 SG B 149 31 18 11S
-0.7 SG B 149 33 16 13S
-0.66 SG B 149 36 13 12S
-0.64 SG B 150 1
13 12S
-0.73 SG B 150 2
12 12S
-0.7 SG B 150 3
18 12S
-0.69 SG B 150 6
26 12S
-0.71 SG B 150 6
12 13S
-0.69 SG B 150 7
15 10S 0.39 SG B 150 7
19 12S
-0.77 SG B 150 7
13 13S
-0.75 SG B 150 8
14 12S
-0.7 SG B 150 9
11 11S
-0.71 SG B 150 9
21 12S
-0.69 SG B 150 9
9 12S 0.38 SG B 150 10 12 13S
-0.78 SG B 150 12 13 10S
-0.73
1CAN102104 Page 63 of 65 SG Row Col
%TW Elev Offset SG B 150 14 11 12S
-0.77 SG B 150 15 10 12S
-0.7 SG B 150 16 19 10S
-0.73 SG B 150 16 13 12S
-0.69 SG B 150 16 6
12S 0.43 SG B 150 17 17 11S
-0.72 SG B 150 17 21 12S
-0.72 SG B 150 17 11 13S
-0.68 SG B 150 17 11 13S 0.38 SG B 150 18 19 11S
-0.72 SG B 150 18 21 12S
-0.68 SG B 150 19 15 11S
-0.71 SG B 150 19 17 12S
-0.7 SG B 150 19 11 13S
-0.71 SG B 150 20 18 11S
-0.72 SG B 150 20 25 12S
-0.7 SG B 150 20 11 12S 0.4 SG B 150 21 11 11S
-0.69 SG B 150 21 11 12S
-0.7 SG B 150 21 13 12S 0.43 SG B 150 21 11 13S
-0.73 SG B 150 22 18 11S
-0.68 SG B 150 22 28 12S
-0.7 SG B 150 23 14 11S
-0.72 SG B 150 23 17 12S
-0.7 SG B 150 23 11 12S 0.43 SG B 150 23 10 13S
-0.71 SG B 150 24 22 11S
-0.69 SG B 150 24 23 12S
-0.66 SG B 150 25 28 11S
-0.71 SG B 150 25 19 12S
-0.61 SG B 150 25 14 12S 0.45 SG B 150 25 16 13S
-0.68 SG B 150 25 12 13S 0.45 SG B 150 26 11 08S
-0.66 SG B 150 26 21 11S
-0.66 SG B 150 26 14 12S
-0.64 SG B 150 26 18 12S 0.47 SG B 150 26 10 13S
-0.66 SG B 150 26 13 13S 0.45
1CAN102104 Page 64 of 65 SG Row Col
%TW Elev Offset SG B 150 27 25 11S
-0.68 SG B 150 27 22 12S
-0.64 SG B 150 27 24 12S 0.47 SG B 150 27 17 13S
-0.66 SG B 150 28 8
11S
-0.68 SG B 150 29 17 11S
-0.71 SG B 150 29 11 13S
-0.62 SG B 150 30 18 12S
-0.66 SG B 150 30 13 12S 0.51 SG B 150 31 10 12S
-0.68 SG B 151 1
10 10S 0.36 SG B 151 1
20 12S
-0.78 SG B 151 2
13 11S
-0.73 SG B 151 2
25 12S
-0.73 SG B 151 2
9 12S 0.35 SG B 151 3
12 10S 0.42 SG B 151 3
26 12S
-0.7 SG B 151 3
17 13S
-0.73 SG B 151 4
27 10S 0.45 SG B 151 4
21 11S 0.4 SG B 151 4
14 12S
-0.69 SG B 151 5
18 10S 0.45 SG B 151 5
29 12S
-0.7 SG B 151 6
9 10S 0.47 SG B 151 6
23 12S
-0.69 SG B 151 7
21 12S
-0.79 SG B 151 7
8 13S 0.32 SG B 151 8
7 10S 0.45 SG B 151 8
12 11S
-0.71 SG B 151 8
21 12S
-0.73 SG B 151 9
21 10S
-0.75 SG B 151 9
15 12S
-0.81 SG B 151 9
12 13S
-0.79 SG B 151 9
13 13S 0.32 SG B 151 10 11 08S
-0.69 SG B 151 10 23 12S
-0.72 SG B 151 10 19 13S
-0.7 SG B 151 11 22 12S
-0.69 SG B 151 11 13 13S
-0.69 SG B 151 12 19 12S
-0.75
1CAN102104 Page 65 of 65 SG Row Col
%TW Elev Offset SG B 151 12 8
12S 0.34 SG B 151 12 10 13S
-0.75 SG B 151 13 11 11S
-0.74 SG B 151 13 13 12S
-0.7 SG B 151 13 11 13S
-0.7 SG B 151 14 12 12S
-0.75 SG B 151 14 10 13S
-0.73 SG B 151 15 15 11S
-0.71 SG B 151 15 10 11S 0.43 SG B 151 15 33 12S
-0.66 SG B 151 15 23 12S 0.4 SG B 151 15 20 13S
-0.71 SG B 151 15 16 13S 0.4 SG B 151 16 21 11S
-0.7 SG B 151 16 27 12S
-0.7 SG B 151 16 9
12S 0.45 SG B 151 16 20 13S
-0.66 SG B 151 16 14 13S 0.42 SG B 151 17 12 11S
-0.73 SG B 151 17 26 12S
-0.69 SG B 151 17 17 13S
-0.69 SG B 151 17 12 13S 0.4 SG B 151 18 9
11S
-0.7 SG B 151 18 12 12S
-0.68 SG B 151 18 20 13S
-0.67 SG B 151 19 19 11S
-0.7 SG B 151 19 23 12S
-0.69 SG B 151 19 14 12S 0.43 SG B 151 19 15 13S
-0.66 SG B 151 20 18 12S
-0.66 SG B 151 20 15 13S
-0.7 SG B 151 21 22 12S
-0.66 SG B 151 24 10 12S 0.49
Enclosure to 1CAN102104 Location of Service Induced Indications SG A TSP Wear (Drilled)
1CAN102104 Page 1 of 1 Location of Service Induced Indications SG A TSP Wear (Drilled)
SG Row Col
%TW Elev Offset SG A 8
53 13 15S 0.3 SG A 58 129 13 15S 0.11
Enclosure to 1CAN102104 Location of Service Induced Indications SG A TTW
1CAN102104 Page 1 of 3 Location of Service Induced Indications SG A TTW SG Row Col
%TW Elev Offset SG A 29 58 10 08S 18.08 SG A 29 59 10 08S 17.93 SG A 42 22 10 08S 18.9 SG A 43 22 11 08S 19.04 SG A 45 88 8
08S 18.47 SG A 46 21 9
08S 18.69 SG A 46 89 10 08S 18.58 SG A 47 21 8
08S 18.81 SG A 47 94 9
08S 18.61 SG A 48 96 8
08S 18.67 SG A 50 22 8
08S 17.82 SG A 50 23 10 08S 17.82 SG A 51 39 8
10S 17.71 SG A 52 104 9
08S 18.74 SG A 53 104 9
08S 18.8 SG A 57 23 9
08S 19.87 SG A 58 24 10 08S 19.43 SG A 61 30 14 08S 19.54 SG A 62 29 15 08S 18.96 SG A 65 31 10 08S 19.05 SG A 66 30 9
08S 19.1 SG A 68 30 8
08S 18.9 SG A 69 30 7
08S 18.39 SG A 69 31 11 08S 18.32 SG A 70 30 11 08S 18.88 SG A 71 30 8
08S 18.93 SG A 71 109 9
08S 18.72 SG A 71 110 13 08S 18.8 SG A 72 29 9
08S 19.34 SG A 72 107 11 08S 18.57 SG A 72 108 11 08S 18.83 SG A 72 109 8
08S 18.85 SG A 72 110 12 08S 18.67 SG A 73 22 8
08S 17.96 SG A 73 23 9
08S 17.98 SG A 73 32 8
08S 18.06 SG A 74 22 9
08S 18.37 SG A 74 23 8
08S 18.9
1CAN102104 Page 2 of 3 SG Row Col
%TW Elev Offset SG A 74 31 11 08S 18.55 SG A 74 108 9
08S 18.68 SG A 74 109 15 08S 18.31 SG A 74 110 17 08S 18.29 SG A 75 108 10 08S 18.48 SG A 75 109 12 08S 18.22 SG A 76 24 9
08S 19.52 SG A 77 22 9
08S 17.28 SG A 77 24 10 08S 18.69 SG A 77 25 11 08S 19.08 SG A 77 108 11 08S 17.5 SG A 77 109 13 08S 18.5 SG A 78 21 10 08S 17.83 SG A 78 111 6
06S 19.52 SG A 79 111 9
06S 19.6 SG A 79 111 9
07S 19.33 SG A 80 110 7
07S 20.13 SG A 81 21 11 08S 18.7 SG A 81 110 12 08S 18.36 SG A 81 111 16 08S 18.49 SG A 81 112 9
07S 21 SG A 82 20 10 08S 18.88 SG A 82 110 11 08S 18.78 SG A 82 111 9
07S 20.58 SG A 87 113 6
06S 20.39 SG A 88 27 11 08S 19.1 SG A 88 28 9
08S 19.04 SG A 88 112 8
06S 19.81 SG A 89 27 10 08S 19.18 SG A 89 28 9
08S 18.5 SG A 90 106 13 07S 18.99 SG A 91 108 13 07S 18.46 SG A 99 101 11 08S 18.2 SG A 100 100 11 08S 18.36 SG A 107 87 9
08S 18.53 SG A 107 88 10 08S 18.99 SG A 117 35 13 08S 18.69 SG A 117 60 8
07S 20.18 SG A 117 61 8
07S 20.09
1CAN102104 Page 3 of 3 SG Row Col
%TW Elev Offset SG A 117 88 9
08S 18.74 SG A 117 90 9
07S 20.06 SG A 118 35 12 08S 18.5 SG A 118 80 10 08S 18.4 SG A 118 86 10 07S 21.56 SG A 118 87 10 08S 18.83 SG A 118 89 8
07S 19.68 SG A 118 89 8
08S 19.17 SG A 118 90 9
07S 20.14 SG A 119 44 12 08S 18.13 SG A 119 45 10 08S 18.11 SG A 119 70 11 08S 18.42 SG A 119 71 11 08S 18.51 SG A 119 78 9
08S 17.76 SG A 119 84 8
07S 19.7 SG A 119 87 8
08S 18.91 SG A 119 88 9
07S 20.16 SG A 120 44 8
08S 17.77 SG A 120 45 8
08S 18.25 SG A 120 73 11 08S 17.58 SG A 121 73 12 08S 17.6 SG A 124 47 10 08S 17.75 SG A 124 62 9
06S 20.57 SG A 124 63 9
06S 20 SG A 125 46 9
08S 18.03 SG A 125 54 8
07S 19.58 SG A 125 55 9
07S 19.81 SG A 126 47 9
08S 18.45 SG A 126 48 10 08S 18.58 SG A 126 52 12 08S 17.81 SG A 127 12 9
06S 17.36 SG A 127 51 11 08S 17.93
Enclosure to 1CAN102104 Location of Service Induced Indications SG B TTW
1CAN102104 Page 1 of 4 Location of Service Induced Indications SG B TTW SG Row Col
%TW Elev Offset SG B 20 51 13 08S 18.79 SG B 20 52 12 08S 18.98 SG B 21 47 12 08S 18.56 SG B 21 48 8
08S 18.94 SG B 21 50 14 07S 20.14 SG B 21 50 11 08S 19.06 SG B 21 51 15 07S 20 SG B 21 52 10 08S 19.75 SG B 21 53 7
08S 18.35 SG B 22 48 9
08S 18.84 SG B 22 49 12 08S 18.59 SG B 22 51 12 08S 18.71 SG B 22 62 12 08S 18.83 SG B 22 63 15 08S 18.81 SG B 23 59 10 08S 17.98 SG B 24 56 11 08S 18.39 SG B 25 71 13 08S 18.09 SG B 25 72 16 08S 18.06 SG B 26 39 10 08S 18.47 SG B 26 40 11 08S 18.46 SG B 26 67 11 08S 18.09 SG B 26 72 11 08S 18.18 SG B 26 73 11 08S 17.29 SG B 27 69 13 08S 17.97 SG B 28 43 13 08S 19.54 SG B 28 67 12 07S 20.94 SG B 28 68 13 07S 20.16 SG B 28 68 12 08S 18.26 SG B 28 69 12 08S 18.73 SG B 28 76 15 08S 17.94 SG B 28 77 17 08S 18.89 SG B 29 44 11 08S 19.26 SG B 29 62 10 08S 18.27 SG B 29 63 9
08S 19.16 SG B 29 68 10 08S 18.12 SG B 29 76 12 08S 18.63 SG B 29 77 11 08S 18.72 SG B 30 69 9
08S 18.53
1CAN102104 Page 2 of 4 SG Row Col
%TW Elev Offset SG B 30 71 8
08S 19.06 SG B 30 72 9
08S 19.06 SG B 31 34 14 08S 18.39 SG B 31 35 13 08S 19.06 SG B 31 38 8
08S 18.78 SG B 31 39 10 08S 19.1 SG B 31 61 9
07S 19.34 SG B 31 62 11 07S 19.95 SG B 31 62 12 08S 19.09 SG B 31 63 13 08S 19.56 SG B 31 74 10 08S 18.51 SG B 32 33 11 08S 18.85 SG B 32 36 10 08S 17.67 SG B 32 43 9
08S 19.25 SG B 32 74 10 08S 18.38 SG B 33 32 11 08S 19.02 SG B 33 34 9
08S 19.09 SG B 33 38 10 08S 17.66 SG B 33 44 9
08S 19.59 SG B 33 80 10 08S 20.57 SG B 33 82 9
08S 19.11 SG B 34 27 12 08S 19.56 SG B 34 33 9
08S 18.7 SG B 34 55 21 08S 18.99 SG B 34 56 20 08S 19.01 SG B 34 82 8
08S 19.8 SG B 34 84 8
08S 19.56 SG B 34 89 9
08S 18.52 SG B 34 90 10 08S 18.06 SG B 35 28 11 08S 19.59 SG B 36 31 9
08S 18.72 SG B 37 32 8
08S 18.28 SG B 38 29 10 08S 19.74 SG B 38 86 13 08S 20.34 SG B 38 87 12 08S 19.75 SG B 39 29 10 08S 19.42 SG B 39 37 12 08S 18.43 SG B 39 53 20 08S 19.28 SG B 39 54 22 08S 18.56
1CAN102104 Page 3 of 4 SG Row Col
%TW Elev Offset SG B 39 91 11 08S 19.6 SG B 39 92 12 08S 19.86 SG B 40 36 12 08S 18.52 SG B 42 65 8
08S 20.48 SG B 43 25 12 08S 18.17 SG B 43 67 9
08S 19.93 SG B 44 25 10 08S 18.98 SG B 44 26 12 08S 18.21 SG B 45 26 10 08S 19.22 SG B 46 21 12 08S 18.13 SG B 46 22 8
08S 18.61 SG B 46 23 9
08S 18.52 SG B 46 98 9
02S 19.34 SG B 46 100 15 08S 19.13 SG B 47 21 10 08S 18.22 SG B 47 99 15 08S 19.18 SG B 55 21 10 08S 18.14 SG B 55 22 8
08S 19.05 SG B 57 26 11 08S 19.7 SG B 58 26 9
08S 19.58 SG B 59 20 10 08S 19.01 SG B 60 21 10 08S 18.74 SG B 66 21 11 08S 18.29 SG B 66 22 10 08S 18.34 SG B 67 22 9
08S 18.38 SG B 67 23 6
08S 18.46 SG B 67 108 12 08S 19.09 SG B 68 110 10 08S 18.54 SG B 74 114 9
08S 17.9 SG B 75 114 10 08S 18.67 SG B 77 20 7
08S 19 SG B 78 20 9
08S 18.7 SG B 89 25 13 08S 18.69 SG B 90 25 12 08S 18.93 SG B 94 24 9
08S 18.41 SG B 94 25 8
08S 18.25 SG B 96 109 7
08S 18.13 SG B 97 109 9
08S 18.59 SG B 102 102 9
08S 16.93
1CAN102104 Page 4 of 4 SG Row Col
%TW Elev Offset SG B 103 21 10 08S 17.42 SG B 103 22 9
08S 17.56 SG B 105 23 11 08S 19.25 SG B 106 24 11 08S 18.61 SG B 109 97 8
08S 18.39 SG B 109 98 9
08S 18.21 SG B 114 82 14 08S 19.09 SG B 114 83 13 08S 18.62 SG B 115 30 13 08S 18.44 SG B 115 31 14 08S 18.26 SG B 116 29 23 07S 20.44 SG B 117 29 24 07S 21 SG B 117 89 10 08S 18.75 SG B 118 28 11 08S 18.78 SG B 118 29 9
08S 18.12 SG B 118 88 10 08S 18.61 SG B 119 25 16 07S 21.12 SG B 119 26 8
08S 18.86 SG B 119 27 11 08S 18.61 SG B 119 28 12 07S 20.58 SG B 119 29 11 07S 20.26 SG B 120 25 16 07S 20.62 SG B 122 30 10 08S 18.65 SG B 122 31 8
08S 18.69 SG B 123 32 11 08S 18.53 SG B 124 32 8
08S 18.65 SG B 126 35 10 08S 19.39 SG B 126 36 8
08S 19.46 SG B 126 72 9
08S 19.87 SG B 126 73 10 08S 20.11 SG B 128 44 10 07S 20.63 SG B 128 45 11 07S 20.04 SG B 128 45 8
08S 18.86 SG B 128 59 9
08S 18.94 SG B 128 60 9
08S 18.59 SG B 129 29 11 08S 18.25 SG B 129 30 11 08S 18.3 SG B 129 46 6
08S 18.81
Enclosure to 1CAN102104 Location of Service Induced Indications SG A TRW
1CAN102104 Page 1 of 1 Location of Service Induced Indications SG A TRW SG Row Col
%TW Elev Offset SG A 51 39 8
10S 17.71
Enclosure to 1CAN102104 Location of Service Induced Indications SG B TRW
1CAN102104 Page 1 of 1 Location of Service Induced Indications SG B TRW SG Row Col
%TW Elev Offset SG B 46 98 9
02S 19.34