LGS UFSAR Figure 9A-3 Deleted

1600 A GOULD A4BT-1600 6-1/C 750 KCM L 125 VDC BATTERY 2A1D101 125 VDC BATTERY 2A2D101 125 VDC BATTERY CHARGER 2A1D103 400 A GOULD TR400R 2 - 1/C 500 KCM L 125 VDC BATTERY CHARGER 2A2D103 400 A GOULD TR400R 2 - 1/C 500 KCMIL 2 - 1/C 350 KCMIL 150 A GOULD TR150R 2/C #2 AWG 70 A GOULD TR70R 125 VDC 200 A BUS (2AD102)

D21 SAFEGUARDS SWITCHGEAR 20A115 2 - 1/C 350 KCMIL 110 A GOULD TR110R 2/C #6 AWG 50 A BUSS FRN-R-50 125 VDC 100 A BUS (2AD501)

D21 DIESEL GEN. CONTROL BOARD 2AC514 6 - 1/C 350 KCMIL 601 A GOULD A4BT-601 225 200 A 125/250 VDC 600 A BUS 2 - 1/C 500 KCMIL (SPLICED TO #4/0 AWG AT BREAKER TERMINALS)

TO RPS/UPS INVERTER 2AD160 WESTINGHOUSE TYPE JD 3 P, TM SET AT LO (1000 A)

SHUNT TRIP COIL DISCONNECTED 225 200 A (20D201) 125/250 VDC 2000 A BUS (2AD105) 1 2

3 3

4 4

5 6

7 8

2/C #8 AWG 30 A BUSS FRN-R-30 RPT BREAKER A20201 9

125 VDC 100 A BUS (2AD162)

RRCS PANEL 20C634 20C787 2 - 1/C 350 KCMIL LIMERICK GENERATING STATION UNIT 2, DIVISION 1 UPDATED FINAL SAFETY ANALYSIS REPORT FIRE PROTECTION EVALUATION REPORT 125/250 Vdc SYSTEM - BATTERIES 2A1D101 & 2A2D101 PROTECTIVE DEVICE COORDINATION FIGURE 9A-17 Sht 6 of 10 REV. 14, 09/08

6 - 1/C 350 KCMIL 601 A GOULD A4BT-601 225 200 A 125/250 VDC 600 A BUS 2 - 1/C 500 KCMIL (SPLICED TO #4/0 AWG AT BREAKER TERMINALS)

TO RPS/UPS INVERTER 2AD160 WESTINGHOUSE TYPE JD 3 P TM SET AT LO (1000 A)

SHUNT TRIP COIL DISCONNECTED 225 200 A (20D201) 125/250 VDC 2000 A BUS (2AD105) 2 4

4

.01

.1 1

10 100 1000 Time in Seconds 5

1 10 100 1000 10000 14773 SCA 2

GOULD A4BT 601A 1/C 350 kcmil 8349 SCA

.01

.1 1

10 100 1000 Time in Seconds

.5 1

10 100 1000 10000 4

WEST NGHOUSE JD 200A 14773 SCA 8349 SCA 1/C 500 kcmil 1/C #4/0 AWG LIMERICK GENERATING STATION UNIT 2, DIVISION 1 UPDATED FINAL SAFETY ANALYSIS REPORT FIRE PROTECTION EVALUATION REPORT 125/250 Vdc SYSTEM - BATTERIES 2A1D101 & 2A2D101 PROTECTIVE DEVICE COORDINATION FIGURE 9A-17 Sht 10 of 10 REV. 14, 09/08