I Enclosure 11
Paaelof2 C::L> rECHNOLOGIES Standby Power Division Date:
Decembef 9, 2020 Reynosa Reynosa Facility ATP-15 IEEE-1188-2005 test Cut-off 1.75 V.P.C. @ 100%, 225.3 Amp at 3hrs discharge rate For order Number: 2516069 Test date:Nov 2020 Discharge time (Temp corrected) :
Cell temperature at the beginning of the discharge (average): 24*c Uncorrected test time = 1 BO minutes Temp. of the cell Com,ction Conductance Float vottage before Cell voltage at the End voltage at 3 Time to reach 1.750V
% of cap at Final Float Serial No.
- befon, Factor readings (0) discharge M beginning of the hours (180 min)
(H,MM) 1.750V voltage discharge re) discharge (V) 1 H0904104 21 0.954 406(
2.221 1.988 1.824 03:06:00 108.32%
2.158 2
H0904072 21 0.954 3971 2.221 1.989 1.800 03:00:00 104.82%
2.156 3
H0904069 21 0.954 3977 2.224 1.989 1.817 03:04:30 107.4<1%
2.159 4
H0604338 21 0.954 4056 2236 1.988 1.848 03:15:00 113.56%
2.157 5
H0702033 21 0.954 4023 2.227 1.978 1.822 03:08:30 109.77%
2.151 6
H0907031 21 0.954 3974 2.221 1.986 1.796 02:58:30 103.95%
2.145 7
H1023297 23 0.977 3719 2.258 1.987 1.780 03:00:00 102.35%
2.166 8
H0914045 21 0.954 3955 2215 1.985 1,800 03:00:00 104.82%
2.162 9
H0608202 21 0.954 4086 2239 1.993 1.854 03:16:00 115.30%
2.161 10 H1023257 21 0.954 3953 2215 1.991 1.831 03:09:30 110.35%
2.157 11 H1023011 23 0.977 3895 2.264 1.982 1.785 03:00:00 102.35%
2.150 12 H1023240 25 1.000 3938 2209 1.988 1.TT6 03:03:30 101.94%
2.166 13 H0814180 21 0.954 4003 2.215 1.984 1.807 03:00:00 104.82%
2.156 14 H1118511 21 0.954 3886 2.215 1.981 1,811 03:01:00 105.40%
2.140 15 H0608113 21 0.954 4112 2236 1.984 1.840 03:13:00 112.39%
2.157 16 H1023333 25 1.000 3907 2.221 1.988 1.79-4 03:07:00 103.89%
2.161 17 H0904067 21 0.954 3958 2.227 1.986 1.815 03:02:30 10628%
2.154 18 H1023374 25 1.000 3915 2.221 1.982 1.783 03:05:00 102.78%
2.160 19 H1 023247 25 1.000 3399 2258 2.017 1.836 03:19:00 110.56%
2.196 20 H1023304 21 0.954 3867 2209 1.980 1.799 02:58:30 103.95%
2.156 21 H1023254 25 1.000 3861 2215 1.9S4 1.766 03:01 :30 100.83%
2.159 22 H1023248 25 1.000 3909 2.215 1.989 1.779 03:04:00 102.22%
2.165 23 H1023315 25 1.000 3879 2.209 1.983 1.762 03:01 :30 100.83%
2.155 24 H1023381 25 1.000 3977 2.226 1.988 1.798 03:07:30 104.17%
2.159 25 H0914035 21 0.954 3949 2.221 1.987 1.819 03:04:30 107.4<1%
2.149 26 H1023320 25 1.000 3965 2.221 1.980 1.759 03:00:30 10028%
2.153 27 H1023313 25 1.000 3902 2215 1.981 1.766 03:01 :30 100.83%
2.154 28 H1023191 25 1.000 3937 2.212 1.987 1.784 03:04:30 102.50%
2.155 29 H1023242 25 1.000 3831 2.219 1.987 1.784 03:04:30 102.50%
2.162 30 H1023375 25 1.000 3833 2.221 1.985 1.756 03:00:30 100.28%
2.164 31 H1023249 24 0.986 3915 2.215 1.988 1.787 03:03:00 103.11%
2.156 32 H1023332 24 0.986 3989 2.216 1.987 1.810 03:08:30 106.21%
2.160 33 H1023193 25 1.000 3927 2.215 1.983 1.769 03:02:30 101.39%
2.150 34 H1023251 24 0.986 3868 2.216 1.992 1.795 03:04:30 103.96%
2.169 35 H1023253 24 0.986 3901 2215 1.986 1.781 03:01:30 10227%
2.162 36 H1023335 24 0.986 3980 2215 1.985 1.799 03:05:00 10424%
2.153 37 H1023331 24 0.986 4016 2215 1.986 1.816 03:10:00 107.05%
2.157 38 H0702065 23 0.977 4036 2269 1.982 1.823 03:09:30 107.76%
2.148 39 H0702076 23 0.977 3997 2282 1.983 1.833 03:13:30 110.03%
2.159 40 H1023334 24 0.986 4001 2.221 1.986 1.815 03:09:30 106.77%
2.162 41 H1023182 23 0.977 3862 2.267 1.984 1.803 03:04:00 104.63%
2.152 42 H1023337 24 0.986 3989 2.215 1.982 1.770 03:00:00 101.42%
2.157 43 H0702077 23 0.977 4060 2.282 1.986 1.834 03:13:30 110.03%
2.148 44 H0604335 21 0.954 4056 2239 1.982 1.838 03:12:30 112.10%
2.158 45 H1022348 23 0.977 3973 2269 1.989 1.822 03:08:30 107.19%
2.152 46 H1023302 23 0.977 3797 2258 1.988 1.795 03:02:30 103.78%
2.160 47 H1023379 23 0.977 3883 2.277 1.996 1.834 03:12:30 109.46%
2.165 48 H0702156 21 0.954 3982 2.233 1.974 1.814 03:04:30 107.4<1%
2.149 49 H0702029 23 0.977 3858 2.302 1.998 1.843 03:19:00 113.16%
2.172 50 H1023224 23 0.977 3820 2.253 1.983 1.791 03:02:30 103.78%
2.165
~-
Name and Signature of quality Manager
Page2 of 2 C:::l:ITECHNOLOGIES Standby Power Division Date:
December 9, 2020 Reynosa Reynosa Facility ATP-15 IEEE-1188-2005 test Cut-off 1.75 V.P.C.@ 100%, 225.3 Amp at 3hrs discharge rate For order Number: 2516069 Test date:Nov 2020 Discharge time (Temp corrected) :
Cell temperature at the beginning of the discharge (average): 24"C Uncorrected test time= 180 minutes Temp. of the cell Correction Conductance Float voltage before Cell voltage at the End voltage at 3 Time to reach 1.750V
%ofcapat Final Float Serial No.
before
- Facto, readings discharge beginning of the hours (180 min)
(H,MM) 1.750V voltage discharge discharge 51 HD702163 21 0.954 3967 2.227 1.975 1.816 03:06:00 108.32%
2.148 52 H1023176 23 0.977 3816 2.268 1.985 1.790 03:02:00 103.49%
2.159 53 H1023373 21 0.954 3897 2.215 1.984 1.820 03:04:30 107.<<%
2.162 54 H1022362 23 0.977 3949 2.270 1.988 1.834 03:14:30 110.60%
2.160 55 H0702216 23 0.977 4086 2.255 1.981 1.802 03:04:00 104.63%
2.140 56 H1023314 23 0.977 3832 2.251 1.985 1.798 03:03:00 104.06%
2.160 57 H1023171 23 0.977 3871 2.258 1.987 1.798 03:03:00 104.06%
2.158 58 H0702079 23 0.977 4025 2.267 1.988 1.830 03:12:00 109.18%
2.151 59 H1023183 23 0.977 3898 2.258 1.991 1.813 03:06:00 105.77%
2.155 60 H1109324 23 0.977 3939 2.281 2.001 1.824 03:09:30 107.76%
2.159