From:

Santos, Cayetano Sent:

Wednesday, October 14, 2020 1:28 PM To:

Vogtle PEmails

Subject:

FW: Slides for Weldolet Alternative Discussion on the Public Call Tomorrow Attachments:

VEGP 3&4 Code Alternative for Weldolets - Presentation for Oct 15 Meeting.pdf From: Leighty, Steven <sleighty@southernco.COM>

Sent: Wednesday, October 14, 2020 12:58 PM To: Gleaves, Billy <Bill.Gleaves@nrc.gov>; Santos, Cayetano <Cayetano.Santos@nrc.gov>

Cc: Arafeh, Yasmeen N. <YNARAFEH@southernco.com>

Subject:

[External_Sender] Slides for Weldolet Alternative Discussion on the Public Call Tomorrow Billy/Tanny, We put together a few high level slides to guide the conversation during the call tomorrow on the draft alternative. There is no new information in the slides, just some talking points to help walk through the draft alternative.

Thanks, Steve Leighty l Southern Nuclear Licensing Supervisor l Vogtle 3&4 706.848.6790 l sleighty@southernco.com

Hearing Identifier:

Vogtle_COL_Docs_Public Email Number:

595 Mail Envelope Properties (BLAPR09MB7313FB6B4CF6ED087A31893CE5050)

Subject:

FW: Slides for Weldolet Alternative Discussion on the Public Call Tomorrow Sent Date:

10/14/2020 1:27:34 PM Received Date:

10/14/2020 1:27:37 PM From:

Santos, Cayetano Created By:

Cayetano.Santos@nrc.gov Recipients:

"Vogtle PEmails" <Vogtle.PEmails@nrc.gov>

Tracking Status: None Post Office:

BLAPR09MB7313.namprd09.prod.outlook.com Files Size Date & Time MESSAGE 775 10/14/2020 1:27:37 PM VEGP 3&4 Code Alternative for Weldolets - Presentation for Oct 15 Meeting.pdf 374783 Options Priority:

Normal Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

October 15, 2020 Alternative Request to ASME Section XI Code Examination Requirements for Weldolets Pre-submittal Meeting Plant Vogtle Units 3&4

2 Background

- Four applicable weldolets total [two in each Unit (3&4)]

- Located on branch connection lines within Automatic Depressurization System (ADS) Stage 1 piping

3 Background

Item No.*

Description Examination Limitation Component B9.31 Branch Connection Weld Branch Connection Geometry SV3-RCS-PLW-013-SW3 B9.31 Branch Connection Weld Branch Connection Geometry SV3-RCS-PLW-01C-SW3 B9.31 Branch Connection Weld Branch Connection Geometry SV4-RCS-PLW-013-SW3 B9.31 Branch Connection Weld Branch Connection Geometry SV4-RCS-PLW-01C-SW3 Weldolet Branch Connections

4 Reason for Request

  • ASME Examination Category B-J Requirements for Pressure Retaining Welds

- NPS >= 4, 100 percent surface and volumetric examinations for branch connection welds (B9.31)

- NPS < 4, Surface examinations only

  • Examination Volume not Achievable for Subject Weldolets

- The configurations of the subject Weldolets are widely used by the industry

- Challenges with these configurations are typical, and are frequently captured in relief requests

5 Proposed Alternative

  • Best Effort Volumetric Examination

- Conducted to the maximum extent practical

- Minimum examination coverage of 40%

  • Surface Examination

- Conducted to the maximum extent practical

  • Acceptance Criteria

- In accordance with IWB-3000 for Class 1 systems

6 Additional Information

  • Section III Surface Examinations were Performed During Fabrication / Installation

- Testing performed and documented in data packages provided by Stone

& Webster, Inc.

- Liquid Penetrant Examination Method

- Results were acceptable

  • Section XI Surface Examinations were Performed After Installation

- Results were acceptable

7 Summary

  • 100% Volumetric Section XI Examination Requirements of Subject Weldolets is Not Achievable

- Best effort volumetric examinations

- Surface examinations

  • Precedent for Approval in Industry