ML20249C815

From kanterella
Jump to navigation Jump to search
PNO-76-200:on 761122,Region I Was Informed That Inadvertent Operation of 1 of 11 Target Rock Safety/Relief Valves Occurred.Licensee Planning to Replace Failed Valve W/New Valve
ML20249C815
Person / Time
Site: FitzPatrick 
Issue date: 11/22/1976
From: Dreher F, Roy G, Thompson D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
PNO-76-200, NUDOCS 9807010234
Download: ML20249C815 (1)


Text

_ _ _ _ _ _ _ _ _ - _ _ _ -.

.yy PRELIMINARY NOTIFICATION November 22, 1976 I

PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-76-200 This preliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest significance. The information presented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date.

Facility:

J. A. FitzPatrick Nuclear Power Plant (DN 50-333)

Niagara Mohawk Power Corporation Power Authority of the State of New York, Inc.

Subject:

INADVERTENT TARGET ROCK SAFETY RELIEF VALVE OPERATION NRC, Region I, was informed that an inadvertent operation of one of the eleven Target Rock Safety / Relief Valve occurred at 2:20 p.m. on November 22, 1976. The reactor was being started up and had just reached the run mode (1000 psig) when the valve relieved. The valve reshut at a reac-tor pressure of 200 psig. Preliminary information indicated that no safety related problems resulted from the event. The reactor will re-main shutdownt for replacement of the valve. The licensee is preparing to make a drywell and torus inspection.

ThisTargetRockSafety/RIliefvalve,No.E, failure (referencetoPNO-76-197) is similar to the one, No. F, that occurred on November 19, 1976. The licensee is planning to replace this failed valve with a new valve.

Media interest is expected because of an unscheduled plant shutdown. The State of New York has been and is being kept informed. A press release is not planned.

NRC, Region I, Philadelphia, Pennsylvania received notification of this occurrence by telephone from the licensee at 2:40 p.m., November 22, 1976.

Contact:

FADreher, IE x27261

GWRoy, IE x27261 DThompson, IE x27541 Distribution:

Chairman Rowden Commissioner Mason S. J. Chilk, SECY Commissioner Gilinsky C. C. Kammerer, CA G. F. Murphy, JCAE g

Commissioner Kennedy L. V. Gossick, EDO E. Volgenau, OIE J. A. Harris, PA

(

B. C. Rusche, NRR H. K. Shapar, ELD T. J. McTiernan, AIA 4 K. R. Chapman, NMSS R. G. Ryan, OSP H St h ; MNBB Transmitted: PBldgif Lug PRELIMINARY NOTIFICATION l

9007010234 761122 PDR I&E PNG-76-200 PDR

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _