f Hope Creek Nuclear Generating Station Safety Parameter Display System Final Validation and Verification Report Public Service Electric & Gas

-March 9, 1989 NOV-1000-88-003.

Revision 1

%DhD P

P

_ _ _ _ - _ _ ___.____.______-m__-__m__.____.______ ._m.m__ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . . _ _ _ _ _ _ _ _ . _ _ . _ _ . _ . . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ . _ _ _ _ _ . . _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _

FINAL V&V REPORT' TABLE OF CONTENTS Preface .................................................... 2 1.0 Overview 1.1 Background ......................................... 3 1.2 Summary of V&V Plan................................ 4 1.3 References.......................................... 5 2.0 System Requirements Review 2.1 Objectives .......................................... 8 2.2 Summary of Activities .............................. 8 2.3 Summary of Results ................................. 9 2.4 Deficiencies Identified / Resolved ................... 9 3.0 Design Review 3.1 Objectives ......................................... 10 3.2 Summary of Activities .............................. 10 3.3 Summary of Results ................................. 12 3.4 Deficiencies Identified / Resolved ................... 12 4.0 Validation Test 4.1 Objectives ......................................... 13 4.2 Summary of Activities .............................. 13 4.3 Summary of Results ................................. 15 4.4 Deficiencies Identified / Resolved ................... 15 5.0 Field Verification Test 5.1 Objectives ......................................... 16 5.2 Summary of Activities .............................. 16 5.3 Summary of Results ................................. 17 5.4 Deficiencies Identified / Resolved ................... 17 6.0 Summary and Conclusions 6.1 Summary ........................................... 18 6.2 Conclusions ........................................ 18 Appendix A - Discrepancy Reports  !

PSE&G 1 NOV-1000-88-003 REV.1  !

i a

__._m.. _ . _ _ _ .__._ _ _ _ _ _ - . _ _ _ _ _ . - - _ - _ _ . - - - - _ _ _ . _ -

V&V FINAL REPdRT

-Preface 1 1

The PSE&G Nuclear Department Computer Group had overall i responsibility for the SPDS design. .The group was responsible for conceptual design, display development, and system integration. NOVA Technologies Inc.

provided all applications programming and the system-reliability evaluation. Essex Corporation provided the Human Factors engineering review. Eigen. Engineering,'

Inc. performed the independent V&V review.of the design and implementation process.

This report.was prepared by.PSE&G using the final V&V-report (reference.1.3.16) from Eigen Engineering Inc.

as .a basis.. - PSE&G' has revised the Eigen: report to provide a document that conforms ;nore closely.to the.

guidelines of NSAC/39, and addresses the closing of all

-open items. PSE&G. felt the original Eigen report's lack of summaryLinformation would hamper audit Lactivities.

This report has been. written by parties with no prior involvement with SPDS activities. Information required to produce this report comes directly from documents referenced in section 1.3, much'of it verbatim. No new information has been created as a result of this report.

i PSE&G 2 NOV-1000-88-003 REV.1 p_ __ _ _ ,_. _ _ _ _ _ _ _ . _ _ _ . _ _ _ _ _ _ _ _ . _ _ _ _ _ _ - %_______.__________-____..- _ _ _ _ _ _ _ _ _ _ _ _ _ _

t; E

I I , 'V&V FINAL REPORT' L

l 1.0 OVERVIEW

1.1 Background

In August 1985, Eigen Engineering Inc. was contracted to perform a Verification and Validation Program on a Hope Creek SPDS which had been implemented by adding a L new set of CRT displays to the existing Control Room Information Display System (CRIDS).

Since the Hope Creek system was already installed and operational, no attempt was made to validate the basic design of the system. Instead, the V&V program concentrated on how well the final system configuration and performance met regulatory requirements.

The V&V Team prepared a program plan meeting the intent of NSAC/39. The Design Review Report (PSE-3210-87-001, Rev. O) was issued in February 1987.

Although the design of the system would, with some modifications, have been acceptable, the fact that the CRIDS was also performing several additional functions caused the overall SPDS performance to fall below acceptable levels. Thus, in March 1987, PSE&G decided to transfer the Hope Creek SPDS functions to a separate, stand-alone system.

This " stand-alone" system (Figure 1) consists of redundant Gould/SEL Computers interfaced with ten CPI remote multiplexer.

In October, 1987, Eigen Engineering, Inc. was contracted to perform the V&V program on the new Hope Creek SPDS.

In December, 1987, Eigen Engineering submitted a revised V&V Plan (Reference 1.3.12) detailing the work to be performed. As in the earlier V&V, a " performance verification" approach was used.

l I

l i

PSE&G 3 NOV-1000-88-003 REV.1

l V&V FINAL REPORT l 1.2 Summary of V&V Plan The V&V program plan addresses the concerns of an NRC audit performed August 27 and 28, 1985 (ref. 1.3.18).

The initial implementation of SPDS, upon which the audit was based, was installed on the plant control Room Integrated Display System (CRIDS). As a result of the audit, and performance concerns with the CRIDS, PSE&G decided to install a separate computer system for the SPDS. To address the V&V concerns documented by the audit, an "after-the-fact" V&V program - as documented in the letter referenced above - was performed on the new SPDS implementation.

The V&V program for the Hope Creek SPDS was performed according to the V&V plan, reference 1.3.12. The plan  !

defines four basic ' activity areas:

Systems Requirement Review .

Design Review Performance Validation Test Field Verification Test The plan discusses the method, and defines the required documentation for completing each activity area.

The following sections summarize the objectives, activities, and results of each of these areas.

PSE&G 4 NOV-1000-88-003 REV.1 1

I

- - _ _ _ - - _ h

[

k- ,

< i'

[.

- V&V' FINAL REPORT 1.3 References The following identifies the documentation used during the V&V Program.

I L Requirements Documentation:

1.3.1. NUREG.0737,LSupplement 1,. Requirements for

' Emergency response Capability-(Generic Letter

.82-33)'

1.3.2. NUREG 0800, Section 18'.2,. Standard Review Plan

- Safety Parameter Display. System (SPDS) .

1.3.3. NSAC/39, Verification and Validation for. Safety j Parameter Display Systems j

- Il i

Design Requirements Documentation:

L . 3 . 4 . Display Design Requirements Summary, H-1-RJXX-C DM-0483-0, 2/13/87 1.3.5. Display Feature Development H-1-RJXX-CDM-0484-0, 2/13/87 1.3.6. .Displ'ay Functional

Description:

-d Man-Machine Interface, H-1-RJXX-CDM-0491-0, 8/5/87 .

System Testing:

1.3.7. . Hope Creek SPDS Acceptance Test Procedure, NOVA-ATP-OOlA,'Rev.E I 1.3.8. PSE&G DCR 4EC-1076, DCP 11/0 (3/29/88) l 1.3.9. Hope Creek Parameter Display System ]

=Precperational' Test Procedure For Multiplexed Digitial and Analog Inputs, M13-STP-004-4EC-1076, .

I Rev. 0-1.3.10. Hope Creek Safety Parameter Display System a Preoperational Test Procedure, M13-STP-003-4EC-1076, Rev 0 1.3.11. Hope Creek SPDS Simulator Dynamic Performance

-Test, DE-CP.SPC-0010, Rev. 0 PSE&G 5 NOV-1000-88-003 REV.1 1

V&V FINAL'REPURT V&V Reports:

1.3.12. HCGS SPDS V&V Program Plan, NOV-1000-87-003, Rev.3, 12/02/87 1.3.13. HCGS SPDS V&V Design Review Report, NOV-1000-87-004, Rev. 1, 8/12/88 1.3.14. HCGS SPDS V&V Factory Acceptance Test Report, NOV-1000-88-001, 4/22/88 1.3.15. HCGS SPDS V&V Preoperational Test Review Report, NOV-1000-88-002, 8/26/88 1.3.16. HCGS SPDS Verification and Validation Program Final Report, NOV-1000-88-003, Rev. a, 9/15/88 1.3.17. HCGS Dynamic Performance Testing Report, PSE&G memo ELE-89-0071, 3/9/89 Correspondence:

1.3.18. Letter dated October 15, 1985, HOPE CREEK SAFETY PARAMETER DISPLAY SYSTEM AUDIT From: Walter R. Butler, Chief Licensing Branch No. 2 Division of Licensing To: Mr. R.L. Mitcl, General Manager Nuclear Assurance and Regulation Public Service Electric & Gas Newark, New Jersey 1.3.19. Letter dated December 14, 1988, CERTIFICATION OF HCGS SIMULATION FACILITY From: S. LaBruna, Vice President Nuclear Operaticns Public Service Electric & Gas To: Dr. Thomas E. Murley Director of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, DC 20555 PSE&G 6 NOV-1000-88-003 REV.1

_ _ _ _ _ _ _ _ _ _ - . _ _ _ A

J

- V&V FINAL REP 6RT Human Factors Review:

1.3.20. Review of the Safety Parameter Display System Hope Creek Generating Station, Document 880926, Essex Corporation System Availability:

1.3.21. HCGS SPDS System Availability Analysis, PO number P1-216265, NOVA TECHNOLOGIES Inc.

PSE&G Procedures:

1.3.22 Engineering Work Book for Standard Change Package, DE-WB.ZZ-0001(Q) 1.3.23 Hardware Preventive Maintenance Procedures,

' NOVA- PMP-001 PSE&G 7 NOV-1000-88-003 REV.1 ww-- _-_--_ _ _ _ _ __

1 V&V FINAL REPORT 2.0 REQUIREMENTS REVIEW 2.1 objectives The objective of the Requirements Review was to.

identify, and document the system requirements for Safety Parameter Display Systems based on NRC guidelines reference 1.3.1, and 1.3.2. These requirements became the basis for. subsequent reviews. .

The objective of the Requirements Review differs from that outlined in NSAC/39 (ref. 1.3.3). As stated in reference 1.3.18, section 3.1.2:

"EEI [Eigen Engineering, Inc.] intends to independently identify and list the system requirements and the sources of the requirements, as described in regulatory documents."

This deviation from the recommended NSAC/39 guidance is 4 the result of using an existing design, in which the '

requirements were established and documented prior to the V&V process.

2.2 Summary of Activities NRC documents NUREG 0737 Supplement 1, NUREG 0800, and NSAC/39 were reviewed to compile a list of system c requirements.

The basic requirements for an SPDS are provided in Supplement 1 to NUREG 0737 (ref. 1.3.1) which is "...a distillation of the basic requirements....from the broad range of guidance documents that the NRC has issued. ...

Specific requirements for the Hope Creek SPDS were i;

developed from NUREG 0800, Section 18.2. (ref. 1.3.2)

This document expands the basic requirements of NUREG 0737, Supplement 1 into specific guidelines to be used  ;

by the NRC in review of SPDS implementation. l In addition, three requirements were identified in NSAC 39, Section 2.0; and three were identified based on the NRC SPDS V&V audit of August 1985. ,

PSE&G 8 NOV-1000-88-003 REV.1

V&V FINAL REPDRT Requirements were grouped into the following categories;

1. Display Format And Content
2. Sensor Scan Intervals
3. Scale Optimization
4. . Data Validity
5. SPDS Failure
6. Electrical Isolation
7. Configuration Control
8. Reliability
9. Location

-10. Procedures And Training

11. Human Factors
12. Operation and Maintenance
13. -System Testing 2.3 Summary of Results The results of this activity was to produce a requirements list from the referenced NRC documents.

-There was no review of PSE&G documentation during-this

activity. The requirements compiled in this activity ;

can be found in section 3.0 of the V&V Design Review  !

i Report (ref. 1.3.13).

2.4 Summary of Deficiencies Identified / Resolved Due to the limited scope of this activity - no review of PSE&G documentation, no deficiencies were identified.

s PSE&G 9 NOV-1000-88-003 REV.1

V&V FINAL REPORT

(

3.0 DESIGN REVIEW j 3.1 Objectives There were two basic objectives to the design review.

The first objective of the design review was to verify -

that the system described in the SPDS design l documentation (References 1.3.4 thru 1.3.6) fully addressed the requirements defined during the requirements review.

The second objective was to review test procedures to ensure that design inputs were used, and system response was adequately tested.

The V&V team attempted not only to confirm the adequacy {

of the design, but alsa to confirm the adequacy of the design documentation in order to ensure an adequate configuration control mechanism.

3.2 Summary of Activities 3.2.1 Design Documentation Review The design review methodology employed by the V&V team for each requirement was to;

1. Identify the task (s) necessary to evaluate the system with respect to the requirement.
2. Summarize tne information evaluated.
3. Identify the specific references used in the evaluation.
4. State a conclusion regarding the adequacy *)

of the system with respect to the requirement.

This activity is documented in section 3.0 of the VGV Design Review Report (ref. 1.3.13).

The Hope Creek SPDS design philosophy, ac described in Reference 1.3.4, Section 2,0 is based on the concept that " plant safety can he assured for a wide range of events and sovere accidents, through adherence to the EOP's and maintaining PSE&G 10 NOV-1000-88-003 REV.1

_________-___D

V&V FINAL REPORT plant conditions as specified therein."

The purpose of the SPDS, therefore, is to provide a focal point for the control room operators to obtain the information necessary to make the decisions required by the EOP(s).

The V&V team accepted this philosophy and thus based their review of the system's parameter set and display features on this principle. In addition, the design documents represent the current display design baseline for configuration control purposes. i 3.2.2 Test Procedure Review The test procedure reviews were performed subsequent, and independent of the design document review. .

Four separate test procedures were written:

Factory Acceptance Test (ref. 1.3.7)

Field Verification Test (ref. 1.3.9)

On-Site Validation Test (ref. 1.3.10)

Simulator Dynamic Performance Test (ref.

1.3.11)

The first test, factory acceptance, was developed and performed by NOVA Technology. The second and third tests, collectively refered to as

" reoperation tests," were developed and written by PSE&G. The final Simulator test was also developed by PSE&G.

The NOVA Technology factory acceptance test, Hope Creek SPDS Acceptance Test Procedure (ref. 1.3.7),

was reviewed and witnessed by the V&V team.

The preoperational tests (ref. 1.3.9 and 1.3.10) had been. subject to multiple levels of site review and approval. On that basis, the V&V review was conducted on an audit basis, i.e. only selected portions of the testing were subjected to detailed review.  !

The Simulator Dynamic Performance Test was written and reviewed internally by PSE&G.

j PSE&G 11 NOV-1000-88-003 REV.1

_ _ _ _ _ _ _ _ _ _ - i

V&V FINAL REPURT 3.3 Summary of Results The results of the Design Review are documented in the V&V Design Review Report, reference 1.3.13.

The results of the Factory Acceptance Test review are documented in reference 1.3.14.

The results of the Preoperational Test Procedures review are documented in the V&V Preoperational Test Review Report, reference 1.3.15.

The Simulator dynamic performance test was not reviewed by the Eigen V&V team. The PSE&G performance test report, reference 1.3.17, addresses the concerns defined in the V&V plan.

3.4 Summary of Deficiencies Identified / Resolved 3.4.1 Design Document Review A total of 105 discrepancies were found in the design documentation. Additionally, there were 22 open items identified from review with the system requirements. These discrepancies are numbered 1-105, and 265-286, respectively, in Appendix A.

3.4.2 Test Procedure Review A total of 26 discrepancies were reported for the Hope Creek SPDS Acceptance Test Procedure, reference 1.3.7. These discrepancies are numbered 106-131.

A total of 10 discrepancies were reported for the Hope Creek Parameter Display System Preoperational Test Procedure For Multiplexed Digitial and Analog Inputs, ref. 1.3.9. These discrepancies are numbered 166-175.

A total of 43 discrepancies wer0 reported for the Hope Creek Safety Param9ter Display System  !

Preoperational Test Procedure, ref. 1.3.10. These discrepancies are numbered 196-238.  !

, No discrepancies were written on the Simulator L

l Performance test due to its qualitative nature.  !

1 1

PSE&G 12 NOV-1000-88-003 REV.1 l

i I

i

'O 1

V&V FINAL REPdRT-

'4.0 VALIDATION TEST 4.1' Objectives IAs: described in NSAC/39, system validation testing is performed to demonstrate that the integrated system meets the requirements.

4.2 Summary of Activities Validation testing for the Hope. Creek SPDS was performed in the following tests:

4.2.1 Factory Acceptance Testing.

This procedure (Reference 1.3.7) tested the functional' adequacy of major system components with respect-to system power-up,. terminal communications, system failover,1 system displays-and database verification.

4.2.2 Integrated System Testing The objective of this test (Reference 1.3.10) was '

to verify that-SPDS hardware and software design-and installation was in accordance with the design philosophy delineated in,the System Design Memoranda.

During installation testing (see 5.0 Field Verification Test) all unique point inputs from the system multiplexer through the Data Input Processor to the system displays were tested.

During integrated system testing input values were simulated into the Display Input Processor to test composed points, complex algorithms, data manipulation, displays, trends, and Man Machine Interface (MMI) features.

In certain cases, where factory acceptance testing had been satisfactorily performed and documentod, only a sanple test was performed during integrated System testing. For example, all point summary displays were tested during factory acceptance

~t testing. During integrated system tasting, therefore, only a sample of the point summary displays were tested.

PSE&G 13 NOV-1000-88-003 REV.1

_ - _ _ _ - - - . - __...-.___,_.-__-_-----.__u.--_--. - _ - - -

a '

V&V-FINAL REPbRT The: ability to take credit for prior testing was accomplished by-strict configuration management of both hardware and software in accordance with GM8--

EMP-009 " Operational Design Change Control" and the guidelines of Design Memoranda

,H-1-RJXX-CDM-0599 "HCGS SPDS software and Database Configuration control". A prerequisite of integrated system testing was to verify the software and database loaded onLthe' computer are in configuration with the Master SPDS software and database files.

Integrated' system testing'also included data links from the Radiation Monitoring System (RMS) and' Uninterruptable Power Supply (UPS).

4.2.3 Dynamic Performance Testing The objective of this test 1(ref. .1. 3.11) ' was to

. validate the effectiveness of the-SPDS by performing plant transient scenarios on the. Hope Creek simulator. These tests were rtin in accordance with the V&V Plan to show response to transient and accident sequences (see requirement, 3.1.9 in V&V Design Review, reference 1.3.13).

The Hope Creek simulator complies with NRC.

requirements as documented in a letter sent to the.

NRC December 14, 1989 (reference'1.3.19).

The Simulator Dynamic Performance Terting used three' scenarios,.and three operator crews. Each scenario was run twice, once with, once without SPDS. The following data was recorded for'each scenario:

1. The elapsed time required to enter the appropriate EOP.
2. The elapsed time required to exit the appropriate EOP.

' 3. The worst case value of the EOP entry parameter.

Following each scenario set, operators were asked for their input.

Evaluation of these results was limited to a PSE&G 14 NOV-1000-88-003 REV.1

l L I V&V FINAL REPdRT ]

qualitative determination of performance since no j real significance can be associated with any i absolute measurements. {

l 4.3 Summary of Results The results of the System Validation Testing V&V review are included in References 1.3.14, 1.3.15, and 1.3.17.

4.4 Summary of Deficiencies Identified / Resolved 4.4.1 Factory Acceptance Testing Factory Acceptance Testing conducted using Document reference 1.3.7 resulted in 34 test exceptions. These exceptions are documented in discrepancy reports 132-165.

4.4.2 Integrated System Testing Testing conducted using Document reference,1.3.10 resulted in 26 test. exceptions. These exceptions are documented in discrepancy reports 239-264.

4.4.3 Dynamic Performance Testing The Simulator Dynamic performance Testing conducted using Document reference 1.3.11 produced no discrepancy, or exception reports due to its qualitative nature.

t Interviews with operators following the Simulator Dynamic performance test did not provide meaningful input due to the operators' limited experience with SPDS prior to performance of the test.

PSE&G 15 NOV-1000-88-003 REV.1

V&V FINAL REPDRT i 5.0 FIELD VERIFICATION TEST 5.1 Objectives The objective of the Field Verification Test was to ensure that all field inputs were properly installed.

5.2 Summary of Activities A test procedure, Hope Creek Parameter Display System Preoperational Test Procedure For Multiplexed Digitial and Analog Inputs, M13-STP-004-4EC-1076, Rev. 0 ,

(reference 1.3.9) was developed by PSE&G to verify all l field inputs.

The plan was reviewed by the V&V team - Eigen Engineering - as discussed in section 3.0 above and documented in reference 1.3.15.

Since much of the validation testing was performed during preoperational testing of the installed system, it was necessary to perform installation verification prior to system validation.

At Hope Creek, this was accomplished-in the following tests; Initial Checkout and Energization Testing (Reference 1.3.8, DCP's 2, 3 & 4)

This testing included cable continuity, card calibration, system diagnostics, and initial energization of equipment.

Installation Testing This test (Reference 1.3.9) verified the correct design and installation of the 10 SPDS multiplexer as delineated in the System Design Memoranda.

The scope of this procedure was to test each field input to the system multiplexer and verify that field data could be transported  ;

thru the system and stored in (or accessed from) the data input processor, i

PSE&G 16 NOV-1000-88-003 REV.1

l?

V&V. FINAL REPURT In addition, digital points were also tested for point specific failures, tag sets, and contact normal status. Analog points were tested for point accuracy, point specific failures, process value units, and alarm values. Each point was also tested for point overlap to ensure.the SPDS indicated value is in agreement with actual plant parameters.

No V&V activities were performed during initial system checkout and energization.

Due to the testing sequence,'any unresolved problems would be identified and corrected during subsequent tests.

5.3 Summary of Results The results of System Field Verification V&V review are contained in Reference 1.3.15.

5.4 Summary of_ Deficiencies Identified / Resolved Performance of the Hope Creek Parameter Display System Preoperational Test Procedure For Multiplexed Digitial and Analog Inputs., reference 1.3.9, resulted in 20 test exceptions. These exceptions are documented in discrepancy reports 176-195.

PSE&G 17 NOV-1000-88-003 REV.1 4

0

l 1

V&V FINAL REPORT 6.O

SUMMARY

AN) CONCLUSIONS 6.1 Summary 1 During the course of the V&V program, the V&V team identified 286 discrepancies (see Appendix A). When Eigen Engineering submitted their final V&V report (ref. 1.3.16), they identified nine open discrepancies. l l

PSE&G has resolved all of these open items. Three  !

items which pertained to documentation that had not j been received, have been closed (references 1.3.20, 1.3.21, and 1.3.23). Two items which remained open awaiting completion of the simulator dynamic testing have been closed.

The remaining four items required testing during the mid-cycle outage in February, 1989. These tests have been identified, performed, and documented in reference 1.3.8.

While resolutions to all discrepancies have been identified, final closure requires final revisions of documentation. This work is currently in progress.

i 6.2 Conclusions The following conclusions are those of Eigen Engineering Incorporated. With the exception of paragraph numbering, and comments within square brackets, the conclusions are taken, in whole, from the

" Summary and Conclusions" section of the Final V&V report prepared by Eigen Engineering (ref. 1.3.16).

The objectives of the V&V program are to provide reasonable assurance that the four design requirements stated in Section IV of NUREG 0800 are satisfied. With respect to these requirements, the V&V team feels that; A. The variables displayed by the SPDS are sufficient i to provide the minimum information required to assess  !

the critical plant safety functions.

l B. The SPDS is suitably isolated from electrical and electronic interference with equipment and sensors that are used in safety systems.  !

PSE&G 18 NOV-1000-88-003 REV.1

\.

V&V FINAL REPURT C. The data validation techniques which have been implemented will be adequate to ensure that the data displayed will be valid..

D. Characteristics of.the SPDS displays.and other operational interfaces, will be sufficient to~ allow reasonable assurance that the information provided will' be readily perceived and comprehended by the HCGS operating staff.

The following sections summarize the conclusions of the V&V review team regarding specific system requirements.

PSE&G 19 NOV-1000-88-003 REV.1

V&V FINAL REPORT 6.2.1 Display Content and Format The content and format of the Hope Creek SPDS displays adequately meet all applicable system requirements. In fact, coordination between specific SPDS displays and specific EOP's provides a.very effective way of meeting the information needs-of the plant operators during emergency operating conditions.

6.2.2 Data Scan Intervals The instrument scan rates and data throughput times specified in the design documents are adequate.

6.2.3 Scale Optim.s ,lon Scale optimization of the SPDS is considered adequate. During an NRC audit of the previous ,

SPDS, trend graph time scales were considered inadequate for transient analysis. In the opinion of the V&V team, these scales are adequate for the stated SPDS purpose of trend monitoring in support of EOP ' s.

6.2.4 Data Validation The EPRI data validation methodology utilized by the SPDS is considered adequate.

6.2.5 SPDS Failure In the opinion of the V&V team, SPDS failure recognition, operator response to SPDS failure, and determination of SPDS operability, are adequately addressed by the system design and operator training.

6.2.6 Electrical Isolation In the opinion of the V&V team, the use of optical isolators provides adequate Class lE isolation.

6.2.7 Configuration Control In the opinion of the V&V team, the configuration control program identified in GM8-EMP-009 PSE&G 20 NOV-1000-88-003 REV.1

.-t a

r LV&V FINAL REPdRT q

adequately governs the initiations development,

implementation:and closeout of SPDS design .f

' changes; including changes to permanent design documents.

(GM8-EMP-009 was superceded'as of 1/1/89 by NA-AP.ZZ-0008(Q). The new procedure requires use of

" workbooks" for design changes. Workbook DE- i

.WB.ZZ-0001(Q) specifically. addresses.affects of changes to SPDS in Exhibit 2,_page 2_(reference 1.3.22).]

6.2.8 Reliability.

No formal reliability report or' analysis has been provided to the V&V team and thus this item remains open.

'[ Reliability data has been documented'in the System Availability Analysis, reference 1.3.21.

System availability has been calculated-to be 99.1 per cent, which is considered adequate by PSE&G.]

6. 2. 9 Location In the opinion of the V&V team, the current design and hardware configuration adequately addresses these requirements.-

6.2.10 Procedures and Training The basic training progr'am which pertains to the h SPDS is considered adequate.

L 6.2.11 Human Factors Although the human factors final report has not-been received, a discussion with Essex Corporation indicates that no open items will be identified in the final report. The V&V team, therefore, i considers this item closed pending receipt of the i human factors final report.

(The Human Factors report, reference 1.3.20, has been issued. There are no open items identified.]

-6.2.12 System-Operation and Maintenance ,

In the opinion of the V&V team, the design philosophy of the Hope Creek SPDS adequately I PSE&G 21 NOV-1000-88-003 REV.1 l

j-V&V FINAL REPURT addresses the requirements associated with system operation.

, Incorporation of. vendor recommended periodic maintenance procedures will satisfy the requirements associated with system maintenance.

[

l PSE&G 22 NOV-1000-88-003 REV.1 9

APPENls7X A DISCREPANCY REPORTS NOV-1000-88-003 Revision 1 l

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 1 Date: 04 / 15 / 88 Page / of /

References:

CDM-0484-0, pgs 2-29, 2-33 thru 2-35

Description:

s i

RCIC (T2422) and HPCI (T2423)

Injection Status's do not incorporate the respective test .

line MOV positions.

Disposition:

DM-484 will be revised +) be consistant with algorithms developed in DM-491, Rev 1.

l l

Disposition Prepar . / /

V & V Review r

' /87 /W

/

Disposition Verified: / /

Signature Date

c HOPE CREEK-GENERATING STATION SPDS.V&V DISCREPANCY REPORT.

Discrepancy No: 2 Date: 04- / 15 / 88 Page '/ of I

References:

'CDM-0484-0, pg 3-32

Description:

Calls for monitoring status of 5 ADS valves. Point B2600, monitors status of all ADS /SRV valves.

Disposition:

Monitoring allADS valves supports decision function j RC/P-4 of EOP-101. DM-484 will be updated to reflect this. '

i d /2'/a Disposition Prepared b : -

V & V Review / k / 27 / b#

~l /

. Disposition Verified: / /

Signature Date e

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ]

i HOPE' CREEK'GENERkTING, STATION p -SPDS V&V DISCREPANCY REPORT-Discrepancy No. 3' Date:'04 /15 /8_8-

. , Page- f. of /

References:

- 1) CDM -04 8 4 0 ', pg 2-13

.2) CDM-0491-0, fig. 5. 2 i 3)- ^

Description:

The -129.0" point on the graph's y-ax'is is'not.shown.

a

. Disposition:

-129 is supported as a margin to action point.B8024. All values.could not be supported on the; trend because of human factors concerns with display co'njestion.

This philosophy is followed in DM-491 Rev. I and'will be included in DM-484 revision.

l l

l Disposition Prepared B : @S V&V-Review: 2c / 8, 7,N M 7 f Disposition Verified:

Signature Date 4tF#N3@. - --

1 HOPE CREEK GENERATING STATION T

SPDS.V&V: DISCREPANCY REPORT Discrepancy No. 4- - Date: 04 /15 /88 Pag e / of /

References:

. 1) CDM-0484-0, pg 3-41

2) CDM-0491-0, fig. 5.2-1 3)

Description:

The display f eature shown on pg 3-41' has not been included in the display shown in fig. 5.2-1.

.I l

t Disposition:

I i

DM-484 will be revised to show the Rx level setpoints supported based on the EOP's.

These setpoints are included in DM-491, Rev. 1.

1

')

i l

Disposition Prepared = f-2f h 8' T7[P8 V&V Review:_ ( ( '

Disposition verified:

Signature Date dr/130  !

l

isOPE CREEK GENERATING STATION'

-SPDS V&V DISCREPANCY REPORT Discrepancy No: 5 .Date: 04'/ 15 / 88-Page- / of /

References:

CDMJ484-0, pg 2-42

[ 'CDM-0491-0 fig 5.2-1

Description:

.j The display feature shown on pg 2-42 has not been j

,~,

incorporated'.into display shown in figure. 5.2-1 -]

-l ,

l Disposition:

DM 484 will be revised to the displays contained in DM-491 Rev. 1 i

i l

l t

Disposition Prepared by: b Y/ 29 / F8  !

~

V&VReview:b) m / /

i /

Disposition Verified: / /  !;

Signature Date

HOPE CREEK GENERATING STATION SPPS V6V DISCREPANCY REPORT Discrepancy No: 6 Date: 04 '/ 15 / 88 .

Page /

of /

References:

CDM-0484-0, pg 2-19 CDM-0491-0, fig 5.2

Description:

The display levels listed on pg 2-19 have not been incorporated into display shown in figure 5.2-1.

Disposition:

See discrepancy #5.

  • l l i l

l l

l l

DispositionPreparedg: -

/ 2k/

V&VReviewb <

/

h / 27 / OY Disposition Verified: / /

Signature Date l

HOPE-CREEK GENERATING STATION SPDS V&V' DISCREPANCY REPORT Discrepancy No: 7 Date: 4 / 15 / 88 Page / o,f . l

References:

CDM-0491-0, Att. A--

Description:

There are some display abbreviations not' listed (i.e. CPS, ISOL, EMER, COOL, PRES,. DEPRESS, ASSD,.

CLRS, FLD)

}

Disposition: Rev. 1 of DM-491 . incorporates all~ abbreviations i

i l

j

! I L i 1

)

l DispositionPreparedby:k!# h @ / 2I / [h V & V Review: b k/87/ bb j

/ f .

' Disposition Verified: / / ,

u_______ -. _ _ _ _ _ _ _ _ _ .

1

j' HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT '

. Discrepancy No: 8 Date: 4 / 15 / 88 Page / of /

L

References:

CDM-0491-0 pgs. 5.10-4 to 7 OP-EO.ZZ-104, Rev. O

Description:

CDM-0491-0 does not reflect offsite release rates described in EOP.

Disposition: DM-491 Rev. 1 has the latest revision setpoints of EOP OP-EO.ZZ-104 (Q) which are:

1.20 E+5 for noble gas and 170 for Iodine Reference page 5.10-8 and F 5.10-2.

I Disposition Prepared b : k / 2k/

V & V Review f /o27 / N I

(

Disposition Verified: / /

Signature ' Date

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __ ._ . . _ _ 1

-HOPE CREEK GENERATING STATION SPDS.V&V DISCREPANCY REPORT l

Discrepancy'No. 9 Date: 04 /15 /88 Page / of /

References:

- 1) CDM-0484-0, pgs 12-3 & 12-4

2) CDM-0491-0, fig. 5.1 .14 & 5.1-15 3)

.D3scription:

The 0484 decision function requires that valid RMS atmosphere unit:' alarms have been received. These alarms are not included in the 0484 or the 0491 point algorithms.

I Disposition:

DM-484 will be revised per DM-491, Rev. 1, DM-491, Rev. 1 supports the RMS release setpoints which are validated by the RMS computer and SPDS computer.

Disposition Prepared B : f h*2k ,

V&V Review- b, .

,f f_ ,!R7,/M

' Disposition Verified: )

Signature Date  !

. d r/131.

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT-Discrepancy No: in Date: 4- / 15 /- 88-Page- / of l

~

References:

CDM-0484-0 .

pgs. 2-29, 2-73,.3-24 3-30, 3-51, & 4

Description:

- CDM-0491-0 figs. 5.2-1, 5.4-1 DIGITAL REPORT #1,pg.~6 The 0484 display feature call-for displaying the number of rods ~not inserted to at least position

~

02. The 0491 documentation describes a digital point (D8000) with 'a YES/NO response.

disposition: . The YES/NO response is based on all RODS full in which exceeds the requirement. DM-484 will be revised to ref. lect-this.

Disposition Prepared by: h / 2k /

V'& V Review: p A h /87 / N f f Disposition Verified: / /_

Signature

  • Date

[

HOPE' CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT -!

Discrepancy No: 11 Date: 4 / 15 / 88 Page / of /

References:

CDM-0491-0 figd. 5.2-1, 5.4

Description:

The text for point D8000 is. contradictory for figs 5.2-1 and 5.4-1.

Disposition: The text for D8000 in DM-491 Rev.1 and on the system for both figures is "All Rods Inserted".

Disposition Prepared by:_ / /

V&VReview:b ) / 27 / bb f (

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATIdN I SPDS V&V DISCREPANCY REPORT H

i Discrepancy No:- 12 Date: 4 / 15~ / '88 Page / of- I

References:

CDM-0491-0 DIGITAL REPORT #1 pg.6 l

l

Description:

No source instrument is listed for point'D8000 in the report. . Design review of.the adequacy-of this. point cannot be completed.

Disposition: DM-491^Rev. 1 page'5.2-11 describes. output from Rx Manual Control System.~ Detailed signal tap included on schematic diagrams,in DCP 6 of DCR-4Ec-1076.

l Disposition Prepared by: ! / / 2@/ /J V & V Review: O

/ f

] h / [7 / OI Disposition Verified: / /

Signature -

Date j

HOPE CREEK GENERATING STATION.

SPDS'V6V DISCREPANCY REPORT Discrepancy No:- 13 -

Date: 04 '/ 15' / 88 Page /~ o,f- /

References:

CDM-0484-0, pgs 4-13 & 4-16

Description:

No analysis'is provided since these decision functions-address observance of inward rod motion and observance that inward rod motion has stopped. Justification for excluding  !

this information from the SPDS is based on " operator knowledge of plant conditions" and the information being "available on the rod. control panels identify inward rod motion and that inward motion has stopped.

Disposition:

Inward motion of the rod can be' verified by the FULL IN Lamp' illuminating and/or the actual position of the rod displayed.

Disposition Prepared by:_

/ 2.9 /M V & V Review: 0<

AdJ f

k /d 7 / N Disposition Verified: / /  !

Signature Date

. HOPE CREEK GENERATING STATION SPDS'V6V DISCREPANCY-REPORT 'I Discrepancy No: la Date: 4 / 15 / 88 Page / of /

References:

CDM-0491-0 Digital Report #1 Description': Point algorithm-and. database show different functions or methods (AVG, CAL, etc.) for the same type of algorithm such as " Alternate".

Ref. B5019, B5050 and B5030.

Disposition: Database PS-J-626 and-DM-491 Rev. 1 are consistant. Both have same functions listed for a given point.

I l

I I

L Disposition Prepared by: N k/29/82 l

i V & V Review:

/

h / 87 / Ek 1

Disposition Verified: / /

Signature Date  ;

=:-__.__-_-..-- .!

HOPE CREEK GENERATING STATION 'f SPDS V&V DISCREPANCY REPORT l Discrepancy No: 15 Date: 4:'/- 15 / . 88 Page / of '/

References:

CDM-0491-0

Description:

' B5070 shows a CAL function for an AVG algorithm on fig. 5.1-7A which is different from figs 5.3-11, 5.6-3, 5.6-2, 5.8-8.

I

\

Disposition: Figure F.1-7A on DM-491 Rev. 1 list B5070 as (AVG) point. This is consistant with'PS-J-0626 and the other figures listed above.

Disposition Prepared by: h f / [h /h V & V Review:

/

k /27 / Ef I

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION I SPDS~V&V DISCREPANCY REPORT Discrepancy No: 16 Date: 4 / 15 / 88 Page.- / of. /

References:

CDM-0491.0

Description:

Block for B5019. fig'5.1-4, different from fig's

-5.2-9, 5.3-12, 5.3-5, 5.3-4, 5.3-2, 5.3-3

-Disposition: PS-J-0626 and fig. 5.1-4 in DM-491 REV. 1 updated to (AVG) which makes all drawings consistant l

4 Disposition Prepared by: ) O h / 2h / Sb V & V Review:

/

h / 27 / b

/

Disposition Verified: / /

Signature -

Date j

a

.g l:

HOPE CREEK GENERATING ~ STATION SPDS V&V DISCREPANCY REPORT L Discrepancy No: 17 Date: a / ic; / na l Page / of l l

~

References:

CDM-0491-0, fig. 5.1-7A

Description:

B8107 shows a CAL function for an. AVG algorithm.

Disposition: DM-491 Rev. 1 shows B8107 as AVG' function Disposition Prepared by_: h/Zh/

V & V Reviews b , 4t/ /o77 / 88

/ f .

Disposition Verified: / /

_- - . _ _ _ _ _ _ _ _ . _ l

HOPE CREEK GENERATING' STATION

'SPDS V&V DISCREPANCY REPORT

' Discrepancy No: 18 Date: 4 / 15 / 88

.Page 1 of l

References:

CDM-0491-0

Description:

Point algorithm and Database printout are using the abbreviation CAL for the conversion type.

Attachment B: SPDS Database shows the only abbreviations being used are DIG (Digital),

ANL (Analog), AVG (Average) and CRV (Curvilinear).

Disposition:' Database description in DM-491 Rev.1 now shows CAL as a calculated point.

Disposition Prepared by: h / /

V & V Review: i /27/bb i /

Disposition Verifi'ed: / /

Signature Date

(.

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 19 Date:' 4 /. 15 -/ 88 Page / o,f /'

~

References:

CDM-0491-0, figs 5.3-8

& 5.3-9

Description:

Algorithm for B6260 (PSP Level), figs- 5. 3-8 and-5.3-9 is in error if B6043 (PC LVL CALC) is in inches. Multiplying an inches calc by 12 does not give you inches. If B6043 is in ft. both B6266 and B6277 CPD's need' revision. Also B6260 algorithm on fig. 5.3-9 requires an alternate-(:) symbol' added.

Disposition: D6260 = B5040, both algorithm are in IN.

See DM-491, Rev. 1.

Disposition Prepared b : h/ / b[

V & V Review I /

k / f 7 /E2 Disposition Verified: / /

Signature Date ,

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ :l

i HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy.No: ?n Date: a . / 1 r; - / nn Page / of /

References:

I CDM-0491-0 1

Description:

QOh Attachment C "EOP Parameter Curves". The Pressure Suppression Pressure (PSP) curve is different from OP-EO.ZZ-102(Q), Rev. O, Sht. 3 of 3, PSP curve DW-P-2. The Co-ordinate (LVL) for EOP-102 is in inches and CDM-0491 is in feet.

Disposition: The current revision on DM-491 Rev.1 is in agreement with the current revision of the EOP's.

I i

Disposition Prepared b : h / 2V/ b V& VReview:b

( /

/[7 /bb Disposition Verified: / /

Signature Date

1 l

l \

L l HOPE' CREEK GENERATING STATION 1 SPDS V&V DISCREPANCY REPORT ]

Discrepancy No: 21 Date: 4 / 15 / 88 _

Page / of. 1 References': CDM-0491-0, pgs. 5.1-10

& 5.7-2

Description:

The basis.for the 47" and 142.5"' alarm points'need to be added. (EOP-102 SP/L-6 and operator caution 23).

Also shouldn't 142.5" and 47" be labeled Hi-Hi and Lo-Lo Alarms respectively on CPD?

Disposition: DM-491 Rev. 1 page 5.1-10 now contain alarm point references for all setpoints.

CPD Fig. 5.1-8 updated to include all alarms Disposition Prepared by: /b /

V&VReview:b f

k / 2.7 / N f

Disposition Verified: / /

Signature Date

i

, HOPE CREEK GENERATING STATION SPDS'V&V DISCREPANCY REPORT i

I Discrepancy No: 22 Date: 4 /'15 / 88 Page / of I

References:

CDM-0491-0, pg. 5.3-9.

I

Description:

The basis for the 57.2 PSIG constant used in point B8122 needs to be addressed.

I Disposition: Basis for 57.2 added to DM-491 Rev. 1 page 5.3-9' l

Disposition Prepared by: A / /

V & V Review:

i i h / 27 / bi Disposition Verified: / /

Signature -

Date

I HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT

Discrepancy No
23 Date: 4- / 15 / 88 Page / of f

References:

CDM-0491-0, pg. 5.3-2

Description:

The basis for the alarm limit of 1071 PSIG needs to be addressed.

Disposition: DM-491 Rev. 1 page 5.3-2 gives basis.

Disposition Prepared by: h / 2.9 / M V&VReview:b h/ 37 / b

( (

Disposition Verified: / /

Signature Date

(

HOPE CREEK GENERATING. STATION SPDS V&V DISCREPANCY REPORT l

Discrepancy No: 24 Date: 4 / 15 / 88

i. Page / of f

References:

CDM-0491-0 pg. 5.'1'  !

Description:

The basis.for the 110 F alarm point should be given here even though it is given later on pg. 5.4-4

-Disposition: Basis included in DM-491 Rev. 1 page 5.1-11 3 i

Disposition Prepa d  : 1 B1 h/h/EP V & V Review I

/ 27 / b2

(

Disposition Verified: / /

Signature Date j

HOPE CREEK GENERATING STATION h SPDS V&V DISCREPANCY. REPORT.

L Discrepancy No: 25 Date: 4' /- 15 / 88 Page / of /

References:

CDM-0491-0 pg. 5.4-8. -

Description:

There is no Section 5.2.9 as. referenced, which discusses "All RODS INSERTED" block.

Should be section 5.2.6.

Disposition: All Rods inserted described on page 5.2-11 ,

section 5.2.6 of DM-491.

Disposition Prepared by: / /

VsVReview0s '

Ji-f 0 /bl /S$

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V. DISCREPANCY REPORT 26 Date: 4 / 15 / 88 Discrepancy No:

Page -l' of l

References:

CDM-0491-0, fig. 5.4-7

Description:

No basis for the 100 limit used in the.T8011'and T8012 algorithm; also the algorithm differ Disposition: Algorithm changed to ensure SLC pressure greater than Rx Pressure for INJ status.

Disposition Prepared by: /2 /

v & v Review: OO t i

/ h /27 /M Disposition Verified: / /

Signature Date

i HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 27 Date: 4 / 1 c; / nn l Page / of /

l--

1

References:

CDM-0491-0, pg.-5.2-5 1'

Description:

Discusses Point B5050 and states that all displayed "value box" values will be green. Point'drawf.ng for B5050 shows a Hi Alarm value of 14.8 PSIG while color change for trend value is described (n1 pg.

5.5-2.

Disposition: The green values are referring to point B6021 and this is clarified in DM-491. Rev.1 page 5.2-5 l

Disposition Prepared by: ,1 h / 2h / l V & V Review:O, ,

h / 2 7 /N Disposition Verified: _/ /

Signature Date-

)

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 28 Date: 4 / 15 / s?_ 3

.Page / of l 1

References:

CDM-0491-0, pg. 5.1-9

Description:

The basis for the 14.8-PSIG alarm point should be given here even though it is given later on pg. 5.5-2, Disposition: Rev. 1 of DM-491 gives basis.

Disposition Prepared by: /d /

V&VReview:b/t u / 27 /88 l

(

Disposition Verified: / /

Signature

  • Date

[;

HOPE, CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 29 Date: 4 / 15 / 88 Page_ / of- 1

References:

CDM-0491-0, pg. 5.5-8

Description:

Change " current value" to " current average value" as CPD B5060 is an average, not direct value.

Disposition: DM-491 Rev. 1 contains " current average value".

3 Disposition Prepared by:

k/ N/

V& V Review h / 2 7 / 88 i (

Disposition Verified: / /

Signature

  • Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 30 Date: 4 / 15'/ 88 Page /- of f

References:

CDM-0491-0, pg 5.5-9

Description:

Provide basis for 3% alarm point and incorporate alarm in CPD B8201, fig. 5.5-9.

i Disposition: 3% alarm does not exist on DM-491, Rev.l.

l Disposition Prepared by: / 2k / h V&VReview:bh @ / 27 / bbi

< r Disposition Verified: / /

Signature Date l

HOPE CREEK' GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy,No: 11 Date: a / in / nn Page / of , )

References:

CDM-0491-0, pg. 5.5-9.

Description:

Change " current value" to " current average.

value" as B8200 and B8201 are average values.

1 4

Disposition: DM-491 Rev. 1 has " current average value"

.i Disposition Prepared b : f / 2.k / 2 V & V Reviewsb /27/d l (

Disposition Verified: / /

Signature Date

______-______________-_______-___n

1 HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT l l

Discrepa'ncy No: 32 Date: 4 / 15 /' 88 l Page / of I li

References:

CDM-0491-0, pg. 5.6-2. l

Description:

Add "B5070" after."Drywell temperature" in the third paragraph for clarification of  ;

PID being discussed.

Disposition: Comment incorporated in DM-491, Rev. 1.

Disposition Prepared by: Y / Ek / 88 V & V Review h '

t

/ E7 / M Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT i

Discrepancy No: 33 Date: 4 / 15 / 88 Page / of 1 Refere'nces: CDM-0491-0, pg. 5.6-2 l

l

-Description: Include the basis for the 340*F alarm limit i in both places along with that for 135'F.

(EOP-102 step DW/T-7).

Disposition: Incorporated basis DM-491 Rev. 1 page 5.6-2 4

l-Disposition Prepared b - h / 2 k/ 8[

V&VReview:b as / 87 / kE

/ f Disposition Verified: / ._/ )

Signature Date

' HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: p Date: 4 / 15 '/ - 88 Page /' of I

References:

CDM-0491-0, pgs. 5.6-2 5.1-9, fig. 5.1-7A

Description:

B5070 turns yellow at 135 F and Red at 340 F.

Point drawing for B5070-should show a Hi and a'Hi-Hi alarm?

Disposition: Hi-Hi ALARM incorporated in DM-491 Rev. 1.

Disposition Prepared by: /2k/

V&VReview:b <

/ 87 / E f

Disposition Verified: / /

Signature -

Date

' HOPE CREEK GENERATING' STATION SPDS V&V DISCREPANCY REPORT-Discrepancy No: '35 Date: 4 / 15 / 88 Page- / ,

of' /

References:

CDM-0491-0, pg. 5.6-6.

Description:

Add "(B5060 )" af ter "'This block", for clarification.

Disposition: Page 5.6-6 now referenced to section.5.5 which has point B5060 included in text in DM-491 Rev. 1. .;

l l

Disposition Prepared by: / / l V & V Review 'b h / 27 / Pb

/ 0 Disposition Verified: / / l Signature Date  ;

HOPE CREEK GENERATING'STATIOMi SPDS V&V' DISCREPANCY REPORT

.l Discrepancy No: 36 Date: 4' / 15 / 88 )

Page / of f- I I

References:

CDM-0491-0, pg. 5.7-3.

Description:

Add "and for Point B5040, fig. 5.1-8".

i

' Disposition: Incorporated DM-491 Rev. 1.

1 i l

Disposition Prepared by: / E /8 V&'VReview:b / 27 / 2h I (

Disposition Verified: / /

9"" * **

( HOPE CREEK GENERATING STATION SPDS'V&V DISCREPANCY REPORT.

Discrepancy No: 37 Date: 4/ 15 / 88 Page '/- of l

References:

CDM-0491-0, pg.5.'7-8.

Description:

Add'"(B5060)" after " temperature ", for clarification.

Disposition: Page 5.7-8 referenced to section 5.5-4 which has point B5060 included. DM-491, Rev. 1.

Disposition Prepared -

f / Ek/M V & V R. lew:b I

, k / 27 / N

/

Disposition Verified: / /

Signature Date

HOPE CREEK GEb3ERATING STATION L SPDS V&V DISCREPANCY REPORT Discrepancy No: 38 Date: 4 / 15 / 88 Page / of l

~

References:

CDM-0491-0, pg. 5.7-9.

Description:

Curves referenced to as SP-L-29 and SP-L-26 are actually OP-EO.ZZ-102, Rev.0, Sh. 1, SP-L-2a and SP-L-2b. Also, these curves are not included in Attachment C.

Disposition: Curves included in Attachment C, curves reference made to EOP OP-EO.ZZ-102 DM-491, Rev.l.

Disposition Prepared by: / /

V & V Review b 9 / l7 / bk

/ /

Disposition Verified: / /

Signature Date

i; HOPE CREEK GENERATING STATION I L SPDS V&V DISCREPANCY REPORT .i a .

39

' Discrepancy No: Date: 4 / 15 / 98 )

Page / of /

References:

CDM-0491-0, fig. 5.7-8

&5.7-9.

Description:

Algorithm for B8032 and B8037 need revis' ion for clarification.

.i Disposition: These points are a function of Suppression Chamber Press, Suppression Pool Temperature, and the NPSH curves for Core Spray.and RHR.

This is clearly defined in DM-491, Rev. 1.

Disposition Prepared by: /-2 /

V & V Review N Ji I

e / $7 / EE i

/'

Disposition Verified: / /

Signature -

Date  !

_ - - _ _ - - _ - _ _ _ _ - - - - - - - - - - - - - - . - - - - - - _ - - - - _ - _ - - - - - - - - _ - - - - - .- - - - - - - - . --1

HOPE CREEK GENERATING STATION- )

SPDS V&V DISCREPANCY REPORT Disc'repancy No: 40 Date: 4 /- 15 / 88 l

Page / of I l

References:

CDM-0491-0, pg. 5.7-10.

i

-l

Description:

Add "(B5084)" after " temperature display" for clarification. Also "section 5.1.1.C2" should read "section 5.1.C.2".

Disposition: 5.1.1.C2 has been corrected to 5.1.C.2 page 5.7-10 refers to page 5.1-11 which .

clearly indicates B5084.

See DM-491 Rev. 1.

l I Disposition Prepared by: M / /

V & V Review: u / 27 /b

' (

l Disposition Verified: / /

Signature Date-u_ _ . _ _ - _ _ _ _ _ _

l l

HOPE CREEK GENERATING STATION .)

SPDS V&V DISCREPANCY' REPORT 1

Discrepancy No: 41 Date: 4' / 15 / 88 Page / of 'l  !

References:

CDM-0491-0, pg.5.8-3.

Description:

Include basis for the 110*F alarm point.

i i

l l

I Disposition: . Basis included DM-491, Rev. 1.

l

.i 1

I I E t

l I

I i

Disposition Prepared by: [ / /2[

V&VReview:b / 2~2 / kE

! (

Disposition Verified: / /

( Signature Date L__________.._ _ . _ _ _ _

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: '42 Date: 4 - / 15 '/' 88 Page / of /

~

References:

CDM-0491-0, pg. .5.8-9.

Description:

Add "(B2600)" after " the open position".

.2 Disposition: Incorporated DM-491, Rev. 1.

Disposition Prepared by: #ff / /

V & V Review d , h / 27 / M8

'l (~

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT

. Discrepancy:No: '43 Date: 4 / 1s / as Page / of /

~

References:

CDM-0491-0, pg. 5.9-6

& fig. 5.9-2.

Description:

Algorithm for PID T2522 appears to give a CLDS indication only when.both supply dampers or both of the exhaust dmapers.are closed..

It should read T2522 = (D4997 +.D5039) *

(D5030 + D5031).

Color-coding description appears ambiguous.

Seems.to say if one supply damper and/or one exhaust damper is NCLSD you get a RED cplor. This also meets the logic for Green color as there are 2. intake and 2 exhaust dampers and with one supply and one exhast closed you get GREEN.

Disposition:

T2522 equation was corrected prior to testing on PS-J-0626 to read :

T2522 = (Not(D4997 )

  • Not (D5039) + (Not(D5030) +

(Not (D5031).

I i

l 1

Disposition Prepared by: / /

V & V Review:

f h

f h / 27 / bEr Disposition Verified: / /

[. .

m_1___x __ _

Signature Date ,

8

HOPE CREEK GENERATING STATION SPDS.V&V DISCREPANCY REPORT Discrepancy No:- t4 Date: 4 / 15 / 88 Page / of I

References:

CDM-0491-0, fig. 5.1-15, pg. 5.10-8

Description:

The algorithm for points B5093 and B5094 are not discussed in section 5.1.E as noted on pg. 5.10-8, para.2 . Need to address these somwhere including the basis for the constant 472.13 being used.

I Disposition:- The conversion factor of 472.13 is based on standard conversion as follows:

UC/sec = (X ucfc) (Y cu f t/ min) (1 * "[6 0 sec )

(1728cu in/cu f t) ~( 6.39ccMu' inch)

This conversion is performed in the RMS system before the data arrives at SPDS. Section 5.1.E addresses OFFSITE algorithm in DM-491, Rev. 1 Disposition Prepared by: fA ) h / 29 /

v s v Review d, h b , / 9 / 7_7 / W Disposition Verified: / /

I Signature Date

HOPE CREEK GENERATING STATION  !'

SPDS V&V DISCREPANCY REPORT Discrepancy No: 45 Date: 4 / 15 / 88-Page I of I

References:

CDM-0491-0, pg. 5.10-6 fig. 5.10-2

Description:

The basis for B6006 algorithm [(5.0E+5) - B5097]

is OP-EO.ZZ-104(Q) entry condition / Entry condition shown on Rev. O of this EOP is 6.3E+5 uC/s.  !

Disposition: B6005=1.20E+5 - B5097 is'the algorithm used in DM-491, PS-J-0626 and is based on current EOP value of 1.20E+5.

l Disposition Prepared b : / / 2h / N V & V Review

( (

h / 27 / bI Disposition Verified: / / __

Signature -

Date  ;

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No:- 46~ Date: 4 / 15 / 88 Page / of I s

References:

CDM-0491-0, pg. 5.10-6, fig. 5.10-3

Description:

The basis for B6006 algorithm [(7.01E+6) - B5097]

is OP-EO.ZZ-104(Q) RR-10, Note 1, of Rev.0..

states Emergency Condition is 3.48E+8 uC/s.

l Disposition: B6006=1.08E+7 - B5097 is consistant with current EOP's, DM-491, Rev. 1 and ECG.

L I

Disposition Prepared by: /N/

V & V Review O /27/bd I (

Disposition Verified: / /

Signature Date j J

l:

HOPE CREEK GENERATING STATION-

.SPDS.VsV DISCREPANCY' REPORT l- Discrepancy No*' 47 Date: 4 / 15 / 88- 1 1

Page. 'l of I.

l I]

References:

CDM-0491-0,pg.5.1-16, fig ~. 5.1-14 q

Description:

The basis for.B5097-Hi Alarm of 5.0E+5' fig.

5.1-14uC/s (ALERT)'is' entry condition of

'OP-EO.ZZ-104(Q). Entry condition shown on Rev. 0 of this EOP is 6.3E+5 uC/s.

' Disposition: Current setpoint'l.20E+5 is consistant with PS-J-0626, DM-491, Rev. 1 and EOP, and ECG.

Disposition Prepared by: / /

V & V Review: b s/ / 27 / 9h

! (

Disposition Verified: / /

Signature Date

~

HOPE CREEK GENERATING STATION' SPDS V&V~ DISCREPANCY REPORT Discrepancy;No: 48 Date: 4 / 15 / 88 Page / of l:

i

References:

CDM-0491-0, pg. 5.10-7 fig'5.10-4

Description:

The algorithm for B6007 is based on OP-EO.ZZ-104(Q) entry condtion of 211 uC/s Iodine. Rev. O of this EOP is 1450 uC/sec.

Disposition:~ Current setpoint B6007=170-B5098-See Discrepancy #47.

i Disposition Prepared by:_ /N/[

V &'V Review O f

i f

k / E7 / N

. Disposition Verified: / /

Signature Date w_ _ __ -

"I -' '

HOPE CREEK GENERATING STATION SPDS V&V-DISCREPANCY REPORT

.' Discrepancy No: 49 Date: 4 / 15 / 88 Page / of '(

References:

' CDM-0491-0, pg. 5.10-7, fig. 5.10-5 c

Description:

The algorithm for'B6008 is based.on OP-EO'.ZZ-104(Q) step RR-10 for 5240 uC/s Iodine Emergency level. Rev. O of this EOP uses 4.22E+6 uC/s Iodine.

9 Disposition: Curent setpoint 1.21E+4-B5098 See Discrepancy #47 l

Disposition Prepared by: / /

V & V Review / [7 / kb f (

Disposition Verified: / /

Signature Date 1

- _ _ _ - _ _ - _ _ _ . _ _ _ . - l

_= . _ _ _ - . _ - - _ _

HOPE CREEK GENERATING STATION SPDS'V&V DISCREPANCY REPORT Discrepancy No: 50 Date: 4 ~/ 15 / 88 Page / of /

! 1

References:

-CDM-0491-0, pg. 5.1-17, fig. 5.1-15

Description:

The alarm point of 211 uC/s Iodine for B5098 is based on the OP-EO.ZZ-104(Q) entry conditions.

-Rev. O of this EOP uses 1450 uC/s Iodine.

Disposition: Current setpoint 170 See Discrepancy #47.

i i

l Disposition Prepared by: /b /

l V&VRevi'ewb _ z k/E7/b8 l-l

(

Disposition Verified: / /

Signature Date

HOPE CREEK'GEMERATING STATION SPDS V&V DISCREPANCY REPORT

]

I Discrepancy'No: 51 Date: 4 / 15 / 88

.Page / o,f l l

References:

CDM-0491-0, pg. 5.10-8 I

?

Description:

. Alarm. values shown here, are not based on

'OP-EO.ZZ-104(Q), Rev. O entry levels as stated.

Disposition: Current alarm values in DM-491 Rev. 1 are in agreement with' current Rev. of EOP Disposition Prepared b : /N/

V & V Review ./ /27/ 2 l i Disposition Verified: / /

Signature Date

L l

' HOPE CREEK GENERATING' STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 52- Date: 4 / 15 / 88-Page- I of I

References:

CDM-0491-0, pg. 5.1-2.

l

Description:

The basis for the alarm value of -38 in. should be addressed here. B5006 should designate -38 in as' Lo-Lo alarm.

I Disposition:- DM-491, Rev. 1 incorporates basis and updates ~

fig. 5.1-3A.

l Disposition Prepared by: .

/] /

V & V Review d f f

] /[7_/ N Disposition Verified: / /

Signature -

Date l

_ _ _ _ _ _ - _ _ _ _ _ _ - _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ ___________a

g _ - - _ _ . .__ ___ ____--_ _ _

i F ' HOPE CREEK GENERATING STATION I SPDS V&V DISCREPANCY. REPORT Discrepancy No: 53 Date: 4 / 15 j 88 Page / o,f /

, . \

l'

References:

CDM-04 91- 0. pg. 5.1-3. j i

i

Description:

Pressure Logic check has been removed from Table-5.1-1.

Some justification should be made for why it isn't a necessary factor.

l Disposition: Instrument Inanges and calibrations are documented via the Instrumetn Calibration Data Sheets which have calculations for Temp./ Pressure Data for inputs. SPDS values displayed in a priority that gives best level data for current plant conditions.

i l

Disposition Prepared b : h / 2 k / Rb V&VReviewb ' /

h / $7 / E ,

Disposition Verified: / /

Signature Date

l HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 54 Date: 4 / 15'/ 88 Page / of /

~

References:

CDM-0491-0, pg. 5.1-4.

Description:

The basis for the alarm value of 1071 psig should be addressed here. Shouldn't this value be listed as a Hi-Hi alarm point on.B5019?-

i Disposition: Basis included in DM-491, Rev, 1  ;

and on Fig. 5.1-4 l

I 1

Disposition Prepared by: . / 7h/

V & V Review:O h/ /$  !

l (

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT l

t Discrepancy No: 55 'Date: 4 / 15 / 88 Page / of /

I

References:

CDM-0491-0, pg. 5.1-5

Description:

Entry condition on OP-EO.ZZ-101(Q), Rev.0 is 5% power. What is basis for changing to 4%?-

Disposition: 4% power based on current Rev. of EOP Disposition Prepared by: / [h /

V&VReviewb -r

, k / 27 / N f

Disposition Verified: / /

Signature Date

_ _ _ _ _ . _ _ . . . t

HOPE CREEK-' GENERATING STATION-SPDS-V&V DISCREPANCY REPORT u

Discrepancy No: 56- Date: 4 / 15'/ 88 Page / of /

~

Reference's: .CDM-0491-0, pg. 5.1-5 .

fig. 5.1-5A o.

l

Description:

. Alarm condition'for B5026 color'~ change-'is 4%-

. power combined with a tripped-status of T2391.

~

CPD for B5026 shows Hi alarm at 101.0%.

What is basis for this number and which one is correct? Or are both of then?'If both, then address the 101.0% also.

Disposition: , These setpoints based on current.EOP's=.

See 5.1-5 for explanation.

Disposition Prepar d bvi. / /

V & V Review M / 27 /

i Disposition Verified: / /

Signature '

Date

HOPE CREEK GENERATING-STATION SPDS V&V DISCREPANCY REPORT DiscrepancyLNo:- 57 Date: 4 / 15 / 88 Page / of- l

~

References:

CDM-0491-0, pg. 5.1-6.

Description:

What is the basis for the alarm poin,t of 14.9 psig?

Shouldn be stated here. Shouldn't thos value be shown as a Hi-Hi alarm point on B50307 Disposition: Basis included in DM-491, Rev.1 CPD included Hi and Hi-Hi alarm.

?

I Disposition Prepared by: k / 7f /

V&VReview:h ' /

h / 27 / 80 Disposition Verified: / /

- _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ . - _ _ _ _ _ _ _ l

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 58 Date: 4 / in / na Page T/ of /

~

References:

-CDM-0491-0, pg. 5.1-9

Description:

Basis for alarm level of 340.F should be'provided here. Shouldn't this valge be shown as a Hi-Hi alarm point ~on B5070?

Disposition: Basis included in DM-491, Rev. 1 and alarm on CPD.

l

(~ l 1

-Disposition Prepared by: / 2- /

V & V Review b /__2.7_/N

/ /

Disposition Verified: / /

Signature Date

HOPE CREEK-GENERATING STATION SPDS V&V DISCREPANCY REPORT -!

L Discrepancy.- No :- 59 Date: 4/ 15 / 88 Page /- of- /

~

References:

.CDM-0491-0, pg. 5;1-10 j

Description:

. Basis for alarm condition of 47" and 142.5" should be provided here..Shouldn't these point be shown as Lo-Lo ahd Hi-Hi alarm points on B5040?

Disposition:

See Discrepancy #21. J i

'l Disposition Prepared by: ) b h/2 /

V & V Review:

a h/27/ bb f

Disposition Verified: / /

Signature Date. ,

__ . - 4

HOPE' CREEK' GENERATING STATION I SPDS V&V DISCREPANCY REPORT l' Discrepancy-No: '60 'Date: 4 / 15 / 88 Page '/ of 1

References:

CDM-0491-0, pg. 5.1-11.

Description:

Basis for 110 F alarm condition should be provided'

'here. Shouldn't this value be shown as s Hi-Hi alarm point on B50847 Disposition:- Basis include in DM-491 Rev. 1 and on Fig.5.1-9 l

i Disposition Prepared by: / /1 /

V&VReviewb, a,s

/ 87 / OE Disposition Verified: / /

Signature Date

.N ' ' '

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY' REPORT Discrepancy No: 61 Date: 4 / 15 / 88 ]

Page / o,f /

References:

CDM-0491-0, pg. 5.2-2, fig. 5.2-1 1

i

Description:

Trend plot on fig. 5.2-1 does not show all appropriate values for which operator actions are described in 1 OP's. Specifically +54 "and -129". I Disposition: DM-491, Rev. 1 has correct setpoints of 12.5 and -38 which is per EGP.

I l

Disposition Prepared by: /7 /

V & V Review , h / I7 / bb i /

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT 1

i Discrepancy No: r;9 Date: i / 1s / An i Page / of I

References:

CDM-0491-0, pg. 5.2-2.

Description:

Basis for -129" alarm condition should be .)

provided here. Shouldn't this value he  !

shown as a Lo-Lo alarm on B5007. 't Disposition: The -129 inch setpoint is not supported by the trend graph. This point is supported and basis given on page 5.2-8 of DM-491, Rev. 1 Disposition Prepared  : /b /

'V&VReview:bu j h / 27 / bb i

f Disposition Verified: /, /

Signature Date

f 1

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY' REPORT .

l L Discrepancy.No: 63 Date: 4 /- 1; / nn l

t. Page / of l 1

References:

CDM-0491-0, pg. 5.2-5,,

fig. 5.2-8

.l

Description:

CPD for B5080 shows an alarm at 14.8 psig but l

.there is nothing on pg.5.2-5 regarding this.

Alarm function is addressed on pg. 5.2-5.

Should it be addressed in both places?

Disposition: Reference included for point B5050 in DM-491, Rev. 1 Disposition Prepared by: / /

V & V Review

/f m h / $7 / Pb

/

Disposition verified: / /

Signature -

Date

l HOPE CREEK' GENERATING STATION SPDS.V&V DISCREPANCY REPORT

~ Discrepancy No: 64 Date: -4 / 1 c; '/ na Page. / of I

References:

.CDM-0491-0,.pg.5.2-12 fig. 5.2-1 l

Description:

PID's used for monitoring MSIV status should be listed-on pg. 5.2-12 4

Disposition: . Point.ID for MSIV are clearly defined on fig. 5.2-1 in DM-491, Rev.1 l

1 Disposition Prepared by: / Z@/ l)1 V&VReviewb, 9 / 27 / 2ff Disposition Verified: / /

9*

HOPE CREEK GENERATING STATION

.SPDS V&V DISCREPANCY REPORT

-Discrepancy No: fi r; Date: 4 / 15 / 88 Page / of f References _: 'CDM-0491-0, pg. 5.3-2

Description:

- Basis for alarm level of 1071 PSIG should be provided.here. Shouldn't this value be shown as a Hi-Hi point on B5019?

Disposition: Basis provided on DM-491-Rev. 1 Fig. 5.1-4 also contains 1071 setpoint.

Disposition Prepared by: / /

V & V Review: < / 2.7 / bk i (

, Disposition Verified: / /

Signature Date

_ ___ _ _ _ _ . _ _z-  ;

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT .

l

..,. Discrepancy No: 66 Date: 4 / 15 / 88 J Page l' of f

References:

CDM-0491-0, fig. 2.1 ..

H

~

Description:

. Add " ALTERNATE" to note 3 or 4-l Disposition: New statement added explaining alternate in'

.DM-491, Rev. 1 Disposition Prepared by: / /

V&VReviewb '

/ / 27 / bh

/

Disposition Verified: / /

Signature Date l

l. _ _ _ _ _ _ _ _ _ _ _ _ _ .  !

I

' HOPE CREEK GENERATING STATION.

SPDS V&V DISCREPANCY REPORT-Discrepancy No:~ 67 ~ Date: 4 / 15 /. 88

-Page / of f

References:

CDM-0491-0, pg. 2.2-10

Description:

Second paragraph has too many "with. blue background" statements.

Disposition: Insert value no 1( nger applies and .this paragraph is deleted in DM-491, Rev. 1 l

Disposition Prepared by: , // /

V & V Review-I /

s h /_D / hh Disposition Verified: /_ /

Signature Date

_ _ _ _ _ _ _ . - _ - _ _ _ _ =

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT

. Discrepancy tha: 68 Date: 4 /~15 / 88 Page / of f

References:

CDM-0491-0, pg. 3.4-1

Description:

The points'is raised of "Where'possible, analog-and digita1Lsignals are logically combined.....?

a) Which points use this' type of validation?

b) Is there documentation to show that all.

possible checks have been done to. verify these points are/arent available?

c) What is the basis for deciding where to apply or exclude this technique?  !

4 Disposition: A) Points using this type of validation are defined in equation section of PS-J-0626.

B) The point develop, drawings and P&ID's and the V&V effort. l C) .If the physical points existed in the field.

DM-491 Rev. 1 gives example = criteria.

i Disposition Prepared by: / /

V&VReview:b'

/

h/N/

Disposition Verified: / /

Signature Date ,

1 l HOPE CREEK GENERATING STATION SPDS.V&V DISCREPANCY REPORT Discrepancy No: 69 Date: 4- / 15 / 88 Page '/ o'f ~ '/-

l.

References:

CDM-0491-0, pg. 4.2-2, para 2-4 i

Description:

Is screen resolution sufficient to meet the 5% of I i

vertical scale requirements when applied to an.

exponential trend plot as in fig. 5.10-1?

l Disposition: DM-491 Rev. 1 clarifies this as 5% Equivalent..

Linear Full Scale which tlig system meets as tested.

q I

Disposition Prepared b : / / /

V& V Review m h /N7 /bb i ' l

, Disposition Verified: / /  !

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 70 Date: 4 / 15 / 88 Page / of /

References:

CDM-0491-0, pg. 4.2-3, para 1 and 2 ]

Description:

What will distinguish this point, representing a value'above or below the graph scale limits, i from a valid indication at the highest or lowest ,

scale limit?  ;

i l

l I

l Disposition: A digital value is included at the trend graph f or 4 confi'FEation . of the trend value. Both-the digital value and the trend value follow normal color coding. This is consistant with i narrow range recorders in the plant which i remain upscale'even though the process is higher than the limits of the recorder.

l Disposition Prepared b : [/ V

/ 2k / 8M V&VReviewh c(/ M7/d I

(

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION

.SPDS V&V DISCREPANCY REPORT:

. Discrepancy No: 71 Date': 4 / 15 /__88

-Page / of I

References:

CDM-0491-0, pg. 5.'l

Description:

Specifies that PID B5030 will' average the medium range sensors. Only NR (Narrow Range) ig- and WR (WideLRange) sensors are described.

Disposition: DM-491 Rev. 1. changes " medium" to

" wide". This provides a narrow range and wide range instrument for Drywell Pressure.

I l

Disposition Prepared b : / /

1' V & V Review I

4c/

(

h / 27 / W

! Disposition Verified: / /

Signature -

Date

l ;. -

L; y ' I h '" HOPE CREEK GENERATING STATION l SPDS V&V DISCREPANCY REPORT

. Discrepancy No: 72' Date: 04 / 15 / 88

'Page / of /

References:

! CDM-0491-0, fig 5.7 L CDM-0484-0, pg 7-23 L

Description:

'CDM-0491-0, fig 5.7-1 screen layout does not reflect the table-layout shown onCDM-0484-0, pg 7-23.

Disposition:

Screen layout in DM-484 will be revised to reflect screen layout of DM-491, Rev 1.

1 Disposition Prepared by: h h/ 2 k / 82 V & V Review . / 23 /

{

Disposition Verified: / /

Signature Date

v 5

' I V, ,,

L , HOPE CREEK' GENERATING STATION 4 'SPDS V&V DISCREPANCY REPORT:-

. Discrepancy-No: n Dates- 04 / 15 '/ 88~

Page / of- '/

- I

' Reference's: CDM-0491-0, pg 5.'l-3

-)

CDM-0484-0, pg 2-2 ~l

Description:

Comparison.of chart on CDM-0484-0, pg. 2-2 with Table  !

5.:1-1 on pg 5~.,1-3 of CDM-0491-0 shows.that the S/D

. Range Drywell Temp , ranges 'Ior - valid readings are directly opposite. Onenshows >135 F, the other <l35 F. -j i

Disposition:, ]

DM-484 will be revised-to reflect DM-491 Rev. 1

.I Disposition Prepared by: h / 2. /

V & V Review: O '

m

(

h / N / bh  !

- Disposition Verified: / /

_ __ _ _ . _ _ -_E-_._ __ _ _

Signature Date

. ]

1-HOPE CREEK GENERATINGLSTATION  ;

SPDS'V&V DISCREPANCY REPORT l 1

Discrepancy No. 74 Dates.04 /15 [88 Pag e /- of 7.

References:

CDM-0491-0

Description:

Following Deficiencies Noted During Comparison Between Point Drawing Information and Database Information:

1. Typo B8119, fig 5.1-7B - should be Zone "D" not "B"

'2. Typo A2279, fig 5.1-7A - has same source instrument as A2285

3. Typo A2267, fig 5.1-7B - has same source instrument as A2266

'4. Differences between D2887 thru D2889'& D2890 source instruments'on Fig. 5.1-10B and database.

5. Differences between D3000 thru D3003' source instrument on Fig. 5.1-10A and database.
6. Differences between D2972 thru D2978, D2999, D2891, D2892,'D2919, D2928, D2929, D2938, D2971, source instruments on Fig. 5.1-10c and database.
7. Different source instruments for A7164 and A7165 on-Fig. 5.1-13 and database.
8. Differences between R9580,'R9590, R9680 on Fig. 5.1-14 and database.
9. Typo fig 5.2-6 on A2224 source instrument designation L 10. Fig. 5.2-7, D4901 & D902 have .ame sourc instrumelt.

Also A3139 and A3163.

[

11. Fig. 5.2-14, A3543 & A3549 have dif f erent source instruments than database, rs/35

f HOPE CREEKLGENERATING STATION H SPDS V&V DISCREPANCY REPORT Discrepancy No. 74'(con't) Date: 04 /15 /88 Page TL of L

References:

1) 2)

3)

Description:

12. Fig. 5.2.-15, A3550, A3544, A2803 have different source j instruments than database.
13. Fig. 5.2-16, D5005 thru D5018 have dif f erent source instrument-nos. than database.
14. Typo on Fig. 5.4-B, D2174 and D2175 have same source instrument.
15. Fig. 5.11-4, D4967 + D4968 source instruments reversed from database.
16. Fig. 5.11-16, D5003 Sou.ce instrument differs from database.
17. Figs. 5.1-7A and B list RTD sensor ranges of 0-250'F.

The database lists the RTD ranges as 40-250*F.

18. Ths calculation line for PID T8011 (Figure 5.4-7) appears to have a' typo- graphical error. (see PID j T8012)

Disposition:

DM-491 Rev. 1 and PS-J-0626 have been revised to be consistant.

Disposition Prepared By: @Sk V& V Review: 9/27/k[r

( ( <

Disposition Verified: __

Signature Date rs/35 2 1:

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT

-s Discrepancy No: 75 Date: 04 / 1 c; '/ gn Page /- of' I

References:

CDM-0484-0, pg 2-40.

CDM-0491-0, fig 5.4-7

Description:

The use of SLC pump discharge pressure is. inconsistent.

CDM-0484-0 states that every pump discharge pressure-must be <(later) psig. CDM-0491 requires pump discharge pressure to be >100 psig.

Disposition:

DM-484 will be revised to reflect the point development drawings in.DM-491 Rev 1.

Disposition Prepared by: I [ /2h/

V&VReview:b / 27 / bb I (

Disposition Verified: / /

Signature .

Date

t HOPE' CREEK' GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 76 Date: 04- /15- / 88 L Page / of l'

References:

l l

CDM-0484-0,pgs 2-55 & 3-50 EOP-206, Rev 0

Description:

With respect.to the current value of RPV pressure relative to the Minimum Alternate Flooding Pressure with at least 1 SRV open, CDM-0484-0, pages 2-55 and 3 make the statement that "The prediction of future plant con-ditions is not within the scope of.the SPDS". A review of-EOP-206, Rev 0 indicates that this decision. function is not an attemp to predict future plant conditions. This decision-function seems to involve an evalutation of th'e success of'  ;

. specific operator activities. If-so, the discrepancy can i be resolved by making-refe'rence to CDM-0484-0, page 2-53.

Disposit' ion:

DM-484 will be revised per the functions described in DM-491, Rev 1.

I Disposition Prepared by: / /

V & V Review:

/ 27 / bb Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy-No: 77 Date:04 / 15 / 88 Page '/ of I

References:

CDM-0484-0, pgs 2-29, 2-30'

Description:

CDM-0484-0 infomation requirements'and information processing-identify.RHR/LPCI. RHR/LPCI is not included'in information processing results.

4 Disposition:

DM-484 will be revised per DM-491, Rev 1.

l Disposition Prepared by: h/ /

VI & V Review- p cue /N/

i (

Disposition Verified: / /  !

Signature Date

p HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 78 Date: 04 / 15 / 80 Page / of /

References:

CDM-0491-0, figs 5.2-4

+ 5.2-5

Description:

RCIC, HPCI and RHR/LPCI injection status is based'on system flow above a specific flow rate and tert return line MOVs closed. The point development drawings for RCIC and HPCI do not include these MOVs.

/

Disposition:

Bint development drawings in DM-491 Rev 1 base INJ status on flow only,which is conservative.

Disposition Prepared by: O /8 /

V & V Review d o// / 2.7 / W l

/ /

Disposition Verified: / /

Signature Date

U b

HOPE CREEK GENERATING STATION

.SPDS V&V DISCREPANCY REPORT

. Discrepancy No: 79 Date: 04 /_.15__/- 88 Page' / of l

References:

CDM-0484-0 CDM-0491-0

Description:

Several of the system flow rates in.CDM-0484-0 have.

I "ltr" for the required flow rate. Specific flow rates are identified in CDM-0491-0 point development drawings. '

1 Disposition:

DM-484 will be revised to reflect the flow rates given.

in DM-491.

f Disposition Prepared by_: Y / N/ 8 V&VReview:b h / I7'/ N

(

Disposition Verified: / /

Signature Date 4

i HOPE CREEK GENERATING STATION SPDS.V&V DISCREPANCY REPORT ,

Discrepancy.No: 80 Date: 04 /15 '/88 Page J qf l

References:

l CDM-0484-0, pg 2-6 CDM-0491-0, pg 5.1-5

Description:

CDM-0491-0, page 5.1-5 states that the reactor power CFPM block alarms when reactor power is >4% and a scram condition exists. CDM-0484-0, page 2-6 identifies the power level as.

>5%.

Disposition:

DM-484 will be updated per DM-491 Rev 1 which is in agreement with the current revision of the EOP.

Disposition Prepared by: h /

2 /

V & V Review d > _/ 27 / S

( l Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 81 Date: 04/ '15 / 88 Page / .of l

References:

CDM-0484-0, pgs 2-1, 2-2, 2-3 CDM-0491-0, figs 5.1.3A l

Description:

CDM-0484-0, pages 2-1, 2-2 and 2-3 provide an analysis resulting.in a CFPM block display feature alarming at

-38" Reactor Level. This level is an entry. condition for EOP-101, Rev 0.

CDM-0491 alarms reactor' level at.+12.5".

f Disposition:

Reactor Level.has alarms at +12.5" (yellow) and

-38" (red). This supports step'RC/L-4 of EOP 101 as well as'the entry condition of -38".

CDM-0484 and CDM-0491 will be revised to reflect these alarm values.

Disposition Prepared by: f h / 2k /

V & V Review i (

h/27/bb Disposition Verified: / /

Signature .- Date .

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT

' Discrepancy' No: 82 lDate: 04 /15- /88 Page / of /

References:

CDM-0491-0, pgs 5,1-2, 5.1-3

Description:

CDM-0491-0, pages 5.1-2 and 5.1-3 implement a CTPM block display feature which alarms yellow at +12.5" and red at -38". The value +12.5" is attributed to an entry condition for EOP-100. Rev 0 of EOP-100 has no such entry condition.

Disposition:

l DM-491 Rev 1 corrected reference to EOP-101.

i l

I' 1

Disposition Prepared ' 'u h /W/

V & V Review j / 27 /hE

~( (

Disposition Verified: / /

Signature Date  ;

( HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY PEPORT .]

i Discrepancy No.

83 Date: 04 /15 /88 Page , / of- l

References:

1) CDM-0484-0, pgs 2-2 l 2)'CDM-0491-0, pg 5.1-3 3)

Description:

Several inconsistencies exist between the table on page 2-2 of CDM-0484-0 and the table on page 5.1-3 of CDM-0491-0.

Disposition:

DM 484 will be revised to be consistent with DM 491 Rev. 1.

Disposition Pre red B : f.2kd[

V&V Review:

i 2.7/9f l f

Disposition Verified:

Signature Date d r/121--

__ _ _ _ _ _ _ _ ___ _ _ - - - l

l HOPE CREEK GENERATING STATION SPDS-V&V DISCREPANCY REPORT l Discrepancy No. 84 Date: 04 /15 /88 Page / of . [-

References:

1) CDM-0484-0, pgs 2-16 2)
3)  !

t

Description:

~

The RPV LVL status block .( ABOVE/BELOW TAF) does not appear on any display included in CDM-0491-0.

l 1

l l

Disposition:

DM 491 Rev. 1 and the system supports a margin to action point for RPV LVL approaching TAF (Point B8025)

DM 484 will be revised to reflect this.

1 Disposition Prepared By: [f h 8/ ,

V&VReview:h. -

] k/27k8.

Disposition Verified: _

Signature Date ]

'dr/120

_ _ - _ _ = _ - _ _ _ - _ _ _ _ _ _ _ _ _ _ _ . - _ _. 1

G s.

HOPE CREEK GENERATING STATION I 'SPDS V&V DISCREPANCY REPORT l

Discrepancy No: 85 Date:04 /15 / 88 Page I of l

References:

'CDM-0491-0, fig 5.2-1 I

Description:

Figure 5.2-1 shows the legend "TAF" instead of "-161" on the Y axis of the Reactor Level trend plot.

Disposition:

Figure 5.2-1 in DM-491 Rev 1 shows TAF and the basis is explained on page 5.2-9.

1 Disposition Prepared b : / 2 h/

V & V Review / k / 2.7 / 08

' (

Disposition Verified: / /

Signature

  • Date

i

't HOPE CREEK GENERATING STATION -

SPDS V&V DISCREPANCY REPORT Discrepancy No: 86 Date: 04 / 15 / 88-Page 1 of I

References:

CDM-0484-0, pg 3-41 i

Description:

The display feature described is not implemented in CDM-0491-0.

-I Disposition:

See discrepancy No. 269 DM-484 will be revised to DM-491 Rev. 1.

i Disposition Prepared b - / /

V & V Revie e h/ /

t

(

Disposition Verified: / / l

. Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 87 Date: ng /~15 ' / gg Page / of. /

References:

CDM-0484-0, pg 2-42

Description:

The display feature described is not implemented in CDM-0491-0.

Disposition:

DM-484 will be revised per DM 491 Rev.l.

f I

Disposition Prepared b - /29/ N V&VReview:b  !

/ d7 / 9E I

f. Disposition Verified: / /

Signature Date

L HOPE CREEK GENERATING-STATION

.SPDS V&V DISCREPANCY REPORT Date: 04 /15 /88

~

Discrepancy No.. 88 Page / of . /

References:

1) CDM-0484-0, pgs 2-19, 2-46, 1-11 2)-CDM-0491-0, fig 5.3-1 3)

Description:

The points 100, 140 and 380 psig are not implemented in the Reactor Pressure trend plot.

I Disposition:

Decision points of 1037 and 1071 psig are supported by the System and the basis given in DM491 Rev. 1. DM484 will be revised to -

reflect this.

Disposition Pre ed  : ['2kd V&V Review: 9/2.7[fd

(

.c '

Disposition Verified: _

dr/119 j

1 HOPE CREEK' GENERATING.'TATION S

SPDS'V&V DISCREPANCY REPORT I

Discrepancy.No: 89' Date: 04 / 15'/ ' 8 8 '-

Page / 'of 'l-l

. l

References:

.CDM-0484-0, pg 12-9

Description:

It identifies the iodine release trend plot as noble

. gas release rate.

Disposition:

DM 484 will be revised to reflect the iodine and, noble gas Trend Plots in DM491 Rev. 1.

a ,

~ Disposition Prepared b : /))' /2h/

V & V Review: / h / 87 / 9E-t Disposition Verified: / /

Signature. Date

1, 1 1

HOPE CREEK GENERATING STATION 4 SPDS V&V' DISCREPANCY REPORT l l

Discrepancy No: 90 Date: 04 /15 M8 I

Page I of I 1

References:

CDM-0484-0, pg 12-14

.CDM-0491-0, figs 5,1-12 & 5.10-1

Description:

The information processing results-identify Reactor Building HVAC status (r' Inning or not' running) as being necessary to support this decision funciton. This status is not implemented in the HVAC e:(haust radiation level.

Disposition:

The SPDS does not use HVAC status. The EOP entry is based on the radiation value regardless of HVAC running which is conservative. DM-484 will be revised to reflect this.

1 Disposition Prepared b : // / 2- /[

V&VReviewb' /N/

(

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION

)

.. SPDS V&V DISCREPANCY REPORT

!~

! . Discrepancy lNo: 91' Date: 04 / 15 / 88 Page / of f

References:

CDM-0484-0, pgs 9-13, 9-15

Description:

The display feature implemented in CDM-0491-0 is not-the display feature required by CDM-0484-0. (e. g.,

the 30 minute historical status was not implemented) 4 Disposition:

DM 484 will be revised to 25 minutes per'DM 491 Rev.1 which is adequate trending time.

i Disposition Prepare b *

/ [k/

V & V Review:

I (

/ E7 / hh Disposition Verified: / /

Signature Date

HOPE-CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 92 Date: 04 / 15 / 881 Page / of /

References:

CDM-0484-0, pg 9-11 CDM-04?l-0, fig 5.9-1

Description:

The display feature required by CDM-0484.is only partially implemented in CDM-0491-0. (e.g.,'the 30 minute historical status is not implemented).

.The' status identified in CDM-0484-0 is NORM / MAX NORM. In CDM-0491-0, the status.is NHI/HI.

Disposition:

DM 484 will be revised to DM 491 Rev. 1.

1 l

l Disposition Prepar b- /[h /

V & V Review: .

h / 27 / W Disposition Verified: __ p / /

Signature Date

I .

E HOPE CREEK GENERATING STATION

-SPDS V&V DISCREPANCY REPORT i

Discrepancy No: 93 Date: 04'/ 15/ 88 Page / of /

L e

References:

1 CDM-0484-0, pg 9-12

Description:

With respect to levels above the maximum safe operating value, the analysis described on page 9-12 will.not provide j the answer required by the decision function. No display-feature implemented in CDM-04910 will provide the required information.

Disposition:

DM-491 provides alarm condition if any Floor Water Level setpoint is exceeded which supports EOP 103. DM-484 will be revised.

1 1

l l

Disposition.Prepa d by_:_ /2/

V & V Review /b7 /O8

( (

Disposition Verified: / /

Signature Date .

f L HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 94 Date: 04 /15_/88 Page / _of /

References:

1) CDM-0484-0, pgs 9-15, 10-9,.10-10, 10-12
2) CDM-0491-0, fig. 5.9-1 3)

Description:

The decisions functions on pages 10-9, 10-10, 10-12 of CDM-0484-0 address temperatures relative to their "(maximum safe operating value)". The required display feature ('rable 9-2, page 9-15) contains no information indicating maximum safe operating temperatures. The display implemented in' Figure 5.9-1 of CDM-0491-0 contains the. max safe. operating temperatures.

Disposition:

DM-484 will be-revised to the. display features in DM-491, Rev. 1.

Disposition Prepared B : f' 2Ed V&V Review: k' 7!Pd' s

(

Disposition Verified:

_ ignature S Date

-dr/132

i HOPE CREEK GENERATING STATION SPDS'V&V DISCREPANCY REPORT Discrepancy No: 95 Date: 04 / 15 / 88 Page / o,f f

References:

CDM-0484-0, pg 10-8 CDM-0491-0,' fig 5.9-1

Description:

The display feature-required on page 10-8 of CDM-0484 does not agree with the display feature implemented in CDM-0491-0, Figure 5.9-1. (Figure 5.9-1 contains an-additional column listing the. MAX SAFE OP TEMP for each.

Reactor Building Room).

Disposition:

See discrepancy No 94.

Disposition Prepared by: h / N/

V&VReviewh a / 27 / W 1

(

Disposition Verified: / /

Signature Date .

HOPE, CREEK GENERATING STATION 5 SPDS V&V DISCREPANCY REPORT j

Discrepancy'No. 96 Date: 04 /15 /88 Page / of f

References:

1) CDM-0484-0, pgs 9-6, 10-6, 11-6
2) CDM-0491-0, pg 5.9-6, figs 5.9-1, 5.9-2 3)

Description:

Pages 9-6,10-6 and 11-6 of CDM-0484-0 identify a HVAC ISLN display-feature. Page 5.9.6, Figure-5.9-1 and Figure 5.9-2 implement a RBVS ISLN display feature with a status-indication 3~

of.CLSD/NCLSD. A discrepancy exists since the display feature.

implemented by CDM-0491-0 is different than that reguried by CDM-0484-0. .

Disposition:

The display function with basis given in DM-491, Rev. I will be incorporated in DM-484.

i Disposition Pre red B : 9-2k V&VReview:h. , 9.h.!J[

Disposition Verified:

Signature Date dr/133

t-HOPE CREEK GENERATING-STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 97 Date: 04 /15' / 88 Page / of /

References:

CDM-0484-0, pg 2-68

Description:

Page 2-68 references page 2-50 to address this decision

~ function. The correct reference-should be to page 2-53.

9 r

. Disposition:

DM-484 will be. revised and incorporate the correct reference stated.

i i

Disposition Prepared b : f/ /

V&VReview:bA,

/

f _h / Z) / $

Disposition Verified: / /

Signature -

Date

\

L;

~ HOPE CREEK GENERATING STATION l SPDS V&V DISCREPANCY REPORT L

l L Discrepancy No. 98 Date: Q4 /15 /88, 1

Page / of _ /

l

References:

1) CDM-0484-0, pg 2-67
2) CDM-0491-0, pg 5.2-12, fig 5.2-1 3) i

Description:

Page 2-67 of CDM-0484-0 identifies an OPEN MSIV display' feature which will provide the total number of MSIV's currently open.

Page-. 5. 2-12 and Figure 5. 2-1 of CDM-0491-0 describe an ..MSIV STATUS display (CLSD/NCLSD) of each MSIV. A discrepancy exists since the display feature required by CDM-0484-0 is not implemented.

Disposition:

DM 484 will be revised to the display contained in DM 491 Rev. 1 Disposition Pre ared y: _ kOM V&V Reviews .

k.!27!fd Disposition Verified:

Signature Date

.dr/118

____-_=____-__-_ _ _ _ . - .

l-HOPE CREEK GENERATING STATION

'SPDS V&V DISCREPANCY REPORT i

Discrepancy No: 99 Date:'4 / 15 7 88 Page / of f

References:

CDM-0484-0 -

EOP 102,.Rev. O Step SP/L-16

Description:

CDM-0484-0 does not contain an analysis of this decision function.

4 Disposition: DM-491 Rev. 1 and the system support'. margin-to limit values and alarms based on the Suppression Chamber Load Limit curve.

Disposition Prepared by: /W/

V & V Review b u ~

/27/ N

< (

Disposition Verified: / /

Signature Date

.s F i HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCYEREPORT i Discrepancy No. -100 Date: 04'/15 /88 Page / of- [

References:

1) CDM-0484-0
2) EOP 203, Rev. 0

'3) Step STC-4~

Description:

'CDM-0484-0 does not contain an analysis of th'is decision function.

I

'l Disposition:

l This decision is supported by displaying all RPV water levels as an alternate displayed value in B5007. If Rx water level cannot be deterbend this point will be question marks.

l.

l l

i l

Disposition Prepared By: h2//-

V&VReviewsb _

9, 7M l

(

Disposition Verified:

Signature Date dr/ll6

~

- HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: '101 Date: 04 / 1 s' / ng Page / of /

References:

CDM-0484-0 EOP 099 and 100

Description:

Decision functions in these EOP's are not analyzed in CDM-0484-0.

Disposition:

DM-484 will be revised to indicate the decision functions supported. The decision functions supported are currently contained in DM-491 Rev 1.

Disposition Prepar d b' : / /

V& V Review

'I (

h /_27 / bb Disposition Verified: / /

Signature

  • Date

T HOPE CREEK. GENERATING STATION SPDS V&V-DISCREPANCY REPORT Discrepancy No: 102 Date: 4 / 1s / 88

^

Page / of I'

References:

CDM-0484-0 EOP 104 and EOP 203 I

Description:

The analyses in CDM-0484-0 were based on Rev. 1 of these EOP's. The latest EOP's available for' review are Rev.0.

Disposition: DM-484 will be revised per the latest EOP revision which are incorporated in DM-491, Rev. 1.

i DispositionPreparedb:/ O /3 /

V&VReview:b 9 / 2.7 /N

/ ( i Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS V6V DISCREPANCY REPORT Discrepancy No: 103 Date: 8 / 26 /.88 Page / of' 'l

References:

CDM-0491-0 Database Analog Report #2

Description:

No drawing reference for points A8000, A8001,

-A7000 and A3014.

Suppression Pool Temp point drawing (fig.5.1-9)-

based on J-0625 Rev. 7 Disposition: Points A8000 and A8001 are for. future inputs and no design drawing exist at this time The drawing referenced were added to PS-J-0626 for the following' points:

A7000 A3014 h

~

Disposition Prepared by: / /

V & V Review d . -

7 /M7 / i i c Disposition Verified: / /

Signature Date j

__ = _

HOPE CREEK GENERATING STATIO24-SPDS V&V DISCREPANCY REPORT-Discrepancy No: 104 Date: -4 / 15 / 88 Page '/ of I

~

References:

CDM-0491-0 Database Digital Report #2

Description:

No drawing reference for points D3483, D3484, D5695, D5696, D8001, D8002, D8003, & D8004.

j Disposition: The drawing references were added to PS-J-0626 for the following points; D5695 D5696 D3483 D3484 D8001, D8002, D8003, and D8004 were originally reserved for UPS status but are deleted from the current revision of the DATABASE PS-J-0626 Disposition Prepared b : y / 2- /

V & V Review a

] k /577 / bd Disposition Verified:

[ /

/

Signature Date

HOPE CP.EEK GENERATING STATION SPDS V&V DISCREPANCY REPORT l

Discrepancy.No los Date: 4 / 15 / 88 l Page / of l

~

References:

CDM-0491-0 Database

Description:

No information is provided for RXXXX.(RMS) points Disposition: Current approved database has all required information for RXXXX points. Database document PS-J-626 Disposition Prepared b : /f/

V&VReview[3 ~L (

'& h /d 7 / N Disposition Verified: / /

i

HOPE CREEK GENERATING STATiDN SPDS V&V DISCREPANCY.REPCRT I i

. Discrepancy No:- 106 Date: '04 _/22 /_88 Page / of /- 1

-I

References:

NOVA-ATP-001A, Rev E

Description:

ATP Section 4.0, page 5 references Rev. 1 of~CDM-0491.

The approved revision is Rev. O.

Disposition:

See Discrepancy No. 166 Disposition Prepared -

/2h / O V&VReviewb / /

(

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION.

SPDS V&V DISCREPANCY REPORT Discrepancy No: 107 Date: 04 /22 . / 88 Page. I of /_

References:

NOVA-ATP-001A, Rev E

Description:

The reference matrix in the ATP - intended to cross-reference the SPT test sections with the appropriate sections of CDM-0491 l and the MMI- extends only through ATP Section 6.8.4. The STP contains sections through 6.31.

Disposition:

Enclosure E of M13-STP-003-4EC-1076 gives the total installed system Test reference matrix which supercedes the Nova Factory Acceptance Test.

l.

I Disposition Prepared b : ,,

@/ /

V & V Review: _ /[7/ 9B DispositionVerifiedh <

  1. h / 27 / @

Signature Date  ;

i

". FE CREEK 3ENERATING 5;AT :N SPOS 7&7 ::3CRIPANCY REPCRT Discrepancy No: 108 Date: 04 /22 88 Page / of /

References:

NOVA-ATP-001A, Rev E

Description:

, ATP Sections 6.22 through 6.27.l'.l.12 were apparently deleted. Since no Test Exception was identified,-

it is unclear if this testing has been deferred or cancelled.

Disposition:

These sections were deleted M13-STP-003-4Ec-1076, from9.13 Sections theand ATP9.12. and are tested in k

Disposition Prepared by . /b/

V & V Review b / _

h/2 / W Disposition Verified: djf w/ h/ 57 / bli Signatu[e ,

Date

1' l l HOPE CREEK' GENERATING-STATION l: SPDS.7&V DISCREPANCY REPORT i

Discrepancy No: 109 Date:-04 /22' /1 Page / of /

References:

NOVA-ATP-001A, Rev E

Description:

ATP Section 6.27.2.2 was apparently' inadequate or incorrect. No Test Exception is identified.

Disposition:

Test Exception 31 was written and this function was tested in M13-STP-003-4EC-1076 section.9.13.

Disposition Prepared by: LA / / N/ kb V-& V Review / /27/PR I Disposition Verifled

  1. f /[ h/2.~7 / N SignaktIre . Date 1

g ROPE CREEK GENEP.ATING STATION

i; , ,

'SPDS V&V-DISCREPANCY REPORT

!:c Discrepancy No 110' Date: 04 /22 ~/ 88 Page / of 'l .

y .

References:

NOVA-ATP-001A, Rev E

, :4.

Description:

t' ATP Sections 6.29 through 6 3' were apparently not performed. No Test Exceptions are identified.

Disposition:

These sections were tested via M13-STP-003-4Ec-1076 steps 9.3, 9.6 and 9.15.

I I

I l

Disposition Prepared b : A / 2k/ ((

V & V Review x / 87 / E'8  !

DispositionVerifiedO r h / d'7 / N Signa (ure Date

_ -- l

HOPE CREEX GENERATING STATICN ,

SPDS V&V DISCREPANCY REPORT _j

' Discrepancy No: 111 Date: 04 /22 / 88 Page / of I _

References:

)

k NOVA-ATP-001A, Rev E i

Description:

i 1

' 1 ATP Section 6.7.1.B; Referenced Figure 2-1 does not appear in CDM-0491-0.

Disposition:

Display Format tested in Section 9.2 of M13-STP-003-4EC-1076.

Disposition Prepared b : Af / 2 /

V&VReview.O '

k /87 / Ob i DispositionVerifiedb i/27 /8E I Signa [ure Date

l HOPE CREEX GENEPATING STATION 1

SPDS V&V DISCREPANCY REPCRT Discrepancy.No: 112 Date: 04 /22 /_l3_,

l Page / of /

References:

NOVA-ATP-001A, Rev E

Description:

Section 6.8.1 L thru Q; Refernced keyboard keys and i screen displays do not appear in CDM-0491-0, 2.2.1, 2.3.1 and 2.3-1.

Disposition:

I Display format and Man Machine Interface tested in M13-STP-003-4Ec-1076 g accordance with DM-491, Rev 1.

In Disposition Prepared -

J// 8/b /_M 1 V & V Review ff y[ k /27 / N DispositionVerifiedh h /87 / N

' Signat'ure Date a_-_____-_____--

(i j HOPE CREEK GENERATING STATION SPDS.V5V DISCREPANCY REPORT-Discrepancy No:- -113 Date: 04 /22- ') 1g_,

Page. / of .l.

References:

NOVA-ATP-001A, Rev E

Description:

Section 6.8.2.A thru I; Referenced arrow-keys do not appear'in CDM-0491-0, ligure 2.3-1.

9 Disposition:-

See Discrepancy No. 112.

l l

i l

Disposition Prepared by: ado f /2k / OO V&V. Review:b ,, / /27 /N

~

DispositionVerified:b /[ 9/ 27 /E I Signatbre . Date

l HOPE CREEK GENERATING STATION

.SPDS.;V&V DISCREPANCY REPORT-

-Discrepancy No: 114 Date: 04 /22 /_88 Page' / of /

References:

i NOVA-ATP-001A, Rev E Descript' ion:

.Section'6.8.3.C; ' Referenced keyboard key'"PT STATUS" does not appear in CDM-0491-0, Fig. 2.3-1 of Section 2.3.1.

Disposition:

See Discrepancy No. 111.

i I

i (i

Disposition Prep p k / bh /

V & V Review n /$7 Disposition Verifie M / E7 /Ef Signatbre Date

HOPE CREEK GENERATING STATION SPDS V6V DISCREPANCY REPORT Discrepancy No: 115- Date: 04 /22 / 88 -

Page l of l

References:

NOVA-ATP-001A, Rev E

Description:

CDM-0491-0, Fig. 2.3-1 and Section 2.3.1 - The following keyboard keys were not tested: TERTIARY DSPLY, PAGE FWD, PAGE BACK, DATA ENTRY BACK, DATA ENTRY FWD, TAB BACK, i TAB FWD, PRIMARY SPDS.

Disposition:

See Discrepancy No. 112..

l Disposition Prep . k / dh/M V & V Review n /27 M I Disposition Verifie /t 24W / b7 /

/ Signatdre Date

HOPE CREEK GENERATING STATION SPDS V&V. DISCREPANCY REPORT l

~ Discrepancy No: Date: 04/22 / 88

~

l- 116 Page / of /

References:

NOVA-ATP-001A, Rev E-

Description:

Sections 6.8.3.N and Q; Referenced keyboard keys "Back Space: and " Exec" do not appear in CDM-0491-0, Fig. 2.3-1.and Section 2.3.1.

Disposition:

See Discrepancy No. 111.

I

\

l Disposition Prepared  : [/ h/ /8 V & V Review A _ / d7 /

Disposition Verifie

/ / b7 / )

Signatu're Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY. REPORT 1 1

Discrepancy No: 117 Date: 04 / 22 /. 88 Page. / of' '/

. l

References:

NOVA - ATP - 001A, Rev. E 1

Description:

Sections 6.9.2, 3, 4, 5; Referenced CPS points B3001, 2, 3, 4, do not appear in CDM-0491-0, Fig.

5.4-1 or Section 5.4.4.

I Disposition:

See Discrepancy No. 209.

Disposition Prepared b : / /

V & V Review a /27 / E l

( l Disposition Verified: / /

Signature Date

_. _.- _-___- - ___ Q

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT.

Discrepancy No: lla Date: 04 / ?? / na Page. '/ o,f )

References:

NOVA-ATP-001A, Rev E

Description:

Sevtion 6.9.14; Point ID A2577'was not checked off.during testing. Was this point in the point status?-

l 1

l

-Disposition:

A2577 verified in B5007 point summary test in step 9.8.2.8 of M13-STP-003-4EC-1076. l I

l l

l

, Disposition Prepared by: f/h/

v s v Review hd 9 /2-7 / &

Disposition Verified O h /87 / N Signa (ure Date j

HOPE'CREEW GENERATING STATION.

SPDS V6V DISCREPANCY REPORT

~! ' Discrepancy No: 119 'Date: 04 /22 '/ 88 Page l- of (

']

References:

NOVA-ATP-001A, Rev E

Description:

Sections 6.10.5.A and 6.10.7.A; Points D5881 thru D5884 and D5889 thru D5892 do not appear in CDM-0491-0, database or on Figs. 5.2-1 and 5.3-1. Points D4924 thru D4931 not tested.

Disposition:

See Discrepancy No.171 l

Disposition Prepared b

  • h @ / 2k / E V & V Review a n / 27 / bh I

(

Disposition Verified: / /

Signature Date

h HOPE CREEK GENERATING STATION' SPDS V&V DISCREPANCY REPORT Discrepancy No: 120 Date: 04 /'22 /- 88 Page l of /

References:

NOVA-ATP-001A, Rev E

Description:

Section 6.10.16; Figure 5.9.1, CDM-0491 Di'gital points under " FLOOR WTR LVL CURRENT STATUS" not tested.

f l

.i Disposition:

See Discrepancy No. 111.

i l

Disposition Prepa /2 /M V & V Review. m /Z7/ 8T

' Disposition Verifie

/d7 /

Signa'ture Date

HOPE CREEK GENERATING STATION-SPDS V&V DISCREPANCY REPORT Discrepancy No: 121 Date: 04 /22 /88 Page / of / i

References:

NOVA-ATP-001A, Rev E ,

Description:

Section 6.27.1.3.6; B5070 calculation algorithm test rusults appears to show B5070 as sum of inputs.- 'Should be an average.

Disposition:

B5070 calculation test performed in section 9.13 of M13-STP-003-4EC-1076.

l Disposition Prepar by: / / ,

V& V Review: / N / [8 Disposition Verified h / N -/hh Signa (ure Date ,

HOPE CREEK GENERATING STATION 3 SPDS V&V DISCREPANCY REPORT i

Discrepancy No: 122- Date: 04 /22 / RR Page / o,f . /- i

References:

NOVA-ATP-001A, Rev E

Description:

CDM-0491-0, Section 2.2.1, para. 1;.The ability to bring up a secondary display by putting cursor in a parameter box and pressing the " execute" key _was not demonstrated in the Factory Test.

Disposition:

See Discrepancy No. llE, i

l Disposition Prepa . / /

V & V Review: _ / /

Disposition Verifie /* /b /

' Signa [ure Date j

. HOPE CREEK GENERATING. STATION-

.SPDS V&V DISCREPANCY REPORT Discrepancy Noi 04 / 22 /88 191 ~Date:

Page _l 6f l'

References:

NOVA-ATP-001A, Rev E

Description:

DELECTED - DUPLICATED IN DR.# 126.

Disposition:

.l I

I i

\

i Disposition Prepared by: // //87// f/[k/18 '

t V & V Review: / /

Disposition Verified: /V/g M k/2M/[2 Signature Date 4 L l

, HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT j

l Discrepancy No: 124 Date: 04 / 22' / 88 l Page [ of /

i

./ .

4 i

References:

i l

' NOVA-ATP-001A, Rev E l

i

Description:

CDM-0491-0, Pg. 2.2-3, pura. 4; The Normal / Alarm )

color coding philosophy for the units when using l

" insert value" mode was not demonstrated. l l

l I

i Disposition:

Insert value was used for test purposes only and not a system supplied function. All color coding l and priority was tested in M13-STP-003-4EC-1076 per l DM-491 Rev 1.

i I

l Disposition Prepared b : f/2k/

V & V Review / _

h / 27 /N Disposition Verified d u ] h / 27 / N Signa (ure Date

HOPE CREEK GENERATING STATION ie 'SPDS V&V DISCREPANCY REPORT Discrepancy No: 125 Date: 04 / 22 / 88 Page / -of_ /

References:

NOVA-ATP-001A, Rev E

Description:

CDM-0491-0, pg'2.2-3, para. 5; Using a tertiaryidisplay .

key to bring up parameter curves was not demonstrated.

l Disposition:

See Discrepancy No. 111..

l Disposition Pr a  : y / /

V & V Revie : r /bY/

Disposition Verified /[7 /

7 Signakure -

Date

E, H PE CREEK GENERATING STATION

' SPDS V&V-DISCREPANCY REPORT Discrepancy No:- 126 Date: 04 / 22 / 88-t Page / of /

L

References:

NOVA-ATP-001A, Rev E

Description:

. CDM-0491-0, Pg. 2.2-3, para. 2; The function described was not included in factory test.

Disposition:

This-function tested in M13-STP-003-4EC-1076.

l l

Disposition Prepa db: h/ /b V& V Review / h /27 /bb Disposition Verified:O k /d7 / N Signature Date

-=_2-____-_. _ _ _ - _. >

8 HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 127 Date: 04 / 22 / 88 Page / of /'

References:

NOVA-ATP-001A, Rev E

Description:

CDM-0491-0, Section 2.2.3, para. 3; The "L***" on

" Margin to Limit" table displays was not demonstrated during factory test.

Disposition:

^

MARGIN TO LIMIT L*** was tested in M13-STP-003-4EC-1076 Section 9.12.

l L

I Disposition Prepa b: ! f / 2k/

V & V Review- f / Z7 / N Disposition Verified h , d h /2.7 / N I- Signa (ure Date

]

HOPE CREEK.dENERATING' STATION SPDS V&V DISCREPANCY REPORT Discrepancy.No: 128 Date: 04 / -22 /88 Page /~ of /'

References:

NOVA-ATP-001A, Rev E

Description:

CDM-0491-0, page 2.2-10, para. 2; Inserted value feature not tested during factory test. ,

1 9

Disposition:

V See Discrepancy No: 2690 Disposition Prepared b : / 2- / i V & V Review

/N/

, t Disposition' Verified: / /

Signature -

Date

HOPE CREEK GENERATING-STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 129 Date: 04 / 22 / 88 Page / of -/

References:

NOVA-ATP-001A, Rev E

Description:

CDM-0491-0, Section 2.3.3; SPDS trouble alarm output capabilities not checked in test.

Disposition:

This function tested in section 9.6 of M13-STP-003-4EC-1076 l

Disposition Prepared b - f/ /

V&VReviewb / / 27 / N Disposition Verified f h /27 / E I Signatbre Date

i HOPE CREEK GENERATING' STATION SPDS V&V DISCREPANCY REPORT <

L l

Discrepancy No: '130 Date: 04 /22 68 Page / of /_

j-

References:

NOVA-ATP-001A, Rev E

Description:

CDM-0491-0, Figure 2.3-2; Except for verifying its existance'this display not tested in factory test.

l Disposition:

This display tested in section 9.6 of-M13-STP-003-4EC-1076 Disposition Prepar d -

h/ 2k / [

V & V Review _

@ /,2 7 / 2P j

. Disposition Verified [ h/27 / 88 Signature Date ,

j HOPE-CREEK' GENERATING' STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 131' Date: 04 / 22 / 88 Page / of /

References:

NOVA-ATP-001A, Rev E.

Description:

CDM-0491-0, page 4.2-3, para. 2; These Trend-graph.

features not tested.

Disposition:

Trend graphs tested in section 9.10 and 9.11 of M13-STP-003-4EC-1076.

f Disposition Prepar by_:

9 / 2k/

V & V Re. view b /27 /d Disposition Verified b d h /77 /d l

Signat[re .

Date

l HOPE CREEK GENERATING STATION

=

SPDS.V&V DISCREPANCY REPOP.T dscrepancy No. 132 Date: 04 /22 /8_8,8 Page / 'of /

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

3)

Description:

Test Exception #1 6.8.1C Response required < 4 sec per DM-491 sec. 2.3.2. Actual time 4.8 sec.

Disposition:

Modified Display's static portion to meet required 4 sec update.

l l

Disposition Prepared By: f*2k- 2 V& V Review: _ _ !27!Oh Disposition Verified:

/Signatbre as/ '

/2 !f8

'Dat d

/~

rs/28 l

HOPE CREEK GENERATING: STATION SPDS V&V DISCREPANCY-REPORT Discrepancy No. 133 Date: 04 /22 /88 Pag e / of / q

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) i 2) 3)

Description:

Test Exception #2 6.8.1G Response required < 4 sec per DM-491 sec 2.3.2. Actual time 4.7 sec.

Disposition:

Modified Display's static protion to meet required 4 sec update.

Disposition Prepared By: h"dkd[

V& V Review: 44 u a bb Dispositio." Verified:b 7'Datb 27 2f 7Si~g n attTr e [

rs/29

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 134 Date: 04'/22 /88 Page / of )

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

3)

Description:

Test Exception #3 6.8.2I should have tabbed to B5007, actually tabbed to B5098.

l 1

Disposition:

Corrected cursor tabbing test in ATP (see replacement text #2)

Disposition Prepare y: I-2/8 2[ MM V& V Review: , M, . .

Disposition. Verified:

Signature Date rs/30

HOPE CREEK GENERATING STATION SPDS. VGV DISCREPANCY REPORT _l I

Discrepancy No. -135 Date: 04 /22 /8_8 Page l of l 4

References:

1) NOVA-ATP-001A, Rev. E, (l/25/88) 2)

.3)

Description:

Test Exception #4 s

6.8.3H)Value of A2574 is thru currently has

"???" 6.8.36)

Disposition:

Corrected by addition of step G.1 (see additional tegt #3)

Disposition Prepared B : h-2M,((

V& V Review:

I

( I 27 EI s

l Disposition Verified:

Signature Date rs/18

[

j; l: HOPE CREEK. GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 136 _

Date: 04 /22 /88 Page / of l

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)
3) i

Description:

Test Exception #5 6.8.30)B5007 value was entered and " unknown function" was not echoed.

j-Disposition:

i ATP corrected to observe " Data input not valid for this field" (see replacement test

  1. 5)

Disposition Prepared By: V/ f* 2k V& V Review f[ N

/ /

Disposition Verified:

Signature Date rs/19

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 137' Date: 04 /22 /88 Page / of f

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

3)

Description:

Test Exception #6 6.9.13 Text description does not' match database  !

6.9.89. 6.9.142,-6.9.159, 6.9.169 j' 6.9.89A, 6.9.144, 6.9.167 6.9.170 6.9.116, 6.9.145, 6.9.-168

, 6.9.38 i i

Disposition:

Made all modifications listed in appropriate files and rebuilt the DB Disposition Prepared By:_ fa 2k-[

V& V Re.iew:

i f!2.7 <

f Disposition Verified:

Signature Date I

1 rs/20

I HOPE CREEK GENERATING STATION i

SPDS V&V' DISCREPANCY REPORT l

l l

Discrepancy No. 138 Date: 04 /22 /88 Page / of I

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

3)

Description:

Test Exception #7 j r

BAT DBExist printout contained point B2477 which is not in DM-491 DATABASE and not accessible thru PIEP step 6,10,lB, also B2479, B8008.  ;

Disposition:

Batch file DBExist recreated from PSE&G.

Dbase III database.

Disposition Prepared B

  • Uk V& V Review: & f/27!9b Disposition Verified - f 27 P8 Signaturq( Dhte rs/21 f

' HOPE CREEK GENERATING ~ STATION-SPDS V&V. DISCREPANCY REPORT Discrepancy No. 139 i Date: 04 /22 /88 Pages / or /

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

3)

Description:

Test Exception #8-1-

6.11.lB) Rx Power not displayed to one decimal place, Drywell Temp is displayed to-one decimal place, Also 6.ll.2A.

i Disposition:

Rx power will be displayed to nearest integer. DM491 will be updated. Software corrected for Drywell Temp. Steps.were retested sat.

Disposition Prepar B -

Nb ,

R& V Review: 27!N Disposition verified:

Signature Date i

rs/22 l i

HOPE CREEK. GENERATING STATION

,- SPDS V&V DISCREPANCY REPORT I

1 i-Discrepancy No. 140 Date: 04 /22 /88 Pag e ) of ]_

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88)

.2)  !

3)

Description:

Test Exception #9 l.

6.11.lc) Radiation vaues not display correctly, value was .,100E+03 vs 1.00E+2 6,11D) value displayed as .990E+02 vs 99.0 6.ll.lE, 6.ll.lF, 6.11.2A Disposition:

i Software corrected to display scientific notation in the format of X.XxE+xx.DM491 updated to show all radiation values in scientific notation IAW plant instrumentation. Retested steps sal Disposition Prepared B : 8-2/

R& V Review: x ~

f f/< u t j Dispos.1 tion Veresied:

~ 11gnature

-> Date rs/23 j

HOPE CREEK. GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 141 Date: 04 /22 /88 Page l of l

References:

1) NOVA-ATP-001A, Rev. E, ( 1/25/8'8 )

2) 3)

Descrip' tion: Test Exception #10

-6.11.2B) Digital points did not change from green to red 9

Disposition:

Section 6.11.2.2 added to test digital-alarms (see replacement test #14)

Disposition Prepared B : 9 29-8 V& V Review: _W WE7!88 i

( '

Disposition Verified:

Signature Date rs/24

_________.m__.--m____i-_----- - - - - - - - -

-HOPE CREEK GENERNTING STATION

' SPDS .V&V DISCREPANCY REPORT 4

2 Discrepancy No. 142 Date: 04 /22 /88 Pag e /- of l-

References:

- 1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

3)

Description:

Test' Exception #11 6.10.19J) Card slot in TEST CARD RACK is defective, cannot access these points.

Disposition:

Repaired card slot, r et es t ed -. s at .

~

.- i l'

' Disposition Prepared B -

-8 V& V Review: 9278'I Disposition: Verified a 2 f8

( Signaturfe ' Dat'e rs/25

HOPE CREEK GENERATING STATION l SPDS V&V DISCREPANCY REPORT Discrepancy No.__ 143 Date: 04 /22 /88 Page / of /

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)
3) .

l l

Description:

Test Exception #12 l

e 6.11.3.1B B8106 did not change to green value on while background, A2280 changed to  ;

white value on black background and not question marks.

Disposition:

Software corrected, retested sat.

Disposition Prepared B

  • k~2k V& V Review: J 27/8f Disposition Verified

( Signature /

8 2.7[n Date rs/17 26

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REFORT Discrepancy No:- 144 Date: 88 04 / 22 /

Page / of /

References:

NOVA- .atp-001 a, Rev E, 1/25/88 -

Description:

Test Exception #13 6.11.3.lC B5070 displayed as white question marks Disposition:

The software was corrected and point retested satisfactory.

l L .-

Disposition Prepa db: .. / /

V & V Revie : _ k / 27 '

L Disposition Verified:

e h / 2 7 / hIf f Signatu[e Date L .I

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 145 Date: 4 / 2 2' / 88 -

4 Page / of /

l

References:

1) NOVA-ATP-001A, Rev. E (1/25/88) 2)

3)

Description:

Test Exception #14 6.ll.3.lM T8013 was not shown as invalid (white question marks)

.value was "YES".

Disposition:' Test corrected. See replacement text #15 in ATP.

I Disposition Prep d  : .

/ f/ N-/ 8 V & V Revie -

/27/2h

~l i I Disposition Verified: / / j Signature Date

l HOPE' CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT j Discrepancy No: 146 Date: 4 / 22 / 88 Page. I pf l

~

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

3)

Description:

Test Exception #15 6.ll.3.lT T2395 was not shown as invalid'(white questions marks) 6.ll.3.1V, 6.ll.3.lW.

i Disposition: Test corrected. See replacement text-#15 in ATP.

Disposition Prepar d -

y @/d/M V & V Review-

/ 2.7 / h8

/

Disposition Verified: / /

Signature Date

l HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT' ,

1 Discrepancy No: 147 Date: 4 / 22 / 88 Page- / of- /

eferences: NOVA-ATP-001A, Rev. E-(1.25.88) 1)

2) 3)

Description:

Test Exception #16 6.ll.3.lK a) When system was powered up inputs did not return. Buss voltage floated up. Installed 1000 resistor across input of analog, inputs and performed test step satisfactorily. This is a hardware problem that need f,ollow up with CPI.

Disposition: This problem exist only with the l test setup and has not been observed  ;

with field installed multiplexer and terminated inputs. This exception  !

l cleared based on performance of M13-STP-004-4EC-1076.

i Disposition Prepared  : [ O /2/

V & V Review -

/ d7 /&

Disposition Verified W /E7 /

Signakure Date

_ _ _ _ _ _ _ _ _ _ _ _ _ - _ d

I

, HOPE CREEK GENERATING STATION I SPDS V&V DISCREPANCY REPORT _

1 Discrepancy No: 148 Date: _

4 / ' 22 - / 88 Page. / of f

'4  !

References:

1) NOVA-ATP-001A, Rev.'E, (1/25'/88)  ;

2)

3) 1

Description:

Test-Exception #17 6.12.1.C) 5) Suppression chamber pressure is displayed to one decimal place 6.13.1.C)1).

Disposition:- Modified display format for.SC Press to display up to 1 decimal.

)

l l

,)

l Disposition Prepa d * [ /[ /

V & V Review- '

h /[ /

Disposition Verified:

t n [ /87 / 9P Signa [ure Date

HOPE CREEK' GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 149 Date: 04 /29/88 Page / of f

References:

1) NOVA-ATP-001A, Rev. E., (1/25/88) 2)
3)  ;

==

Description:==

. Test Exception #18 6.12.4C) Trend line was below red alarm line yet the tr'end was displayed in yellow.  ;

Disposition:

Trends will be tested by M13-STP-003-4EL-1076 (Ref. CRIF #18) l Disposition Pre ared B : Y'/M V&V Review fd7!@

Disposition Verifie a B 7 27 ,

( Sig~natur{ ' Ddt e -

rs/1

HOPE' CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT r.

Discrepancy No.- 150 Date: 04 /22 /88 l

Page / of f

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

3) l

Description:

Test Exception #19 6.13.1A) SP LVL PT is B5040 It should be B6260 1

i Disposition:

Changed SPLVL pt from B5040 to-B6260 in all appropriate displays Disposition Prep ed  : @"2YM V&V Review: 2-7 Disposition Verified u 72/

' Date 8h

( Signaturd r

rs/2

E ]

lc 't t

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy.No.- 151 Date: 04 /22 /88 Page / of f

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

3)

Description:

' Test. Exception #20 1

6.13.1A) Screen has "RX" for reactor vessel should have "RPV" Disposition:

Made all approrplate changes of RX RPV where' applicable Disposition Pre e  : h i'1b V&V Review / _

f 87 Disposition Verifie

-( Signaturgf d 27

'Dath rs/3 l

HOPE CREEK GENERATING STATION l

SPDS V&V DISCREPANCY REPORT Discrepancy No. 152 Date: 04 /22 /88 Pag e, / . of /

References:

1) NOVA-ATP-001A, Rev. 3, (1/25/88)

~2) 3)

Description:

Test Exception #21

'6.13.1C)7) Drywell and Suppression Temperature are displayed to one decimal place 6.14.1.C)5)

Disposition:

Modified display format for Dh5ST to displays 1' decimal Disposition Pre ed  : - & .

Ta2Y V&V Revie : x f!27 28 DispositionVerifiedh j N Signature ( 'Date i l

i

.rs/4

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 153 Date: 04 /22 / 88 Page / of (

References:

NOVA-ATP-001A, Rev E (1/25/88)

Description:

Test Exception # 22 Condenser Vaccumn is displayed as an integer.6.13.lC)8 1

Disposition:

Change all condenser vaccumn points display format to display 1 decimal.

Disposition Prepa d  : -

/dk/

V & V Review _ /b/

DispositionVerifiedh a / k /2 7 / 88 Signatbre ,

Date i

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy.No. 154 Date: 04 /22 /88 Page / 'o f /

References:

1) NOVA-ATP-001A', Rev. E, (1/25/88) 2)

3)

Description:

Test Exception #23 6.27.1.3.7 T T8013 is. red in alarm when point.says yes Disposition:

All digital Tag Sets are verified in M13-STP-003&4 4EC-1076 per database requirements in PS-J-0626 (See CRIF #21) 1 l

Disposition Pre red y: A kN V&V Review _

87!b8 Disposition Verified h h / 2 b

/ Signature ( Date(

U.. -_- ___naliL

.t .

HOPE CREEK GENERATING. STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 155 Date: 04 /22 /88 Page /- of /

References:

-1) NOVA-ATP-001A, Rev. (1/25/88) 2)

3)

Description:

Test Exception #24 Suppression chamber pressure graph is displayed as 0-200 PSIG, should 1 be -5 to 250 PSIG 6.15.4, 6.15.1 j 6.17.lA) 6.16.1, 6.16.4 Disposition:

Changed axis of graphs and associated programs to trace SC Press from -5 to 250 PSIG.

l Disposition Prepared By: ,

$~$

V&V Review: k Disposition Verified /f L A -

Da te I signature (

rs/7

NCPE CREEK GENERATING STATION SPDS V&V' DISCREPANCY REPORT Discrepancy No:

156 Date: .04 /22 '/1 Page / of l

References:

l I.

NOVA-ATP-001A, Rev E (1/25/88) I

Description:

Test Exception # 25 i

B6019 changed to white question marks instead of green on black. Step-6.16.2C.

4 Disposition:

Alarm priority to be tested during M13-STP-093-4EC-1076.

\

i Disposition Prepared b : I h /h/h V & V Review: n -

/ /27 /bb DispositionVerified:b [ h /27 / 2I Signabure .

Date

- _ _ - _ _ . - _ _ _ _ _ . _ -_ ._ -_-_ a

HOPE' CREEK GENERATING STATION SPDS V&V DISCREPANCY-REPORT l

,1 i

l

)' ,

. Discrepancy No: 157 Date:'04 /22 / 88 i l i, . ,.

r,.

Page / of ~/

t  ;

~

References:

NOVA-ATP-001A, Rev E - (1/25/88 )

I Description':

Test Exception # 26 DAPA channel-'R6035 did not. change to green on black.

Disposition:'

Alarm priority to be tested during M13-STP-003-4EC-1076.

Disposition Prepared  : [ k/Sk/[

V & V Review _ /27/ ,

DispositionVerifiedbu

, h/27 /

Signatbre Date

1 HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 158 Date: 04 /22 /88 Page / of /

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 21 3)

Description:

Test Exception #27 Step 6.17.1 "SC Level" should be "SP Level", "hX Press" should be "RPV Press" Disposition:

Changed the description that is displayed for "SC" to "SP" and "RX" to "RPV" Disposition Prepared By: f _

"[k V&V Reviews /.7 2 8 Disposition Verified: 9!27!P[

' Signatur( 'Dat e rs/10:

I

< HOPE CREEK GENERATING STATION i' SPDS V&V DISCREPANCY REPORT Discrepancy No. 159 Date: 04 /22 /88 Page /. of_/

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)'

3)

Description:

Test Exception #28 6.17.2 PTS B8032 and B8037 will not display a 5 place interger. Remove decimal and display as 5 plac-e interger..

Disposition:

Changed display format for B8032 & B8037 to display both pts as intergers

^

Disposition Prepared B : fMJ 9a2V V&V Review: 47!PI Disposition Verified

/ Signature /

] !d

'Da t'e rs/11

i

' HOPE CREEK GENERATING STATION SPDS'.V&V DISCREPANCY REPORT-Discrepancy No. 160 Date: 04 /22 /88 Page /. of f

References:

-1) NOVA-ATP-001A, Rev. E, (1/25/88)-

2):

3)

Description:

Test Exception #29 6.17.2' Batch File for SPLCDAT does not exist. SPLCDVT, B5040TT, SPTAVAL, SPTCDAT, SPTCDVT, B5084TT,.

RBDAVAL, RBDDVAL/ RBCDAT, SPTCDVT, RBCDTT Disposition:

All files created during and shortly after ATP Disposition Pre are  : k-2k((

V&V Review & P#

t

( < s Disposition Verified:

Signature Date rs/12

-HOPE CREEK' GENERATING STATION

. -SPDS V&V. DISCREPANCY-REPORT F

,i Discrepancy No. 161 Date: 04 /22 /88

.Page /. of /'

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

.3)

Description:

Test Exception #30 6.21.2 Batch File for PCIDAT is incorrect.

I, T point's will not cyle unless BACH is running. BAT file needs,to be rewritten to set field inputs.

. Disposition:

Batch file modified to set inputs and ATP corrected-to resume BACH (see replacement text #32)

Disposition Prep e  : h-2k-g V&V Review -

/

U t

(

  • Disposition Verified:

Signature Date rs/13

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 162 Date: 04 / 22 /88 Page / of_ /

References:

NOVA-ATP-001A, Rev. E (1/25/88)

Description:

Test Exception #31 6.27.2.2 Batch File for B8118T does not match the procedure. . Values and expected results are not in accordance with procedure.

Disposition:

the batch file was modified to yield correct result.

1 Disposition Prepar b: A k / 2h/ 38 V & V Review _ A k /[7 /b 8 ~

/ (

Disposition Verified: / /

Signature Date

HO"E CREEK GENERATING STATION-4 SEDS V&V DISCREPANCY REPORT y _ Discrepancy No. 163 Dat'e : 04-/22 /88' Pag e / o'f , )

. 6

References:

1) -NOVA-ATP-001A, Rev._E, (1/25/88)~
2) >

3)

Description:

Test Exception #32 6.27.'1.3.19 Batch File for B5007. ATP mod i'f i ed .

Disposition:

Batch file changed to initialize and-change -inputs to B50tI7 ATP modified (see replacement text #38)

Disposition Prepared B : kd '

V& V Review A - 9!WI I

f (

Disposition Verified: _

Signature Dit.e i

rs/15 f

_ __ j

I HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 164 Date: 04 /22 /88 Page /- of l

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88)
2) 4
3) .l f

Description:

Test Exception #33

6. 28. A hhen PACE is initialized with a field input at 0 eng. value the point will not alarm even though.the value is below the alarm. -

Disposition:

This problem fixed.

See CRIF #25 l

Disposition Prepared By: Ya2/d]

V& VReview:b C( f 7'/!N

(

{ f '

Disposition Verified:

Signature Date rs/16 i I

l

\

. t.

HOPE CREEK. GENERATING STATION

  • SPDS VSV DISCREPANCY REPORT Discrepancy No, 165 Date: 04 /22 /88 Pag e / of I

References:

1) NOVA-ATP-001A, Rev. E, (1/25/88) 2)

3)

Description:

Test Exception #34 s

6.28 Batch File for B50070TT is incorrect for test intent Disposition:

B5007 Trend Test performed by M13-STP-003-4EC-1076 successful completion of'this test will ensure B5007 trend operability.

Disposition Prepared B *

[ "

f'2k[

v s v Review d h / dyh2 Disposition Verified O s/ E 85

' Signatur( ' D a t'e rs/17 1 1

E--__-_________'_______ __ __

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: .

166 Date: 8 / 26 / 88-Page / of f

References:

1) Preop Test M13-STP-004-4EC-1076, Rev.0 2);

3)

Description:

Section 2.1.l' lists-Design Memoranda H-1-RJXX-CDM-0491, Rev. 1 as a reference.-The latest revision available to the V&V team is-Rev. O.

l Disposit. ion: Rev. 1 of DM-491 will be issued after~all test j comments are received. At that time it shall be reviewed to ensure completed testing is not affected, i

I Disposition Prepared b : ,

/ /

V & V Review: '

/

h /d) /N

' Disposition Verified: / /

9"" "#* "*

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 167 Date: 8 / 26 / 88 Page / of  ;

References:

1) Preop Test M13-STP-004-4EC-1076, Rev. 0 2) 3)

Description:

Acceptance Criteria 6.6 through 6.11 state that a '

various functions of the system meet tolerances or requirements specified in the procedure. The test procedure is not a design document, therefore, these criteria should reference design documentation. i Disposition: Tolerances were derived from vendor manuals for the MUX /DEMUX configuration. These mancals are listed under referrace 2.12 of the test procedure. The overall system tolerance is also given in section 3.0 of DM-491.

i l

i l

Disposition Prepar d b : / /2k/

V & V' Review i t

/27 /Pk Disposition Verified: / /

j Signature Date

--.I

HOPE CREEK GENERATING STATION SPDS'V&V DISCREPANCY' REPORT Discrepancy No: 16R Date: 8 / '26 / 88 Page / . of '/

References:

1) Preop Test M13-STP-004-4EC-1076,.Rev.0 2) 3)

Description:

Steps 9.1.4.1.and 9.2.4.1 state that CRIDS may be used to verify SPDS point in PIU 10, only. Per Enclosure A and E data sheet, several SPDS '

I points in cabinet 9 were verified with CRIDS.

Disposition: The procedure had a typo in step 9.2.4.1, PIU 10 should be PIU 9. This typo;has been corrected on the original document.

,l l

Disposition Prepared b -

/ / /

V & V Review: / E7 / h h Disposition Verified k/27 / N l .-

Signat[re Date j

HOPE CREEK GENERATING STATION I SPDS V&V DISCREPANCY REPORT l

l

-Discrepancy No: 169 Date: 8 / 26 / 88 j Page / of /

References:

1) Preop. Test M13-STP-004-4EC-1076, Rev. 0 2) 3)-

Description:

The data' sheets in-Enclosures A and E indicate that CRIDS was frequently used to verify the indication of an SPDS point. Since CRIDS data is supplied from the SPDS, this verification technique is invalid since it only requires that SPDS agree with itself.

Disposition: CRIDS was used for MUX 9 and 10 only. The SPDS and CRIDS computer read and process the inputs for these points completely independent on one another.

1 4

Disposition Prepa ed b : k /1k /

V & V Review h/N/ k Disposition Verified

h. 9/E7/9fr Signatdre Date '

HOPE CREEK GENERATING STATION l' )

'SPDS V8V DISCREPANCY REPORT Discrepancy No: 170 Date: 8 / 26 / 88 Page / .of f

' Re f e rence's : 1) Preop Test M13-STP-004-4EC-1076, Rev. 0 2) 3)

Enclosure A Data Sheets are not included for the

~

Description:

following analog inputs. (Ref. CDM-0491, Rev. O, Att, B and DCP 11, ODCN I216/0)

A9300 A9835 thru A9838 A9304 A9840 thru A9846 A9826 thru A9832 I

I Disposition:' These points are transmitted via a data link from the VAX computer and do not have specific voltage inputs. They are tested in M13-STP-003 4EC-1076.

I l

Disposition Prepa b -

/ 2k /

V & V Review / d7 / 99 l Disposition Verified x h/27/bb

' Signatbre Date l ,

1 J

HOPE CREEK GENERATING STATION j

_; SPDS..VSV DISCREPANCY REPORT J

)

Discrepancy No: - 171 Date: 0

/

26 7

88' -

Page / of / l 1

References:

1) Preop Test M13-STP-004-4EC-1076, Rev. 0 2) 3)

Description:

Digital points D4924 thru D4931 and D8001 thru D8004, do not appwar in DCP.ll, ODCN I216/0/

(Ref. CDM-0491, Rev. 0, Att. B).

Disposition: Point D8001 thru D8004 were deleted as this information is transmitted directly via the UPS Data Link. Points D4924 thru D4931 were corrected to D5881 thru D5884 and D5889 thru D5884. All this information is in approved .

drawing PS-J-0626 " Hope Creek SPDS Database".

The Att. B database in DM 491, Rev. 1 has been deleted.

Disposition Prepa b -

Y/N/

l V & V Review A . Be,//

(

k /_ / l Disposition Verified: / /

Signature Date

[

h. a

)

L L

. HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT l '

' Discrepancy _No: 172 Date: 8 / 26 / 88 Page / of I

References:

1). Preop Test M13-STP-004-4EC-1076, Rev. 0 2) 3)

Description:

Procedure steps 9.1.4 and 9.2.4 do not adequately verify point overlap for points in cabinets 9 and

10. During system installation, signal terminations in MUX's 1-8 remained undisturbed. All signals in MUX's 9 and 10, however, were reterminated. The i data recorded in Enclosures A and E-(for cabinets 9 and 10) do not provide sufficient information to verify that the correct sensor is ' connected to the slot and channel listed on the data sheet.

Disposition: Exisitng CRIDS cabinet inputs that supply MUX's 9 and 10 were not disturbed during construction except for the Drywell Temp Input. These inputs were tested by cable' checks and loop test under DCP 2, 3, 10 of DCR 4EC-1076.

I i

i Disposition Prepared b : / /

V & V Review -

/N /

Disposition verified d h/ 27 /NI l Signa [ure Date

f HOPE CREEK GENERATING STATION

.SPDS V&V DISCREPhMCY REPORT Discrepancy No: 173 Date: 8 / 26 /' 88 Page / of l

References:

. 1) Preop Test M13-STP-004-4EC-1076, Rev.0 2) 3)

Description:

Multiple discrepancies exist between CDM-0491, Rev. O, Att. B, DCP 11, ODCN 1216/0.and Enclosure

~

A regarding. alarm type (i.e. Hi/Hi/Hi or Lo/Lo/

Lo);-alarm value; and sensor / process values.

Disposition': ODCN I216 is the SPDS approved database.

The database in DM-0491, Rev. 0'is deleted in DM-491, Rev. 1. Changes that occured between the two databases were documented-as test exceptions during NOVA-ATP-001 or on Change Request Information Forms per DM-0599.

Disposition Prepared b : / 2- /

V & V Review '

/ 27 / b i i Disposition Verified: / /

Signature Date l

' HOPE CREEK GENERATING STATION.

SPDS V&V DISCREPANCY. REPORT Discrepancy No: 174 Date: 8 / 26 ' / '88 Page / of I' 1 l

l

References:

1) Preop Test M13-STP-004-4EC-1076,'Rev.0 2) 3)

Description:

CDM-0491, Rev. O, Att. B; and DCPll, ODCN'1216/0 show high and low reasonable limits for analog values. No basis is provided for.how these values were determined.

Disposition: High and' low limit failure are hardware limited at 2% and documented in DM-0491, Rev. 1 and existing CPI vendor documentation.

l Disposition Prepared b : [ ' , ' /2h /8h V & V Review a f- /[7 / bh I (

Disposition Verified: / /

Signature . Date

l HOPE-CREEK GENERATING STATION j

'SPDS V&V DISCREPANCY REPORT u i Discrepancy No: 175 Date: 8 / 26 / 88 I Page / of 1 I i i

References:

1) Preop Test M13-003-STP-004-4EC-1076, Rev. 0 la 2)
3) ,

i l-

Description:

In enclosure A, high and low reasonable limit values are identified as instrument failure values and are given with sensor units vs.

process units.

i

)

i j

u Disposition: The high and low reasonable limits are the limits which the instrument is considered invalid (failed).

The sensor units were the best method of determining.

the exact failure as M&TE equipment can be used to verify the exact voltage. The low failure condition must be verified by a voltage value since -- ]

the process value is zero clamped.

t l

i I

Disposition Prepared by: / /

V & V Review / 27 / bb Disposition Verifie h/ [7 /

Signat<ure Date

3:

l l,x t

! u g:.:

HOPE CREEK GENERATING STATION M[?i; SPDS V&V DISCREPANCY REPORT Discrepancy No'. 176 Date: 08 /26 /88 Page /, of l

References:

1) Preop Test M-13-STP-004-EC-1076, Rev. 0 2) 3)

J

Description:

Test Exception #1 Step 9.1.2.4A 3) added in procedure to verify contact normal-green status and contact abnormal red status for SPDS points l

. Disposition:

Add step in procedure body which was'omitted l.

during procedure typing.

Disposition Prepared B : -2k V & V Review: rQfd' E7 P[I Disposition Verified 2./ 27[W

' Signatute ' 'D a t'e rs/31

t

HOPE CREEK GENERATING STATION SPDS V&V. DISCREPANCY REPORT s,.

Discrepancy'No. 177 Date: 08_-/26 /88

- Pag e / ~- of /

References:

1) Preop Test M-13-STP-004-EC-1076, Rev. 0 2) 3)

Description:

Test Exception #2 Step 9.1.2.2, 9.1.2.3-16 channel digital test fixture.must plug into surge  ;

suppression card for 8 channel digital i cards.- Also must'use switches 8 thru 15 correspondence to channels 1 thru 8.

Disposition:

Add note in procedure body to plug 16 channel test fixture into input of surge suppression card for 8 channel digitals.

Also add use switches 8 thru '15 for I simulation 120VAC of channels 1 thru 8 Disposition Prepared B :  ! ~

V& V Review , f 27 [ l Disposition Verified 27 [f

'Dath Signaturh rs/32

e s HOPE CREEK' GENERATING STATION ,

i SPDS V&V DISCREPANCY REPORT Discrepancy No. 178- Date: 08 /26 /88 Page /. of /

References:

1) Preop Test M-13-STP-004-EC-1076, Rev. 0 2) i 3) l

Description:

_ Test Exception #3 Change 08000 to slot 11 channel 7 (BDIFile only) change descriptions.

D7037 " Torus WRT clnup ISLN VLV MV-4681 D7035 " Torus WTR clnup ISLN VLV MV-4679' D3638, 03640 change loop to LP D7034, D7036, change " cleanup" to "clnup" to "clnup D7130, D7131, D7139 Take out "VLV" D4992 Take out "VLV" D7046, D7047 Take out "VLV" D7100 Take out " " in HV-514 -

MUX 1 and 2 slot 15 change channels to O thru 7 (BDIFile only)

Disposition:

Description changes shall be-made as noted j on BDIFile and Database PS-J-0626. Changes made to fit descriptions to available character fields.

D8000, and MAX 1 and 2 channel changes make to BDIFile so that file is in accordance with field wiring and PS-J-0626.

Disposition Prepared By:_ 9-2PO V & V Review: x & @

Disposition Verified p U

/ Signature 6 'Date rs/33

L.

t I

HOPE CREEK GENERATING STATION

.SPDS V&V DISCREPANCY REPORT Discrepancy No. 179 Date: 08 /26'/88 Page / of /

References:

1) Preop Test M-13-STP-004-EC-1076, Rev. 0 2) 3)

Description:

Test Exception #4 ANALDG Point A2807 Data sheet does not match l actual plant scaling of RX Fuel Zone Level _ f (Ref. point A2804) DATA SH. ENCL A PG 67 of 227-(+ P+10 M42) .

l Disposition: l Change scaling of procedure DATA sheet to

-311 to -111 inches to match . actual plant scaling revise PS-J-0626 to reflect correct plant scaling-(see CRIF #34).

Disposition Prepared By: f*2((

V& V Review: 0, wff f!87!P[

Disposition Verified: /[ 27 [f

' Signature / ' Da t'e i

rs/34

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No.- 180 Dat'e : 08 /26 /88

-Page / of* /

1

References:

1) Preop Test M-13-STP-004-4EC-1076,'Rev. 0
2) l 3)

Descripti'on: Test Exception #5 Max.7 1CC655 A/D card gain select 2 is out of cal. Gain select 2 is the only gain used on this MUX.

+

Disposition:

l Recal gain select 2 of A10 card for ICC655

)

k l

I l

Disposition Pre ared  : h h'2Y'$$

V&V Review a -

ff !E7/8 Disposition Verified W 4-f /Z7fn

' Sig nature' Datd 1

dr/100

HOPE CREEK GENERATING STATION

'SPDS V&V DISCREPANCY REPORT 1.

Discrepancy No. '181 Date: 08 /26 /88 Page / of' /

References:

- 1) . Preop Test M-13-STP-004-4EC-1076,.Rev. .0 2) 3)-

Description:

. Test Exception #6 .

Point's ' A2815 (Encl A PG 72) and A . ,

(CNCL A PG73) have incorrect'conversiv.'

details.  ;

I Disposition:

Change'A2815 and A2816 slope to .0025 and intercept to -2.5. This will give;a range of 0 to 10 which is I. A' . W. DATABASE PS-J-0626. Update PS-J-0627-C~BPVFILE' Source Code to reflect correct conversion details (see CRIF #37) l i

i Disposition Prepared B.'/: h 9-ZhSh V&V Review: L Gd// _ [f Disposition erifled: k/7!bfDate'

/SignatGre / l

.dr/101

HOPE CREEK GENERATING STATION SPDS.V&V. DISCREPANCY REPORT Discrepancy No.- 182 Date: 08 /26 /88

~

Page / of /

References:

1). Preop Test M-13-STP-004-4EC-1076, Rev. 0 2) 3)'

Description:

Test Exception #7.

Points A7065 (Encl A PG 125) does not have conversion details.

Disposition:

Change A7065 slope to .25 and intercept to -2.50. This will give a range of 0 to 1000 which is I. A. W. database

.PS-J-0627-C. Update PS-J-0627-C BPVFILE

. Source Code to reflect correct conversion details (see CRIP #37)

Disposition Pre are y: h 8-27-f2 V&V Review r 8'/ '

Disposition Verified 2/ h

/ Signature / Datb dr/102.

l

- - - - - 1

m.

I HOPE. CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 183 Date: 08 /26 /88 Page / of "l

References:

1) Preop Test M-13-STP-004-4EC-1076, Rev. 0 2) 3)

Description:

Test- Exception # 8 Mix 9 cabinet 102655A Hardware slots 15 and 17 analog input cards are not within the tolerance specified in the procedure.

' Disposition:

Calibrate analog input ca: 3s in . mux 9 hardware-slots 15 and 17 then reperform point check I.A.W. M13-STP-004-4EC-1076 Affected points A2574, A2575, A2576, A577, A2578, A8000, A8001, A2159, A2161, A2163, A2165, A2160, A2162,.A2164, A2166..

Disposition Prepared B : kd V6V Review- M& W87!98 Disposition Verified f- d

/ Signature / Dat6 dr/103

HOPE. CREEK-GENERATING STATION SPDS V&V DISCREPANCY-REPORT Discrepancy No.- 184 Date: 08 /26 /88 Pag e / of ' /

References:

1) Preop-Test M-13-STP-004-4EC-1076, Rev. 0-2) 3)

Description:

Test Exception'#9 Points A194 and A195 do not indicate correctly.

I

'1

] l i

Disposition:

Change conversion detail offset'from 2.125 to -2.125 for both points which will give the required 0 to 100% range.

Reference CRIF #37 (Also see T.E.13) I 1

I Disposition Prepared = f*2.V V&V Review: $ f /Z7/EP Disposition Verified / 2 M

/ Signature (

(Date i

dr/104

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT t

Discrepancy No. 185 Date: 08 /26 /88 Page / of /

References:

1) Preop Test M-13-STP-004-4EC-1076, Rev. 0 2)

'3)

Description:

Test Exception #10 Point D8000 is not connected to Rx Man control panel 102616, therefore overlap test cannot be performed.

Disposition: See Discrepancy Report #239.

l l

1 Disposition Prepared y: d[

V&V Review

(

& h/27!N 1

Disposition Verified:

Signature Date dr/105  !

HOPE CREEK' GENERATING STATZON

~

SPDS V&V DISCREPANCY REPORT Discrepancy-No. 186 Date: 08 /26 /88 Pag e / of /

References:

1)- Preop Test M-13-STP-004-4EC-1076, Rev. 0 2) 3)

Description:

' Test Exception #11 Points D2131, D2132, D2174, D2175 have their tag sets backwards, need tag set reversal.

Disposition:

i.

Points shall have BDIFILE and PS-J-0626 changed such that an open contact (logic

0) is " TRIP" and a closed contact (logic l j 1) is reset. Also update T2391 equation to T2391 = (Not D2131 + D2132)* (Not D2174 +

Not D2175)

I Disposition Prepared B : /~

V& V Revi ew s f k27!P[

Disposition Verified W I

f] f/87/ff

' Dat'e Signatury'

'dr/106 i

1 HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT

. Discrepancy No. 187 Date: 08 /26 /88 Page /- of /

Referencess 1) Preop Test M-13-STP-004-4EC-1076, Rev. 0 2) 3)

Description:

Test Exception #12 t

Points D5881, D5882, D5883, D5884, D5889, D5890, D5891, D5891, D5892 have their tag sets backwards.

l Disposition:

Points-shall have BDIFILE an'd PS-J-0626 changed such that an open contact (logic

0) is "NCLSD" and a closed contact (logic
1) is "CLSD".

h l

Disposition Pre are  : k'2-V&V Revie : A N Disposition Verified /

( Signaturp Ds :e dr/107 l - . _ _ _ - _ _ _ _ _ _ _ -

> HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT

. Discrepancy No. 188 Date: 03 /26 /8,8,8 Page l of l

References:

1) Preop Test M-13-STP-004-4EC-1076, Rev. 0 2) 3)

i

Description:

Test Exception #13 The points listed below had values that did not read within the overlap tolerance or were at 0% value during plant overlap test.

A2227, A7081, A3129, A7080, A'3128, A2224, A194, A195 (Step 9.2.4) A3167, A3165 Disposition:

These points are flows which require a square root function by; the computer for correct indication. Add square root for correct indication. Add square root function in'BPVFILE and update J626. O cutoff for flow shall be at 10% of input.

Disposition Prepared  : h ,

V&V Revie rf /b7 &

Disposition Verified: Od ._

2.7 E

' Signature / 'D a t'e dr/108

w- --w--- m - m~

SPDS V&V DISCREPANCY REPORT Discrepancy No. 189 Date: 08 /26 /8E!

Page / of. ;

References:

1) Preop Test M-13-STP-004-4EC-1076, Rev. 0 '

2) 3)

Description:

Test Exception #14 3.2.4 The following analog points were reading 0% of scale' when the point overlap test was performed. The procedure specifies the points should be between 5% and 95% of scale when the overlap test is performed.

A7096 A7126 A3139 A7078 A7104 A3138 A7.087 A7088 A7117 A7086 A7089 A7054 A7100 A7106 A2068 A7128 A7065 A2491 A2814 A7054 A7053 A2806 A2875 A7130 A2817 A7090. A7.123 A7091 A7098 A7110 A7121 A7073 A3163 A7163 Disposition: The procedure specifies between 5 and 95% scale so that a point that is non-linear in the field compared to a computer linear scaled point would not be overlooked. The  ;

points listed below that were reading 0% are acceptable based on verification of a linear field input. The point numbers and L

linear field device used for verification are listed. All flow I points were verified to have sq rt extraction external from the l computer.

' Point #_ Indicator Point # Indicator A7096 1NK-AI-6317A A7073 1ND-AI-6352A3 A7078 1NB-AI-6352A4 A7163 1KL-PD1C-5825B A7087 1KJ-AI-6396B A7126 1PK-AI-6375C A7086 1KJ-VI-63928 A7104 1NK-AI-6429C A7100 1NK-AI-6373B A7088 1KS-VI-6392C A7128 1PK-AI-6377D A7089 1KJ-AI-6396A A2814 1GS-PR-4960B1 A7106 INK-AI-6373C A2806 1GS-PR-4960B2 A7065 1NB-AI-6352B2 A7130 1PK-AI-6375D A7054 1BM-PI-R600B A7090 1KJ-VI-6392D A2875 1GS-AR-5039B A7091 1KJ-AI-6396D A2817 1GS-AR-5041B(Red) l A7110 INK-AI-6429D A7123 1PJ-AI-6431 A7098 1NK-AI-6529BA A3163 1BC-FI-8603D A7121 1PJ-AI-6381 A3139 1BC-FI-8603B A2068 1BE-F1C-R600 l

A3138 1BC-FI-R603C A2491 1FC-F1C-R600 l 1BH-PI-R600H l A7117 1PJ-AI-6386 A7053 I 'A7054 1BA-PI-R600A A3137 IBC-FI-R603A Disposition d  : / b2I~M V&V Review _

9/z1/FF j Di spos i tion' Veri f i e'd Q,(,/ W#_ ___ _ (/22/Ps Date l

Signature ,

j l dr/109

l HOPE CREEK GENERATING STATION

.SPDS V&V DISCREPANCY REPORT

.I Discrepancy No. 190 ,

Date: 08 /26'/88 Page / of f

References:

1) Preop Test M-13-STP-004-4EC-1076, Rev. 0 2) 3)

Description:

Test Exception #15 9.2.4 The points listed below had valves that did not read within the overlap tolerance:

A208, A209, A210, A211 Disposition:

These points are flows which require a square root function by the computer for correct indication. Add the square root function in BPV':ILE and update J626.

O cutoff shall be applied at 10% of input. Also, update full scale value from 24.7 to 20.79 as per actual plant scaling.

I Disposition Prepared  : h'2M V&V Review: A J h/27!Oi Disposition Verified: ff EM f I signatu r/3 'Date l

,dr/110

HOPE CREEK GENERATING-STATION SPDS V&V DISCREPANCY ~ REPORT

-Discrepancy No. 191 Date: 08'/26 /88 Page / of /

References:

1) Preop Test M-13-STP-004-4EC-1076, Rev. 0 2) 3)

Descriptions Test Exception #16 9.2.4 The points listed below had values that did not read within the overlap tolerance: A2162, A2164, A2160, A2166.

Disposition:

The process value scaling of these points chould be 0 to 160 mv for 0 to 100 mv input. Change BPVFILE and J626 to reflect a 0 to 160 my process scale.

{

i Disposition Prepare By: Id k 2f V&V Review CMD _ h/57!Pd Disposi lon Verified 8 [I

' Signaturd ' Da t'e ,

dr/111 I

\

I H0PE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 192 Date: 08 /26 /88 Page / of l-

References:

1). Preop Test M-13-STP-004-4EC-1076, Rev. 0

2) j 3)

Description:

Test Exception #17 9.2.4 Points A8000 and A8001 are spare inputs in the field so a point overlap test cannot be performed.

Disposition:

Points A8000 and A8001 were implemented in SPDS for future installation of RACS pump room temperatures. These points are spare at this time therefore no point overlap test is required.

l Disposition Prepared  : f"h V&V Review: / f27 N I Disposition Verifie / h

/ Signaturp 'Date dr/112' e_--__-__--_-________-__ _ __

i HOPE CREEK GENERATING STATION l SPDS V&V DISCREPANCY REPORT i

Discrepancy-No. 193 Date: 08./26 /88 Page / of. /'

References:

1) Preop Test M-13-STP-004-4EC-1076, Rev. 0 2) 3)

Description:

Test Exception #18 9.2.4 Rx Fuel Zone level point A2804 and A2807 are currently overranged so a point overlap test cannot be performed between 5 and 95% of scale.

Disposition:

These points are currently consistently reading with plant indications (B21-R610 and IBB-LR-R615). These points are acceptable based on the same scaling as plant indication and the calibrated input test.

Disposition Pre ared B : Sk V&V Review: / N Disposition Verified 6 k/27!N "Date

' Signature /

dr/1J3

HOPE CREEK GENERATING' STATION SPDS V&V DISCREPANCY - REPORT Discrepancy No. '194 Date: 08./26 /88, Page / of /

References:

1) Preop Test M-13-STP-004-4EC-1076, Rev. 0 2) 3)

Description:

Test Exception #19

! 9.2.4 The following points were reading question marks when the plant overlap teR was performed.

A7061' A7064 A7084 A7060 A7062 A7095 A7063 A7085' A7139 Disposition:

None of the points listed n.re SPDS pointr therefore, SPDS indications are not affected.

-Disposition Prepared B : k"2k V&V Review: & 0 _ /27!?ff Disposition Verified !Z7!hd

/ Signature / 'Dats

dr/114 g

c-__-

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 195 Date: 08 /26 /88 Page / of /

References:

1) Preop Test M-13-STP-004-4EC-1076, Rev. 0 2) 3)

Description:

Test Exception #20 9.2.4 Point A2287 passed the overlap test, however, the value is exceptionally low for current plant conditions.

4 i

i Disposition:

Plant A2287 has a resistance input from the field which was verified to be abnormally low for plant conditions. This does not affect this test, however, a work order has been written to investigate the field problem.

Disposition Prepared By: "

VGV Reviev f

p

(

Y /S?/?V Disposition Verified: Date Signature dr/115

i, HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 196 Date: a / og / on Page / o,f /

l

References:

1) Preop Tese M13-003-4EC-1076, Rev. 0 2) 3)

Description:

Section 3.1.1 lists Design. Memoranda H-1-RJXX CDM-0491, Rev. 1 as a reference. The latest revision available to the V&V team is Rev. O.

Disposition:

See Discrepancy NO. 166. 4 Disposition Prepared by: /2k/

V& V Review a p Q / b7 / PEI 1;

I

(

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING' STATION 4 SPDS V&V DISCREPANCY REPORT .f Discrepancy No: 197 Date: 8 / 26 '/ 88 Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev.10.
2) (Test Exception 23) 3)

Description:

Criterion 6.1 was not successfully met'during performance of this test.

i 1

Disposition: Normal operating staff will be able to operate the SPDS system during normal and abnormal plantti.r -

operation. The only system operation that cannot  ;

be performed from a control room console i a computer reboot. An operator would only be required to reboot a computer if both SPDS computers failed.

In the unlikely event of a double computer failure the appropriate people can be displatched'(operator or computer person ) to reboot a computer per procedure before the unlikely event of a second computer failure.

V & V Review h n /8,I / N Dispositionverifiedh wM r

@/ 27 /O i Signature Date j i

1 HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 198 Date: 8 / 26 / 88 i Page / of (

References:

1) Preop Test M13-003-4EC-1076, Rev. 0 2) 3)

Description:

Criteria 6.10, 6.11, 6.18, 6.21, and 6.35 state that various functions of the system meet tolerances or requirements spaecified in the procedure. The test procedure is not a design document, therfore these criteria should reference design documentation.

A Disposition:.

See Discrepancy NO: 167.

l.

l I i

(-

Disposition Prepared b : / /

V & V Revie r / /

(

Disposition Verified: / /

Signature Date

HOPE _' CREEK' GENERATING STATION SPDS V&V, DISCREPANCY REPORT-Discrepancy No: 199 0 26 88 Date: / 7 '{ '

l l

Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev'. O,'Section 9.2 2) 3)

Description:

CDM-0491, Rev. O, pg. 2.3-4 states that the top two line of each CRT will contain the time, date, and plant identification. Per enclosure A i to PTP-003, this information is on one line and I and plant identification is not included. 1 1

f Disposition: Rev. 1 DM-04 91, Sect. 2. 3. 2.1.1 is in agreement with M13-003-4EC-1076, Rev. O

{

1 l

l Disposition Prepared by_: /_ /

V & V Review b A

/

a

/

h/M/N Disposition Verified: _

/ /

' Signature Date  ;

l l

HOPE CREEK GENERATING STATION i SPDS V&V DISCREPANCY REPORT 'f

^l Discrepancy No: 9nn Date: 8 / 26 / 88 Page /' of /

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Section 9.2 2) 3)

Description:

The information block described on page 2.3-4 of CDM-0491, Rev. O does not appear on the SPDS.

Disposition: Section2.3.2ofDM-0491,Rev.kdescribestheSPDS CRT layout. This layout is in agreement with the configuration tested in M13-STP-003-4EC-1076.

1 1

Disposition Prepared y: I / 2_  ;

V & V Review.

4 (

/ 87/ Pb  !

Disposition Verified: / /

Signature -

Date  ;

i' ' HOPE CREEK GENERATING STATION SPDS V6V DISCREPANCY REPORT Discrepancy No: 201 Date: 8 / 26 /' 88 Page / of- I

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Section 9.3 2) 3)

Description:

This section uses "ON LINE", " FAILED"~, " BACKUP",

and " PRIME" to described' operational status.

CDM-0491, Rev. O, Fig. 2.3-2 uses "IN SERVICES",

OUT OF SERVICES" and " FAILED".

1 Disposition: Figure 2.3-2 and the associated text description in DM-0491, Rev. 1 is in agreement with the configuration tested by M13-STP-003-4EC-1076.

l l

Disposition Prepared by: / /

V & V Review

_CL./

(

/ [7 / hE

,- Disposition Verified: / /

_ .__ _ _ _ l

HOPE CREEK' GENERATING STATION i SPDS V&V DISCREPANCY REPORT I

Discrepancy No: 909 Date: n / 26 / RR Page I of /

lL

References:

1) Preop Tes M13-003-4EC-1076, Rev. O Section 9.3 2) 3)

l

Description:

CDM-0491, Rev. O does not discuss any color coding for the SPDS-SYSTEM STATUS display.

l Disposition:- The color coding in section 2.3.2.1.3 of DM-0491, Rev. 1 is consistant with the configuration tested in M13-STP-003-4EC-1076.

Disposition Prepared  : / / -

V & V Revie

<// /b/

t' Disposition Verified: _/ /

Signature Date

HOPE CREEK' GENERATING' STATION- )

SPDS V&V-DISCREPANCY REPORT'- i 1

l  ; Discrepancy No: 203 Date: 8/ .26 / 88 i

. Page- / o,f /

l

References:

1).'PrCop Test M13'-003-4EC-1076, Rev.0 2) 3)

Description:

Step 9.4.2.1 states that the UPS status' block.

indicates 60 minutes. Per CDM-0491, Rev. 0,-pg.

2.3-5, the time is 30 minutes.

1

-Disposition: The UPS time was changed based on actual UPS test data which is documented in M13-STP-003- {

4EC-1076. DM-0491, Rev.1 has been changed to -l

. reflect 60 minutes on the UPS.  !

E i

l Disposition Prepared b : / /

V.& V Review.

/ N/

(

Disposition Verified: / /

L Signature Date ,

L l

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 204 Date: 8 / 26 / 88 Page / of /

References:

1) Preop Test M13-003-.4EC-1076, Rev'.-0 Section 9.4
2) i 3)

Description:

The UPS message block on pg. 2.3-5 of:

CDM-0491, Rev. O, does not appear on the SPDS.

Disposition: DM-0491, Rev. le Sect. 2. 3. 2.1. 3 is in agreement with the configuration tested in M13-STP-003-4EC-1076.

Disposition Prepared b : / /

V & V Revie i

A

/

/ 27 / bb Disposition Verified: / /

Signature , Date

_ _ _ _ _ - _ _ _ _ _ . _ - - ._____-__)

HOPE CREEK GENERATING STATION <

SPDS V&V DISCREPANCY REPORT l

l Discrepancy No: onn Date: a / ? r, /~ 88 Page / of /

References:

1) Preop 'Iest M13-003-4EC-1076, Rev.'0 2) 3)

i

)

Description:

Step 9.4.2.2 stated that the normal indication is " ON LINE". CDM-0491, Rev 0, Fig. 2.3-2 shows

" BATTERY BACK-UP".

I I

D4sposition: Fig. 2.3-2 and associated text in DM-491, Rev. 1 is in agreement with the configuration tested in I M13-STP-003-4EC-1076.

)

i Disposition Prepared b : / /

V& V Review 5 r / [7 / hY l

(

Disposition Verified: _/ /

Signature -

Date

-__--.-_-_O

HOPE CREEK _ GENERATING STATION SPDS V6V DISCREPANCY REPORT Discrepancy No: 206 Date: 8 / 26 / 88 Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. 0 2) 3)

Description:

Step 9.4.2.5 (and the NOTE:) use 30 minutes vs.

60 minutes.

Disposition: Corrected M13-003-4EC-1076 Rev. O per T.E

  1. 13 to indicate 60 minutes.

i l

l l

i Disposition Prepared b : /

V& VReviewh h/b/N DispositionVerifiedb -

j /b/N

< g Signature Date

l- HOPE CREEK. GENERATING STATION' f SPDS V&V DISCREPANCY REPORT Discrepancy No: 207- Date: 8 ./ 26 j 88 Page / of /

l- 1

References:

'l) Preop Test.M13-003-4EC-1076,'Rev.* 0, Sect;9.7

'.]

2) 1 3)

.I

Description:

As described in other sections of this test, failure of an SPDS computer,. MUX communication link.and/or UPS communication link will give an "SPDS SYSTEM TROUBLE" annunciator. No alarms are mentioned in this section resulting from an RMS computer failure.

Disposition: Failure of any syste, status display communication link causes the top MUX block to turn white causing.the annunciator alarm. The test verified that the top MUX health indicator changing from green to an alarm condition causes the annunciator to actuate. A test was also performed to show that the RMS block changing from green to an .!

alarm condition causes the. MUX block to change colors The RMS link box causing the annunicator to actuate is also tested.in a revision of DCP 11 of DCR 4EC-1076.

4 Disposition Prepare b .

9/ /

-V & V Review /b /N Disposition Verifie af-] h /27 /F#

!. Signa (ure Date t_____ _ _ _ _ _ _ _ _ _

HOPE CREEK GENERATING STATZON SPDS V&V-DISCREPANCY REPORT l ' Discrepancy No: 208 Date: 8 / 76 7 88 Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. 0 2) 3)

Description:

Att. J, columns 7 and 8 list high and low tolerances fdr the data points being tested. l For R9700 through R9708, the low tolerance value (9.73 E+0) is higher than the high tolerance level (1.02 E+0).

i 1

i l

. Disposition: Corrected typo on M13-STP-003-4EC-1076 Attachment J from 9.73 E+0 to 9.73 E-1

.I 4

i 1

Disposition Prepared b :  ! /b/

V &.V Review w

/b /

Disposition Verified k /27 /N Signatbre -

Date j

HOPE. CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Disert.pancy No: ono Date: 8 / 26 / 88 Page } of -l

References:

1) Preop Test M13-003-4EC-1076, Rev.' 0 2) 3)

Description:

Steps 9.8.2.2 thru 9.8.2.4 test point B3001 thru B3003 (SRM Ch.AA-C periods). These points do not exist in CDM-0491, Rev. O. On Fig. 5.4-1 of CDM-0491 these parameters are shown by A2160, A2162, and A2164.

i Disposition: DM-0491, Rev. 1 has point development drawings for SRM periods (Fig. 5.4-9 thru 5.4-12) and text describing these points (Section 5.4.4) which is in agreement with the tested configuration.

i l

l Disposition Prepared b : / Zh /

V & V Review 4/ / [7 /

(

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy.No: 210 Date: 8 / 26 / 88 Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. 0 2) 3)

Description:

Stepa 9.9.2.4 amd 9.9.2.5 indicate a Hi and Hi-Hi  ;

ala rr.1 status for B6260. Per CDM-0491, Rev.0, '

Fig's 5.3-8/9, B6260 has no alarm setpoints. '

B5040 (which uses A2230 and A2368 as inputs and is an input to B6260) has a Hi alarm only.

Disposition: See Discrepancy 213.

I PS-J-0626, DM-491, REV. 1, and DCP 11 of DCR 4EC-1076 all use B5040 for Suppression Pool level indication. The alarms are applied and tested as'B5040. The alarms on B6260 have been deleted as this point is no longer used for Suppression Pool Level.

l Disposition Prepar d b

  • h / 2k / ((

V & V Review

/

/

/D/

Disposition Verified: / /

Signature . Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT l

Discrepancy No: 211 Date: 8 /'26 / RA E

Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. 0 2) l 3)

Description:

Enclosure D (Step 9.9.4), indicates that multiple alarm points exist for several composed points which are not described in CDM-0491, Rev. O.

l These points include, B5007 , B5019, B5030, B5084, B5050 and B5260.

Disposition: Rev. 1 of DM-491, database PS-J-0626, and the final tested configuration are in agreement on alarm setpoints.

Disposition Prepared b : h h/ /

V & V Review:

( i

/ / ?7 / Pb Disposition Verified: / /

Signature Date

HOPE. CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 212 Date: 8 / 26 / 88 Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. 0 2) 3),

Description:

CDM-0491, Rev.0, Fig.5.1-8 shows alarm for '

point B5040. This point is not included.in Enclosure D. .

i

-l i

Disposition: The alarm values are applied to B6260 which  !

uses B5040 as its primary input.. Suppression Pool level is revised in DCP 11 to use point B5040 and the alarms are tested as applied to B5040 in this DCP.

l l

l l

i Disposition Prepared b : f' f/[ /b V & V Review: / E7 / h)O '

(

Disposition Verified: / /

l Signature -

Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 213 Date: 8 / 26 / RR Page / of /

References:

1) Preop Test M13-003-4EC-107E, Rev. 0 2) 3)

Description:

Step 9.10.2.6 uses B6260 for Suppression Pool Level. Per CDM-0491, Rev. O this parameter is displayed by B5040.

Disposition: B6260 at the time of the test was an alternate displayed value of B5040 (Highest Priority) or B6043 (calculated value). This was changed by DCP 11 of 4EC-1076 such that B5040 is the value displayed. This is tested via this DCP. DM-491, Rev. 1 and the DCP have been revised to show B5040 as Suppression Pool Level.

l I

l I

i 1

l l

t Disposition Prepared y: / / / /b V & V Review / b7 / hh I (

Disposition Verified: / /

Signature Date  ;

[ ___ _ _ _

~

HOPE CREEK GENERATING STATION SPDS.V&V DISCREPANCY REPORT Discrepancy No: 214 .Date: 8' / 26 / 88 Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9.12 2) 3)

Description:

Point B5084 is used'as an input to several margin-to-limit curves, (i.e. HCTL, HCLL, CS, NPSH, and.RHR NPSH)..The inputs used to test this point are not the same as shown in CDM-0491, Rev. O Fig. 5.1.9 Disposition: Point A9845 was changed to point A9837 based on the actual Suppression Pool Temp / Inputs used in the plart (Reference Drawing 10855-J373(Q)-74 Rev. 5) The tested configuration is in agreement with.the reference. drawing, DM-491, Rev. 1, and PS-J-0626.

I L

l Disposition Prepared b : /79/

V & V Review

( {

/ 7 / 9I J Disposition Verified:- ,

/ /

9"" "#*

  • l.

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 215 Date: 8 / 26 / 88-Page / of /

References:

1) Preop Test M13-003-4EC-1(76, Rev. 0, Sect. 9.12 2) 3)

L .

Description:

The CS Data Table in Enclosure M indicates a desired value of 0.0 for test 10. As shown on the Core. Spray Pump NPSH Limit curve, the desired value for these temperature and pressure inputs is approximately 2500 gpm.

9 Disposition: The slope of the curve at.the given pressure and temperature on the curve is so small that the' tolerance of the NPSH Limit interpretation covers the 2500 gpm figure.and the 0.0 figure. This curve was revised as a result.of.EOP changes and contains a larger slope which caused the tolerance to be reduced.

Disposition Prepared b : h / [k /

V& V Review h / [O / N Disposition Verified: /__ /

Signature Date

l

HOPE CREEK GENERATING STATION SPDS.V&V DISCREPANCY REPORT Discrepancy No
216 Date: 8 / 26 / 88 Page / of /-

L, .

References:

1) Preop-Test M13-003-4EC-1076, Rev. O, Sect 9.12
2) .
3) i

Description:

The acceptable range for the CS NPSH flow limit data seem excessively broad in tests 3, 5, and 8.

l-Disposition:

See Discrepancy No. 215 Disposition Prepared b : /2/

V & V Review /t / h / 2.7 / bb i (

DispositionLVerifiedi / /

Signature Date

HOPE CREEK GENERATING STATION l SPDS V&V D2SCREPANCY REPORT L

Discrepancy No: 217 Date: 8 / 26 /.88 Page t' of f

References:

1) Preop Test M13-003-4EC-1076,.Re'.

v O, Sect 9.13 2) 3)

Description:

B3001 thru B3004 - Step 9.13.3.1 Per CDM-0491, Rev. O, Att. B, no such points exist. Per ODCN I216/0, B3001 thru B3004 are SRM Channels A-D period. Per CDM-0491, Rev. O, Fig.

5.4.1, SRM Channels A-D periods are provided by A2160, A2162, A2164, & A2166.

Disposition:

See Discrepancy No. 209.

Disposition Prepared by: [ / /

V&VReview:b / /[7/[I_ b i (

Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS-V&V DISCREPANCY REPORT ,

Discrepancy No: 218 Date: 8 / 26 / 88 Page / of /

i

References:

1) Preop Test M13-003-4EC-1076, Re'v. O, Sect.-9.13
2) i 3)

Description:

B5003 - Step.9.13.2.17 _

Per step 9.13.2.17, the point being tested is B8039 i

Disposition: Step 9.13.2.17 had a typo. Point B8039 has been corrected to B5003 which is the point actually tested.

I l

I Disposition Prepar d b -

I

/ /b V & V Review / _/ 7/ PI Disposition Verifie /b7 /

Sign [ture Date

-HOPE CREEK GENERATING STATION-SPDS V6V DISCREPANCY REPORT-Discrepancy No: 219 Date: 8 / 26 / 88 Page / of /

References:

1) Preop Test M13-003-4EC-1076, Re'v. O ', Sect. 9.13 2) 3)

Description:

B5004 - Step 9.13.2.10.

Per step 9.13.2.10, the point being tested is B8120 i

I l .

Disposition: Step 9.13.2.10 had a typo. Point B8120 has been corrected to B5004 which is the point-actually tested, l

J Disposition Prepared -

h/ /

V & V Review 4 _ /b/

E Disposition Verified / _

/ 27 / b l

' Signatbre -

Date

'l

' HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy.No: '220 Date: 8 / 26 / 88 I Page / of /

1

References:

1) Preop Test M13-003-4EC-1076, Re v'. O, Sect 9.13 2) 3)

Description:

B5005 - Step 9.13.2.13.

This step uses inputs for A8039 and A8040. Per CDM-0491, Fig. 5.1-3A, inputs to B5005 are B8039 and B8040.

l Disposition: Typo corrected in procedure.

Points should be B8039 and B8040 V & V Review: /h /

Disposition. Verified:b h/N / b f (

Signature Date

HOPE CREEK GENERATING STATION' SPDS V6V DISCREPANCY' REPORT I

Discrepancy No: 221 Date: 8 /26 / 88 Page / of I -i

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9.13 2) 3,)

Description:

B5006'- Step 9.13.2.19 Per CDM-0491, Rev. O, Fig. 5.1-3D, B5006 is-the average of A2593 and A2596. No date is~ recorded in step 9.13.2.19 to show A2593 and A2596' inputs being averaged.

t l

t

. Disposition: The actual inputs are applied per a testing ,

batchfile drawing PS-J-0627-0-I-8 which does j apply inputs on A2593 and A2596. The response to these inputs is B5006 which has an expected value and tolerance in the procedure..

l Disposition Prepared by: h /h/

V&VReview:b /27/ .

Disposition Verified h] '

/b7 /r5 I

/ Signa [ure Date

)

l HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT >

Discrepancy No: 222 Date: a /x / nn Page / of / l

References:

1) Preop Test M13-0.03-4EC-1076, Rev. O, Sect. 9.13  :[
2)  !

3)

.l

Description:

B810 2 - Step 9. :.3. 2. 9 This step, does not verify an invalid output from B8102 if T8013 is set to 0. (Ref. DM-491, Rev. O, Fig. 5.1-3B).

t Disposition: Added test to DC;P 11 of 4EC-1076 to test B8102 output for both states of T8013. Initial {

test only verified B8102 output when T8013 j was a 1. .;

L Disposition Prepared by: )) h / b /_k V & V Review: x 4_ h/ b7 / Ei Disposition Verified: / /  !

HOPE CREEK GENERATING STATION. 1 SPDS V&V DISCREPANCY REPORT Discrepancy _No: 223- Date: 8 / 26 / 88 1 Page / of l

References:

1) Preop Test M13-003-4EC-1076, Rev'. O, Sect. 9.13 2) 3)

Description:

B5080 - Step 9.']3.2.18 i This step does not verify that B5008 will indicato invalid if T2396 is true. (Ref CDM-0491, Rev. O, Fig. 5.1-3C) j I

Disposition: B5008 is invalid if T2397 is true. B5008 was verified to.go invalid when T2397 was true (A208 at 1.5) and valid when T2397 was false (A208.5)

(

Disposition Prepared  : - 9 / 29/ 88 V & V Review b / 7 / rF P Disposition'Verifie 4//]' / b7 /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 224 Date: 8 / 26 / 88 Page / ,f. o I i

References:

1) preop Test M13-003-4EC-1076, Rev. O, Sect 9.13 2) 3)

Description:

B5030 - Step 9.13.2.20 CFPMCT Batch File, Page 4 Line 4 inserts a value of 10 for point A7000 . Previously A inserted values for A2805 and A2806 provide 1

,a value'of 102.5 for B8105. Since 10 psig is'out of range for A7000, the value displayed for B5030 should be 102.5 psig -

not 10 psig. (Ref. CDM'0491, Rev. O, Fig. .5.1-6)

Disposition: Point A7000 was inserted which means it is a valid point, therefore it is still used by point B5030. An inserted point overrides all  ;

failures.  !

I Disposition Prepared  : @ / 2. k /

V & V Revie /N/

Disposition Verified h/M /b8 l Signa'ture

  • Date c --_ __

-HOPE CREEK GENERATING STATION I SPDS V&V DISCREPANCY REPORT '

_ Discrepancy No: 225 Date: 8 / 26 / 88 Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9'.13 2) 3)

Description:

.B8105 - Step 9.12.6 This step does not verify that B8105 will average i the inputs to A2805 and A2806. (Ref. CDM"0491, j Rev. O, Fig. 5.1-6)  ;

i l

Disposition: Step 9.13.2.20 verifies B8105 averaging Enclosure l C reference step for B8105 has been corrected I i

.i l

Disposition Prepared b - h/ /b V& V Review: >r / // b Disposition Verified:

J 7 /2-7 /

Signature Date .

L_ _ _ _ _ _ _ _ _ __ __ _ -. .i

i HOPE CREEK GENERATING = STATION

-SPDS V&V' DISCREPANCY REPORT

. Discrepancy No:  ??n Date: a / og- / an-

) )

Page of

References:

1)- Preop Test M13-003-4EC-1076, Rev. O Sect. 9.13 2) 3)

Description:

B5040 - Step 9.13.2.26 Step calls for batch file SPLCDCT. This filo does not test B5040 (Ref. CDM-0491, Fig. 5.!-r).

The only_ reference to B5040 in SPLCDCT is tc lasert values to test B6010 through B6013.

I 1

l Disposition: Step 9.13.2.20 verifies B5040 averaging enclosure C step reference on B5040 has been corrected. l l

I l

I i

l Disposition Prepared -

/ /

V & V Review ,/ $ 7 # [

Disposition Verifie b / /E7 / d  :

-Sign [ture -

Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: _ 227 Date: 8 / 26 / 88 Page / of )

References:

1) Preop Test M13-003-4EC-1076, Rev. 0, Sect. 9.13 2) 3)

Description:

B5070 - Step 9.13.2.7 Per CDM-0491, Rev. O Fig'd 5.1.7A/B, B5070 is an average of 5 inputs. Step 9.13.2.7 sums the inputs but does not take the average.

Disposition: B5070 is a sum of composed average points l that have bee n corrected f or percent drywell volume. B5070 adds these points together. The i tested configuration is consistant with DM-491, j Rev. 1 and PS-J-0626.

1 Disposition Pre ared b : $/h/

V & V Review _

h / 2.7 /E 8

  • c h sposition Verified: / /

EOPE CREEK GENERATING STATION

-SPDS-V&V DISCREPANCY REPORT

. Discrepancy No:  ??g Date: a /,' 1/ ns Page l of -l

References:

'l ) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9.13 2)-

3)

Description:

B5084 - Step 9.13.2.20 Batch file CFPMCT includes point A9837'which is not on Fig. 5.1-9. Fig. 5.1-9 includes point A9845 which is not included in CFPMCT. (Ref. CDM-0491, Rev. O, Fig. 5.1-9).

)

Disposition:

See Discrepancy 214.

\

i i-

  • 1 1.

1 disposition Prepar b- I / /

V.& V Review W /E7/hk l

' (

Disposition Verified: -

/ /

t'a Signature- Date j L_________._______.-.__. _ _ _ _ . _ 1

i.

HOPE CREEK' GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 229- Date: 8 / 26 / 88 Page / .of /

References:

1) Preop. Test M13-003-4EC-1076, Rev. O Sect. 9.13 2) 3)

Description:

B5080/B5081 - Step 9.12.4 This step does not show.that these points' average the inputs.

r Disposition: Step 9.13.2.20 verifies. averaging-of B5080-and B5081. Enclosure C. reference steps have been corrected.

i Disposition Prepared b : h A / /

V & V Review / [7 /P8 Disposition Verified: a h /27 /N Signabure Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 230 Date: a / 96 / nn Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9.13 2) 3)

l

Description:

B5093/B5094 - Step 9.13.3.3 Per Fig. 5.1-15, B5093 = R9605

  • A9304
  • 472.13, and B5094 = R9601
  • A9300
  • 472.13. Step 9.13.3.3 I inputs values to R9580 and R9590. No values' are indicated for A9304 and A9300. (Ref. CDM-0491, Fig. 5.1-15)

~

\

Disposition: The. configuration tested for these points is in agrement with the algorithms in DM-491, Rev. 1 and PS-J-0626.

l i

Disposition Prepared  : / /

V & V Review k i

/ 27 / E

/

-Disposition Verified: / /

Signature Date

-I HOPE CREEK GENERATING STATION SPDS V6V DISCREPANCY REPORT 1

Discrepancy No: 231 Date: 8 / 26 / 88 Page / 'of /

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9.13
2) ,

3)

Description:

B9680 - Step 9.13.3.3 This point is listed in ODCN I216/0 as FRVS Iodine Release. CDM-0491, Rev. O Fig. 5.1-14 shows B9680 as FRVS Vent Gas Release-(EFFL)..

Per Enclosure C, B9680 is tested in step 9.13.3.2.

The correct step is 9.13.3.3.

Disposition: ODCN I216/0 has the cor' rect description and is in agreement with DM-491 Rev. 1. figure 5.1-15.

I f

i Disposition Pre ared  : /h/

V&VReviewd C . / 2-) / N f (

Disposition Verified: / /

Signature Date L______.____________.___..__ _ _ _ _ . _ _ _ _ _ _ . _ . . _ . . _ _ _ _ _ _ _ . _

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT-Discrepancy No: 232 Date: 8 / 26 / 88 Paga / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9.13 2) 3)

Description:

B5097 - Step 9.7.5.27 It is not clear what is being tested in this step.

Item D) verifies that B5097 does not alarm. This step does not. test the calculation of B5097.

i i

Disposition: Item ~D) verifies.that B5097 does not alarm because the area monitor Hi alarms are transmitted as a status byte from the VAX computer. This is a negative logic test to verify that a non area monitor Hi alarm ~ status at the VAX computer is not interpreted by the SPDS as a high alarm. The SPDS maintains its own setpoints based on the EOP entry condition. Step 9.13.2.20 which is  ;

referenced in Enclosure C actually test this calculation.

Disposition Prepared b : / /

V & V Review ,, d /b7/bb Disposition Verified h/27 /9b

' Signa (ure Date

_ _ _ _ _ _ _ _ - . _ _ _ . _ _ _ _ __ _ _ _ _ _ . _ _ _ . . _ .J

1 i HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT l

Discrepancy No: 213 Date: 8 / 26 / 88 Page / of l

References:

1) Preop Test M13-003-4Ec-1076, Rev. O, Sect. 9.13
2) .
3) ,

I 1

Description:

B5098 - Step 9.13.2.20 Batch file CFPMCT inserts values to points R9580, R9590 and R9680 to test B5098. These points are not used in the B5098 development. (Ref. CDM-0491, j Fig. 5.1-15).

l Disposition: The tested configuration is in agreement with ,

DM-491 Rev. 1 figure 5.1-15.

I Discw ':ition Prepared '/ / / h Vi 1 Review /[7 / b ff f (

Disposition Verified: / /

Signature Date

~ _ _ _ _ _ . . _ I

HOPE CREEK. GENERATING STATION SPDS V6V DISCREPANCY REPORT.

l

. Discrepancy No: 234 '

Date: 8 /'26 / 88 Page ') of, l

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9.13 2 )-

3)

Description:

B6004 - Step 9.13.3.4 The' required display format.for this point is

-,- Hrs: Min. It is not clear that this format was achieved during the retest of part D of this step.

(Ref. CDM-0491, Rev. O, Fig. 5.8-1)

The color change (Green / Red) when the elapsed' time reaches 24 hrs, was not tested. (Ref. CDM-0491 Rev. O, pg. 5.8-6)

Disposition: Added note in M13-003-4EC-1076.to clarify which readings were from the Suppression Pool B6004 point and which were from the stopwatch.

Issued test to test B6004 above 95 F for 24 hrs.

in DCP 11 of 4EC-1076.

1 Disposition Prepa d  : h/ /

V & V Review A /b7 /bh

/

Disposition Verified: __

/- /

Signature Date o j

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 235 Date: a / 26- / AR Page ) , of l

References:

1) ~ Preop Test M13-003-4EC-1076, Rev. 0,. Sect. 9.13 2) 3)

I

Description:

B6009 - Step 9.14.2.24 This point is tested in step 9.13.2.23 vs.

step 9.13.2.24.

Disposition: Corrected typo in Enclosure C of M13-STP-003-4EC-1076.

]

l f-Disposition Prepared  : / /

V & V Review A

/ 27 /

Disposition Verified , r[ /d7 /b  ;

Signat(re ,

Date

i i

HOPE CREEK GENERATING STATION  !

SPDS V&V DISCREPANCY REPORT Discrepancy No: 236 Date: 8 / 26 / 88 i Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9.13
2) i 3)

Description:

T2423 - Step 9.13.2.21 Batch File RLCDCT returned T2423 = 0 for A2068 = 240.

(Ref. CDM-0491, Rev. O, Fig. 5.2-5)

Disposition: The returned answer is correct for PS-J-0626 and DM-491 Rev. 1 T2423 = A2068 > 240 i

l Disposition Prepared -

~

h / [k/

V & V Review

(

/N/

Disposition Verified: / /

Signature Date

I l HOPE CREEK GENERATING STATION l SPDS V&V DISCREPANCY REPORT Discrepancy No: 217 Date: 8 / 26 / 88 Page } of 1

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9.13 2) 3)

Description:

T2541/T2542 - Step 9.13.2.21 The equations for these points are incorrect.

(Ref. CDM-0491, Rev. O, Fig. 5.2-7)

Disposition: These equations are revised and tested in DCP 11 of DCR 4EC-1076 to give an "INJ" status only when injecting to the vessel.

Disposition Prepa h/ /

'V & V Review / N /W

/ f Disposition Verified: / /

Signature Date ,

h

'j, j

y HOPE CREEK GENERATING STATION SPDS V&V DISCREPANC1f REPORT i

l s l l

Discrepancy No: pas Date: a / 26 / RR l Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev. O, Sect. 9.14 i
2) l
3) '

T

Description:

Since no description of the SPDS validation methodology has been received by the V&V team, no evaluation of adequacy of this test section can be performed.

Disposition: DM-491, Rev. 1 gives detailed description of both onscale and offscale signal validation.

The methods described in DM-491 Rev.1 are in agreement with the tested configuration.

I Disposition Pre ared  :

/ /

V & V Review i <

/ 27 / Mr Disposition Verified: / /

Signature Date

HOPELCREEK' GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy.No: 239 Date: 8 / 26 / 88 Page / of /

References:

- 1) Preop Test M13-003-4EC-1076, Rev. 0 2) 3)

Description:

Test Exception #1 All rods in signal point D8000 is-not connected to the Rx Manual Control System. This point will be.(step 4.1) connected during the next outage.

Disposition: All testing of-point D8000 has been completed satisfactory. This point will be connected

'during the next plant outage and tested at that time. This open item will be explained on the operator aid at each station.

l l

Disposition Prepared b : f / 2k/

V & V Review f

i h / 2.7 / W y Disposition' Verified: , _ _ ,

/ /

Signature Date

{

Y HOPE CREEK GENERATING STATION SPDS_V&V DISCREPANCY REPORT Discrepancy No: 240 Date: 8 ~/ 26 / 88 Page.- / 'of /

References:

1) Preop Test M13-003-4Ec-1076,'Rev. 0 2 ).

3)

Description:

Test Exception #2.

4.4.5.5 All discrepancies that exist are covered by a Change Request Information Form which is included in the current revision of the software DCP 11 of DCR 4EC-1076.-

Upon sucpessful completion of the integrated system test, the master disk will be updated which will clos'e this ex'ception. This-is in accordance with DM-491.

Disposition: This item closed at completion of test.

I i

I l

l Disposition Prepared b : / /

V & V Review h /[7 /b5 Disposition Verified: / /

Signature Date

f

'~

HOPE CREEK: GENERATING. STATION SPDS V&V. DISCREPANCY: REPORT j

Discrepancy No: 241 Date: 8 / 26 / 88

'PageI l' of l

References:

1) . Preop Test M13-003-4EC-1076, Rev." 0' 2) 3)

Description:

Test Exception #3 q' 9.2.1.4, 9.16.2.2 HCTL curve is' scaled on the X axis in 200 psig increments with a tick mark every 100 psig 198.7.and 135 hash marks are

.not included.

SPLL curve is scaled in 200 psig increments on X axis with tick mark 'very e 100.psig.

'1108 and 127 hash marks are not included.

4 Disposition: Scaling of.the graph was performed logically such that numbers would not be in such close proximity to prevent operators from distinguishing between dif ferent numbers. Scaling of the HCTL' and SPLL curves are acceptable as is.

Disposition Prepared by: / /

V&VReview:h '

/

-] h/b/

Disposition Verified: / /

E _ _ _ _ _ _ _ _ _ _ _ _ - - . - - - - - - - - - - - - - - - - - - - - - - - - - - "

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 242 Date: 8 / 26 / 88 Page / of /

References:

1) Preop Test M13-00304Ec-1076, Rev.0 2) 3)

Description:

Test Exception #4 Point D8000 "All RODS INSERTED" signal is missing from Reactor Water Level Control and Rx Power Control Displays (step 9.2.1.4) 1 Disposition: Point D8000 has been added to Rx Water Level and Rx Power Displays and tested successfully.

l Disposition Prepared b -

h / 2f/

V & V Review; 4 r /27/ &

Disposition Verified 1 9/ b /

/ '

! Signature Date l

r HOPE CREEK GENERATING STATION-

.SPDS V&V DISCREPANCY REPORT

. Discrepancy No: 243 Date: 8 / 26 / 88 Page- / of /

References:

1) Preop Test M13-003-4EC-1076, Rev.0" 2) 3)

Description:

. Test Exception #5 9.2.1.4 SRM period points on Reactor Power are points A2160, A2162, A2164,A2166. They should be points B3001, B3002, B3003, B3004.

Disposition: The correct SRM period ppints were'added to the  :

Rx Power Display and retested successfully. 'j l

Disposition Prepar b -

[ /2k /

V& V Review. -

/b / i Disposition Verified t c

/b7 /9bI Signature Date

.HOPZ.' CREEK GENERATING STATION j

'SPDS V&V DISCREPANCY-REPORT

/ 26 Discrepancy No: 244 Date: 8 / 88 1

, -1 Page / of /

\

References:

1) Preop Test'M13-003-4EC-1076, Rev.0' f 2) 3)

Description:

Test Exception #6 9.2.1.4 Suppression Pool Temperature Control.

cannot tab to.the Suppression Pool Temp HRSamin Display.to verify that this is point B6004.

5 Disposition: Suppression Pool HRS: Min' Display was verified as the correct point on the display by successful completion of step 9.13.3.4 D.

4 Disposition Prepared b : / f/ 2k/cd8 V & V Review / //

Disposition Verified i

vt c

h/U /h[

Signature Date

i HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 245 Date: 8 / 26 / 88 -

Page / of l  !

References:

1) Preop Test M13-003-4EC-1076, Rev. "O 1
2) l
3) f

Description:

Test 5'xception #7 .

9.,2.1.4 Point D3728 is missing from the Primary Containment Isolation Valves Display. Field exist on the CRT but has no point assigned.

\

l Disposition: Point D3728 has been added to the Primary Containment Display and retested satisfactorily.

Disposition Prepared :_ / 2k/ 3 V & V Review / b7 /

Disposition Verified

(

it l

_ 9 / 17 /b8 I Signature Date L - __-_-_

HOPE CREEK GENERATING STATION SPDS V6V DISCREPANCY REPORT Discrepancy No: 246 Date: 8 / 26 / 88 Page / of /

References:

1) Preop Test M13-003-4EC-1076, Rev.0 )
2) 1 3) i

Description:

Test Exception #8 9.2.1.5 Display for Rx level and DW Press did not i appear with all Data in 4 4 seconds. Both displays were less than 5 seconds.

l Disposition: Display response is adequate based on Guideline i Criteria in NUREG-0700 Section 6.7 Exhibit 6.7-6 ';

which gives a response time for complex querrys in Graphic form of 2 to 10 seconds. (

CDM-0491, Rev. I will indicate these update times.

l Disposition Prepared b : f/ 1 k/

V & V Revie r

h /[7 /bI Disposition Verified: / /

Signature Date

e HOPE-CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy.No: 247 Date: 8 '/ 26 / 88 Page / of: I

References:

1) Preop Test M13-003-4EC-1076, Rev, 0 2) 3)

Description Test Exception #9 9.2.1.6, 9.16.2.4 Rx Pressure Point B5019 is shown as interger rather than to 1 decimal place.

Disposition: Rx pressure point presentation as an interger is acceptable based on all setpoints (1037 and 1071) being interger and a pressure range of 0 to 1500 psig and 850 to 1050 (narrow range).

Disposition Prepared -

/ / 2// fd V & V Review 9/ b /

Disposition V ifiedq r /N / b[

Signature Date

~ - - - - - - ---- - - - - - -- - --_ - - _ - _ _ -

1 1

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT 1

Discrepancy No: 248 Date: 8 / 26 / 88 '

Page /- of' /

References:

1) Prepp Test M13-003-4Ec-1076, Rev. 0 .i 2) 3)

4 l \

I

Description:

Test Exception #10 9.9.2.3 Point B6260 changed to white question marks.

Disposition: Correct software such that two points that are on scale validated both go white on black with the top composed point indication green on white. This is per DM-491. Reperform section 9.9.1 thru 9.9.2.3 before continuing test.

i l

Disposition Prepared b  : / /

V & V Revie : s 4/ h/ /

Disposition Verified: e 2

/-7/w Sign /ture Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT

\

Discrepancy No: 249 Date: 8 / 26 / 88 Page / of l

References:

1) Preop Test M13-00304EC-1076, Rev. 0 2)
3)  !

I

Description:

Test Exception #11 i

9.9.4.1 (B) Point B5050 changes to yellow in alarm should change to Red when in alarm i

Disposition: Procedure DhfA sheet is in error correct ENCLOSURE D point B5050 to a desired High High Alarm of 57.2 with reset of 54.65, a desired High a'sarm of 14.8 with reset of 12.25 and a tolerance of .l.

l Disposition Prepare.1 by: [ f / dk / ,8[

V& V Review f ._ / /

Disposition Verified

/ f

/N /W Signature Date

- - _ _ _ _ _ - _ - _ - _ i

n- HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 250 Date: 8 / 26 / 88 Page / of' -l

References:

1) Preop Test M13-003-4EC-1076, Rev."0 2) 3)-

Description:

Test Exception #12 Steps 9.5.4.3, 9.5.4.4 RMS link Block did not change to FAILED and values for points stayed a status of green value on black background.

Also steps 9.5.4.6, 9.5.4.7, and 9.5.4.10 values stayed green on black with the RMS LINE OFFLINE.

Disposition: Correct software such that the RMS status block goes to " FAILED" on a link failure and marks all RMS to SPDS transmitted points BAD (while question marks) . The annunciator shall also actuate. Retest step 9.5.4 after correction of software. This is per DM-491.

Disposition Prepared b : h /h / r V & V Review / I7 /

Disposition Verified 1

h/ $7 / 9ff .

l Signa (ture Date l

_ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ 1

,1 HOPE CREEK GENERATING' STATION SPDS V&V DISCREPANCY REPORT,. 1 l

Discrepancy No: 251 Date: A / 9 s; ~/ nn_

Page / of- /

References:

1) _ Preop Test.M13-003-4EC-1076, Rev.0 2) 3)

Description:

Test Exception #13 9.4.2.8B, 9.4.2.12A,C, 9.4.2.15 Annunciator did not actuate, battery on system.

status menu was yellow on red. BATTERY did not change to red in color at 5 minutes.-

. Disposition:

Correct software such that annunciator actuates-at 5. minutes battery life remaining and when UPS goes to bypass at end of battery life.

Correct BATTERY to be yellow on black and time from 30 to 60 minutes based on 3h hour battery display. Retest section 9.4'.l.

Disposition Prepared by: @/ [k/

V & V Review / / 8~7 / N DispositionVerified:b sr[ /C / N_

Signa [ure Date

T ,

HOPE CREEK GENERATING STATION 03 3: SPDS V&V DISCREPANCY REPORT Discrepancy No:' 252 Date: a / ' x - / ' 'an Page- 1 of f

References:

1). Preop Test M13-003-4EC-1076,.Rev.0 2) 3)

Description:

Test Exception #14 9.12.1 HCTL' curve margin to limit values are question marks.

1 Disposition: Rework 'and' retest all curves before running PREOP. Record margin values and colors for all values recorded. Add color codes on Enclosure.M DATA sheets for desired, High and Low tolerances. CS Data Table Input 9 and 10 tolerances should be changes as follows:

Input 9 - High tolerance 4300, Low 200 Input 10 High tolerance 3000.

This makes tolerances 20% of a grid of the CS curve which is constant with all curve interpretations. 20% of 1 grid is equivalent to 2.5% of the Y axis. Change PSP input 11 to 39.8623 rather than setting B6272 old.

Add note on how to calculate PSP desired level.

(step 9.12.6(E).

l-Disposition Prepared b :

^

h7 / 2k /

V & V Review e / b /b Disposition Verified h

/

u e /27/& l

/ I Signature Date j

HOPE' CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 2sq Date: 8 / 26 / RR Page / of l l

1

References:

1) Preop Test M13-003-4EC-1076, Rev.0 {
2)  !
3) j l

Description:

Test Exception #15 9.13.3.4 Suppression Pool minutes count up 'j over 60 minutes and do not reset to 00.

l

)

Disposition: Fix software such that minutes go from '

60 to 00 and do not continually count up retest after completion.

~.

f Disposition Prepared by: t/i/ /N/

V & V Review A h /b /N Disposition Verified: A f-[ h /27 /N

' Signature Date f

i ;1 i

HOPE CREEK GENERATING! STATION SPDS V&V' DISCREPANCY REPORT Discrepancy No: 254 Date: 8 / 26 / 88 1 1

Page / of I .

l l .

References:

1) Preop Test M13-003-4EC-1076, Rev.0 2).

3) l

Description:

Test Exception #16 Points A8000 and A8001 are spare point and should not be n'. sed in the Rx Bldg. Hi Temperature Calculation. 2quation functioned as intended.

Disposition: 9.33.2.20 Points A8000, A8001 do not have sensors designed and installed in the field (RTD Inputs).

1 Disposition Prepare y: h /2k /

V & V Review / 27 /b V Disposition Verified h ,

h/ M /28 Signa [ure Date

~ -

\ .

I HOPE CREEK GENERhTING' STATION 1 LSPDS V&V DISCREPANCY. REPORT. f Discrepancy.No: 255 Date: 8 / 26 / 88 Page I of' I

[

References:

1) Preop Test M13-003-4EC-1076, Rev.0
2) ,
3) ,.

Description:

Test Exception #17 9.14.4.3-SRM Period' Indications are either "INF" or "???" for value,-there

'is'no. period digital value.

Disposition: Correct equation for' points on SRM period for a 0 to 100 MV input scaled

~

0 to 160 MV. Reperform step 9.13.3.2.

i Disposition Prepared by: f /2k/ 1 V & V Review VI /M /N l Disposition Verifie w // h / 2-7 / Et Signa,ture Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 256 / 26 Date: 8 /_88 Page 1 of 2

References:

1) Preop Test M13-003-4EC-1076,Rev.~0 2) 3)

Description:

Test Exception #1 9.14.3.3B Point B8116 indicated a green on black status.

9.14.3.4 Points A3543 'nd A3549 indicated a green on black status. Point B8039 indicated green on black w'ith the high level of 50.00.

9.14.3.5B Point B8200 changes to a white on black status.

9.14.3.6B Point B8201 changes to a white on black status of 10.00 9.14.3.7B,C Point B6278 changed to a value of 5.50E-4 and a green on white status points R9633 and R9634 are green on black status.

Disposition Prepared b : A  ! / 2k / b V&VReview:b /b/ E Disposition Verified as f Q / 2_7 /h Signa (ture Date

HOPE CREEK GENERATING' STATION ~ '

SPDS V&V DISCREPANCY REPORT l Discrepancy '. No : . 256 (cont) Date: 8 / 26 / 88 Page 2 of. 2

References:

1) Preop Test M13-003-4EC-1076, Rev.0 2)-

3)-

DISPOSITION- Correct software per'DM-491 and retest 9.14.3.3B, 9.14.3.4, 9.14.3.5B,'and

, 9.14.3.6B.

Step 9.14.3.7B and C are acceptable as is because on SCALE FAILURE ARE NOT performed' on radiation points.  ;

1 9

L l

Disposition Prepared b : / 2k / 8 V & V Review b / / 27 /k '

Disposition Verified:

/

A

(

/27/ '

Signature Date

_ - -_ __ _ _ - _-- _ - .-.-- - _-_- l

HOPE CREEK' GENERATING STATION SPDS V&V DISCREPANCY REPORT ,

Discrepancy No:. 257 Date: 8 '/ 26 / 88 Page '/ of- I 1 .

References:

1 )' Preop Test M13-003-4EC-1076, Rev.0 2)

.3)

-Description: Test Exception #19 9.11.2.8 Trend fails at' 182 inches '

and changes white in color.

9.11.2.27 Trend fails as~is (77) and is' white in color.

Disposition:' Failure of Trends is adequate and per DM-491. System operation is as desired.

i i

Disposition Prepared  : [ /2 /

V & V Revie i

/ b7 / ET Disposition Verified: / /

Signature '

Date

. HOPE CREEK GENERATING STATION SPDS VSV DISCREPANCY REPORT ,

Discrepancy No: 258 Date: 8 /_7 6 / 88 Page l_ of 1

References:

1) Preop Test M13-003-4EC-1076, Re'v. 0 2) 3)

Description Test Exception #20 9.10.2.3 E) F) B5026 goes to ??? status when power is at 125 or 0%. all composed points that comprise B5026 are a normal green on black status.

9.10.2.9 E) Digital value went to white question marks when scale was at value of 0. Digital vlaue returns to green value with point B5098 set at .l.

Disposition: Problem has been corrected and retested

_per DCP 11 of DCR 4EC-1076.

Disposition Prepared b : / /

V & V Revie f

J n

( _/

h /77 / H Disposition Verified: / /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 259 Date: 8 / 29 / 88 Page / of I

References:

1) Preop Test M13-003-4Ec-3 076, Rev.0
2) l 3) l

Description:

Test Exception #21 Step 9.3 This section will be performed initially with MUXES 9,10,4 only, when the system (all MUXES) are available on the s new SPDS, one failure will be performed to verify all input MUXES are operable on both computers.'

Disposition: Section 9.3.2.3, 9.3.1, and 9.3.2 was successfully tested with all MUXES, UPS and RMS ONLINE.

Disposition Prepar d b -

f / h / [O V & V Revie s r.:t/r] h / D /N Disposition Verified:

I a M

(

Q /87 h Signature Date

f HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 260 ..

Date: 8 '/ 26 / 88 Page 1 of 1

References:

1) Preop Test M13-003-4EC-1076, Rev. 0 l

Description:

Deleted - Duplicated in DR 197 I

1 Disposition:

1 i

Disposition Prepared by: / /

V & V Review W f, 9 / 2-7 / O

/

aa amas 4 <> < ara vsmsun ces a / __ /_

HOPE CREEK GENERATING STATION.

SPDS V&V DISCREPANCY REPORT Discrepancy No: 261 Date: 8 / 26 / 88-Page / of /

References:

1) Preop Test'M13-003-4EC-1076,-Rev'. 0 2) 3)

Description:

Test Exception #23 Step 9.3.2.15 CPU B is not indicated as OFFLINE because the computer is HALTED the instant the computer.is placed OFFLINE.

Disposition: Change procedure to the following:

A .) After Failover, verify CPU A is indicated as PRIME and CPU B is indicated as failed.

B) After Failover, verify CPU on the top line of the display is ?hite in color.

I Disposition Prepared b - $h.$ # Y/ Th/ [E V & V Review:  ;, /2Y /b

/

Disposition Verified: / /

Signature Date  !

HOPE CREEK GENERATING STATION

.SPDS V&V DISCREPANCY REPORT Discrepancy No: 262 Date: 8 / 26 / 88 Page / of' l

References:

1) Preop Test M13-003-4EC-1076, Rev.0 2) 3)

Description:

Test Exception #24 9.17.3.17 Computer HALTED approximately 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> into testing.

Disposition: Restart computer and reperform warranty test.

Vendor to install erro trapping program to identify HALTING OF COMPUTER.,

Problem has been corrected and system retested per DCP 11 of DCR 4EC-1076.

1

(

l i

Disposition Pre ar . / /

v & V Revie : -

__ h /d7 / E7f Disposition Verified

/

/ 27 Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 263 Date: 08/26/88 Page 1 of _2_

References:

1) Preop Test M13-003-4EC-1076, Rev. O

Description:

Test Exception #25 9.17.3.1 Review of the'PC Isolation display revealed several discrepancies with color coding of values (ie; color cod ing should be green when closed and red when tactss>:) . Also several equations were incorrect. Suppression Pool Temperature Margins points (4) are in inverse order on screen (pts B6000, B6001, B65002, B6003).

9.17.3.1 SRM period indications are reading approximately 125 seconds. Actual plant' period indications on SRM drawers are approximately 400 to INF seconds.

PSP curve used on SPDS is referenced to the bottom of the suppress. ion pool . EOP curve for PSP is referenced to the suppressed pool level instrument TAPS.

Disposition:

Correct the normal state for the following points:

D7097, T2400, T2408, T2437, T2438, T2463, T2465, T2465, T2466, T2467, T2468, T2475, T2480, T2481, T2482, T2483, T2484, T2485, T2501, T2502, T2503, T2504, T2505, T2506, T2507, T2508. (Normal state shall be 1) Correct the following equations as follows: T2463 = D5881* D5882* D5883* D5584 T2464 = D5889* D5890* D5891* D5892 T2522 = (Not D4997* Not 5039) +

(Not D5030* Not D5031)

T8005 = Not D7095* Not D7096 T8006 = Not D7093* Not D7094 Problems in step 9.17.3.1 were corrected and retested per DCP 11 of DCR 4EC-1076.

Disposition Pre r y:

V&V Review,b e I Disposition Verified: '

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 263 (con't) Date: 8/26/88 Page _1_of_jl

References:

1) Preop Test M13-003-4EC-1076, Rev. O Disposition (con't):

Initiate work order to investigate SRM recorder output calibrations. This item does not affect operability because correct counts per seconds source range neutron flux is available on the SPDS displays.

The current PSP curve used on SPDS will be replaced with a new PSP curve using the instrument TAP of the Suppression Pool Level as the zero reference point. The SPDS PSP curve display will be blanked on the display until the new curve is installed. This curve is not required for SPDS operability.

l Disposition Prepare By:

V&V Review

,/- .

Disposition Verified:

Signature Date t  ;

1 HOPE CREEK. GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No. 264 Date: 08 /26 /88 Pag e / of . /

References:

1) ~ Preop Test M13-003-4EC-1076,'Rev. 0 2)-

3)

Description; . Test Exception'#26 Step 9.7.4.7 Data Sheet' on Enclosure J contains x values equivalent to 1% equivalent linear full scale vs 5% as procedure says. Enclosure I data sheets contains points from muxes .9 and 10, muxes 9 and 10 points are not transmitted to vax and CRIDS computer. CRIDS computer can only read log

. values up to exponent + 7. Therefore, values less than.E7 read zero and greater than E+7 read 1E+7.

  • Steps 97.6.15, 18, 21 system exerciser cannot be used to set desired statuses of high, low low, and low Disposition:

Change x values as follows: .012 to .6, .005 to .25, .006 to

.3. Delete mux 9,and 10 points from Enclosure I.

CRIDS values less than or greater than an exponent of + 7 are acceptable based on the on-scale readings which were siithin the tolerance specified.

Steps 9.7.6.15, 18,21 use the system POKE command and in.nert statuses per PACE Users Manual.

Disposition Pre ared -

k'M V&V Review d Disposition Verifie ~ / Signature /

2.7h bat 6 dr/135

)

1'

'HOPEfCREEK GENERATING STATION SPDS.V&V DISCREPANCY REPORT ,

l Discrepancy No. 265 Date: 09 /21__/88 Page / of-[

References:

1) Design Review Report, _NOV-1000-87-004, Rev. 1. j
2)  ;
3)  !

Description:

Open item- V&V Design Review,'Section 3.2.1 j Attachment B (SPDS database) does not provide data throughout tiems for composed analog (Bxxxx), cmposed digital (Txxxx) and RMS (Rxxxx)' points.

o Disposition:

DM 491 Rev. I contains criteria for composed points data throughput.

Disposition Pre ared  : O 2P V&V Review '

I "

/27/F8'

(

Disposition Verified:

Signature Date dr/122

HOPE CREEK GENERATING STATION SPDS VSV DISCREPANCY REPORT I,

Discrepancy No: ___ 266 Date: 9:/ 21 -/ 88' l Page l ,o f I

References:

1) Design Review Report, NOV-1000-87-0'04, Rev. 1

Description:

Open Item - V&V Design Review, Section 3.2.2 Verification that SPDS CRT update time is  !

consistent with system design deferred to system testing.

Disposition: DATA Throughput to the CRT's are tested in M13-STP-003-4EC-1076. DM-491 cont ains criteria for update times.

l Disposition Prepa d  : / /

V & V Revie : / _ h/ /

Disposition Verifie4 i

/d7 /PI Signature Date

l HOPE CREEK GENERATING STATION

'SPDS'V&V DISCREPANCY. REPORT l

Discrepancy No: 267 Date: 9 / 21 / 88 L .Page l of: I

References:

1) Design Review report, NOV-1000-87-004, Rev.1 1

Description:

Open Item - V&V Design Review, Sections 3.1.4, 3.1.9, 3.3.2, 3.4.4, 3.4.5, 3.4.2, 3.3.1

~

Discrepancies between CDM-0484-0 display requirements and CDM-0491-0 display design.

Disposition:

See Discrepancy'No. 275.

Disposition Prepared -

k /29 / @

V & V Review /N /

/ f Disposition Verified: / /

Signature Date .

HOPE CREEK GENERATING. STATION

'SPDS V&V DISCREPANCY REPORT Discrepancy No: 268 Date: 9 / 21' / 88 Page i of l eferences:

1) Design Review Report, NOV-1000-87-004, Rev.'l

Description:

VOID - This discrepancy number not used. '

Disposition:

1 Disposition Prepared by: f / 2h / 8 l V 5 V Review: N M / /

l Disposition Verified: N/A i

/ /

Signature Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT L Discrepancy.No. 269 Date: 09 /21 /8_88 1

I Page / of. /

l 1) Design Review Report, NOV-1000-87'004, Rev. 1 i

References:

. 2)  ;

3) i

Description:

Open' item- V&V Design Review, Section 3.3.3 The Reactor Water Level trend graph is inadequate since EOP 203, step STC-6 involves a decision based.on RPV level relative to -276 inches as monitored by Fuel Zone indication. This level is well below the lowest displayed' level of -200 inches.

Disposition: ,

The EOP decision functions supported by the trend graph are +12 inches and -38 inches.

Other significant level conditions are supported by .iargin-to-limit tables.

1 Disposition Prepare  : [/fA ) '2bJ8 V&V Review A __

U 22 Disposition Verified: a Dat'e

~

/ Signature (

dr/323

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT

, Discrepancy-No. 270 Date: 09 /21 /88- ,

Page / of /

References:

1) Design Review Report, NOV-1000-87-004, Rev. 1

'l 2)

'3)

Description:

Op'en item- V&V Design Review, Section 3.3.3

.The: suppression Chamber Pressure-trend graph is inadequate since Fig. 5.5-1~of CDM-0491-0 shows non-linear y-axis scaling.

Disposition:

DM 491 Rev. I as well as the tested system-contain a linear y-axis scaling for suppression chamber pressure.

Disposition Pre are By: Y 2kh V&V Revie '

t _ f '

/ {

Disposition Verified:

Signature Date

--_mst _-_- .

7 l'

HOPE CREEK GENERATING STATION  !

SPDS V&V DISCREPANCY REPORT I

Discrepancy th). -271 Date: 09 /21 /88 l Page I of l 1 1

References:

.) Design Review Report, NOV-1000-87-004, Rev. 1 )

2) 3)

l

Description:

Open item- V&V Design Review, Section 3.3.3 The drywell temperature trend graph does not provide sufficient low'end: range to display normal drywell temperatures below 100 degrees F(e.g. during plant shutdown).

Disposition:

The display was designed to show the operator the trend toward EOP entry conditions. In order to accotiplish this with the required scale resolution a range was chosen which does not cover the low end but does provide a sufficient margin (35DEGF) of trending before an EOP entry point.

Disposition Pre ared By: ) h[k V&V Review / m N

Disposition Verified d h b d 9/27[@

/ Signatur6 'Date dr/126

l i

. HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT i

Discrepancy No. 272 Date: 09 /21 /88 i Page / of' l l

References:

1) . Design Review Report, NOV-1000-87-004, Rev..J 2) 3)

Description:

Open item- V&V Design Review, Section 3.3.3 The suppression pool level graph does not provide sufficient resolution for normal operational levels (74.5 to 78.5 inches).

4 L

Disposition:

The graphic representation was designed to ensure EOP entry conditions are readily seen on'the graph. The value between 74.5 to 78.5 is distinguishable as a green line.

l l N Disposition Prepa ed -

972.Y-88 V&V Review jt n Disposition Verifie et Jf/ f 2I l / Signature [ ' Dat'e

HOPE CREEK CENERATING STATION SPDS V&V DISCREPANCY REPORT a l

l Discrepancy No. 273 Date: _09 /21 /88 {

j Page I of / j

References:

1) Design Review Report, NOV-1000-87-004, Rev. 1
2) i i

3)

Description:

Open item- V&V Design heview, Section 3.4.1, 3.4.2 Inadequate description of Data Validation technique in CDM-0491-0 Disposition:

DM-491 Rev. I contains detailed description of on-scale and of f-scale signal validation which is consistant with the configuration tested in M13-STP-003-4EC-1076.

Disposition Pr re ' y:

k-NOh V&V Review ,

Disposition Verified:

Signatu're Date dr/128

. HOPE' CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT

~

Discrepancy No: 274 Date: 09 / 21 / 88 Page i of I l

References:

Design Review Report NOV-1000-87-004, Rev 1

Description:

Open item - V&V Design Review, Section 3.4.3 Trend plot "off-scale" indication does not d.i.ffer from "on-scale" indicati.on at limits of trend plot y-axis scale.

Disposition:

Digital value on Trend gives actual.. indicaiton. Trend graph will trun white at actual inst'ument r over range conditions. This is consistant with DM-491 Rev 1 and M13-STP-003-4Ec-1076 tested configuration.

Disposition Prepared b - A /2 /

V& V Review:

~/

A ~

/

r /N/

Disposition Verified: _/ /

Signature Date

l:

HOPE'CR?AK GENCRATING.STATIOM SPDS V&V DISCREJMCY REPORT Discrepancy No: 275 Date: 9 / 21 / 88 Page / .of /

References:

1) Design Review Report, NOV-1000-87-004, Rev.1 i

l-

Description:

Open Item - V&V Design Review, Section 3.4.4, 3.4.5 Inconsistencies between'CDM-0484-0 and CDM-0491-0 regarding display features required and implemented.

Disposition: DM-484 will be updated to DM-491, Rev.1 display features. DM-491 provides basis for displayed functions.

Disposition Prepared  : 8 / Z$/ / [g V & V Review L

x

(

[ h / [~[ / F8 Disposition Verified: / /

Signature Date

1 HOPE CREEK GEN 5 RATING STATION-SPDS V&V DISCREPANCY REPORT Discrepancy No: 276 _ Date: 09 ~/~21' 2 88 Page / of- /

References:

Design Review Report NOV-1000-87-004, Rev 1

.l

=j j

Description:

t Open item - V&V Design Review, Section'3.5.1 Incorrect description in CDM-0491-0 regarding SPDS-failure indication.

t Disposition:

DM-491 Rev 1 describes the failure modes.of SPDS as tested in M13-STP-003-4EC-1076.

i 1:

1 1

. Disposition Prepared -

f__ / 2k/((

V & V Review

( (

/ /d7 /hh Disposition Verified: ._ / /

t Signature . Date

b--

(.

HOPE' CREEK GENERATING STATION

'SPDS VSV DISCREPANCY REPORT j Discrepancy.No: 277 Date: 09' /'21- '/ 8 8 ___

Page I of. l

References:

l Design Review Report.NOV-1000-87-004, Rev 1 l

Description:

Open item - V&V Design Review, Section 3.6.1 Verification of class lE isolaiton via optical isolators.

i l

l' Disposition:

Verification and justificaiton for use of class lE isolation-Fiber Optic Reciever Transmitters is documented in DCP 9 of DCR 4EC-1076. This DCP also issued the FSAR change for the new isolation device.

i.

V & V Review- / /

Disposition Verified r /N  !

Sign [ture Date

HOPE CREEK GENERATING STATION-SPDS V&V DISCREPANCY REPORT Discrepancy.No: 278 Date: 09 / 21 / 88 Page / of f

References:

Design Review Report NOV-1000-87-004, Rev 1 '

Description:

Open item - V&V Design Review, Section 3.7.1 Verification that SPDS design and installation was performed per approved plant procedures.

Disposition:

SPDS design and installation was accomplished via GM8-EMP-009 which is approved by PSE&G.

Disposition Prepared b - / 2h/

V & V Review. _ / d7 /H Disposition Verified b h/ 2~7/N Signatu're -

Date S

. HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 279 Date: 09 / 21 '/ 88 -

Page 'l - of /

References:

Design Review Report NOV-1000-87-004, Rev 1

Description:

Open item - V&V Design Review, Section 3.7.2 Verificaiton that SPDS Lesson Plan is procedurally controlled'to reflect EOP revisions.

Disposition:

EOP changes that result in changes to the SPDS computer are controlled by GM8-EMP-009 which has appropriate reviews and signoffs to ensure the training center maintains configuration control.

Disposition Prepared b : 7 / 2k/

V & V Review /17 / 9F ,

Disposition Verifie b / 27 /

Signa (ture -

Date

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT l l

Discrepancy No: 280 Date: 09' /'21 / 88 Page '/' of /

References:

' Design Review. Report NOV-1000-87-004, Rev 1 f l

Description:

Open item - V&V Design Review, Section 3.8.1 Reliability analysis unavailable for review.

I Disposition:

Reliability calculation are being performed via -!

GM8-EMP-005 to document the system reliability.

'I1 Disposition Prepar b-  ! f / 2h/

V & V Review

  • I t

/ N / hk Disposition Verified: / /

Signature -

Date L_______________-- - -

1

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 281 Date: 9 / 21 / 88 Page / of /'

References:

1) Design Review Report NOV-1000-87-004, Rev.'l .

Description:

Open Item - V&V Design Review, Section 3.11.1 Human factors report unavaiable for review.

Disposition: Telecon with Essex Corp. indicates'that.no open item will be identified in the Human Factors Final Report. This item is considered closed pending receipt of the final report titled

" REVIEW OF SAFETY PARAMETER DISPLAY SYSTEM" Essex document # 880926.

i

.l Disposition Prepared by- / / ,

V & V Review

! I

/ 2.-7 / N Disposition Verified: / /

L- - _ _ _ _ _ _ _ _ _

i HOPE CREEK GENERATING STATION SPDS-V&V DISCREPANCY REPORT

-Discrepancy No.. 281 Date: 09'/21./88 Page _l of . l-1

References:

'l)' Design Review Report, ::OV-1000-87-004, . Rev. 1 2) 3)

Description:

Open' item- V&V Design Review, Section 3.8.2 l

Verification of program to document SPDS operating experience to establish actual system reliability.

l i

i Disposition:

The process to document actual system reliability is by the use of system log books. This is documented in VPM-MSP-010.

I Disposition Prepared By: ] flk V&V Review: W ff 9/tf/pf k

Disposition Verified (( Signatute Date de/124

i

< HOPE CREEK GENERATING STATION

, SPDS V&V DISCREPANCY REPORT Discrepancy No. 283 Date: 04 /15-/88 Page / of l_ '

References:

1). Design Review Report, NOV-1000-87-004', Rev.~l _

2) 3)

Description:

Open Item-- V&V Design Review, Section 3.12.2' Verification that vendor recommended periodic maintenance has been incorporated in plant procedures.

Disposition:

Vendor maintenance procedure NOVA-PMP-001 will be incorporated by PSE&G for periodic maintenance on system.

I l

Disposition Prepared .:  ! k'N(h V&V Review- x U t.

( <

Disposition Verified:

sigria tu r e vate dr/117

( -

HOPE CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: 284 Date: 09 / 21 / 88 Page I of f

References:

Design Review Report NOV-1000-87-004, Rev 1

Description:

Opem iteln - V&V Design Review, Section 3.12.1 Verificaiton that no additional operating staff is needed to ,

operate SPDS during normal / abnormal operation deferred to validation testing.  ;

Disposition:

This item remains open pending completion of procedure DE-CP.SPC-0010 " Hope Creek SPDS SIMULATOR DYNAMIC PERFORMANCE TEST" Disposition Prepa e ys s d / 2k/

Vi V Review -

// / /

'l (

Disposition Verified: / /

Signature -

Date L__________

-4 HOPE. CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT Discrepancy No: -285- Date: 09 / 21 / 88 Page / of / -

i

References:

Design Review Report NOV-1000-87-004, Rev 1 1

Description:

l Open item --V&V Design Rev.icw, Section 3.13.1 Verificaiton that'each applicable CPDS feature is tested.

l l

Disposition:

M13-STP-003-4EC-1076 Enclosure E provides Test Reference Matrix between requirement vs Test procedure and step.

\

l Disposition Prepared b A t/ / /

V&VReview.O _ / 27/ d l Disposition V rified A / 2_7 /&

Signatur'e Date

' HOPE' CREEK GENERATING STATION SPDS V&V DISCREPANCY REPORT I

I l Discrepancy Noi 286 Date: 09 / 21 / 88 Page / of l-l'

References:

' Design Review Report NOV-1000-87-004, Rev l~

Description:

Open item - V&V Design Review, Section 3.1.5, 3.1.9

- Verification'that CFPM alarm conditions are annunciated elsewhere in the control room deferred to validation testing.

- Verification of EOP/SPDS walkthrough of transient l scenarios.

Disposition:

This item remains open pending completion of man in the loop test DE-CP.SPC-0010. ,

Disposition Prepared b - f / [k /

V& V Review i

x

(

/ [.7 / N Disposition Verified: / /