Text
September 18, 1989
' Docket No. 50-313 Mr. T. Gene Campbell Vice President, huclear Arkansas Power and Light Company Post Office Box 551 Little Rock, Arkansas 72203
Dear Mr. Campbell:
SUBJECT:
SAFETY EVALUATION, COMPLIANCE WITH ATWS RULE 10 CFR 50.62 REQUIREMENTS, ARKANSAS NUCLEAR ONE, UNIT (TAC N0. 62122)
The staff has concluded that the ATWS design proposed by Arkansas Power and Light for Arkansas Nuclear One, Unit 1 (ANO-1) is in compliance with the ATWS Rule requirements of 10 CFR 50.62 paragraph (c)(1) and (c)(2). Paragraph (c)(1) defines the requirements for the ATWS Mitigation System Actuation Circuitry (AMSAC); paragraph (c)(2) defines the requirements on the subject Diverse Scram System design. This conclusion is based upon information provided in your submittals dated October 9, 1985, December 16, 1988, and April 26, 1989.
It is our understanding that the Anticipated Transients Without Scram (ATWS) modifications for ANO-1 will be implemented during the ninth refueling outage planned for late summer - early fall 1990. You should proceed on this schedule even though the staff has not yet completed its review of the use of Technical Specifications for ATWS requirements. Based on the enclosed Safety Eialuation, TAC No. 62122 is considered closed.
Sincerely,
/s/
C. Craig Harbuck, Project Manager Project Directorate IV Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation
Enclosure:
As stated cc w/ enclosure:
See next page DISTRIBUTION
'" Docket tile.
NRC PDR Local PDR PD4 Reading G. Holahan ADR4 F. Hebdon P. Noonan OGC-Rockville C. Harbuck E. Jordan B. Grimes ACRS (10)
PD4 Plant File f0(
DOCUMENT NAME: ANO LTR/62122 l
/
PD4/L-PD4/PM PD4/Dh PNoor}
CHarbuck:bj FHebddn 09//<//89 09/17/89 09/1h/89
$72[$b$ $$$
Jf P
6,*
- y -.
'(h76 Zij A
[fi**<
UNITED STATES NUCLEAR REGULATORY COMMISSION n
5
'p WASHINGTON, D. C. 20555
....+/
September 18, 1989
' Docket No. 50-313 Mr. T.-Gene Campbell Vice President, Nuclear
. Arkansas Power and Light Company Post Office Box 551 Little Rock, Arkansas 72203
Dear Mr. Campbell:
SUBJECT:
SAFETY EVALUATION, COMPLIANCE WITH ATWS RULE 10 CFR 50.62 REQUIREMENTS, ARKANSAS' NUCLEAR ONE, UNIT (TAC NO. 62122)
The sthff has concluded that the ATWS design proposed by Arkansas Power and Light.for Arkansas Nuclear One, Unit 1 (ANO-1) is-in compliance with the ATWS Rule.requirementsof.10CFR50.62 paragraph (c)(1)and(c)(2).
Paragraph (c)(1),
defines the requirements for the ATWS Mitigation System Actuation Circuitry (AMSAC); paragraph (c)(2) defines the requirements on the subject Diverse Scram System design. - This conclusion is based upon information provided in your submittals-dated October 9,'1985 December 16, 1988, and April 26, 1989.
It is our understanding that the Anticipated Transients Without Scram (ATWS) modifications for ANO-1 will be implemented during the ninth refueling outage planned for late summer - early fall 1990. Ycu should proceed on this schedule even though the staff has not yet completed its review of the use of Technical Specifications for ATWS requirements. Based on the enclosed Safety Evaluation, TAC No. 62122'is considered closed.
Sincerely,
?
C. Craig Harbuck, Project Manager Project Directorate IV Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation L
Enclosure:
As stated cc w/ enclosure:
-See next page N
'g.
-' k' z.
f Mr.;T. Gene Campbell
. Arkansas Power.& Light Company-Arkansas-Nuclear One, Unit 1 t
1 i
.cc:'
l i
- Mr. Early Ewing,- General Manageri i
. Technical Support and Assessment Arkansas Nuclear One-P. O. Box 608 Russellville, Arkansas 72801 i
Mr. Nie'l Carns Director-Nuclear Operations
' Arkansas Nuclear One i
i
.P. O. Box 608' 72801 Russellville, Arkansas' Mr. Nicholas S. Reynolds
> Bishop, Cook, Purcell & Reynolds
-1400 L Street, N.W.
Washington, D.C..
20005-3502 Mr. Robert B. Borsum Babcock & Wilcox-Nuclear. Power Generation Division 1700 Rockville Pike, Suite 525.
Rockville,= Maryland 20852
' Senior Resident ~ Inspector U.S. Nuclear Regulatory Commission
- 1. Nuclear Plant Road
. Russellville, Arkansas 72801 Regional Administrator,' Region IV I
U.S. Nuclear Regulatory Commission Office of Executive Director for Operations 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 l
Honorable Joe W. Phillips i
- County Judge of Pope County
-Pope County Courthouse Russellville, Arkansas 72203 g,
l Ms. Greta Dicus, Director
~ Division of. Environmental Health Protection Arkansas Department of Health 4815 West Markam Street Little Rock, Arkansas 72201 i