ML20246L193

From kanterella
Jump to navigation Jump to search
Requests Addl Info to Continue Review of Amend 1 to NEDO-21617, Analog Transmitter/Trip Unit Sys for Engineered Safeguard Sensor Trip Units, in Order to Complete Review
ML20246L193
Person / Time
Site: Brunswick 
Issue date: 04/27/1978
From: Parr O
Office of Nuclear Reactor Regulation
To: Sherwood G
GENERAL ELECTRIC CO.
Shared Package
ML20246L184 List:
References
NUDOCS 8903230310
Download: ML20246L193 (3)


Text

1 NEDO-21617-A UNITED STATE 5

[

e*g NucksAR REGULATORY cOMMisslON j' s

  • C,

i wasamoton, o. c. nosos

{-

g..:.../

UE Central Files - Topical Reports t.

General Electric Company ATTN: Dr. G. G. Sherwood, Manager Safety and Licensing 175 Curtner Avenue San Jose, California 95114 1

Gentlemen:

NED0-21617, " ANALOG TRANSMITTER / TRIP UNIT SYSTEM FOR

SUBJECT:

ENGINEERED SAFEGUARD SENSOR TRIP INPUTS" We have reviewed.%nendment No.1 to the subject report and find that The Enclosure we need additional information to complete our review.

contains our request for additional information.

Please infom us of $he date you plan to provide the requested'

)

If you wish to discuss the matters of the Enclosure, infonnation.

please contact us.

Sincerely,

. P'ar$ Chief Light Water Reactors Branch No. 3 Divir, ion of Project Management

Enclosure:

Request for Additional

)

Infomation cc w/ enclosure:

i Mr. L. Gifford General Electric Company 4720 Montgomery Lane Bethesda, Maryland 20014 l) m2pgggggg.

P e

_ mym g-

~ ~ * '

NEDO-21617-A ENCLOSURE (D

REQUEST FOR ADDIT 10tlAL INFORMATION ON ANALOG TRANSMITTER / TRIP UNIT SYSTEM NE00-21617_

32.21 The respanse to question 032.11 is incomplete and unacceptable.

The d

I staff's review of GESSAR included a review of the automatic depressuri -

~

zation system (ADS) function and the proposed pressure relief function in BWR/6 plants.

These functions were designed with dual logics in l

each division of the' system equipment, specifically Logics "A" and 4

"E" in division 1 and Logics "B" and "F" in division 2.

A coincidence of the 2 logics of either division will actuate the system.

These within division logics are designed to meet the si,,ngle failure ' criterion in order to pr, event inadvertent actuation of ADS or pressure relief.

Therefore, provide a complete description which demonstrates how the l

above stated design basis is implemented for those portions.of the logics within the Analog Transmitter / Trip Unit System.

Include appro-priate electrical and physical diagrams as necessary in responding to lg this concern.

I 32.22 The response to question 032.18 on equipment qualification is not acceptable.

l In order for the staff to evaluate the qualification of the analog i

transmitter / trip unit system equipment included on the topical report, we require that the qualification information, which is currently required by the staff on all licensing applications, be provided.

(

i i

i b._

.._.....--:,...__.,.,..w,,,..,,y7,,,.,,,._

4...

l

NEDO-21617-A l

2-N

.s i

Therefore, provide a description of (1) how each piece of equipment has been qualified to IEEE 323-1974; (2) the acceptance criteria; (3) test I

procedures; and (4) test results.

9 I

e d

e l

e i

,