1 NEDO-21617-A UNITED STATE 5
[
e*g NucksAR REGULATORY cOMMisslON j' s
- C,
i wasamoton, o. c. nosos
{-
g..:.../
UE Central Files - Topical Reports t.
General Electric Company ATTN: Dr. G. G. Sherwood, Manager Safety and Licensing 175 Curtner Avenue San Jose, California 95114 1
Gentlemen:
NED0-21617, " ANALOG TRANSMITTER / TRIP UNIT SYSTEM FOR
SUBJECT:
ENGINEERED SAFEGUARD SENSOR TRIP INPUTS" We have reviewed.%nendment No.1 to the subject report and find that The Enclosure we need additional information to complete our review.
contains our request for additional information.
Please infom us of $he date you plan to provide the requested'
)
If you wish to discuss the matters of the Enclosure, infonnation.
please contact us.
Sincerely,
. P'ar$ Chief Light Water Reactors Branch No. 3 Divir, ion of Project Management
Enclosure:
Request for Additional
)
Infomation cc w/ enclosure:
i Mr. L. Gifford General Electric Company 4720 Montgomery Lane Bethesda, Maryland 20014 l) m2pgggggg.
P e
_ mym g-
~ ~ * '
NEDO-21617-A ENCLOSURE (D
REQUEST FOR ADDIT 10tlAL INFORMATION ON ANALOG TRANSMITTER / TRIP UNIT SYSTEM NE00-21617_
32.21 The respanse to question 032.11 is incomplete and unacceptable.
The d
I staff's review of GESSAR included a review of the automatic depressuri -
~
zation system (ADS) function and the proposed pressure relief function in BWR/6 plants.
These functions were designed with dual logics in l
each division of the' system equipment, specifically Logics "A" and 4
"E" in division 1 and Logics "B" and "F" in division 2.
A coincidence of the 2 logics of either division will actuate the system.
These within division logics are designed to meet the si,,ngle failure ' criterion in order to pr, event inadvertent actuation of ADS or pressure relief.
Therefore, provide a complete description which demonstrates how the l
above stated design basis is implemented for those portions.of the logics within the Analog Transmitter / Trip Unit System.
Include appro-priate electrical and physical diagrams as necessary in responding to lg this concern.
I 32.22 The response to question 032.18 on equipment qualification is not acceptable.
l In order for the staff to evaluate the qualification of the analog i
transmitter / trip unit system equipment included on the topical report, we require that the qualification information, which is currently required by the staff on all licensing applications, be provided.
(
i i
i b._
.._.....--:,...__.,.,..w,,,..,,y7,,,.,,,._
4...
l
2-N
.s i
Therefore, provide a description of (1) how each piece of equipment has been qualified to IEEE 323-1974; (2) the acceptance criteria; (3) test I
procedures; and (4) test results.
9 I
e d
e l
e i
,