Jump to navigation Jump to search
Special Rept:On 890521,Channel 6 of Steam Generator 1B Loose Parts Monitor Sys Inoperable for More than 30 Days.Caused by Loose Wiring or Faulty Accelerometers.Work Request 506860PS Written to Investigate & Repair Channel
ML20246G007
Person / Time
Site: Catawba 
Issue date: 07/06/1989
From: Tucker H
DUKE POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 8907140122
Download: ML20246G007 (2)


Text

s

.,; K d

' (/h 1) y g' i

J Duge POWER COMPDT

.[ ;q '

' ~. P.O. HOX 33189 i-

%N,'

GLAMLOTTE. N.C. 28242 7g[HALH.YUCKER

..g m.nowe

-g.

vms reemment (704) 373 % 531-gy, mum nca enoperman

lj

. July 6, 1989 Document Control Desk U. S. Nuclear Regulatory Commission Washington, D. C.

20555

Subject:

Catawba Nuclear Station, Unit 1 Docket No. 50-413 Special Report Gentlemen:

Pursuant to Technical Specificat.lon 3.3.3.9, please find attached a Specia1 Report concerning the inoperability of Channel No. 6'of the Catawba Unit i Vibration-and Loose Parts Monitor System for more than thirty days. Channel No.~ 6.

.was declared. inoperable on May 21, 1989. This report was schedulled for submittal to the NRC on June 30, 1989. I apologice for the slight' delay.

- Very'truly yours, b.

B. Tucker b

JGT/3/SR9-54 xc:

Mr. S. D. Ebneter Regional Administrator, Region II U. S. Nuclear Regulatory Commission 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323 Mr. W. T. Orders NRC Resident Inspector Catawba Nuclear Station 89071401g(($o3Its PDR ADO PDC S

)

e,v,

\\

I CATAWBA NUCLEAR STATION, UNIT 1

)

SPECIAL REPORT I

INOPERABILITY OF CHANNEL No. 6 OF THE STEAM GENERATOR IB

)

l LOOSE PARTS MONITOR SYSTEM 1

i On May 21, 1989 Channel No. 6 of the Catawba Nuclear Station Unit 1 Steam Generator IB Vibration and Loose Parts Monitor System was declared inoperable.

The inoperability of Channel No. 6 was discovered by Operations personnel when i

the Channel emitted c 60 cycle signal after being selected for indication.

{

Previous malfunctions of this system at Catawba Nuclear Station involved loose 4

wiring, loose connections, or faulty accelerometers.

Channel No. 10 of the Unit 1 Steam Generator 1A is operable. Therefore, a redundant channel is available. Work request 506860PS was written to investigate and repair the channel. The repair will be ca:.ied out during a future outage of sufficient duration. This work is to be performed during an outage due to Channel No. 6 being located in the steam generator cavity. This cavity is inaccessible during power operation because of radiological considerations.

The inoperability of Channel No. 6 for more than 30 days is reportable pursuant to Catawba Technical Specification 3.3.3.9.

l l

I

. _ _ _ - _ _ _ - - _ _ _ _ _ _ -