APPENDIX B
.C&D Charter Power Systems Incorporated
~
Plymouth. Meeting, Pennsylvania NOTICE OF NONCONFORMANCE l
Based on the results of an NRC inspection conducted on May 8-11, 1989, it appears that certain of your activities were not conducted in accordance with NRC requirements.
2 Nonconformance i
B.1 Criterion III of Appendix'B to 10 CFR Part 50 states in part:
" Design changes...shall be subject to design control measures commensurate with those applied to the original design...."
Quality System Program Policy Manual, Revision K, dated December 7,1987, i
Section 2.1.2.1 states, in part, " Engineering shall verify product design by similarity, emperical calculations and/or tests."
Contrary to the above, prior to being notified by Limerick Generating i
Station, Unit 1 C&D CPS did not test latest revision of replacement circuit boards at the battery charger final acceptance test to verify i
that the output of the battery charger would meet specification requirements.
(89-01-02)
B.2 Criterion V of Appendix B to 10 CFR Part 50 states: " Activities affecting quality shall be prescribed by documented instructions, procedures, or
.I drawings, of a type appropriate to the circumstance and shall be accomplished in accordance with these instructions, procedures, and or drawings.
Instructions, procedures, or drawings shall include l
appropriate quantitative or qualitative acceptance criteria for l
determining that important activities have been satisfactorily I
accomplished."
1.
Quality System Program Policy Manual, Revision K, dated December 7, 1987, Section 4.2 states in part: " Engineering and/or Quality Assurance shall prepare detailed... test procedures which include the characteristics / criteria necessary to produce the product to the required standards...."
Contrary to the above, final acceptance test procadure TP-9503, paragraph 4.6, dated January 13, 1984 states: " Set the current limit at 115 percent of rated output unless otherwise specified on release,"
i but does not specify how this is accomplished.
(89-01-03) l 8907130114 890710 PDR QA999 EMVCDBAT 99900765 FDC
C&D Charter Fh;er System.
Incorporated Plymouth Heeting, Pennsylvania 2.
Quality System Program Policy Manual, Revision K, dated December 7, 1987 Section 4.8.2 states:
" Quality Assurance shall maintain records of' inspections and tests performed to assure compliance to the applicable quality requirements in accordance with respective proce-dures.
Such records include as minimum; date, personnel performing the inspection or tests; material, part or product identity, quanti-ties inspected, accepted / rejected; test results; disposition."
Contrary to the above, C&D CPS QA records or Bill of Materials did not identify the value of the pre-load resistors used in the final acceptance test for battery chargers shipped to Limerick Generating Station, Unit 1.
(89-01-04)