ML20246B136
| ML20246B136 | |
| Person / Time | |
|---|---|
| Site: | Sequoyah |
| Issue date: | 08/17/1989 |
| From: | Lapoint J TENNESSEE VALLEY AUTHORITY |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| NUDOCS 8908230263 | |
| Download: ML20246B136 (2) | |
Text
_
b TENNESSEE VALLEY AUTHORITY Sequoyah Nuclear Plant P.O. Box 2000 Soddy-Daisy Tennessee 37379 August 17, 1989 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C.
20555 Gentlemen:
In the Matter of
)
Docket Nos. 50-327 Tennessee Valley Authority
)
50-328 SEQUOYAH NUCLEAR PLANT (SON) - TECHNICAL SPECIFICATION (TS) 3.7.11.1.B.1 NOTIFICATION On August 16, 1989, at 1109 Eastern daylight time (EDT), with both units at 100 percent power, limiting condition for operation (LCO) 3.0.5 was entered because of inoperability of all four diesel generators. The diesel generatore had been declared inoperable the previous day (August 15, 1989) at 1109 EDT because of lack of performance of an adequate surveillance test on the fuel oil in the 7-day fuel oil tanks; the extension afforded by Surveillance Requirement (SR) 4.0.3 was employed. LCO 3.0.5 was entered upon expiration of the 24-hour extension, since the surveillance test had not yet been completed. At that time, the four high-pressure fire pumps were accordingly declared inoperable, and action statement 3.7.11.1 was entered.
Initial notification of the event was reported by telephone at 1457 EDT on August 16, 1989, in accordance with action statement b.2.b of TS 3.7.11.1.
The surveillance test on the fuel oil was successfully completed, and the diesel generators and fire pumps were returned operable at 1451 EDT, August 16, 1989.
If you have any questions concerning this submittal, please telephone M. A. Cooper at (615) 843-6651.
Very truly yours.
TENNESSEE VALLEY AUTHORITY
\\
J. T. LaFoint Site Director l
cc: See page 2 V
f,C 8908230263 890817 pm ADOCK 05000327 FDC g
An Equal Opportunity Employer
_2_
U.S. Nuclear Regulatory Comission August 17, 1989 cc: Ms. S. C. Black, Assistant Director for Projects TVA Projects Division U.S. Nuclear Regulatory Comission One White Flint, North 11555 Rockville Pike Rockville, Maryland 20852 Mr. B. a. Wilson, Assistant Director for Itapection Programs TVA Projects Division U.S. Nuclear Regulatory Commission Region II 101 Marietta Street, NN, Suite 2900 Atlanta, Georgia 30323 NRC Resident Inspector Sequoyah Nuclear Plant 2600 Igou Ferry Road Soddy Daisy, Tennessee 37379 l
. _ _ _ _ _ _ _ - _ _