SUBJECT:
Alternate Compensatory i Measures Instituted Per FPOR-16 1
REFERENCES:
- 1) PSC letter, 1
i Williams to Doc.
Control Desk, dated March 16, 1989 (P-89077) i
- 2) NRC letter, Heitner to Williams, dated May 18, 1989 (G-89185)
Gentlemen:
Per (,ur commitment made in Reference (1), this letter submits a copy of Engineering Evaluation EE-FP-0015B and its 10 CFR 50.59 Safety Evaluation for your review and approval. This eveluation involves using a bearing water pump not previously qualified for use in Fire Protection Shutdown /Cooldown Train A per Fire Protection Operability Requirement FPOR-16.
Train A includes the use of Bearing Water Pumps P-2101 and P-2106 to supply bearing water to the operating circulator when this train is used for fire protection shutdown /cooldown.
These pumps were qualified as reliable for this use, in part, based on meeting equipment and electrical separation / segregation criteria defined in Appendix R of 10 CFR 50, as applicable per the Fort St. Vrain Fire Protection Program Plan (FPPP), which was approved by the NRC in Reference (2).
8906300266 890615 PDR ADOCK 05000267 A,
i F
PNU
>M g6h A
b
'I w
Y W-
\\
P-89231 June 15, 1989 EE-FP-0015B evaluates using P-2101-S in combination with P-2101 or P-2106 when the need arises.
It was determined that P-2101-S meets proper equipment separation.
However, adequate electrical cable separation from Train B components does not exist.
EE.FP-0015B and its Safety Evaluation conclude that P-2101-S ma)- be used in combination with P-2101 or P-2106, with certain compensatory
- measures, to meet Train A requirements per FPOR-16.
Please see the attached evaluations for more information.
Should you have any questions or comments concerning this issue, please contact Mr. M. H. Holmes at (303) 480-6960.
Very truly yours, 42.. & !ll A. Clegg Crawford Vice President Nuclear Operations ACC/GMK/km Attachment cc: Regional Administrator, Region IV ATTN: Mr. T. F. Westerman, Chief Projects Section B Mr. Robert Farrell Senior Resident Inspector Fort St. Vrain