Forwards AEOD Technical Rept Re Mispositioning of Reverse Acting Valve Controllers
ML20245B680
Person / Time
Site: Susquehanna Talen Energy icon.png
Issue date: 12/03/1987
From: Stewart J
NRC OFFICE FOR ANALYSIS & EVALUATION OF OPERATIONAL DATA (AEOD)
To: Rosenthal J
NRC OFFICE FOR ANALYSIS & EVALUATION OF OPERATIONAL DATA (AEOD)
Shared Package
ML20245B685 List:
References
NUDOCS 8904260219
Download: ML20245B680 (1)


Text

-. -. - -. - - - - -

- -. = _. -.. - - -.

4 f%,#

Doq 0,

UNITED STATES i

8 k

NUCLEAR REGULATORY COMMISSION 7.

E WASHINGTON, D. C. 20555

'+4 r

December 3,1987 MEMORANDUM FOR: Jack E. Rosenthal, Chief Reactor Operations Analysis Branch Division of Safety Programs, AE0D THRU:

George F. Lanik, Chief Reactor Systems Section GE and CE Reactor Operations Analysis Branch Division of Safety Programs, AEOD FROM:

Joseph P. Stewart, Reactor Systems Engineer Reactor Systems Section GE and CE Reactor Operations Analysis Branch Division of Safety Programs, AE0D

SUBJECT:

MISPOSITIONING OF " REVERSE ACTING" VALVE CONTROLLERS I

A copy of the subject AE0D technical review report is enclosed. This study was initiated in response to an event at Susquehanna Unit 2 which involved controllers of service water regulating valves for room coolers. The investigation of this event of mispositioning of the " REVERSE ACTING" valve controllers found:

I.

If a loss-of-coolant-accident occurred while the valve controllers were mispositioned, and the accident made the controllers inaccessible, then the LPCI and core spray system could become inoperable because of overheated switchgear.

2.

The licensee's corrective actions were adequate and appropriate.

A data search for similar events of mispositioning of " REVERSE ACTING" controllers causing both trains of safety systems to become inoperable during postulated accidents was negative. Therefore, this report finalizes and concludes the investigation of the event, n

Joseph P. Stewart, Reactor Systems Engineer Reactor Systems Section GE and CE Reactor Operations Analysis Branch Division of Safety Programs, AE0D fnclosures: As stated cc w/ enclosure:

//

L. Gifford, GE

$ //

R. Borsum, B&W

[

C. Brinkman, CE I

M. Beaumont, W POQ,._.

(

_