Ack Receipt of Util 861212 Proposed Amend to Physical Security Plan,In Response to Miscellaneous Amends & Search Requirements.Response to Encl Comments Requested within 30 Days from Ltr Receipt
ML20238D801
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 09/03/1987
From: Hopkins J
Office of Nuclear Reactor Regulation
To: Nauman D
SOUTH CAROLINA ELECTRIC & GAS CO.
References
TAC-65321, NUDOCS 8709110403
Download: ML20238D801 (3)


Text

.

L8M E0 d33 I

Docket No. 50-395 Mr. D.A. Nauman Vice President - Nuclear Operationc South Carolina Electric & Gas Company P.O. Box 764 (Mail Code 167)

Columbia, South Carolina 29218

Dear Mr. Nauman:

SUBJECT:

MISCELLANEOUS AMENDMENTS / SEARCH REQUIREMENTS VIRGIL C. SUMMER STATION (TAC #65321)

This is to acknowledge receipt of the South Carolina Electric and Gas Company letter, dated December 12, 1986, which transmitted a proposed a:aendment to the Virgil C. Summer Station Physical Security Plan, in response to the Miscellaneous Amendments and Search Requirements.

The submitted document has been reviewed and we have determined that additional information and~ revisions to the plan are required prior to our approval.

The enclosed comn.ents are based upon pertinent NRC regu-lations and published guidance describing methods, acceptable to the NRC staff. for implementing specific parts of those regulations.

i It is requested that you provide your response to these comments within 30 days from receipt of this letter.

The reporting and/or record keeping requirements contained in this letter affect fewer than ten respondents; therefore, OMB clearance is not required under P.L.96-511.

Should you have any questions concerning the enclosed comments, please contact the reviewer, Barry Manili, at (301) 492-7077.

Sincerely, Jon B. Hopkins, Project Manager Project Directorate II - 1 Division of Reactor Projects I/II Office of Nuclear Reactor Regulation

Enclosure:

DISTRIBUTION W/ ENCLOSURES:

Physical Security Plan Comments RSGB rf Sec rf BManili CBuracker (2) cc w/ enclosure:

Region II PAnderson 1

See next page JHopkins LDocket= Filet 50 395 N Case File NRC"PDR' 8709110403 870903 RErickson Local PDR PDR ADOCK 05000395 LBush F

PDR 0FC

RSp
RSGB
RSGB tf

. : _ _ _ _ _f_g _ _ _ : RSGB:PD II,

.3

/ :PD II-1

,gg

CBurack{ed
LBush ~
REr Kson
PAnde(on
JHopkins NAME :BMahili

_____.____________.____________.____________.___s DATE$(/1/87

$ 8/h87

$f/[/87

$f//

7

$$/3 /87

./3/87

Mr. D. A. Nauman-South Carolina Electric & Gas Company Virgil C. Sumer. Nuclear Station cc:

Mr. William A. Williams, Jr..

Technical Assistant - Nuclear. Operations Santee Cooper P.O. Box 764 (Mail Code 167)

Columbia, South Carolina 29218 J. B. Knotts, Jr., Esq.

Bishop, Liberman, Cook, Purcell and Reynolds 5b36 ig n l

Resident Inspector / Summer NPS c/o U.S. Nuclear Regulatory Commission l

Route 1, Box 64 Jenkinsville, South Carolina 29065 l

.i Regional Administrator, Region II U.S. Nuclear Regulatory Commission, 101 Marietta Street, N.W., Suite 2900 Atlanta, Georgia 30323 Chainnan, Fairfield County Council

)

P.O. Box 293 i

i Winnsboro, South Carolina 29180 Attorney General Box 11549 Columbia, South Carolina 29211 Mr. Heyward G. Shealy, Chief

)

Bureau of Radiological Health j

South Carolina Department of Health j

and Environmental Control 2600 Bull Street Columbia, South Carolina 29201 i

_1-_

__E___.____._zj

Docket No. 50-395 COMMENTS ON PHYSICAL SECURITY PLAN CHANGES (MISCELLANE0US AMENDMENTS AND SEARCH REQUIREMENTS)

VIRGIL C. SUMMER NUCLEAR STATION Provide a schedule for implementing the amended safeguards requirements within 180 days after Commission approval of the proposed security plan.

4 Reference 10 CFR 73.55.

Stipulate that in a plant safety emergency, reasonable action may be-taken to suspend any safeguards measures in accordance with 10 CFR j

50.54(x) and (y) when this action is immediately needed to protect the 1

public health and safety.

Reference 10 CFR 73.55(a) and Generic Letter 87-08 (Q&A #2).

4 State that vital area access controls will not be dropped for life I

threatening situations not involving public health and safety.

Reference 10 CFR 50.54(x) and (y) and Generic Letter 87-08 (Q&A #3).

i Provide a commitment that the search requirements will be implemented within 60 days after Commission approval of the proposed revisions.

l Reference 10 CFR 73.55(d)(1).

1 d

h Provide a commitment that if security force members leave the protected j

area to perform official duties subsequent to their initial entry and search, they will be searched prior to re entry into the protected area if they have not been under direct observation or accompanied by another member of the security force.

Reference 10 CFR 73.55(d)(1) and Generic i

l Letter 87-08 (Q&A #11).

l Expand the commitment on page 1-37-A to ensure prompt access to vital equipment to accommodate the potential need for rapid ingress or egress i

of individuals during emergency conditions or situations.

Indicate how this prompt access will be ensured (e.g., by issuing override keys to appropriate operators and security force members at the start of each shift, or by other acceptable means).

Reference 10 CFR 73.55(d)(7)(ii) and Generic Letter 87-08 (Q&A #6).

'f Provide a commitment that the secondary power supply systems for both the i

alarm annunciator equipment and non portable communications equipment i

shall be located within a vital area.

Reference 10 CFR 73.55(e)(1) and Generic Letter 87-08 (Q&A #16).

Indicate what additional components of the secondary power supply system i

I will be protected as vital.

Reference 10 CFR 73.55(e)(1) and Generic Letter 87-08 (Q&A #18).

Revise the commitment on page 13-3 to maintain a log indicating name, l

badge number, time of entry, and time of exit of all individuals granted l

access to a vital area except those individuals entering or exiting the reactor control room.

Reference 10 CFR 73.70(d).