George S. Thomas Ql vice mesoeni.wuci.o, moem -
NYN-87137 gggg New Hampshire Yankee Division November 30, 1987 United States'. Nuclear Regulatory Commission Region I 631 Park-Avenue King of Prussia. PA 19406 Attention:
Mr. William T. Ruseell Regional Administrator
References:
-(a)
Facility Operating License NPF-56, Construction Permit CPPR-136, Docket Nos. 50-443 and 50-444
.(b)
IE. Bulletin 85 03 " Motor-Operated Valve Common Mode Failures During Plant Transients Due to Improper Switch Settings," dated November 15, 1985 (c)
PSNH Letter (SBN-1052) dated May 15,19t'6, ' Response to IE'Bulletin 85-03," G. S. Thomas to Dr. T. E. Murley, Jr.
Subject:
Response to IE'Bulletin 85-03
Dear Sir:
In accordance with the requirements of IE Bulletin 85-03, enclosed is the report for Seabrook Station on matters relating to motor opera.ted valves.
Should you have any questions regarding this information, please contact Mr. Warren'J. Hall at (603) 474-9574 extension 4046.
Very truly yours, Geor
. Thomas Enclosures I
cc Document Control Desk United States Nuclear Regulatory Connission Washington, DC 20555 Mr. Victor Nerses, Project Manager l
Project Directorate I-3
]
Division of Reactor Projects United States Nuclear Regulatory Commission Washington, DC 20555 Mr. A. C. Cerne NRC Senior Resident Inspector Seabrook Station
.)
Seabrook, NH 03874 8712040453 871130 sk PDR ADOCK 05000443 f
G PDR P.O. Box 300. Seabrook, NH 03874. Telephone (603) 474-9574
______._________________________________J
1 STATE OF NEW HAMPSHIRE
{
Rockingham, ss.
November 30, 1987 Then personally appeared before me, the above-named George S. Thomas who, being duly sworn, did state that he is Vice President - Nuclear Production of Public Service Company of New Hampshire, that he is duly authorized to execute and file the foregoing information in the name and on the behalf of Public i
Service Company of New Hampshire, and that the statements therein are true to f
the best of his knowledge and belief.
sabu b bmnwu Beverly E.-4111oway, Notarygublic Hy Commission Expires: March 6, 1990 l
l l
l 1
'l l
ENCLOSURE 1 TO NYN-87137 l
REPORT FOR IE BULLETIN 85-03 On May 15, 1986, Reference (c) was submitted as the initial response to IE Bulletin 85-03, ' Motor-Operated Valve Common Mode Failures During Plant Transients Due to Improper Switch Settings".
Thirty motor-operated valves were identified for evaluation in accordance with the requirements outlined in the Bulletin.
This report describes the evaluations performed and results achieved to date with regard to the thirty identified valves.
Program Descriptions l
l As stated in Reference (c), design criteria was obtained from Westinghouse and i
I United Engineers and Constructors (UE&C) for the thirty identified valves.
l This information was used in a calculation which defined a maximum and minimum 4
thrust for each valve. The interval between the maximum and minimum calculated thrust values is referred to hereinafter as the " calculated range."
The Seabrook Station Motor-Operated Valve Analysis and Test System (MOVATS) and other methods were employed to measure actual thrust values for each valve to verify that the measured thrusts fell within the calculated ranges. An engineering review of the test results was performed. As a result of the engineering review, five categcries were defined as shown below; and each valve wac placed in the most appropriate category.
CATEGORY CATEGORY DESCRIPTION I
MOVs which require immediate actions operability cannot te declared.
II MOVs which are operable but should receive performance improvements.
III MOVs which are operable but are being evaluated for optional performance improvements.
IV MOVs which are operable and require no performance improvements.
V MOVs which are operable but require alternate test methods for verification. to this report contains a Summary Report Data Sheet for each of the thirty identified valves.
The data sheets are grouped in accordance with the above categories.
1 of 2
Eight emergency feedwater valves are placed in Category V because they are equipped with motor operators manufactured by Rotork, Inc.
These Rotork operators utilize an unbalanced spring pack in their design.
During the course of our program, it was discovered that the MOVATS test equipment, as i
provided, was partially incompatible with the unique Rotork operator design.
l As a result, it was not possible to obtain all the test data required by the j
Bulletin utilizing MOVATS equipment alone.
Two attempts were made by MOVATS i
Inc. to produce compatible test equipment for this application; but these i
devices failed to produce acceptable results. Therefore, New Hampshire Yankee (NHY) working in conjunction with a subvendor developed suitable test j
equipment to test the Rotork operators. An ongoing effort is in progress to perfect this equipment and validate its test results. As such, data presented in this report for these Category V valves is preliminary.
Switch adjustments will not be made until the test method has been verified. Justification for 1
continued operation of these eight valves is provided in the preface to the Category V grouping of Summary Report Data Sheets in Enclosure 2.
Program Results:
In accordance with the requirements of IE Bulletin 85-03, each of the thirty motor operated valves identified in Reference (c) has been verified operable by the following review and test programs:
- 1) Maximum practical differential pressure testing.
2)
Design basis review as documented by Reference (c).
j
- 3) Calculated ranges established for maximum performance.
- 4) Verification of correct setpoints using one or more of the below test methods:
a) MOVATS testing.
j b) Westinghouse design criteria.
c) NHY procedure for limit switch setting.
d) Testing performed at vendor facilities.
As stated in Reference (c), fifteen percent of the identified valves will be inspected and tested every refueling outage.
Tests will be performed using NHY precedures and signature analysis technology to the extent possible.
In addition, a procedure has been developed to acquire data at motor control centers.
This procedure will be utilized whenever major maintenance is performed on these motor operated valves. A trending program, using data acquired at MCC's, is planned for these MOVs but cannot be incorporated at this time due to developmental problems with software.
It is currently planned to implement this program as soon as the software demonstrates an established confidence level.
Open action items are identified in Enclosure 3 of this report.
2 of 2
I l
l l
ENCLOSURE 2 TO NYN-87137 1
-m___m_m___--_.___
i CATEGORY I MOVs WHICH REQUIRE IMMEDIATE ACTION OPERABILITY CANNOT BE DECLARED (THERE ARE NO VALVES IN THIS CATEGORY)
CATEGORY II MOVs WHICH ARE OPERABLE BUT SHOULD RECEIVE PERFORMANCE IMPROVEMENTS The MOVs assigned to this category have open action items identified.
These open action items have been evaluated and categorized as performance improvements. A detailed description of each open action iten is provided in the Summary Report Data Sheet.
Each MOV has been successfully demonstrated operable by testing under maximum practical DP conditions during the startup l
test program, i
SUMMARY
REPORT DATA SHEETS FOLLOW FOR VALVE TAG ID NUMBERS:
1-CS-LCV-112D 1-FW-V-346 1-FW-V-347 1-SI-V-89 1-SI-V-93
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-CS-LCV-112D Valve Function:
RWST to Charging Pump A Isolation Valve ID (Manuf.)
Westinghouse Model 08002GM82FBB000 Type Ga:e Size (in.)
8 Rating (psi) 150 Valve Operator (Manuf.)
Limitoraue/W EMD Model SMB-00 Output Speed Motor Speed (RPM) 1.700 (RPM)
Not available 1
Design Basis DP (psi)
Open 200 Close 200 Test DP (psi)
Open 17 Close 17 As Found Switch Settings Open 2.5 Close 2.5 Final Switch Setting Open 2.5 Close 2.5 As Found Thrust (lbs.)
Open 3,457 Close 4.191 Final Thrust (lbs.)
Open 5.611 Close 5.697 Maximum Design Thrust (lbs.)
10.500 Open Torque Switch Bypass Setting (I)
As Found 6.8 l
As Left 21 1
As'found valve condition and corrective actions taken:
- 1) Excessive grease in spring pack - removed excessive grease and cleaned.
2)
Bypass setting 6.8% - increased to 21% by design modification.
- 3) Open and close thrust below calculated ranges - spring pack suspected of being out of specification:
See open action item and comment.
Open Action Item:
Remove, disassemble, and inspect the spring pack cartridge to determine if it is within specification. Reassemble, and reinstall the spring pack and perform MOVATS testing. The spring pack will be replaced if it cannot be i
restored to within specifications.
Tracking Document:
87 RES 1017.
Comments:
This valve was demonstrated operable during maximum practical DP testing.
The open action item stated above is considered to be a performance improvement.
IE BULLETIN 85-03 l
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-FW-V-345 I
Valve Function EFW Pump A Recirculation Isolation Valve ID (Manuf.)
Velan Model B12-7074P-02TS Type Globe Size (in.)
4 l
Rating (psi) 900 Valve Operator (Manuf.)
Limitorque Model SMB-00 Output Speed Motor Speed (RPM) 1,700 (RPM)
Not available Design Basis DP (psi)
Open 1,596 Close 1,596 Test DP (psi)
Open 1,357 Close 1,237 As Found Switch Settings Open 2.0 Close 2.0 l
Final Switch Setting Open 2.0 Close 2.0 As Found Thrust (lbs.)
Open 8.640 Close 9,160 Final Thrust (lbs.)
Open 8,860 Close 8,800 Maximum Design Thrust (1bs.)
14,000 Open Torque Switch Bypass Setting (I)
As Found 4.8 As Left 20.4 As found valve condition and corrective actions taken:
- 1) Valve backseating - adjusted open limit switch.
2)
Bypass setting 4.8% - increased to 20.4% by design modification.
,0 pen Action Item Perform MOVATS testing during DP conditions.
Tracking Document: Work Request 87W005693.
I Comments:
The calculated minimum thrust value is not yet available.
Further diagnostic testing under dynamic conditions shall be performed to assist in the calculation of a minimum thrust value.
This valve has been demonstrated operable under maximum practical DP conditions.
i IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET 1
)
Valve I.D.:
1-FW-FV-347 Valve Function:
EFW Pump B Recirculation Isolation Valve ID (Manuf.)
Velan Model B12-7074P-02TS Type Globe Size (in.)
4 Rating (psi) 900 Valve Operator (Manuf.)
Limitorque Model SMB-00 Output Speed Motor Speed (RPM) 1,700 (RPM)
Not available Design Basis DP (psi)
Open 1.596 Close 1.596 Test DP (psi)
Open 1,540 Close 1,540 As Found Switch Settings Open 2.0 Close 2.0 Final Switch Setting Open 2.0 Close 2.0 As Found Thrust (lbs.)
Open 10,000 Close 10.806 Final Thrust (1bs.)
Open 10,440 Close 10,060 Maximum Design Thrust (lbs.)
14,000 Open Torque Switch Bypass Setting (%)
As Found 5.1 As Left 23.7 As found valve condition and corrective actions taken:
1)
Bypass setting 5.1% - increased to 23.7% by design modification.
Open Action Item:
Perform MOVATS testing during DP conditions.
Tracking Document: Work Request 87W005694.
Comments:
The calculated minimum thrust value is not yet available. Further diagnostic testing under dynamic conditions shall be performed to assist in the calculation of a minimum thrust value. This valve has been demonstrated operable under maximum practical DP conditions.
I
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET I
l Valve I.D.:
1-SI-V-89 Valve Function:
SI Pump B Recirculation Isolation Valve ID.(Manuf.)
Velan/ Westinghouse Model 1.5TM78FN Type Globe Size (in.)
1-1/2 l
Rating (psi) 1.500 Valve Operator (Manuf.)
Limitorque Model SMB-00 Output Speed Motor Speed (RPM) 1,700 (RPM)
Not available Design Basis DP (psi)
Open 2.750 Close 2.750 Test DP (psi)
Open 900 Close 900 As Found Switch Settings Open _ 1.5 Close 1.0 Final Switch Setting Open
_,1.5 Close 1.5 As Found Thrust (lbs.)
Open 10.296 Close 12.055 Final Thrust (lbs.)
Open 11.920 Close 11.284 Maximum Design Thrust (lbs.)
14.000 Open Torque Switch Bypass Setting (%)
As Found 20.6 As Left 20.6 As found valve condition and corrective actions taken:
- 2) Close torque switch had irregular continuity - removed, cleaned and reinstalled switch.
Open Action Item:
Install a new torque switch limiter plate.
Increase the close torque switch setting to achieve a thrust value greater than 11,800 lbs but less than 14,000 lbs. Tracking Document:
87 RES 882.
Comments:
This valve was demonstrated operable during maximum practical DP testing.
The open action item stated above is considered to be a performance improvement.
IE BULLETIN 85 '
SUMMARY
REPORT DATA SHEET Valve I.D.:
'1-SI-V-93
. Valve Function:
SI Pumps Common Recirculation Isolation Valve-ID (Manuf.)
Velan/ Westinghouse Model 2TM78FN Type Globe Size (in.)
2 Rating (psi) 1,500 Valve Operator'(Manuf.)
Limitorque/W EMD Model SMB-00 Output Speed
. Motor Speed (RPM) 1,700 (RPM)
Not available Design Basis DP (psi)
Open 2,750 Close 2,750 Test DP (psi)
Open 900 Close 900 As Found Switch Settings Open 1.5 Close 1.5 Final Switch Setting Open 1.5 Close 1.5
.As Found Thrust (lbs.)
Open 11,693 Close 9.931 Final-Thrust (1bs.)
Open 10,532 Close 11.132
' Maximum Design Thrust (1bs.)
14,000 Open Torque Switch Bypass Setting (I)
As Found 23 As Left 23 As found valve condition and corrective actions taken:
- 1) Valve backseating - adjusted open limit switch.
i
- 2) As left thrust below calculated range.
Open Action Item:
Install a new torque switch limiter plate. Increase the close torque switch setting to achieve a thrust value greater than 11,800 lbs. but less than 14,000 lbs.
Tracking Document:
87 RES 881.
' Comments:
This valve was demonstrated operable during maximum practical DP testing.
The open' action item stated above is considered to be a performance improvement.
CATEGORY III l
MOVs WHICH ARE OPERABLE BUT ARE BEING EVALUATED FOR OPTIONAL PERFORMANCE IMPROVEMENTS MOVs in this category developed actual thrust values at the torque switch trip setpoint which exceeded the calculated maximum thrust but were below the maximum design thrust.
It was verified that each valve had successfully been tested under dynamic conditions during the startup test program and would perform its intended safety function.
These valves will be the subject of further engineering evaluations.
If'it is identified that a lover torque switch setting is preferred, the torque switch setting will not be lowered until the valve can be tested under dynamic conditions.
SUMMARY
REPORT DATA SHEETS FOLLOW FOR VALVE TAG ID NUMBERS:
1-CBS-V-53 1-CS-LCV-112E 1-SI-V-111 1-SI-V-112 1-SI-V-114 1-SI-V-139
]
l l
1 l
l l
l l
1
1 IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET.
j Valve I.D.:
1-CBS-V-53 i
Valve Function:
RWST to SI Pump B Suction Isolation Valve ID (Manuf.)
Westinghouse Model 06001GM92FBB000 Type Gate Size (in.)
6 Rating (psi) 150 Valve Operator (Manuf.)
Limitorque/W EMD Model SMB-000 Output Speed Motor Speed (RPM) 1.700 (RPM)
Not available Design Basis DP (psi)
Open 200 Close 200 Test DP (psi)
Open Close As Found Switch Settings Open 2.0 Close 2.0 Final Switch Setting Open 2.0 Close 2.0 As Found Thrust (lbs.)
Open 9.898 Close 7.687 Final' Thrust (lbs.)
Open 9.949 Close 7.485 Maximum Design Thrust (1bs.)
~10.400 Open Torque Switch Bypass Setting (%)
As Found 28 As Left 28 As found valve' condition and corrective actions taken:
- 1) Operator would not stay latched in manual - adjusted mechanism.
Comments:
Valve not required to operate under dynamic conditions, l-L l
l.
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-CS-LCV-112E Valve Function:
RWST to Charging Pump B Suction Isolation Valve ID (Manuf.)
Westinghouse Model 08002GM82FDB000 Type Gate Size (in.)
8 Rating (psi) 150 Valve Operator (Manuf.)
Limitorque/W EMD Model SMB-00 Output Speed Motor Speed (RPM) 1.700 (RPM)
Not available Design Basis DP (psi)
Open 200 Close P00 Test DP (psi)
Open 17 Close 17 As Found Switch' Settings Open 2.5 Close 2.5 Final Switch Setting Open 2.5 Close 2.5 As Found Thrust (lbs.)
Open 9,932 Close 9.623 Final Thrust (lbs.)
Open 10,018 Close 9.366 Maximum Design Thrust (lbs.).
10.600 Open Torque Switch Bypass Setting (!)
As Found 6.7 As Left 20.4 As found valve condition and corrective actions taken:
- 2) Bypass setting 6.7% - increased to 20.4% per design modification.
l 1
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-SI-V-111 Valve Function:
SI Pump B Discharge Cro4> Connect Isolation Valve ID (Manuf.) _. Westinghouse Model 04002GM87FHB Type Gate Size (in.)
4 Rating (psi) 900 Valve Operator (Manuf.)
Limitorque/V EMD Model SB-00 Output Speed Motor Speed (RPM) 1.700 (RPM)
Not available Design Basis DP (psi)
Open 1.750 Close 1.750 Test DP (psi)
Open 1.600 Close 1.600 As Found Switch Settings Open 2.0 Close 2.0 Final Switch Setting Open 2.0 Close 2.0 As Found Thrust (lbs.)
Open 16.324 Close 15.196 Final Thrust (1bs.)
Open 15,353 Close 15.729 Maximum Design Thrust (lbs.)
16.000 Open Torque Switch Bypass Setting (I)
As Found 38 As Left 38 l
l l
As found valve condition and ccrrective actions taken:
- 1) Excessive grease in spring pack - removed excessive grease and cleaned.
l
- 2) Operator would not stay latched in manual - adjusted mechanism.
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET l
l l
Valve I.D.:
1-SI-V-112 Valve Function:
SI Pump A Discharge Cross Connect Isolation Valve ID (Manuf.)
Westinghouse Model 04002GM87FHB Type Gate Size (in.-)
4 Rating (psi) 900 Valve Operator (Manuf.)
Limitoraue/W EMD Model SMB-00 Output Speed Motor' Speed (RPM) 1.700 (RPM)
Not available Design Basis DP (psi)-
Open 1,750 Close 1.750 Test-DP (psi)
Open 1,600 Close 1.600 As Found Switch Settings Open 2.0
'Close.
2.0 Final Switch Setting Open 2.0 Close 2.0 As Found Thrust'(lbs.)
Open 16.059 Close 12.199 Final Thrust (lbs.)
Open 15.659-Close 15.145 Maximum Design Thrust (lbs.)
16.000 Open Torque Switch Bypass Setting (I)
As Fonnd 37 As Left 37 As found valve condition and corrective actions taken:
- 1) Lubrication degradation found in spring pack area - degraded lubricant removed; further sampling of gear housing produced satisfactory findings.
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-SI-V-114 Valve Function:
__SI Pumps Discharge to Cold Legs Isolation Valve ID (Manuf.)
Westinghouse Model 04002GM88FNB Type Gate Size (in.)
4 Rating (psi) 1,525 Valve Operator (Manuf.)
Limitorque Model SB-00 Output Speed Motor Speed (RPM) 1,700 (RPM)
Not avellable Design Basis DP (psi)
Open 2,750 Close 850 Test DP (psi)
Open 1,600 Close 1,600 As Found Switch Settings Open 1.5 Close 1.5 Final Switch Setting Open 1.5 Close 1.5 As Found Thrust (lbs.)
Open 8,440 Close 16,020 Final Thrust (lbs.)
Open 13,500 Close 13,140 Maximum Design Thrust (1bs.)
14,700
/
Open Torque Switch Bypass Setting (I)
As Found 38 As Left 38 As found valve condition and corrective actions taken:
- 1) Limit switch contacts and fingers coated with grease - removed grease and cleaned contacts.
- 2) Declutch lever would not latch into manual - adjusted mechanism.
r
IE BULLETIN 85-03
(
SUMMARY
REPORT DATA SHEET l
Valve I.D.:
1-SI-V-139 Valve Function:
High Head Safety Iniection Header Isolation Valve Valve ID (Manuf.)
Westinghouse Model 04002GM88FNB010 Type Gate Size (in.)
4 l
Rating (psi)
.2,500 Valve Operator (Manuf.)
Limitorque/W EMD Model SB-00 Output Speed Motor Speed (RPM) 1,800 (RPM)
Not Available Design Basis DP (psi)
Open 2.750 Close 850 Test DP (psi)
Open 1,350 Close 1,350 As Found Switch Settings Open 1.75 Close Final Switch Setting Open 1.75 Close As Found Thrust (lbs.)
Open 14,304 Close 12.160 Final Thrust (lbs.)
Open 14.304 Close 12,180 Maximum Design Thrust (lbs.)
14,600 Open Torque Switch Bypass Setting (I)
As Found 37.5 As Left 37.5 As found valve condition and corrective actions taken:
- 1) Declutch lever would not latch in manual - adjusted mechanism.
- 2) Spring compensator cover gasket found torn - gasket will be replaced when material has been received from the vendor.
Comments:
The close torque switch is not wired into the control circuit by Westinghouse design.
The close thrust is set by limit switch setpoint which corresponds to a stem nut deflection.
The as-found and as-left stem nut deflections meet the Westinghouse acceptance criteria.
)
l
CATEGORY IV MOVs WHICH ARE OPERABLE AND REQUIRE NO PERFORMANCE IMPROVEMENTS
SUMMARY
REPORT DATA SHEETS FOLLOW FOR VALVE TAG ID NUMBERS:
1-CBS-V-47 1-CBS-V-49 1-CBS-V-51 1-CS-LCV-112B 1-CS-LCV-112C 1-CS-V-142 1-CS-V-143 1-CS-V-196 1-CS-V-197 1-CS-V-90 l
l l'
I
l l
(
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-CBS-V-47 Valve Function:
RWST to SI Pump A Suction Isolation Valve ID (Manuf.)
Westinghouse Model 08002GM82FBB000 Type Gate Size (in.)
8 Rating (psi) 200 Valve Operator (Manuf.)
Limitorcue/W EMD Model SMB-00 Output Speed Motor Speed RPM 1.800 (RPM)
Not available D sign Basis DP (psi)
Open 200 Close 200 Close Test DP (psi) rpen As Found Switch Settings Open 2.25 Close 2.25 Final Switch Setting Open 2.25 Close 2.25 As Found Thrust (lbs.)
Open 5.965 Close 7.826 Final Thrust (lbs.)
Open 8.688 Close 8.061 Maximum Dsign Thrust (lbs.)
11.000 Open Torque Switch Bypass Setting (I)
As Found 4.5 As Left 21 As found valve condition and corrective actions taken:
- 1) Excessive grease in spring pack - removed excessive grease and cleaned.
- 2) Valve backseating - adjusted open limit switch.
3)
Bypass setting 4.5% - increased to 21% per design modification.
Comments:
Valve not required to operate under dynamic conditions.
l l
l
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET l
Valve I.D.:
1-CBS-V-49 Valve Function:
RWST to SI Puap A Suction Isolation l
Valve ID (Manuf.)
Westinghouse Model 0600lGM92FBB000 Type Gate Size (in.)
6 Rating (psi) 150 Valve Operator (Manuf.)
Limitorqua/W EMD Model SMB-000 Output Speed Motor Speed (RPM) 3.400 (RPM)
Not available Design Basis DP (psi)
Open 200 Close 200 Test DP (psi)
Open Close As Found Switch Settings Open 3.0 close 3.0 Final Switch Setting Open 2.5 Close 2.5 As Found Thrust (lbs.)
Open 6,604 Close 6,714 Final Thrust (lbs.)
Open 6.226 Close 6,540 Maximum Design Thrust (lbs.)
8,000 Open Torque Switch Bypass Setting (%)
As Found 27 As Left 27 As found valve condition and corrective actions taken:
- 1) Excessive grease in spring pack - removed excessive grease and cleaned.
- 2) One operator bolt missing - installed missing bolt and tightened the remaining three.
Comments:
Valve not required to operate under dynamic corditions.
i
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-CBS-V-51 Valve Function:
RWST to SI Pump B Suction Iso 18 tion Valve ID (Manuf.)
Westinghouse Model 080020M82FBB000 Type Gate Size (in.)
8 Rating (psi) 150 Valve Operator (Manuf.)
Limitorque/W EMD Model SMB-00 Output Speed Motor Speed (RPM) 1,700 (RPM)
Not available Design Basis DP (psi)
Open 200 Close 200 Close Test DP (psi)
Open As Found Switch Settings Open 1.5 Close 1.5 Final Switch Setting Open 1.5 Close 1.5 As Found Thrust (lbs.)
Open 8,634 Close 8,230 Final Thrust (1bs.)
Open 8,548 Close 8.340 Maximum Design Thrust (lbs.)
9,400 Open Torque Switch Bypass Setting (I)
As Found 21 As Left 21 As found valve condition and corrective actions taken:
- 1) Excessive grease in spring pack - removed excessive grease and cleaned.
- 2) Declutch lever would not latch in manual - adjusted mechanism.
Comments:
- Valve not required to operate under dynamic conditions.
l
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-CS-LCV-112B Valve Function:
VCT to Charging Pumps Suction Isolation Valve ID (Manuf.)
Westinghouse Model C4000GM82FBB000 Type Gate Size (in.)
4 Rating (psi) 150 Valve Operator (Manuf.)
Limitorque/W EMD Model SB-00 Output Speed Motor Speed (RPM) 3.400 (RPM) __ Not available Design Basis DP (psi)
Open 200 Close 200 Test DP (psi)
Open 24 Close 22 As Found Switch Settings Open 2.0 Close 1.75 Final Switch Setting Open 2.0 Close 1.75 As Found Thrust (lbs.)
Open 9.267 Close 12.556 Final Thrust (ibs.)
Open 10,643 Close 8.849 Maximum Design Thrust (lbs.)
14.000 Open Torque Switch Bypass Setting (%)
As Found 38.7 As Left 38.7 As found valve condition and corrective actions taken:
- 1) Excessive grease in spring pack - removed excessive grease and cleaned.
- 2) Declutch lever would not latch in manual - adjusted mechanism.
- 3) Broken tripper 12, worn cam, and bent tripper #1 - replaced damaged components.
I l
l l
l
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-CS-LCV-112C Valve Function:
VCT to Charging Pumps Suction Isolation Valve ID (Manuf.)
Westinghouse Model 04C00GM82FBB000 Type Gate Size (in.)
4 1
Rating (psi) 150 Valve Operator (Manuf.)
Limitoraue/W EMD Model SB-00 Output Speed Motor Speed (RPM) 3.400 (RPM)
Not available Design Basis DP (psi)
Open 200 Close 200 Test DP (psi)
Open 21 Close 20 As Found Switch Settings Open 2.0 Close 1.75 Final Switch Setting Open 2.0 Close 1.75 As Found Thrust (lbs.)
Open 5.331 Close 8.108 Final Thrust (lbs.)
Open 6.730 Close 5.838 Maximum Design Thrust (1bs.)
14.000 Open Torque Switch Bypass Setting (2)
As Found 37.5 As Left 37.5 As found valve condition and corrective actions taken:
No abnormal conditions noted.
l
,s_--_
I i
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-CS-V-142 l
Valve Function:
Normal Charging Header / Containment Isolation Valve ID (Manuf.)
Westinghouse Model 03001GM99FNB000 Type Gate Size (in.)
3 Rating (psi) 2,035 Valve Operator (Manuf.)
Limitorque/W EMD Model SB-00 Output Speed Motor Speed (RPM) 3,400 (RPM)
Not available Design Basis DP (psi)
Open 2.750 Close 2.750 Test DP (psi)
Open 1,500 Close 2,600 As Found Switch Settings Open 1.5 Close Final Switch Setting Open 1.5 Close As Found Thrust (lbs.)
Open 11.355 Close
<5,380 Final Thrust (lbs.)
Open 11,629 Close 8,196 Maximum Design Thrust (lbs.)
16,000 Open Torque Switch Bypass Setting (Z)
As Found 43.5 As Left 43.5 As found valve condition and corrective actions taken:
- 1) Jumper wire between LS-4 and LS-5 found loose at tenminal 4 - tightened connections.
- 2) Excessive grease in spring pack - removed excessive grease and cleaned.
- 3) Close thrust below calculated range - close limit switch adjusted to increase closing thrust to within the calculated range.
Comments:
- This valve closes on limit switch control - the torque switch is not wired into the close control circuit.
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:'
1-CS-V-143 Valve-Function:
Normal-Charging Header Isolation Valve ID (Manuf.)-
Westinghouse Model 03001GM99FNB000 Type-Gate Size-(in.)
3 Rating (psi) 2.035 Valve Operator'(Manuf.)
Limitorque/W EMD Model SB-00 Output Speed Motor Speed (RPM)'
3.400 (RPM)
Not available Design Basie.DP (psi)
Open 2,750 Close 2.750 Test DP- (psi)
Open 1.500 Close 2.670 As Found Switch Settings Open 1.25 Close Final Switch Setting' Open 1.25 Close As Found Thrust-(1bs.)
Open 12.525 Close
<4.580 Final Thrust (lbs.)
Open 12,525 Close 10.289 Maximum Design Thrust (lbs.)
16,000 Open Torque Switch Bypass Setting (I)
As Found 48 As Left 48 As found valve condition and corrective actions taken:
- 1) Close thrust below calculate range - close limit switch adjusted to achieve a close thrust within the calculated range.
j comments:
This valve closes on limit switch control - the torque switch is not wired into the close control circuit.
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET I
Valve I.D.:
1-CS-V-196 i
i Valve Function:
Charging Pump A Recirculation Isolation Valve ID (Manuf.) Velan/ Westinghouse Model 2TM78FN Type Globe Size (in.)
2 Rating (psi) 1,500 Valve Operator (Manuf.)
Limitorque/W EMD Model SMB-00 Output Speed Motor Speed (RPM) 1,700 (RPM)
Not available Design Basis DP (psi)
Open 2,750 Close 2,750 Test DP (psi)
Open 1,500 Close 2,670 As Found Switch Settings Open 1.5 Close 1.5 Final Switch Setting Open 1.75 Close 1.75 As Found Thrust (lbs.)
Open 7.660 close 14,784 Final Thrust (lbs.)
Open 12,748 Close 13,080 Maximum Design Thrust (lbs.)
14,000 Open Torque Switch Bypass Setting (I)
As Found 27.6 As Left 27.6 As found valve condition and corrective actions taken:
- 1) Excessive grease in spring pack - removed excessive grease and cleaned.
- 2) Yoke to valve body bolts loose - tightened bolts.
- 3) Declutch lever would not latch into manual - adjusted mechanism.
- 4) Open thrust below calculated range - torque switch balanced and the settings increased to achieve thrusts within the calculated range.
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-CS-V-197 Valve Function:
Charging Pump B Recirculation Isolation Valve ID (Manuf.) Velan/ Westinghouse Model 2TM78FN Type Globe Size (in.)
2 Rating (psi) 1.700 Valve Operator (Manuf.)
Limitorque/W EMD Model SMB-00 Output Speed Motor Speed (RPM) 1.700 (RPM)
Not available Design Basis DP (psi)
Open 2.750 Close 2.750 Test DP (psi)
Open 17 Close 2.236 As Found Switch Settings Open 1.25 Close 1.5 Final Switch Setting Open 1.75 Close 2.0 As Found Thrust (lbs.)
Open 9.606 Close 10.941 Final Thrust (lbs.)
Open 12.123 Close 12.736 Maximum Design Thrust (lbs.)
14,000 Open Torque Switch Bypass Setting (I)
As Found 17 As Left 22 As found valve condition and corrective actions taken:
- 1) Excessive grease in spring pack - removed excessive grease and greased.
- 2) Dirty switch contacts - cleaned contacts.
- 3) Open thrust below calculated range - balanced torque switch and increased both the open and close torque switch settings to maintain the close thrust within the calculated range and put the open thrust within the calculated range.
4)
Bypass setting 17% - increased to 22Z by design modification.
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-SI-V-90 Valve Function:
SI Pump A Recirculation Isolation Valve ID (Manuf.) Westinghouse /Velan Model 1.5TM78FN Type Globe Size (in.)
1.5 Rating (psi) 1.500 Valve Operator (Manuf.)
Limitorque/W EMD Model SMB-00 Output Speed Motor Speed (RPM) 1.700 (RPM)
Not Availatie Design Basis DP (psi)
Open 2.750 Close 2.750 Test DP (psi)
Open 900 Close 900 As Found Switch Settings Open 1.4 Close 1.4 Final Switch Setting Open 1.4 Close 1.5 As Found Thrust (lbs.)
Open 11.310 Close 11.074 Final Thrust (lbs.)
Open 12.838 Close 12.601 Maximum Design Thrust (Ibs.)
14.000 Open Torque Switch Bypass Setting (%)
As Found 18 As Left 20.3 As found valve condition and corrective actions taken:
- 1) Valve backseating - adjusted open limit switch.
- 2) Bypass setting 18% - increased to 20.3% by design modification.
- 3) Open and close thrust slightly below calculated range - adjusted torque switch settings to achieve thrusts within the calculated range.
L
CATEGORY V MOVs WHICH ARE OPERABLE BUT REQUIRE ALTERNATE TEST METHODS FOR VERIFICATION
SUMMARY
REPORT DATA SHEETS FOLLOW FOR VALVE TAG ID NUMBERS:
1-FW-FV-4214A 1-FW-FV-4214B 1-FW-FV-4224A 1-FW-FV-4224B 1-FW-FV-4234A 1-FW-FV-4234B 1-FW-FV-4244A 1-FW-FV-4244B 1-SI-V-138 m.._...___.
PREFACE TO CATEGORY V The Rotork test data presented in this report is the result of a preliminary analysis of data acquired with test equipment developed by NHY. NHY is con-tinuing in its engineering efforts to perfect the test equipment and validate the test results.
HISTORY:
As the result of testing during the startup test program, the eight l
motor operators on these valves were removed and returned to their l
vendor (Rotork). At the manufacturer's facility, the units were disassembled and the spring packs were modified to increase the net output torque from 25 ft-lbs to the 40-45 ft-lbs range.
Each unit was calibrated and tested over its entire range of setting by the manufacturer.
The final setpoints were established and verified for each unit.
OPERABILITY VERIFICATION:
Each valve and motor operator was installed and set in accordance with NHY procedures. The torque switch setpoints were established by the vendor and have not changed since their return from the vendor.
Each valve and motor operator was tested under maximum practical DP conditions and demonstrated operable after the installation.
Initial attempts to perform MOVATS testing on the eight EFW isolation valves appear to have yielded questionable results.
For this reason, torque switch adjustments have not been made and will not be made until the NHY developed test equipment can be demonstrated reliable for both open and close data acquisition cycles.
CONCLUSION:
In accordance with the requirements of IE Bulletin 85-03, the proper switch settings have been established and set correctly by the manufacturer (Rotork Inc.) in coordination with the valve vendor (Masonellan).
Installation and setpoint verification was performed using NHY procedures.
Operability was then demonstrated at maximum practical differential pressure during the startup test program.
Alternate test methods are being pursued at this time. Until these methods have been perfected, operability will continue to be demonstrated using maximum practical differential pressure testing and/or MOVATS MCC testing each refueling outage.
l l
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-FW-FV-4214A Valve Function:
EFW Supply to Steam Generator A Isolation Valve ID (Manuf.)
Masoneilan Model 90-21114 Type Globe Size (in.)
4 Rating (psi) 900 Valve ID Operator (Manuf.
Rotork Model 11-NA1 Output Speed Motor Speed (RPM) 1,800 (RPM) 29 Design Basis DP (psi)
Open 1,650 Close 1,560 Test DP (psi)
Open 1.480 Close 1,475 As Found Switch Settings Open 3.25 Close 2.25 Final Switch Setting Open 3.25 Close 2.25 As Found Thrust (lbs.)
Open Close 5,930 **
Final Thrust (lbs.)
Open Close 5,930 **
Maximum Design Thrust (lbs.)
5,000 Open Torque Switch Bypass Setting (I)
As Found N/A ***
As Left N/A ***
As found valve condition and corrective actions taken:
- 1) Close thrust higher than the calculated maximum - manufacturer input being sought to assist in evaluation and recommend corrective action.
Comments:
Test fixture is under development for open direction testing.
Data is preliminary - see Preface.
Open torque switch is not bypassed by design.
l
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-FW-FV-4214B Valve Function:
EFW Supply to Steam Generator A Isolation i
Valve ID (Manuf.)
Masoneilan Model 90-21114 i
Type Globe Size (in.)
4 Rating (psi) 900 Valve Operator (Manuf.)
Rotork Model 11-NA1 Output Speed Motor Speed (RPM) 1,800 (RPM) 29 Design Basis DP (psi)
Open 1,650 Close 1,560 Test DP (psi)
Open 1,460 Close 1,450 As Found Switch Settings Open 3.0 Close 2.75 i
Final Switch Setting Open 3.0 Close 2.75 Close 5,216 **
As Found Thrust (lbs.)
Open Final Thrust (lbs.)
Open Close 5.216 **
Maximum Design Thrust (lbs.)
5,000 Open Torque Switch Bypass Setting (I)
As Found N/A ***
As Left N/A ***
As found valve condition and corrective actions taken:
- 1) Close thrust higher than the calculated maximum - manufacturer input being sought to assist in evaluation and recommend corrective action.
Comments:
Test fixture is under development for open direction testing.
- Data is preliminary - see Preface.
Open torque switch is not bypassed by design.
I I
l
7 l
l i
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-FW-FV-4224A Valve Function:
EFW Supply to Steam Generator B Isolation Valve ID (Manuf.)
Masonellan Model 90-21114 Type Globe Size (in.)
4 Rating (psi) 900 Valve Operator (Manuf.)
Rotork Model 11-NA1 Output Speed Motor Speed (RPM) 1,800 (RPM) 29 Design Basis DP (psi)
Open 1.650 Close 1,560 Test DP (psi)
Open 1,460 Close 1,455 As Found Switch Settings Open 2.75 Close 2.75 Final Switch Setting Open 2.75 Close 2.75 As Found Thrust (lbs.)
Open Close 4.599 **
Final Thrust (1bs.)
Open Close 4,599 **
Maximum Design Thrust (1bs.)
5,000 Open Torque Switch Bypass Setting (I)
As Found N/A ***
As Left N/A ***
As found valve condition and corrective actions taken:
No abnormal conditiens noted.
Comments:
)
Test fixture is under development for open direction testing.
l
- Data is preliminary - see Preface.
Open torque switch is not bypassed by design.
1 l
l l
1 1
1
\\
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-FW-FV-4224B
' Valve Function:1
'EFW Supply to Steam Generator B Isolation Valve ID (Manuf.)
Masonellan Model 90-21114 Type Globe Size (in.)
4 1
Rating (psi) 900 l
Valve Operator (Manuf.)
Rotork Model 11-NA1 Output Speed Motor Speed (RPM) 1.800 (RPM) 29 Design Basis DP (psi)
Open l'650 Close 1.560
)
Test DP (psi)
Open 1.460 Close 1.450 1
l As Found~ Switch Settings Open 3.0 Close 2.75 i
Final Switch Setting-Open 3.0 Close 2.75 i
As Found Thrust (lbs.)
Open Close' 7.749 **
Final Thrust (lbs.)
Open Close 7.749 **
Maximum Design Thrust (lbs.)
5.000 Open Torque Switch Bypass Setting (I)
As Found N/A ***
As Left N/A ***
As found valve condition and corrective actions taken:
- 1) Close thrust higher than the calculated maximum - manufacturer input being sought to assist in evaluation and recommend corrective action.
Comments:
Test fixture is under development for open direction testing.
- Data is preliminary - see Preface.
- . Open torque switch is not bypassed by design.
i e____
l
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-FW-FV-4234A
. Valve Function:
EFW Supply to Steam Generator C Isolation Valve ID (Manuf.)
Masonellan Model 90-21114 Type.
Globe Size (in.)
4 Rating (psi) 900 Valve Operator (Manuf.)
Rotork Model 11-NA1 Output Speed Motor Speed (RPM) 1,800 (RPM) 29 Design Basis DP (psi)
Open 1,650 Close 1.560 Test DP (psi)
Open 1.425 Close 1,420 As Found Switch Settings open 3.25 Close 2.75 Final Switch Setting Open 3.25 Close 2.75 Close 6,741 **
As Found Thrust (lbs.)
Open Final Thrust (lbs.)
Open Close 6,741 **
Maximum Design Thrust (lbs.)
5,000 1
Open Torque Switch Bypass Setting (%)
As Found N/A ***
As Left N/A ***
As found valve condition and corrective actions taken:
- 1) Close thrust higher than the calculated maximum - manufacturer input being sought to assist in evaluation and recommend corrective action.
I Comments:
Test fixture is under development for open direction testing.
Data is preliminary - see Preface.
Open torque switch is not bypassed by design.
I i
l l
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-FW-FV-4234B Valve Function:
EFW Supply to Steam Generator C Isolation Valve ID (Manuf.)
Masonellan Model 90-21114 Type Globe Size (in.)
4 l
Rating (psi) 900 Valve Operator (Manuf.)
Rotork Model 11-NA1 Output Speed Motor Speed (RPM) 1,800 (RPM) 29 Design Basis DP (psi)
Open 1,650 Close 1.560 Test DP (psi)
Open 1,430 Close 1,425 As Found Switch Settings Open 2.75 Close 2.75 Final Switch Setting Open 2.75 Close 2.75 As Found Thrust (lbs.)
Open Close 6.699 **
Final Thrust (lbs.)
Open Close 6,699 **
Maximum Design Thrust (1bs.)
5,000 Open Torque Switch Bypass Setting (I)
As Found N/A ***
As Left N/A ***
As found valve condition and corrective actions taken:
- 1) Close thrust higher than the calculated maximum - manufacturer input being sought to assist in evaluation and recommend corrective action.
Comments:
Test fixture is under development for open direction testing.
Data is preliminary - see Preface.
Open torque switch is not bypassed by design.
I i
I
l
)
IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET
- Valve I.D.:
1-FW-FV-4244A
. Valve Function:
EFW Supply to Steam Generator D Isolation Valve ID (Manuf.)
Masonellan Model 90-21114 Type Globe size (in.)
4 Rating (psi) 900
-Valve Operator (Manuf.)
,Rotork Model 11-NA1 Output Speed Motor Speed (RPM) 1,800 (RPM) 29 Design Basis DP (psi)
Open 1.650 Close 1.560 Test DP (psi)
Open 1.,440 Close 1.435 As'Found Switch Settings Open 2.75 Close 2.25 Final Switch Setting Open 2.75 Close 2.25 As Found Thrust (1bs.)
Open Close 7.081 **
Close 7.081 **
Final Thrust (lbs.)
Open Maximum Design Threit.(lbs.)
5.000 Open Torque switch Bypass Setting (Z)
As Found N/A ***
As Left N/A ***
-As found valve condition and corrective actions taken:
1)' Close thrust higher than the calculated maximum - manufacturer input being sought to assist in evaluation and recommend corrective action.
Comments:
Test fixture is under development for open direction testing.
Data is preliminary - see Preface.
- Open torque switch is not bypassed by design.
1 l
l l
E IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET Valve I.D.:
1-FW-FV-4244B l-Valve, Function:
EFW Supply to Steam Generator D Isolation l
Valve ID (Manuf.)
Masoneilan Model 90-21114 Type-Globe Size (in.)
o Rating (psi) 900 Valve Operator (Manuf.)
Rotork Model 11-NA1 Output Speed Motor Speed (RPM) 1,800 (RPM) 29 Design Basis DP (psi)
Open 1.650 Close 1.560
-Test DP (psi)
Open 1,480 Close 1,470 As Found Switch Settings Open 3.0 Close 2.75 Final Switch Setting Open 3.0 Close 2.75 As Found Thrust (lbs.)
Open Close 6.258 **
Final Thrust (lbs.)
Open Close 6,258 **
Maximum Design Thrust (lbs.)
5.000 Open Torque Switch Bypass Setting (Z)
As Found N/A ***
As Left N/A ***
As found valve condition and corrective actions taken:
- 1) Close thrust higher than the. calculated maximum - manufacturer input being sought to assist in evaluation and recommend corrective action.
Comments:
Test fixture is under development for open direction testing.
Data is preliminary - see Preface.
Open torque switch is not bypassed by design.
1 IE BULLETIN 85-03
SUMMARY
REPORT DATA SHEET
)
Valve'I.D.:
1-SI-V-138
)
Valve Function:
High Head Safety Iniection Isolation
{
Valve ID (Manuf.)
Westinghouse Model 04002GM88FNB010 Type Gate Size (in.)
4 Rating (psi) 2,500 Valve Operator (Manuf.)
Limitorque/W EMD Model SB-00 Output Speed Motor Speed (RPM) 1,800 (RPM)
Not available Design Basis DP (psi)
Open 2,750 Close 850 Test DP (psi)
Open 1,350 Close 1,350 As Found Switch Settings Open 1.0 Close N/A
- Final Switch Cetting Open 1.0 Close N/A
- As Found Thrust (lbs.)
Open Close Final Thrust (lbs.)
Open Close Maximum Design Thrust (lbs.)
14.600 Open Torque Switch Bypass Setting (I)
As Found 35.1 As Left 35.1 As found valve condition and corrective actions tak_e_n:
No abnormal conditions were noted.
Comments:
Due to local interference, portions of the MOVATS Test System could not be installed.
The close seating force applied to the valve by the motor operator is set by a limit switch setpoint based on a measured stem nut deflection (Westinghouse method).
This dimension was field verified to be 0.218 inches. This~is within the Westinghouse acceptance criteria between 0.20 and 0.28 inches.
The unseating force of the MOV is based on limit switch ectting for the first 35.1I.
Full locked rotor power is available to unseat the valve for 35.1% of its open stroke.
The valve has been demonstrated operable during the phase one testing program under DP conditions.
Based on the testing and setting methods described above, this valve and motor operator are set correctly and the requirements of IE Bulletin 85-03 are satisfied.
Switch s'etpoints are set in accordance with Westinghouse requirements.
Thrust values meet the Westinghouse acceptance criteria for stem nut deflection. All other parameters were verified using the motor operated valve analysis and test system.
)
ENCLOSURE 3 TO NYN-87137 l
l l
)
I i
1 l
l l[
OPEN ACTION ITEMS
SUMMARY
REPORT The following is a summary of open action items.
It is anticipated that all open action items will be resolved by the end of the first refueling outage.
Revised summary report data sheets will be submitted on or before that time.
OPEN ACTION TAG ID #
DESCRIPTION TRACKING ITEM DOCUMENT 1
1-CS-LCV-112D Unresolved Spring Pack Question 87 RES 1017 2
1-FW-V-346 MOVATS Data During Max Practical DP WR87 WOO 5693 3
1-FW-V-347 MOVATS Data During Max Practical DP WR87W005694 4
1-SI-V-89 Increase Close Thrust 87 RES 882 5-1-SI-V-93 Increase Close Thrust 87 RES 881 6
1-FW-FV-4214A Confirm Station Developed Test Method NYN-87137 1-FW-FV-4214B Confirm Station Developed Test Method NYN-87137 1-FW-FV-4224A Confirm Station Developed Test Method NYN-87137 1-FW-FV-4224B Confirm Station Developed Test Method NYN-87137 1-FW-FV-4234A Confirm Station Developed Test Method NYN-87137 1-FW-FV-4234B Confirm Station Developed Test Method NYN-87137 1-FW-FV-4244A Confirm Station Developed Test Method NYN-87137 1-FW-FV-4244B Confirm Station Developed Test Method NYN-87137 I