Text

_ - _ - _ _

July 23, 1987 Docket No. 50-133 l

Mr. J. D. Shiffer, Vice President l

Nuclear Power Generation, Licensing Pacific Gas and Electric Company i

77 Beale Street, Room 1451 San Francisco, California 94106

Dear Mr. Shiffer:

SUBJECT:

REQUEST FOR ADDITIOW1 INFORMATION, HUMBOLDT BAY POWER PLANT UNIT N0. 3 By letter dated April 29, 1987 we issued our Safety Evaluation Report (SER) for the Humboldt Bay Power Plant, Unit No. 3 Decommissioning.

In that SER we determined that your Decommissioning Plan and proposed Technical Specifications (TS) were acceptable. Since that time, however, our regional staff has reviewed your proposed TS with respect to their inspection programs and has concluded that certain changes would improve surveillance, clarify the TS requirements and reduce misunderstandings during these inspections.

Enclosures 1 and 2 identify changes in the TS that Region V and NRR staff agree are needed.

We have determined that these changes should be made as part of our action on your proposed decommissioning plan. Therefore, we request your response within 30 days of the date of this letter.

The reporting and/or recordkeeping requirements contained in this letter affect fewer than ten respondents; therefore, OMB clearance is not required under P.L.96-511.

I Sincerely, original signed by Peter B. Erickson, Project Manager Standardization and Non-Power B707300485 870723 Reactor Project Directorate PDR ADOCK 05000133 Division of Reactor Projects III, IV, G

PDR V and Special Projects Office of Nuclear Reactor Regulation i

Er.sosures:

As stated I

cc w/ enclosure:

l See next page l

DISTRIBUTION:

l

? Docket. File _

PErickson EJordan EHylton l

NRC & Local PDR HBerkow JPartlow PDSNP Reading 0GC-BETH ACRS (10)

PDSN{

PDSNP PDS g EHy ton PErick

  • HBerWw 07b}G/87 07/])/8h 07/79/87 l

1

i U

'SQ C4Gg

'o UNITED STATES 8(

g NUCLEAR REGULATORY COMMISSION l

o

-V h

WASHING TON, D, C. 20555 k..... f July 23, 1987 Docket No. S0-133 Mr. J. D. Shiffer, Vice President Nuclear Power Generation, Licensing Pacific Gas and Electric Company 77 Beale Street, Room 1451 San Francisco, California 94106 1

Dear Mr. Shiffer:

I

SUBJECT:

REQUEST FOR ADDITIONAL INFORMATION, HUMBOLDT BAY POWER PLANT UNIT N0. 3 By letter dated April 29, 1987 we issued our Safety Evaluation Report (SER) for the Humboldt Bay Power Plant, Unit No. 3 Decommissioning.

In that SER we determined that your Decommissioning Plan and proposed Technical Specifications (TS) were acceptable. Since that time, however, our regional staff. has reviewed your proposed TS with respect to their inspection programs and has concluded that certain changes would improve surveillance, clarify the TS requirements and reduce misunderstanding during these inspections.

Enclosures 1 and 2 identify changes in the TS that Region V and NRR staff agree are needed.

)

We have determined that these changes should be made as part of our action on your proposed decommissioning plan. Therefore, we request your response within 30 days of the date of this letter.

The reporting and/or recordkeeping requirements contained in this letter affect fewer than ten respondents; therefore, OMB clearance is not required under P.L.96-511.

4 Sincerely, Peter B. Erickson, Project Manager Standardization and Non-Power Reactor Project Directorate Division of Reactor Projects III, IV, V and Special Projects Office of Nuclear Reactor Regulation

Enclosures:

As stated cc w/ enclosure:

See next page i

i Mr. J. D. Shiffer Pacific Gas and Electric Company Humboldt Bey Nuclear Power Plant cc Philip A. Crane, Jr., Esq.

Mr. Joseph 0. Ward, Chief Pacific Gas and Electric Company Radiological Health Branch Law Departnent State Dept. of Health Services Post Office Box 7442 714 P Street, Office Bldg. #8 San Francisco, California 94120 Sacramento, California 95814 1

Chairman Director 1

Humboldt County Board of Supervisors Energy Facilities Sitino Division County Courthouse Energy Resources Conservation &

l l

825 Fifth Street Development Comission ll Eureka, California 95501 1516 9th Street l

Sacramento, California 95814 l

Linda J. Brown, Esquire j

l Donohew, Jones, Brown & Clifford Gretchen Dumas, Esq.

100 Van Ness Avenue,19 Floor Public Utilities Commission San Francisco, California 94102 of the State of California l

5066 State Building l

U.S. Environmental Protection Agency San Francisco, California 94102 i

Region IX Office ATTN: Regional Radiation Representative Public Affairs Officer 215 Freemont Street Region V I

San Francisco, California 94105 U.S. Nuclear Regulatory Commission l

l 1450 Maria Lane I

Regional Administrator Walnut Creek, California 94596 Nuclear Regulatory Commission, Region V 1450 Maria Lane, Suite 210 Office of' Intergovernmental Walnut Creek, California 94596 Management State of California Michael R. Sherwood, Esq.

1400 10th Street, Room 108 Sierra Club Legal Defense Fund, Inc.

Sacramento, California 95814 2044 Fillmore Street l

San Francisco, California 94115 Bruce Norton, Esq.

2002 East Osborn Dr. Perry Aminato Phoenix, Arizona 85064 Department of Conservation Division of Mines & Geology 1416 9th Street, Room 1341 Sacramento, California 95814 Scott L. Fiedler, Esq.

517 Third Street, Suite 14 Eureka, California 95501 l

l o

REQUEST FOR ADDITIONAL INFORMATION HUMBOLDT BAY UNIT N0. 3, TECHNICAL SPECIFICATIONS 1

FOR DECOMMISSIONING i

paragraph Comment II.B.

A local area map defining the unrestricted areas used for offsite dose calculations for gaseous and liquid effluents should be included in TS.

In addition, a site map clearly defining the restricted area pursuant to 10 CFR 20.3(a)(14) should be included.

II.C.

What activities, such as decontamination and/or removal of structures, systems and components are permitted by the description titled " Principal Activities"? Reference to Regulatory Guide (R.G.) 1.86 Section C.5 may be used.

III.B.I.

"A thorough visual in!- etion" lacks specificity. This might be acceptable it ; procedure was required by section VII.E. which provide for consistent inspections on a continuing basis.

III.B.2.

The stated 10.5 feet elevation above mean low low water level may become a source of confusion.

For clarity the TS should also specify the minimum level from the top of the spent fuel pool liner.

The stated gap water level of +9 inches above mean low low water level may also be a source of confusion. Level should be specified with respect to a fixed location on the spent fuel pool.

III.B.2.b.

TS requires that the Spent Fuel Pool water shall be sampled and analyzed at.least once per quarter to determine water quality.

Since water quality appears to be an important factor in preventing BORAL can deterioration (ref. Inspection Report No. 50-133/87-01), the pool water should be sampled more frequently than quarterly.

Table,III-2 The " acceptable range" column should be titled " limits" for clarity.

4 i Paragraph Comment i

Table III-2 An action statement to require use of the cleanup system above the limiting value should be provided.

If the g

activity cannot be reduced to less than the limit prior to the next required sample, a 30 day report to NRC should be made.

If the peak activity for any measurement exceeds a value indicative of 10% clad degradation under static conditions an immediate report to NRC should be required.

IV.B.3.b.

The report should go to the Regional Administrator and should describe the compensatory measures and schedule of corrective actions.

j IV.B.3.c(1)

A seven day verification of water level is reasonable if a l

low water level alarm setpoint is added to the TS.

IV.B.3.c.(8).

A specific gravity number should be stated in the TS.

j l

i IV.B.4.a.

Fire Hose Stations listed on Table IV-1 should be operable j

at all times.

V.A.4.

Offsite dosimeters should have their location documented l

on a map as part of the TS.

j i

Offsite water sampling should be specified (location and radionuclides). The sampling should be in a downstream r

location with respect to surface water and groundwater, j

i V.A.6 Onsite sampling should be described as to radionuclides j

sampled and the location.

V.B.1 The TS should require that the Offsite Dose Calculations Manual (0CDM) be in compliance with R.G. 1.109.

i l

V.B.2.

One purpose of the process monitor is to detect inadvertent discharge of radioactive effluent. Therefore, the alarm setpoint must be set lower than the 10 CFR 20 Appendix B concentration at the site boundary. Specify the setpoint in the TS.

I V.B.3.d.

TS should specify that area radiation detection instruments be calibrated at least annually, l

V.B.3.e.

TS should specify that portable radiation detection 3

instruments be calibrated at least annually.

1

q m.

' Paragraph Comment V.B.6.

TS should require that ground water be monitored for tritium. Thirty day reporting levels should be established for ground water parameters.

VI.A.1 The maximum filter size should be specified in micrometers for radwaste filters.

VI.A.2.

TS should specify that radioactive waste should not be j

stored for greater than five years. See Generic Letter 80-38.

VI.B.I.

The limits expressed in 40 CFR 190 (25 mrem per year) should also be specified.

VII.C.4.d.

TS should include training on 10 CFR 19, 20, 61 and 71 as a minimum. A retraining frequency should be specified.

VII.E.

Procedures list should include calibration of instruments.

effluent releases, transportation and emergency plan implementing procedures.

VII.F.

" Periodic drills" should be replaced with " Drills / exercises described in the Emergency Plan".

VII.H.1.

The annual report should go to the Regional Administrator, Region V with a copy to NRC Document Control Desk. The date for submittal of the annual report should be specified (nonnally within 90 days after January I of each year).

VII.H.2.

The Semiannual Effluent Release report should be submitted to the Regional Administrator with a copy to the NRC Document Control Desk.

VII.I.1.f and g TS should specify requirements for leak testing and inventories of sealed sources.

Enclosure No. 2 provices a TS example for guidance.

4

1 Enclosure ?

I 1

I GUIDANCE FOR T.S. ON SEALED SOURCE LEAK TESTING I

1 l

1.

Each sealed source containing radioactive material in l

excess of 100 microcuries of beta and/or gamma l

emitting material or 10 microcuries of alpha-emitting material shall be tested for leakage and/or contamination.

If the test reveals the presence of contamination in excess of 0.005 microcuries of removable contamination, the source shall be immediately removed from service and decontaminated, repaired, or disposed of in accordance with commission regulations.

A report shall be prepared and l

submitted to the Regional Administrator, U.S. Nuclear l

Regulatory Commission, Region V within 30 days of the l

date the leak test result (greater than 0.005 -

microcuries) is known.

The report shall specify the source involved, the test results, and corrective I

action taken.

Records of leak test results shall be l

kept in units of microcuries.

2.

Test Requirements - Each sealed source shall be tested for leakage and/or contamination by the licensee or other persons specifically authorized by the Commission or an Agreement State.

The test method shall have a detection sensitivity of at least 0.005 microcuries.

3.

Inspection and Tests - Each sealed source (excluding startup sources and fission detectors previously subject to core flux) shall be tested for leakage and/or contamination as follows:

(a) Sources in Use - At least once per 6 months for all sources containing radioactive material, other than hydrogen 3, with a half-life greater than 30 days and any form other than gas.

(b) Stored sources not in use - Each sealed source and fission cetector shall be tested prior to use or transfer to another licensee unless tested within the previous 6 months.

Sealed sources and fission detectors transferred without a certificate indicating the last test date shall be tested prior to being placed into use.

l 4.

All sealed sources containing quantities of radioactive material in excess of those specified in i

10 CFR 20 Appendix C shall be physically inventoried at least every 365 days.

1 If a source cannot be located during the inventory then a report must be submitted pursuant to 10 CFR 20.402.