Reviews Response to Insp Repts 50-373/87-27 & 50-374/87-26 on 870911.Violation Re Failure of Procedure LOA-FP-01, Fire Alarm Response Occurred.Util Must Submit Corrective Actions & Date of Full Compliance within 30 Days
ML20236D100
Person / Time
Site: LaSalle  
Issue date: 03/15/1989
From: Miller H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Reed C
COMMONWEALTH EDISON CO.
References
NUDOCS 8903220458
Download: ML20236D100 (2)


See also: IR 05000373/1987027

Text

_ _ _ _

. - _ _

-

=-

fY

.

,

MAR 151989

-

'

,

Docket No. 50-373

..

Docket No. 50-374

'

Commonwealth Edison Company

'

ATTN: Mr. CordeT1' Reed

-

Senior Vice President

. Post Office. Box 767

. Chicago, IL 60690

Gentlemen:

' SUBJECT: LASALLECOUNTYSTATION, UNITS 1'ANb2,RESPONSETOINSPECTION

. REPORT NOS. 50-373/87027 AND 50-374/87026

References:' (a)' Letter dated September 11,l1987,J..J._ Harrison to

Cordell Reed

(b) Letter dated October 13,:1987, L..D. Butterfield to

A. B. Davis

~(c) Letter dated January 4, 1988, J. J. Harrison to

Cordell Reed.

In Reference (a), the NRC brought to your attention a ' violation of your

commitment to the fire protection program requirements. The violation pertained

. to the failure of Procedure No. LOA-FP-01 entitled " Fire Alarm Response" te

describe the need for brigade assistance upon receipt of an alarm in the

control room.

This provided for an' unacceptable time delay in fire brigade

response to.a fire through the allowed and established practice of dispatching

an individual to an alarmed area, without alerting and assembling the fire

brigade, after an unplanned control room annunciation of the activation of a

fire detector / alarm. Reference (b) documented Commonwealth Edison Company's-

(CECO) position that a violation was not warranted.

In Reference (c), the NRC

acknowledged.the receipt of CECO's position and indicated that this issue was

being referred'to NRC Headquarters.

The NRC has completed its review of thiscissue. Based on our review of your

referenced submittal.. we have concluded that a violation' of NRC requirements .

did occur. The governing fire protection guidelines. relating-to fire brigades'-

for LaSalle Station are contained in' Appendix A to Branch Technical Position-

APCSB 9.5-1 and the document entitled " Nuclear Plant Fire Protection Functional

Responsibilities, Administrative Controls and: Quality Assurance", dated June

20, 1977. .These documents are based on the philosophy that delays'in fire

brigade response could result in potentially more severe fire conditions, with

resulting adverse consequences for achieving safe, shutdown'following a fire.

Licensees who have committed to implement these guidelines.should develop.

procedures which call for assembling the fire brigade upon receipt of'a report

of a fire or an alarm on the control room annunciator panel. ;The.present LaSalle

Station procedures do not meet the LaSalle license condition requirement to

implement these guidelines.

QDY

.

8903220458 890315

DR

ADOCK 050

3

3(

,

_

_=- :

-

_

- ________

-

/

-

..

-

MAR 151989

  • Commonwealth Edison Company

2

Therefore, we request that you provide a written response, within thirty days

of the date of this letter, describing the following:

(1) the corrective

'

actions that have been taken and the results achieved; (2) the corrective

actions that will be taken to avoid further violations; and (3) the date when

full compliance will be achieved.

Consideration may be given to extending

your response time for good cause shown.

Should you have any further questions regarding this matter, we will be

glad to discuss them with you.

Sincerely,

DalGINAL SIGNED BY HUCERT J. LHJia

H. J. Miller, Director

Division of Reactor Safety

cc:

H. Bliss, Nuclear

Licensing Manager

G. J. Diederich, Station

Manager

DCD/DCB (RIDS)

Licensing Fee Management Branch

P. Shemanski, NRR

Resident Inspector, RIII

Richard Hubbard

J. W. McCaffrey, Chief, Public

Utilities Division

David Rosenblatt, Governor's

Office of Consumer Services

ye

RIII

RIII

R II

RI

f

NRR

'

(

ffth p><,

RI

R

V4

RT\\W

W

Ulie/jk

Gardner

H rrison

ooper

ro e

Holahan

Sk

r

Mi er

03/08/89

03/o7/89

03/o6/89

03/03/89

3/10/89 03//y/89 03/gh/89 03//V/89

l'K

-tw wl&oM

- _ _ _ _ _ _ _ _ _ _ _ _ .