ML20235T474

From kanterella
Jump to navigation Jump to search
Forwards Response to Rev 1 to IE Bulletin 79-26, Boron Loss from BWR Control Blades, Per License Condition 7(d).Plant Does Not Have Control Blades Which Exceed 34% Boron Depletion for Current Cycle
ML20235T474
Person / Time
Site: LaSalle 
Issue date: 07/13/1987
From: Allen C
COMMONWEALTH EDISON CO.
To: Denton
NRC, NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
2214K, IEB-79-26, NUDOCS 8707220152
Download: ML20235T474 (2)


Text

- _ -

-/ m\\ Commonwedith Edison

'e' f..i. / One First Nation 1 Plaza, Chicago, Illinois 2 Address Reply to: Post Offic Box 767 i'\\_,/

Chicago, Illinois 60690 0767.

July 13, 1987 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

Subject:

LaSalle County Station Unit 2 License condition (7) Id)

NRC Docket No. 50-374 Reference (a):

I.E.Bulletin 79-26 Rev.'sion 1, Boron Loss from BVR Contral Blades

Dear Mr. Denton:

Attached is Commoreealth Edison's (CECO) response to satisfy NPF-18, License condition (7) (d). Unit 2 Initial Critical for Cycle 2 was June 16, 1987.

If you have anv questions regarding this matter, please contact this office.

Very truly yours, C. M. Allen Nuclear Licensing Administrator es Attachment cc:

P. Shemanski NRC Resident Incpector - LSCS Region III Administrator M.C. Parker - IDNS

-2214K l

8707220152 B70713

~

s PDR ADOCK 05000374 G

PDR

\\ \\'

1.

~

J ATTACHMENT l

i j,

Response to IE Bulletin 79-26 Revision 1, I

Boron Loss from BWR Control Blades (NPF-18, License Condition (7)(d))

Item 1.

In accordance with LTP-1600-29, Control Blade End-of-Life Projection, LaSalle tracks control blade exposure history on a monthly basis.

Exposure records are maintained and updated on four 3-foot segments for each control blade on a continuing basis.

Item 2.

For the current cycle, LaSalle does not have any control blades which exceed 34% boron depletion (all control blade segments are depleted less than 10%).

By using LTP-1600-29 to predict the depletion of each segment, any control blade having a segment which will exceed 34% boron depletion (1.962 snvt) in the next cycle can be discharged prior to beginning that cycle.

Item 3.

Prior to the initial startup for LaSalle 2 Cycle 2, a single rod subcriticality check (LTP-1600-30) was performed utilizing the analytically determined strongest rod.

In addition, during CRD testing each control blade was fully withdrawn and criticality was not achieved.

LTS-1100-14, Local Shutdown Margin Suberitical De%cnstration, was performed on 6-16-87 (prior to initial critical for Cycle 2) utilizing the strongest control rod, 54-43; 58-43 (Lymmetric rod to 02-43, the Fine Motion Control Rod Drive); and a roc diagonally adjacent to the strongest rod. With this three rod local shutdown margin demonstration, a shutdown margin of at least 1.372% WK/K was demonstrated, which is in excess of 1.232% WK/K (.38% WK/K + R) required by Technical Specifications for Cycle 2.

A beginning of cycle shutdown margin (LTS-1100-1) was also determined from the initial critical on 6-16-87.

The beginning of cycle shutdown margin was determined to be 2.81% WK/K for Unit 2.

A boron loss shutdown margin increment was not required for the Unit 2 Cycle 2 shutdown margin tests because all control blade segments

]

are less than 34% depleted (see Item 2).

A boron loss increment for j

future cycles will not be necessary since the General Electric

]

B C original equipment control blades will be discharged prior to j

4 exceeding 34% boron depletion, j

i 1

l l

I l

i l

3339K I

_-__-_--__A