Amend 24 to License NPF-38,changing App a Tech Specs by Revising Description of Fire Detectors in Component Cooling Water Pump Room a & Implementing Name Changes & Correcting Typos for Charcoal Filter Units
ML20235S613
Person / Time
Site: Waterford 
Issue date: 10/01/1987
From: Calvo J
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20235S615 List:
References
NUDOCS 8710090062
Download: ML20235S613 (7)


Text

j..e l

of UNITED STATES

, /' i NUCLE AR REGUL ATORY COMMISSION WASHINGTON, D, C. 20555 y.

p/'

,1

~f f 3

%..o j

F LOUISIANA POWER AND LIGHT COMPANY DOCKET NO. 50-382 WATERFORD STEAM ELECTRIC STATION, UNIT 3

)

AMENDMENT TO FACILITY OPERATING LICENSE 1

Amendment No. 24 I

License No. NPF-38 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Louisiana Power and Light i

Company (the licensee) dated February 23, 1987, complies with j

the standards and requirements of the Atomic Energy Act of 1954,

)

as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the f'

Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

8710090062 871001>

PDR ADDCK 05000382 PDR:.

p

j a.

1 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C(2).of Facility Operating License No.

NPF-38 is hereby amended to read as follows:

(2) Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 24, and the Environmental. Protection Plan contained in Appendix B, are hereby incorporated in the license.

The licensee shall operate the' facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION Q,.c. ' b. [ccU-O

/

Jose A. Calvo, Director j

Project Directorate - IV j

Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical l

Specifications Date vi Id>uance: October 1,1987 1

1

ATTACHMENT TO LICENSE AMENDMENT NO. 24 TO FACILITY OPERATING LICENSE NO. NPF-38 DOCKET NO. 50-382 Replace the following pages of the Appendix A Technical Specifications with the attached pages.

The revised pages are identified by Amendment number and contain vertical lines indicating the areas of change.

The corresponding overleaf pages are also provided to maintain document completeness.

Remove Insert 3/4 3-51 3/4 3-51 3/4 3-53 3/4'3-53 I

e.

TABLE 3.3-11 FIRE DETECTION INSTRUMENTS TOTAL NUMBER OF INSTRUMENTS

  • i ELEVATION HEAT FLAME SM0KE ZONE ROOM NAME/ NUMBER (ft)

M (x/y)

(x/y) 1.

REACTOR AUXILIARY BUILDING RAB 1A Main Control Panels 1,2,3,4,6,7,8,35,36 +46 10/0 RAB 1A Control Poom Proper /304

+46 20/0 RAB IB Emergency Equip. H&V Room /314

+46 0/12 RAB 10 Computer Room (above raised floor)/306 +46 5/0 Computer Room (below raised floor)/306 +46 0/7 RAB 2 Ventilation Equip. Room /299

+46 0/36 RAB 3 RAB Corridor to Relay Room /261

+35 0/1(3) 4/0

)

RAB HVAC Switchgear Equip. Room /323

+46 0/10

)

RAB 3A RAB Battery Exhaust Fan Room /406

+69 0/2 l

l l

RAB 4 Cable Vault /260

+35 0/27 j

RAB 5 Electrical Penetration Area "A"/263

+35 0/13 i

RAB 6 Electrical Penetration Area "B"/263A

+35 0/14 RAB 7 Relay Room /262

+35 (3) 12/0 Isolation Panels (9 Compartments

+35 2/0

- 2 per comp.)

RAB 8A High Voltage Switchgear Room "A"/212A

+21 0/1(1) 18/0 j

RAB 8B Electrical Equip. Room /225B and High

+21 0/1(2) 28/0 Voltage Switchgear Room "B"/212 480V Switchgear 3A32 Room

+21 (2) 2/0 RAB 8C High Voltage Switchgear Room

+21 (1) 8/0 "A-B"/212B l

RAB 8E CEA M/G Set Room /216

+21 2/0 RAB 9 Remote Shutdown Panel Room /217

+21 1/0 RAB 11 Battery Room "B",, _a

+21 2/0 RAB 12 Battery Room "AB"/214A

+21 2/0 RAB 13 Battery Room "A"/214

+21 2/0 l

RAB 15 Emergency Diesel Gen. "B" Room /222

+21 0/1 RAB 15A Emergency Diesel Gen.

"B" Feed TK

+46 0/1 Room /328A j

RAB 16 Emergency Diesel Gen. "A" Room /221

+21 0/1

)

RAB 16A Emergency Diesel Gen. "A" Fer:d Tk.

+46 0/1 l

Room 328A j

RAB 17 CCW Heat Exchanger "B"/236

+21 0/4 RAB 18 CCW Heat Exchanger "A"/220

+21-0/4 RAB 19 CCW Pump "A"/235

+21 0/2 l

RAB 20 CCW Pump "AB"/234

+21 0/2 RAB 21 CCW Pump "B"/233

+21 1/0 RAB 23 Corridor to CCW Pumps /218, Corridor

+21-0/39 to CCW Heat Exchangers/219 and l

Corridor to Emergency Diesel Gen./225A (1) Common Resistor Wire I

(2) Common Resistor Wire (3) Common Resistor Wire WATERFORD - UNIT 3 3/4 3-51 AMENDMENT N0. IE, 24

TABLE 3.3-11 (Continued)

FIRE DETECT]CN INSTRUMENTS TOTAL NUMBER CF

]NSTRUMENis' ELEVATION HEAT FLAME SHOKE 20NE ROOM NAME/ NUMBER (ft) 1xfy] (x/y) [x/yj 1.

REA:TCR AUXILIARY BUILDING (Continued)

RAb 23 Equip. Access Area /226 (wing area)

+21 15/0 RAB 27A H&V Room /124

+7 0/6 RAB 278 Electrical Area and Health Physics

+7 0/35 Offices /122 RAB 27C I&C Room /120

+7 0/6 l

RAB 270 Communications Equip. Room /123

+7 1/0 RAB 31 Corridors and Passageways

-4 0/24 Corridors on eastside

-4 0/21 RAB 32 Wing Area westside - Auxiliary Com-

-35 32/0 ponent Cooling Water Pump "A"/853 and Pipe Penetration Area /8100

-4 Wing Area Center /853 and 8100

-35 &

28/0

-4 Wing Area eastside-Component Cooling

-35 31/0 Water Pump "B"/B53 and Pipe Penetration Area /8100

-4 RAE 33 5/D Cooling Heat Exchangers A&B/820

-35 0/18

& B4B RAB 34 Valve Operating Enclosure Bay Room

-15.5 2/0 "A"/B54 Valve Operating Enclosure Bay Room

-15.5 4/0 "B"

BSSA RAB 35 Safety Injection Pump Room B/816

-35 10/0 RAB 36 Safety Injection Pump Room A/ BIS

-35 10/0 Rf: 2' Hotor-Driven Emergency feedpump

-35 0/1 "A"/849A RAB 38 Motor-Driven Emergency Feedpump

-35 1/0 "B"/8498 RAB 39 General Equipment Area /05, 12, 13,

-35 0/10

& 49 Corridors & General Equip. Areas /B5,

-35 0/28 1, 2, 3, 4, 39, 40, 41, 42, 44 & 46 East Corridor & General Equip. Areas /

-35 0/15 B17, 23 & 25 BA Make-up Tank "A"/B3B

-35 4/0 BA Make-up Tank "B"/853A

-35 4/0 RAB 40 Diesel Storage Tank "A"/B50

-35 3/0 RAB 41 Diesel Storage Tank "B"/B52

-35 3/0 1

WATERFCED - UNIT 3 3/4 3-52 Amendment Nc. Y, 24

I

'. s TABLE 3.3-11 (Continued)

FIRE DETECTION INSTRUMENTS TOTAL NUMBER OF INSTRUMENTS

  • ELEVATION HEAT FLAME SM0KE ZONE ROOM NAME/ NUMBER (ft)

(x/y)

(x/yl (x/y) 2.

REACTOR CONTAINMENT BUILDING **

RCB 1-1 Annulus /420

+46, +21 35/0 RCB 1-2 Annulus /420

+ 21, -4 34/0 RCB 2 Electrical Penetration Area A

+21 24/0 RCB 3 Electrical Penetration Area B

+21 21/0 RCB 4 Reactor Cable Trays

+46 16/0 CT 1&3 Wet & Dry Cooling Tower "A" Cable Tray 1/0 CT 2&4 Wet & Dry Cooling Tower "B" Cable Tray 1/0 i

3.

FUEL HANDLING BUILDING l

FHB 2 Purification Pump Room /B155, Fuel Pool

+1 10/0 l

Pump "A"/B157, Fuel Pool Pump "B"/

j B156, Fuel Pool Heater Exchanger /

S158 and Access Area /B-161 Emergency Filter Train Unit /B152

+1 6/0 Emergency Elect. Equip. Room /B151

+1 1/0 FHB 4 Operating Floor /361

+46 15/0 1

l 4.

CHARCCAL AIR FILTER UNITS

)

l E-35 (3A-SA) FHB Emergency Filter Train "A"

+1 1/0 l

E-35 (3B-58) FHB Emergency Filter Train "B"

+1 1/0 E-17 (3A-SA) Shield Building Ventilation

+46 1/0 System Filter Train "A" E-17 m -(M chield Building Ventilation

+46 1/0 System Filter Train "B" E-23 (3A-5A) Controlled Ventilation Area

+46 1/0 l

System Filter Train "A"

E-23 (3A-SB) Controlled Ventilation Area

+46 1/0 l

System Filter Train "B" S-8 (3A-SA) Control Room Emergency Filter

+46 1/0 Train "A" S-8 (3B-SB) Control Room Emergency Filter

+46 1/0 Train "B" TABLE NOTATIONS

  • (x/y):

x is the number of Function A (early warning fire detection and notification only) instruments.

I y is the number of Function B (actuation of fire suppression systems and early warning and notification) instruments.

    • The fire detection instruments located within the containment are not required to be OPERABLE during the performance of Type A containment leakage rate tests.

WATERFORD - UNIT 3 3/4 3-53 AMENDMENT NO. JE, 24

l

N5 m uis m :Cs LOOSE-F W DETECliCN I N S T RUP.E N T Ai l c h l

LIu!iiN: CON: ?i }Cs rc; cr>[ RAT JCN 3.3.3.9 The loose-part cetection system shall be OPERABLE.

l APPLICAE]LITY:

MODES I and 2.

1 I

ACTION:

l With one or more loose-part detection system channels inoperable for a.

1 more than 30 days, prepare and submit a Special Report to the i

l Commission pursuant to Specification 6.9.2 within the next 10 days outlining the cause of the malfunction and the plans for restoring the channel (s) to OPERABLE status.

b.

The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVE1LLANCE REQUIREMENTS f

4.3.3.9 Each channel of the loose part detection system shall be demonstrated OPERABLE by performance of:

a.

a CHANNEL CHECK at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, b.

a CHANNEL FUNCTIONAL TEST at least once per 31 day:., and i

1 c.

a CHANNEL CALIBRATION at least once per IB months.

]