ML20235H947
| ML20235H947 | |
| Person / Time | |
|---|---|
| Site: | Rancho Seco |
| Issue date: | 06/29/1987 |
| From: | Andognini G SACRAMENTO MUNICIPAL UTILITY DISTRICT |
| To: | Martin J NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V) |
| References | |
| 87-12, GCA-87-249, NUDOCS 8707150329 | |
| Download: ML20235H947 (2) | |
Text
_ - _ _ _ _ - _ - _ _ _
f SACRAMENTO MUNICIPAL UTILITY DISTRICT 2 6201 S Street, P.O. Box 15830, Sacramento CA 95852-1830,(916) 452 3211 l
AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA 1
m GCA 87-249 I3 e
- o JUN 2 91987 F6 !"
L 55@03
,'l O9 n<
J.
B. Martin, Regional Administrator
]' lJ E3 1
U.S. Nuclear Regulatory Commission
(
33 Region V, Office of Inspection & Enforcement 1450 Maria Lane, Suite 210 r
Walnut Creek, CA 94596 Docket No. 50-312 Rancho Seco Nuclear Generating Station l
License No. DPR-54 SPECIAL REPORT NO. 87-12: OVERDUE GAGE CALIBRATION FOR SIXTEEN TECHNICAL SPECIFICATION LISTED FIRE ZONES
Dear Mr. Martin:
l The Sacramento Municipal Utility District hereby submits Special Report No. 87-12 in accordance with Technical Specifications, Section 3.14 and 6.9.5.E.
During Cold shutdown conditions on May 16, 1987, the following fire zones were declared technically inoperable:
Eone Area 12 West DC Control Room Mezzanine Level 14 Wet 480 VAC Room Mezzanine Level 15 West Cable Tray Area 16 East Cable Tray Area 17 East 480 VAC Room Mezzanine Level 19 East DC Control Room Mezzanine Level 36 West Battery Room Grade Level 37 West 4160 VAC Room 38 East 4160 VAC Room 39 East Battery Room 40 North Diesel Room 41 South Diesel Room 75 B Switchgear Room Nuclear Services Electrical Building (NSEB) 76 A Switchgear Room NSEB 77 B Electrical Equipment Room NSEB 78 A Electrical Equipment Room NSEB
/
A 1s 8707150329 970629
[lY PDR ADOCK 05000312 b/
I S
PDR j l l
.T:s -cy/
RANCHO SECO NUCLEAR GENERATING STATION C 14440 Twin Cities Roaa, Herald, CA 95638 9799;(209) 333 2935
k*...
J.
B. Martin 0 UN
.GCA 87-249 Page.2 All of these inoperabilities were due to the calibration being overdue.for the Cardox System level and pressure gages.
The
- gages were recalibrates on June 16, 1987, per Work Request No.
132700 which was completed in the field on June 17, 1987.
It should be.noted that1the as-found condition of all of these gages.
showed that the insturments were still within the required tolerance.
.. Zone 15 carbon dioxide' suppression was also inoperable from May L
i 26, 1987 through June 15, 1987 to repair the local disable switch.- The disable switch was repaired under Work Request No.
130495.
Zone 41 carbon dioxide suppression has been inoperable since May
- 2 6, 1987, due to a-clearance (i.e., tag out) on this subsystem.
Door AU-132 is the entry to Zone 41.
That door was removed because of interference it was causing with diesel generator work.
The. door reinstallation is scheduled to be complete by i
July 10, 1987.
l The proper compensatory measures were established per Technical Specification 3.14.4 for each inoperable subsystem listed above.
The compensatory measure for Zone 41 will remain in-place until the. interfering-work is complete.
I If there-are any questions concerning this report, please contact Mr. Ron W.
Colombo at (916) 452-3211, extension 4236.
Sincerely,
[
Ca o
Chief Executive Officer, Nuclear
.l Attachment cc:
A. D'Angelo G.-Kalman INPO j
l l
L
___