Notice of Violation from Insp on 890117-20.Violation Noted: on 890120,three Splices in Limitorque Valve V-14-30,used to Extend Power Leads for Termination to Terminal Blocks,Did Not Conform to Splice Configuration Specs
ML20235H244
Person / Time
Site: Oyster Creek
Issue date: 02/15/1989
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20235H235 List:
References
50-219-89-02, 50-219-89-2, NUDOCS 8902230534
Download: ML20235H244 (1)


Text

.

l

.k r{

APPENDIX A-NOTICE OF VIOLATION General Public Utilities Nuclear Corporation Docket No.

50-219 Oyster Creek Nuclear Facility License No. DPR-16 f

I As a result of the inspection conducted on January 17-20, 1989, and in accord-l ance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (Enforcement Policy) (1988), the following violation was identified:

10 CFR 50, Appendix B, Criterion V requires that activities affecting quality be accomplished in accordance with procedures..."

Licensee Procedure No. A100-SME-3780-03 which references Procedure 732.2.009 revision 0, dated February 22, 1980 entitled nsta11ation of Raychem Splices" references Raychem Installation Guide 1050 and Inspection Guide 2050 for WCSF type In-line splice.

Raychem Drawing 47005-006-03 provides size and assembly details which show a six irch splice length with a tyo inch seal length at each end of the splice.

Contrary to the above, on January 20, 1989, three splices were identified in Limitorque Valve No. V-14-30, used to extend the power leads for termination to a terminal block, which did not conform to the. splice configuration specified by Raychem Drawing 47005-006-03 in that the splice seal lengtn was less than two inches.

This Violation is a Severity Level V.

Supplement I.

Pursuant to the provisions of 10 CFR 2.201, General Public Utilities Nuclear Corporation is hereby required to submit to this office within thirty days of the date of the letter which transmitted this Notice, a written statement or explanation in reply, including: (1) the corrective steps which have been taken and the results achieved; (2) corrective steps which will be taken to avoid further violations; and (3) the date when full compliance will be achieved. Where good cause is shown, consideration will be given to extending.

this response time.

i 0FFICIAL RECORD COPY IR OC 89 0003.0.0 02/16/89 890223o334 89021s