{{#Wiki_filter:. , r, 1 CLEVELAND ELECTRIC ILLUMINATING COMPANY PERRY NUCLEAR POWER PLANT ANNUAL ECCS' OUTAGE REPORT' JANUARY 1, 1988 - DECEMBER 31,~1988 DOCKET NUMBER: 50-440 LICENSE NUMBER:- NPF-58 k Submitted ~By: ~ Directbr,/PPTD eg ', 1 Ge'f1Fril Managger, PPOD l gg2230188890214 R ADOCK 05o00440 PDC 1

PERRY UNIT 1 1988 ECCS OUTAGES \\: This comprises the 1988 Annual ECC System-Outage Report, which is < submitted in accordance-with USAR - TMI Action Plan Item II.K.3.17 '(Appendix 1A) and NUREG-0807 Section 6.3.3. The report covers'the period from January 1, 1988 to December 31, 1988. This.information was compiled from a review of Perry's " Active " Limiting Condition for operations (Active LCO) log for 1988. Performance of instrumentation surveillance tests which do not render.any ECCS subsystems inoperable are not included in this report. Also, Low Pressure Coolant Injection (LPCI) outages in support of Shutdown Cooling operations were not included, as plant design requires these outages. This method is consistent with that used in the 1987 report. The following definition of " system outage" was used in the pre-- paration of this report: "The inability of an ECC system to perform its intended function during a time when the system is required to be operable."

s 4 a 1988 LPCI'"A"~(E12A)' OUTAGES' -. TIME. -TIME OUTAGE ENTERED. CLEARED DURATION DESCRIPTION + 0815 1720 9 HR Operational Condition: 1 1/2-1/2 5 MIN . Applicable Tech' Spec: 3.5.1 E12-F024A Tagged Shut'To Allow-Test Equipment Hookup. 1742 ~2304 1 DAY Operational Condition: 1 2/22 2/23 5 HR. Applicable _ Tech Spec 3.5.1 - 22 MIN RHR "A" Inop For Flushing in Preparation For SDC Operation. 0610 23321 17 HR-Operational Condition: l' 3/16 3/16 22 MIN Applicable Tect Spec: 3.5.1-RHR "A" Not Fi'. led'and-Vented. + 0400 0331 2 DAYS Operational Condition: 1 4/11 .4/14 23 HR. Applicable Tech Spec: 3.5.11 31 MIN RHR "A" Inop For Divisional Outage. + 0331 0940 1 DAY Operational Condition:'1. 4/14 4/15 6 HR Applicable Tech Spec: 3.5.1 9 MIN LPCI "A" InopfTo Repair Injection Valve Permissive Pressure Switch. + 2120 1836 2 DAYS Operational Condition: 1 4/15 4/18 21 HR Applicable Tech Spec: 3.5.1 16 MIN RHR "A" Pump Breaker Racked Out During SPCU (G42) Operation.. 1130 1915 7 HR Operational Condition: 1 d 5/13 5/13 45 MIN Applicable Tech Spec: 3.5.1 I RHR "A" Pump Auto Start l Relay Repair Work. 0815 0925 1 HR Operational Condition: 1 6/11 6/11 10 MIN Applicable Tech spec: 3.5.1 RHR "A" Pump Failed Fill l and Vent SVI Due To A Vent Valve Problem, l + Planned Outage 1 I i ______-__---__a

c e ll e., 1988 LPCI "A" (E12A) OUTAGES' .TIMEJ . TIME ' OUTAGE ENTERED. CLEARED- -DURATION i DESCRIPTION 0630 2005 13..HRl Operational Condition: 6/16- ~6/16 35 MIN. Applicable Tech Spec:. 3. 5.1' RHR "A" Loop'Not FilledLand -Vented. + 0445 0050 21 DAY Operational. Condition: 1: 7/11 7/14 20 HR Applicable Tech-Spec:l3.5.1 5 MIN RHR "A"JInop-For-Maintenance and Repetitive' Tasks. 1835 1207 17 HR Operational' Condition:'1. 7/29 7/30-32 MIN Applicable Tech. Spec: 13.5.1' RHR "A"'Inop.Due-To'ESW (P45): "A" Inop For Failing an SVI. 1030' 1645 6 HR. Operational ~ Condition: 3I 9/17 9/17 15 MIN Applicable Tech Spec: 3.5.1 RHR "A" Inop For. Flushing in Preparation for SDC Operation. 0600 ~2245 16 HR Operational' Condition:11 10/19 10/19 45 MIN Applicable Tech Spec::3.5.1 RHR "A" Inop Due To a. Low Pressure Alarm Received After. Pump Shutdown From Suppression Pool Cooling Operation. + Planned Outage l 4 h 'l f

b w t 4 4 H j. ~ r o 1988 LPCi'"B"'(E12B) OUTAGES ' TIME' TIMEL ' OUTAGE LENTERED CLEARED DURATION-DESCRIPTION + .2125-1810 2 DAY ' Operational Condition:11' 2/15 2/18 20 HR Applicable' Tech; Specs 3.6.3.21 45 MIN RHR "B" Inop Due1To ECCW (P42) i "B" Maintenance and' Repetitive Tasks., j 0000 0320 3 HR. ~ Operational Condition: 1- '3/12 3/12~ 20 MIN' Applicable Tech Spec: 3.5.1L RHR "B"'Not Filled and Vented. 0155 0100-2 DAY Operational Condition: 1; 3/13 3/16 23 HR Applicable ~ Tech Spec:.3.5.1 5 MIN 'RHR'"B" Inop ToLRepair?Two Snubbers. + 1330 1330 -2 DAY . Operational Condition:'1 5/17-5/19

Applicable Tech Spec: 3.5.1

.RHR "B"~Inop For. Maintenance .and Repetitive Tasks. 1524 0755 16 HR Operational ~ Condition: 4-6/24 6/25 31 MIN Applicable' Tech Spec:.3.4.9.2 RHR ")B" SDC Inop Due To ECCW (P42) "B""Inop Due To a Failed SVI. + 0330 0105 2 DAY Operational Conditiots: 1 7/5 7/8 21 HR Applicable Tech Spec: 3.5.1 35 MIN RHR "B" Inop For Maintenance and Repetitive Tasks. + '0945 1400 2 DAY Operational Condition: 1 8/23 8/25 4.HR Applicable Tech spec: 3.6.3.2 15 MIN RHR "B" Containment Spray Mode Inop To Install a DCP On The Hydrogen Mixing Compressor. .1505 0450 13 HR Operational Condition: 1 9/14 9/15 45 MIN Applicable Tech Spec: 3.5.1-RHR "B" Inop Due To ECCW (P42) "B' Inop Due To a Failed SVI. + Planned Outage

4 M e h b 1988 LPCI "B" (E12B) OUTAGES l-TIME' TIME OUTAGE ENTERED CLEARED-DURATION DESCRIPTION + 0325 2130 2 DAY Operational Condition: 1 11/14 11/16 18 HR Applicable Tech _ Spec: 3. 5.1. 5 MIN lRHR "B" Pump Breaker Racked Ou For Maintenance and Repetitive Tasks. In Addition,'ESW (P45). "B" Inop For1 Maintenance. + Planned Outage l l t I ._____-_________-_-_a

w-- l n l j l I 1988 LPCI "C" (E12C) OUTAGES l l I i f' TIME TIME OUTAGE q H ENTERED CLEARED DURATION DESCRIPTION 4 L + 0900 1700 2 DAYS Operational. Condition: 1 I 2/15 2/18 8 HR Applicable Tech Spect-3.5.1 RHR "C" Inop For Maintenance. { and Repetitive Tasks. i + 1330 1445 2 DAYS Operational Conditions.1 5/17 5/19 1 HR Applicable. Tech spec: 3.5.1

15. MIN RHR "C" Inop For Maintenance.

+ 0330 0105 2 DAYS Operational Condition: 1 7/5 7/8 21 HR Applicable Tech Spec: 3.5.1 35 MIN RHR "C" Inop For Maintenance and Repetitive Tasks. 1505 0450 13 HR Operational' Condition: 1 9/14 9/15 45 MIN Applicable Tech Spec: 3.5.1 RHR "C" Inop Due'To ECCW (P42) "B" Inop Due To a Failed SVI. + 0325_ 1711 2 DAY Operational Condition: 1 11/14 11/16 13 HR Applicable Tech Spec: 3.5.1 46 MIN RHR "C" and ESW (P45) "B" Inop For Maintenance and Repetitive Tasks. + Planned Outage i

-{ ) 1988 LPCS (E21) OUTAGES t TIME TIME OUTAGE ENTERED CLEARED DURATION DESCRIPTION + 0400 0331 2 DAY Operational Condition: 1 4/11 4/14 23.HR-Applicable Tech Spec: -3.5.1 d'I 31 MIN ~LPCS Inop To Perform Maint-enance and Repetitive Tasks. l -+ 0445 0140 20 HR Operational Condition: 1-7/11 7/12 55 MIN Applicable Tech spec: 3.5.1 LPCS Inop To. Change Oil'In The Waterleg Pump (Repetitive Task)~ 1835 1207 17 HR Operational Condition:.'1 7/29 7/30 32 MIN Applicable Tech Spec::3.5.1 LPCS Inop Due To ESW (P45) "A" Inop For Failing an SVI. Planned Outage + 4

L, f. t p' L L 1988 HPCS (E22) OUTAGES l' TIME TIME OUTAGE ENTERED CLEARED DURATION DESCRIPTION + 0500 1825-1 DAY Operational Condition: 1 3/3 3/4 13 HR Applicable Tech Spec:.3.5.1 25 MIN HPCS Inop To Repair An Oil Leak On The Waterleg. Pump.. 1445 2025 5 HR Operational Condition: 1 3/9 3/9 40 MIN Applicable Tech Spect 3.5.1 HPCS Inop For Not Having a Suppression Pool Water Supply.. + 2030 1229 7 DAYS Operational Condition: 1 3/22 3/30 15 HR Applicable Tech Spec: 3.5.1 59 MIN HPCS Inop To Replace The Mechanical Seal On The Pump. + 0845 1155 5 DAYS Operational Condition: 1 4/25 4/30 3 1:R Applicable Tech Spec: 3.5.1 10 MIN HPCS Inop To Perform Maint-enance and Repetitive. Tasks'.- 0705 0225 19 HR Operational Condition: 1 6/29 6/30 20 MIN Applicable Tech spec:

3. 5.1 -

HPCS Inop Due To Leak .) Detection Line Break l Instrumentation Problem. 0645 0740 1 DAY Operational Condition: 2 9/17 9/18 55 MIN Applicable Tech Spec: 3.5.1 HPCS Inop Due To Leak Detection Line Break Instrumentation Problem. + Planned Outage _}}