{{#Wiki_filter:i i i't l (MC) Rev. 10 l Effective Date l l INFORMiATION ONLY J I ANNUNCIATOR RESPONSE AR-801 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 C] / FSA ANNUNCIATOR RESPONSE i APPROVED BY: Interpretation Contact Lu/l.Q?$- Al'r# (sIGNATV E ON FI(E) DATE: INTERPRETATION CONTACT: Manager, Nuclear Plant Operations Support 9003120115 990304 DR ADOCK 05 2

1 TABLE OF CONTENTS / \\, SECTION PAGE 1.0 PURP0SE................................................................. 1

2.0 REFERENCES

1 2.1 IMPLEMENTING REFERENCES............................................. 1 2.2 DEVELOPMENTAL REFERENCES............................................ 1 3.0 PERSONNEL INDOCTRINATION................................................ 1 4.0 INSTRUCTIONS............................................................ 1 5.0 FOLLOW-UP ACTIONS....................................................... 1 8 ENCLOSURE 1 An n u n c i ato r Re s pon s e................................................ 2 Ov t 1 l l l t I l l O k-J l AR-801 Rev. 10 Page i 2

I l9 1.0 PURPOSE ,o i 1.1 Establish a reference document for each Annunciator Window on the FSA Lampbox. 1.2 Establish operator actions for valid Annunciator alarms on the FSA Lampbox. 1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the FSA Lampbox. 2.0 RFFERENCES 2.1 IMPLEMENTING REFERENCES 2.1.1 AP-880, Fire Protection 2.2 DEVELOPMENTAL REFERENCES 2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-050 3_. 0 PERSONNEL INDOCTRINATION 3.1 The Fire Service Annunciator System is powered from ACDP-40 Breaker 19. 4.O INSTRUCTIONS 4.1 Respond to alarms on the FSA Lampbox as indicated on Enclosure 1, Annunciator Response. 5.0 FOLLOW-UP ACTIONS l l None O AR 801 Rev. 10 Page 1 J

/3 V FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-01' FS-01-01 FIRE WTR TANK 3A LEVEL LOW INDICATED CONDITION: TANK LEVEL s35'8" REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: REFILL TANK j DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 1 SENSING ELEMENT: FS-47-LS O v AR-801 Rev. 10 Page 2

7 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-02 FS-01-02 . _4 ~ FIRE WTR TANK 38 LEVEL LOW INDICATED CONDITION: TANK LEVEL s35'8" REDUNDANT INDICATION WHICH WILL RIR 'RM: x OPERATOR ACTION FOR A VALID Ns'L TANK i DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-48-LS O AR-801 Rev. 10 Page 3 a

/ \\. FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-04 FS-01-04 l l l CO2 TANK PRESS hl/LO l 0 INDICATED CONDITION: CARD 0X TANK PRESSURE RELAY RAR ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM: - CARD 0X PANEL WINDOW CO-1-2 ALARM - LOCAL PRESSURE INDICATOR CO-1-PI OPERATOR ACTION FOR A VALID ALARM: - WALK DOWN C0 SYSTEM AND ENSURE NO LEAKS - ENSURE PROPER OPERATION OF CARD 0X UNIT DISCUSSION: CARD 0X TANK RELAY RAR IS ACTUATED WHEN CARD 0X TANK PRESSURE AS SEEN BY CO-1-PS1 IS 2325 PSIG OR s275 PSIG. REFERENCf%: DWG 208-031 FS-21, DWG FL-16996 4 SENSING ELEMENT: CARD 0X TANK RELAY RAR i O AR-801 Rev. 10 Page 4

i i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-05 FS-01-05 1 l PUMP TEST RET WATER TO TANK 1 \\ INDICATED CONDITION: FLOW IN FIRE SERVICE RECIRC LINE ltS40'PM l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: NONE l l DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-12-FS l O l l AR-801 Rev. 10 Page 5

I = I l ) ,i, ' _j FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-07 FS-01-07 I ( l l FREON SYSTEM ACTIVATED i I INDICATED CONDITION: FREON SYSTEM ACTIVATED IN CABLE SPREADING ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM: 73 f ) OPERATOR ACTION FOR A VALID ALARM: NOTIFY FIRE BRIGADE TO INSPECT CABLE SPREADING ROOM. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: KIB FREON SYSTEM INTERFACE FIRING UNIT l ?y ( i \\s.> AR-801 Rev. 10 Page 6

O FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01 08 FS-0F 08 l l FDWTR PP & TUR8 DR 3A (HAZ 1) INDICATED CONDITION: CARD 0X HAZARD ZONE 1 RELAY PE ACTUATED (FWP-2A) REDUNDANT INDICATION WHICH WILL VERIFY ALARM: - CARD 0X PANEL WINDOW CO-1-1 ALARM - LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM: - LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON FWP-2A - DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED - REFER TO AP-880 (FP). DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-3-TS1 THROUGH CO-3-TS7.

REFERENCES:

DWG 208-031 FS-21, DWG FL-16995 4 i SENSING ELEMENT: HAZARD ZONE 1 RELAY FE O AR-801 Rev. 10 Page 7

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-09 FS-01-09 L l i FDWTR PP & TURB DR 3B (HAZ-2) l INDICATED CONDITION: CARD 0X HAZARD ZONE 2_ RELAY PE ACTUATED (FWP-28) REDUNDANT INDICATION WHICH WILL VERIFY ALARM: - CARD 0X PANEL WINDOW CO-2-1 ALARM - LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM: - LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON FWP-2B - DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED - REFER TO AP-880 (FP). DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-4-TS1 THROUGH CO-4-TS7

REFERENCES:

DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 2 RELAY PE t O AR-801-Rev. 10 Page 8

l 'O \\,,/ FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-10 FS-01-10 TURB GEN BRGS 1-5 (HAZARD-3) l-1 INDICATED CONDITION: CARD 0X HAZARD ZONE 3 RELAY PE ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM: - CARD 0X PANEL WINDOW CO-3-1 ALARM - LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM: - LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON TURBINE GENERATOR BEARINGS 1 THROUGH 5 - DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED - REFER TO AP-880 (FP). DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-5-TS1 THROUGH CO-5-T54

REFERENCES:

DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: 1AZARD ZONE 3 RELAY PE lO l AR-801 Rev. 10 Page 9

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-11 FS-01-11 TURB GEN BRGS 6-9 (HAZARD-4) INDICATED CONDITION: CARDOX HAZARD ZONE 4 RELAY PE ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM: - CARD 0X PANEL WINDOW CO-4-1 ALARM - LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM: - LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON TURBINE GENERATOR BEARINGS 6 THROUGH 9 - DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED - REFER TO AP-880 (FP) DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE DETECTORS CO-6-TS1 THROUGH CO-6-T54

REFERENCES:

DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 4 RELAY PE O AR-801 Rev. 10 Page 10

l 1 ( FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-13 FS-01-13 FIRE PUMP 3B l RUNNING i INDICATED CONDITION: POWER IS APPLIED TO FSP-1 MOTOR AND FSP-1 PUMP SHOULD BE RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: NONE DISCUSSION: FIRE PUMP HOUSE FANS (AHF-33A & AHF-33B) ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL PUMP FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING COLD WEATHER OPERATIONS PER OI-13.

REFERENCES:

DWG 208-031 FS-14, FS-03 SENSING ELEMENT: mal-1 LO AR-801 Rev. 10 Page 11

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-14 FS-01-14 FIRE PUMP 3B + CONTR PWR OFF 1 INDICATED CONDITION: CONTROL POWER TO FSP-1 IS OFF OR RELAY FAILURE (ACDP 7 BREAKER #9) REDUNDANT INDICATION WHICH WILL VERIFY ALARM: O OPERATOR ACTION FOR A VALID ALARM: DISCUSSION:

REFERENCES:

DWG 208-031 FS 14, FS-04 SENSING ELEMENT: mal-1 1 1 O AR-801 Rev. 10 Page 12

l I.- FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-15 FS-01-15 l CABLE SPR ROOM AUTO FANS OFF l INDICATED CONDITION: SELECTOR SWITCH PLACED IN THE "0FF' POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: VERIFY SELECTOR SWITCH IS IN THE AUTO POSITION. INSTALL TEMPORARY FANS IF NECESSARY. DISCUSSION: j i

REFERENCES:

) SENSING ELEMENT: FSE-592 ) I AR-801 Rev. 10 Page 13 l 4

FIRE SYSTEM ANNUNCIATOR RESPONSE l FS-01-16 FS-01-16 F.S. TANK INSTR HEAT TRACE FAIL ' l l INDICATED CONDITION: OUTSIDE AIR TEMP s34 DEG F; HEAT TRACE FAIL REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: DETERMINE IF TEMP REQUIRES A CHANGE IN THE FIRE SERVICE SYSTEM LINEUP. CHECK HEAT TRACE LINES. DISCUSSION: CHECK METEOROLOGICAL STATION INDICATION

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-49-TS l i O l AR-801 Rev. 10 Page 14

~ 1 i 's FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-01 FS-02-01 ' FIRE PUMP 3A OVERSPEED i INDICATED CONDITION: FSP-2A OVERSPEED 22100 RPM REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OFERATOR ACTION FOR A VALID ALARM: DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM

REFERENCES:

DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: SKID MOUNTED SPEED SWITCH O AR-801' Rev. 10 Page 15

~# I i %( FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-02 FS-02-02 FIRE PUMP 3A HI M/ATER TEMP i F INDICATED CONDITION: HI-WTR TEMP ON COOLING WTR 2190 DEG F i REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: CHECK WATER LEVEL IN DIESEL COOLING SYSTEM. DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM

REFERENCES:

DWG 208-031 FS-2-7, FS-01 SEN5ING ELEMENT: FS-15-TS l AR-801 Rev. 10 Page 16 1

l i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-03 FS-02-03 1 l FIRE PP 3A LO LUBE OlL PRESS l INDICATED CONDITION: LO LUBE OIL PRESS s10 PSIG l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: REFILL WITH OIL IF NECESSARY. I J DISCUSSION: l

REFERENCES:

DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: FS-40-PS l l i l l I l O AR-801 Rev. 10 Page 17

('. l-l ~ FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02 FS-02-04 FIRE PUMP 3A NOT IN AUTO i l INDICATED CONDITION: DIESEL CONTROL SWITCH NOT IN AUTO OR TEST REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: RETURN SWITCH TO AUTO ] DISCUSSION: l l

REFERENCES:

DWG 208-031 FS-2-7, FS-01 l SENSING ELEMENT: CS I 1 I O I AR-801 Rev. 10 Page 18

p, ] 4 4 T. FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-05 FS-02-05 FIRE PUMP 3A Fall TO START f. i I. L INDICATEli CONDITION: PUMP NOT RUNNING UP TO SPEED 90 SECONOS AFTER DIESEL. RECEIVES AN AUTO START l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: . O OPERATOR ACTION FOR A VALID ALARM: DISCUSSION: PUSH LOCAL RESET PUSH BlITTON TO RESET ALARM

REFERENCES:

DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: REL AY 7R 1 l l l l l 1 I AR-801. Rev. 10 Page 19 i I

) FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-06 FS-02-06 s i l I L FIRE PUMP 3A i I RUNNING I i i I ) 1 i _m. INDICATED CONDITION: DIESEL IS RUNNING AND UP TO SPEED REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ,-m () OPERATOR ACTION FOR A VALID ALARM: NONE DISCUSSION: FIRE PUMP h00SE FANS (AHF-33A & AHF-33B) ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL PilMP FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING COLD WEATHER OPERATIONS PER OI-13.

REFERENCES:

DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: RELAY 15R ,n-\\ N t AR-801 Rev. 10 Page 20 l

l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-07 FS-02-07 i l l' l = r l I~ j l l l FIRE PUMP 3A FUEL LEVEL LO l t l l INDICATED CONDITION: FUEL TAW LEVEL s66.5% FULL REDUNDANTINDICATIONWHICHWILhERIFYALARM: I OPERATOR ACTION FOR A VALIO ALARM: REFILL TANK i DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-13-LS t l l AR-801 Rev. 10 Page 21

l 1. l ) FIRE SYSTEM ANNUNCIATOR RESPONSE FS 02-09 FS-02-09 v FIRE PUMP 3C OVERSPEED I I I INDICATED CONDITION: FSP-2B OVERSPEED 22100 Rf M REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ,f i ) OPERATOR ACTION FOR A VALID ALARM: } DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM J

REFERENCES:

DWG 208-031 FS-8-7.3, FS-02 SENSING ELEMENT: SKID MOUNTED SPEED SWITCH g l i l ) l 4 l ,m. 1_ ' AR-801 Rev. 10 Page 22 u

l*' .j l l is,, j L.,p' .Nj. FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-10 FS-02-10 = _. _ f \\ .\\ FIRE PUMP 3C 1 _a. HI WATER TEMP. { j L' { ? \\ \\ I l. f~~ i l l. INDICATED CONDITION: HI WATER TEMP ON COOLING WTR 2190 DEG F l-(h: REDUNDANT INDICATION WHICH WILL VERIFY ALARM: v l l \\. [ OPERATOR' ACTION FOR A VALID ALARH: CHECK WATER LEVEL'IN DIESEL COOLING' SYSTEM. DISCUSSION: PUSH LOCAL RESET POSH BUTTON TO CLEAR ALARM ~ i i i

REFERENCES:

DWG 208-031 FS B-13 FS-02 J SENSING ELEMENT: FS-16-TS l l,, l' ( h AR-801 Rev.-10 Page 23 i

s ] () FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-11 FS-02-11 r ~ f l l FIRE PP 3C LO LUBE OIL PRES

=

h-CM .q L- - i INDICATED CONDITION: L LUBE CIL PRESS s10 PSIC i REDUNOANT INDICATION WHICH WILL VERIFY ALARM: ( ('~'\\ (_) OPERATOR ACTION FOR A VALIO ALARM: REFILL WITH OIL IF NECESSARY l DISCUSSION:

REFERENCES:

DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: FS-41-PS ~ " ' - ~ , rx 'x.. - AR-801 Rev. 10 Page 24

I, t~.. !.4 l FIRE SYSTEM' ANNUNCIATOR RESPONSE - FS 12 FS-02-12 [ [ 1 FIRE PUMP 3C NOT IN AUTO ~ k INDICATED CONDITION:, DIESEL CONTROL SWITCH NOT IN AUTO OR TEST REDUNDANT INDICATION WHICH WILL VERIFv' ALARM: 1 \\ OPERATOR ACTION FOR A VALID ALARM: RETURN TO ALITO l' . DISCUSSION: ..r l

REFERENCES:

DWG 208-031 FS-8-13, FS-02 i-SENSING E'EMENT: CS L 1 1 ' \\ i-( !, l i L , %_/-. I AR-801 Rev'. 10 Page 25 ll-

1 l L.. I~ l'Aj - FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-13 FS-02-13 l l FIRE PUMP 3C l FAIL TO START l l i INDICATED CONDITION: DIESEL NOT UP TO SPEED AND RUNNING 90 SECONDS AFTER RECEIVING AN AUTO START SIGNAL l, REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l OPERATOP. ACTION FOR A VALID ALARM: 1 DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM l

REFERENCES:

DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: RELAY 7R l l r AR-801 Rev. 10 Page 26

l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-14 FS-02-14 l FIRE PUMP 3C t RUNNING j. l l INDICATED CONDITION: DIESEL IS RUNNING AND UP TO SPEED l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: O Q OPERATOR ACTION FOR A VALID ALARM: NONE l DISCUSSION: ) FIRE PUMP HOUSE FANS (AHF-33A & AHF-33B) ARE USED FOR FIRE PUMP COOLING AND 4 COMBUSTION AIR FOR DIESEL PUMP FIRE PUMPS AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING COLD WEATHER OPERATIONS PER OI-13

REFERENCES:

DWG 208-031 FS-8-13, FS-02 ) l SENSING ELEMENT: RELAY 15R i l-NJ AR-801 Rev. 10 Page 27

l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-15 FS-02-15 l t FAE PUMP 3C t l FUEL LEVEL LO t l l a t I 1 l INDICATED CONDITION: FUEL TANK LEVEL s50% FULL t l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: REFILL TANK l l DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-14-LS O AR-801 Rev. 10 Page 28

r, a l* FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-01 FS-03-01 l c=

=

MN TRAN SF 3-1 1..se O'.'O TRBL l. l l INDICATED CONDITION: MAIN TRANSFORMER #3-1 DELUCE VALVE (FSV-69) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-68), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: O&') j OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING l. DISCUSSION: j ) l

REFERENCES:

DWG 208-031 FS-5, FD-302-231 SHT 01 OF 05 l SENSING LLEMENT: K-2, K-5 l O i AR-801 Rev. 10 Page 29

F. I~ l x FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-02 FS-03-02 l l I l MN TRANSF 3-2 FIRE SYS TR8L l INDICATED CONDITION: MAIN TRANSFORMER #3-2 DELUCE VALVE (FSV-66) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-65), OR CIRCUIT TROUBLt REDUNDANT INDICATION WHICH WILL VERIFY ALARM: I OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING l DISCUSSION: l

REFERENCES:

DWG 208-031 FS-6, FD-302-231 SHT 01 0F 05 l SENSING ELEMENT: K-2, K-5 l [ O AR-801 Rev. 10 Page 30 l

{ l v' FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-03 FS-03-03 l MN TRANSF 3-3 FIRE SYS TRBL INDICATED CONDITION: MAIN TRANSFORMER #3-3 DELUGE VALVE (FSV-64) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-63), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-07, FD-302-231 SHT 010F 05 SENSING ELEMENT: K-2, K-5 AR-801 Rev. 10 Page 31

~ [ l l e I I FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-04 FS-03-04 UNIT TRANSF 3 FIRE SYS TRSL l l INDICATED CONDITION: UNIT AUX TRANSFORMER DELUGE VALVE (FSV-72), LOSS OF l POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-71), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ^ O i OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION: l REfcRENCES: DWG 208-031 FS-08, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 l AR-801 Rev. 10 Page 32

r FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-05 FS-03-05 l STRT-UP TRAN 3 l FHtE SYS TRBL l INDICATED CONDITION: START UP TRANSFORMER DELUGE VALVE (FSV-61) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-60), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: '0 1V OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION: l

REFERENCES:

DWG 208-031 FS-09, FD-302-231 SHT 010F 05 SENSING ELEMENT: K-2, K-5 i i l l 1 l i O i AR-801 Rev. 10 Page 33

) FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-06 FS-03-06 VVATER CURTAIN TROUBLE INDICATED CONDITION: TURBINE BUILDING WATER CURTAIN DELUGE VALVE (FSV-239) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-238), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION: l

REFERENCES:

DWG 208-031 FS-22, FD-302-231 SHT 01 0F 05 l SENSING ELEMENT: K-2, K-5 i O AR-801 Rev. 10 Page 34

~. FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-07 FS-03-07 TUR8 LUBE OIL FIRE SYS TRBL INDICATED CONDITION: TURBINE LUBE OIL DELUGE VALVE (FSV-10) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-108), OR CIRCUIT TROUBLE REDUNDANT Ii4DICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INVESTIG%TE AREA FOR TAMPERING l DISCUSSION:

REFERENCES:

DWG 208-031 FS-10, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 = O l AR-801 Rev. 10 Page 35

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-08 FS-03-08 FEEDWTR PUMP FIRE SYS TRBL __E d INDICATED CONDITION: FEEDWATER PUMP CONSOLES DELUGE VALVE (FSV-67) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-62), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION: l

REFERENCES:

DWG 208-031 FS-10, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 O AR-801 Rev. 10 Page 36

Ik_,/ FIRE. SYSTEM ANNUNCIATOR RESPONSE FS-03-09 FS-03-09 s l 1 H2 SEAL OlL FIRE SYS TRBL i INDICATED CONDITION: HYDROGEN SEAL OIL DELUGE VALVE (FSV-82) LOSS OF POWER 4 TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-83), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH KELL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION: l

REFERENCES:

DWG 208-031 FS-12, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 l l l i AR-801 Rev. 10 Page 37

4 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-10 FS-03-10 B/U ES XFMR TRBL INDICATED CONDITION: BACKUP ES TRANSFORMER DELUGE VALVE (FSV-832) LOSS OF i POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-831), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION: l IFERENCES: DWG 208-031 FS-22, FD-302-231 SHT 010F 05 SENSING ELEMENT: FSCP-4 O l l AR-801 Rev. 10 Page 38

t FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-11 FS-03-11 ( l i l FIRE PUMP HSE SPRINKLER ACT INDICATED CONDITION: FIRE PUMP HOUSE SPRINKLER SYSTEM ACTUATED 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-17-PS i l i O I AR-801 Rev. 10 Page 39

[. l 1 I l f\\ \\,,/ FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-12 FS-03-12 i RB MAINT BLD SPRINKLER ACT INDICATED CONDITION: FIRE SPRINKLER SYSTEM HAS ACTUATED IN THE RB MAINTENANCE SUPPORT BLDG REDUNDANT INDICATION WHICH WILL VERIFY ALARM: SPRINKLER SYSTEM PRESSURIZED O TO >30 PSIG tv/ OPERATOR ACTION FOR A VALID ALARM: CHECK RBMSB FOR FIRE DISCUSSION:

REFERENCES:

55 211-031 FS-02 SENSING ELEMENT: FS-508-PS2 ' O AR-801 Rev. 10 Page 40

(. I FIRE SYSTEM ANNUNCIATOR RESPONSE 'FS-03-13 FS-03-13 TURB BLDG BEL 119' SPR ACT d l INDICATED CONDITION: SPRINKLER SYSTEM BELOW TURB BLDG 119' ELEVATION 4 ACTUATED 210 PSIG I i REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ,O 1 l OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE. REFER TO AP-880 (FP) i DISCUSSION: )

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-24-PS l 'O AR-801 Rev. 10 Page 41 l l

r, 9 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-14 FS-03-14 l / TURB BLDG BEL 119' SPR ACT 4 INDICATED CONDITION: SPRINKLER SYSTEM BELOW TURB BLDG 119' ELEVATION ACTUATED 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM: O OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-25-PS l i i \\ O AR-801 Rev. 10 Page 42

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-15 FS-03-15 OUTAGE SUPP BLDG FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN OUTAGE SUPPORT BUILDING REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 211-031 FS-076 SENSING ELEMENT: FS-472-FS 1 l 1 i O i.. AR-801 Rev. 10 Page 43

I. l. .-w s__ FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-01 FS-04-01 MAIN TRANSF 3-1 FIRE 4 INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ,\\ k ) OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO ~ AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-05 SENSING ELEMENT: K-4 l l i l l t,- t t ,r' AR-801 Rev. 10 Page 44

c. i, v. l r l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-02 FS-04-02 l I l l MAIN TRANSF 3-2 FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO l AP-880 (FP) l DISCUSSION: l

REFERENCES:

DWG 208-031 FS-06 SENSING ELEMENT: K-4 l I 1 O AR-801 Rev. 10 Page 45

~ ) FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-03 FS-04-03 MAIN TRANSF 3-3 FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: s(') OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-07 SENSING ELEMENT: K-4 /^s () AR-801 Rev. 10 Page 46

1-FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-04 FS-04-04 ( i i l UNIT TRANSF 3 FIRE INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY 1 l-REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l. OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFEP. TO AP-880 (FP) i DISCUSSION: 1 [

REFERENCES:

DWG 208-031 FS-08 i l SENSING ELEMENT: K-4 i O AR-801-Rev. 10 Page 47

O FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-05 FS-04-05 ) STARTUP I I TRANSF 3 FIRE 1 1 I. i INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP) DISCUSSION: l

REFERENCES:

DWG 208-031 FS-09 I SENSING ELEMENT: K-4 i l-l 1. l AR-801 Rev. 10 Page 48

j/l"'m, -x,,/ FIRE SYSTEM ANNUNCIATOR RESPONSE F5-04-06 FS-04-06 I ~ l l l 1, WATER CURTAIN FIRE I INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: (~h, (, j OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO j AP-880 (FP) l DISCUSSION:

REFERENCES:

DWG 208-031 FS-22 SENSING ELEMEKf: K-4 l ~g AR-801 Rev. 10 Page 49 L

I s FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04 FS-04-07 m l l \\ n l TURB LUBE OIL l: SYSTEM FIRE I-j. l l l INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN,'OR HAS BEEN OPENED LOCALLY. l l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA REFER TO l AP-880 (FP) DISCUSSION: -=- j-

REFERENCES:

DWG 208-031 FS-10 SENSING ELEMENT: K-4 l i I l': ('; i O AR-801 Rev. 10 Page 50 1

1 i ' '1,,' FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-08 FS-04-08 1 I l FEEDWTR PUMP CONSOLE FIRE INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: q,) OPERATOR ACTION FOR A VALIO ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-11 SENSING ELEMENT: K-4 I j l 1 -~, 7 ) LJ t s AR-801 Rev. 10 Page 51 l

T l l o V W). , j'w/ - FIRE SYSTEM ANNUNCIATOR RESPONSE-FS-04-09 FS-04 09. ~ __ ___7- ._. _L ' H2 GEAL OIL UNIT FIRE j t INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: '~ OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP.-880 (FP) DISCUSSION: ~

REFERENCES:

DWG 208-031 FS-12 SENSING ELEMENT: K-4 { O AR-801 Rev. 10 Page 52 T: t

('.- } u: ~ g FIRE SYSTEM ANNUNCIATOR RESPONSE Fh-04-10 FS-04-10 ) ~ i B/U ES XFMR FIRE i INDICATED CONDITION:, DELUGE VALVE SHOULD GE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-040 MT-140 SENSING ELEMENT: FSCP-4 I O AR-801 Rev. 10 Page 53 j

O V FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-11 FS-04-11 i TURB BLDG BEL 145' SPR ACT INDICATED CONDITION: TURB BLDG BELOW 145' ELEVATION SPRINKLER SYSTEM ACTUATION 210 PSIC REDUNDANT INDICATION WHICH WILL VERIFY ALARM: O OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-26-FS O AR-801 Rev. 10 Page 54

l' i l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-12 FS-04-12 i l l TURB BLDG BEL l 145' SPR ACT l l 4 INDICATED CONDITION: TURB BLDG BELOW 145' ELEVATION SPRINKLER SYSTEM ACTUATION 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM: !O l OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA REFER TO { AP-880 (FP) DISCUSSION: l 1 l.

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-27-FS l 0 i AR-801 Rev. 10 Page 55

l t. l l(d 7 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-13 FS-04-13 1 CONT COMP BEL 108' l SPR ACT i INDICATED CONDITION: CONTROL COMPLEX BELOW 108' ELEVATION SPRINKLER SYSTEM ACTUATION 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP) i DISCUSSION: t

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-33-FS l> l l l. AR-801 Rev. 10 Page 56 l

I- ?- ( /\\v} FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-01 FS-05-01 l 1 l l CHARCOAL FLTR l AHFL-1 TRBL \\ INDICATED CONDITION: PURGE EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE 1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM: 'O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION: l

REFERENCES:

DWG 208-031 FS-24, FS-13 { SENSING ELEMENT: K-2, K-5 l l 4 m AR-801 Rev. 10 Page 57

9 l

i. p.,

(,) FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-02 FS-05-02 l l Jumm_ CHARCOAL FLTR AHFL-2A TRBL l INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF. POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE l REDUNDANT INDICATION WHICH HELL VERIFY ALARM: (C'D OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING l DISCUSSION:

REFERENCES:

DWG 208-031 FS-25, FS-14 SENSING ELEMENT: K-2, K-5 i O AR-801 Rev. 10 Page 58 l

e 1 l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-03 FS-05-03 l CHARCOAL FLTR AHFL-2B TRBL l INDICATED CONDITION: AUX BLDC MAIN EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE 1 l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: O OPERATOR ACTION FOR A VALID alt.RM: INVESTICATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-15 SENSl i iLEMENT: K-2, K-5 l l O l AR-801 Rev. 10 Page 59

1 l O' O FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-04 FS-05-04 i l CHARCOAL FLTR l AHFL-2C TR8L L._- INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARC0AL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-16 SENSING ELEMENT: K-2, K-5 t O l AR-801 Rev. 10 age 60

i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-05 FS-05-05 l CHARCOAL FLTR AHFL-2D TRBL INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARCOAL FILTER DELUGE SYSTEM i LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE f REDUNDANT INDICATION WHICH h3LL VERIFY ALAR *'- O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-17 SENSING ELEMENT: K-2, K-5 i-L AR-801 Rev. 10 Page 61

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-06 FS-05-06 i ) CHARCOAL FLTR AHFL-4A TRBL e INDICATED CONDITION: CTRL COMPLEX EMERCENCY CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-18 l SENSING ELEMENT: K-2, K-5 O t AR-801 Rev. 10 Page 62

I. l FS-05-07 l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-07 i t l CHARCOAL FLTR l AHFL 48 TRBL INDICATED CONDITION: CTRL COMPLEX EMERGENCY CHARCOAL FILTER DELUGE SYSTEf4 LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: lO OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION-

REFERENCES:

DWG 208-031 FS-19 SENSING ELEMENT: X-2, K-5 I I l l I i O AR-801 Rev. 10 Page 63

\\ FIRE SYSTEM ANNUNCIATOP. RESPONSE FS-05-08 FS-05-08 CHARCOAL FLTR AHFL-15 TRBL INDICATED CONDITION: NUCLEAR SAMPLE ROOM CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TR0llBLE REDUNDANT INDICATION 43ICH WILL VERIFY ALARM: O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-20 SENSING ELEMENT: K-2, K-5 t l O AR-801 Rev. 10 Page 64

e f l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-09 FS-05-09 ADMIN BLDG WAREHOUSE FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN WAREHOUSE OR ADMIN BLDG REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:

REFERENCES:

SENSING ELEMENT: l l l O AR-801 Rev. 10 Page 65

j FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-10 FS-05-10 OFFICE BLDG TROUBLE / FIRE INDICATED CONDITION: RUSTY BUILDING FIRE OR INSTRUMENT FAILURE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: ZONE 1-3 ALARM O AR-801 Rev. 10 Page 66

1 I FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-11 FS-05-11 ) CONTROL BLDG TROUBLE / FIRE 1 I i l INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN CONTROL BLDG REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: ZONE 4-11 ALARM 1 AR-801 Rev. 10 Page 67

I, .Q k/ . FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-12 FS-05-12 l SWITCH GEAR RM TROUBLE / FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN SWITCHCEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: ZONE 12-13 ALARM f 1 AR-801 Rev. 10 Page 68

a FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-13 FS-05-13 l l l l l l FIRE PROT TROUBLE t IND CATED CONDITION: FIRE PROTECTION TROUBLE PLANT OR OFFICE AREA CAB REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ALARM PANELS LOCATED ON 124' ELEV. CONTROL COMPLEX AND 1st FLOOR OF RUSTY BLDG IN TELEPHONE TERMINATION OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION: THIS ALARM MAY COME IN WHEN THE HALON PROTECTION SYSTEM IS PLACED IN " TEST"

REFERENCES:

DWC 208-031 FS-21 SENSING ELEMENT: PLANT AREA CAB, OFFICE AREA CAB l I O 'AR-801 Rev. 10 Page 69

4. l. l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-14 FS-05-14 t EMER DSL GEN ROOM TROUBLE INDICATED CONDITION: LOSS OF POWER OR CIRCUIT FAILURE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA j DISCUSSION: )

REFERENCES:

DWG 208-031 FS-23 SENSING ELEMENT: OR, RSR, TSR l l O i AR-801 Rev. 10 Page 70

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-15 l FS-05-15 ~ EMER DSL GEN ROOM FIRE INDICATED CONDITION: ONE OF TWENTY SENSORS HAS ACTUATED. FSV-101 SHOULD BE OPEN. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:

REFERENCES:

DWG 208-031 FS-23 SENSING ELEMENT: OR i O AR-801 Rev. 10 Page 71

i. I'& I \\ ' v FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-01 FS-06-01 m) l CHARCOAL FLTR AHFL-1 FIRE i INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-24, FS-13 SENSING ELEMENT: K-4 [ i O AR-801 Rev. 10 Page 72 l

1 l l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-02 FS-06-02 l l l l CHARCOAL FLTR AHFL-2A FIRE q l l i l -{ i l INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: 1 !(3 lQ OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) DISCUSSION: J

REFERENCES:

DWG 208-031 FS-25, FS-14 r i l SENSING ELEMENT: K-4 1 i I I l l r r AR-801 Rev. 10 Page 73 L

f%

\\.
IRE SYSTEM ANNUNCIATOR RESPONSE FS-06-03 FS-06-03 CHARCOAL FLTR AHFL-2B FIRE 4

INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-15 SENSING ELEMENT: K-4 O AR-801 Rev. 10 Page 74

v. r" N FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-04. FS-06-04 I l-CHARCOAL FLTR AHFL-2C FIRE l i I INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) l DISCUSSION:

REFERENCES:

DWG 208-031 FS-16 j SENSING ELEMENT: K-4 1 i l l l [ AR-801 Rev. 10 Page 75

1.. E (), FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-05 FS-06-05 I CHARCOAL FLTR AHFL-2D FIRE 1 I 1 I I J INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY I REDUNDANT INDICATION WHICH WILL VERIFY ALARM: I bQ OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) j DISCUSSION:

REFERENCES:

DWG 208-031 FS-17 SENSING ELEMENT: K-4 i AR-801 Rev. 10 i' age 76 I

l 4 ): FIRE-SYSTEM ANNUNCIATOR RESPONSE FS-06-06 FS-06-06 t .J i CHARCOAL FLTR AHFL-4A FIRE l' l l l l. INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY t i i REDUNDANT INDICATION WHICH KELL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA, REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-18 I SENSING ELEMENT: K-4 I i AR-801 Rev. 10 Page 77 l.

a i n i f_ FIRE SYSTEM ANNUNCIATOR RESPONSE' FS-06 FS-06-07 CHARCOAL FLTR AHFL-48 FIRE 4 l i INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY i REDUNDANT INDICATION WHICH.WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-19 SENSING ELEMENT: K-4 O AR-801 Rev. 10 Page 78

I, ia ,~ ! (_) FIRE SYSTEM ANNUNCIATOR P'SPONSE FS-06-08 FS-06-08 c l CHARCOAL FLTR AHFL-15 FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: /~n (_,) OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) DISCUSSION:

REFERENCES:

DWG 208-031 FS-20 I SENSING ELEMENT: K-4 !(V \\ ) AR-801 Rev. 10 Page 79

1 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-09 FS-06-09 TSC TROUBLE INDICATED CONDITION: ALARM AT PYROTRONICS PANEL REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A' VALID ALARM: INVESTICATE TSC FIRE SYSTEM DISCUSSION:

REFERENCES:

DWG 209-031 FS-39.- SENSING ELEMENT: TSC FIRE PP.0TECTION CONTROL PANEL O AR-801 Rev. 10 Page 80

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-10 FS-06-10 l TSC FIRE 1 l INDICATED CONDITION: FIRE OR INSTRUMENT FAILURS IN TSC REDUNDANT INDICATION WHICH WILL VERIFY ALARM: b Q OPERATOR ACTION FOR A VALID ALARM:.INVESTICATE TSC. AREA DISCUSSION:

REFERENCES:

DWG 209-031 FS-39 i l SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL ( 1 O l l AR-801 Rev. 10 Page 81

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-11 FS-06-11 TSC FILTER AHFL-20 TROUBLE I INDICATED CONDITION: ALARM AT LOCAL PANEL REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE TSC FILTER ROOM i DISCUSSION:

REFERENCES:

DWG 209-031 FS-39 SENSIr0 ELEMENT: TSC FIRE PROTECTION CONTROL PANEL 1 l l O AR-801 Rev. 10 Page 82

9 .e e FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-12 FS-06-12 l l TSC FILTER j AHFL-20 FIRE 1 I l l l INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN AHFL-20 REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE TSC FILTER ROOM DISCUSSION:

REFERENCES:

209-031 FS-39 l SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL l O AR-801 Rev. 10 Page 83

e. I' FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-13 FS-06-13 RECORD STORE VAULT FIRE INDICATED CONDITION: WATER FLOW INTO RECORD VAULT SPRINKLER SYSTEM REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA FOR FIRE. NOTIFY J ADMINISTRATIVE SUPERVISOR. DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-70-FI 3 O AR-801-Rev. 10 Page 84 k

E r o (.. l '-( FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-14 FS-06-14 i I CONT COMPLEX l FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP) u DISCUSSION:

REFERENCES:

DWG 208-031 FS-24 SENSING ELEMENT: K-4 I t i O -AR-801 Rev. 10 Page 85 L

I e ) () FIRE SYSTEN ANNUNCIATOR RESPONSE FS-06-15 FS-06-15 i CONT CCDMPLEX FIRE SYS TRBL INDICATED CONDITION: LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING. INVESTIGATE LOSS OF CONTINUITY IN HALON SYSTEM FIRING CIRCUIT. DISCUSSION:

REFERENCES:

DWG 208-031 FS-24 SENSING ELEMENT: K-5, K-2 AR-801 Rev. 10 Page 86 (LAST PAGE) >}}