f CEgy k UNITED STATES p
s-j NUCLEAR REGULATORY COMMISSION WASH 4NOToN, D.C. 30006 4001 49.....
BALTIMORE GAS AND ELFCTRIC COMPANY DOCKET NO 50-317 CALVERT CLIFFS NUCLEAR POWER PLANT UNIT NO.1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.226 License No. DPR-53 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment by Baltimore Gas and Electric Company (the licensee) dated October 22,1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; j
1 B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with th's Commission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the h9alth and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.2. of Facility Operating License No. DPR-53 is hereby amended to read as follows:
9003200206 900317 PDR ADOCK 05000317 p
[.
P 1
2.
Technical SpecificatKms l
The Technical Specifications contained in Appendices A acJ B, as revised l
through Amendment No. 226, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
t 3.
This license amendment is effective as of the date of its issuance and shall be implemented during the spring 1998 refueling outage.
l FOR THE NUCLEAR REGULATORY COMMISSION S. Singh Bajwa, Director i
Project Directorate I-1 Division of Reactor Projects - 1/11
[_
Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical j'
Specifications Date of issuance: March 17, 1998 I
I l
'/
a U4
'j y
\\
UNITED STATES g
[
NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. - aaai BALTIMORE GAS AND ELECTRIC COMPANY DOCKET NO. 50-318 CALVERT CLIFFS NUCLEAR POWER PLANT. UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE i
Amendment No. 200 License No. DPR-69 l
1.
The Nuclear Regulatory Commission (the Commission) has found that:
i l
l A.
The application for amendment by Baltimore Gas and Electric Company (the j
licensee) dated October 22,1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's l
rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; t
I C.
There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; l
D.
The issuance of this amendment will not be inimical to the common drJense and security or to the health and safety of the public; and h
l E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the i
Commission's regulations and all applicab'e requirements have been satisfied.
2.
Accordingly, the license is smended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.2. of Facility i
Operating License No. DPR 69 is hereby amended to read as follows:
1 l
l
~
l
/
2.
Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 200, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of the date of its issuance and shall be implemented during the spring 1998 refueling outage.
FOR THE NUCLEAR REGUI.ATORY COMMISSION M
4&/
i
/ J
\\
S. Singh Bajwa, Director Project Directorate I-1 Division of Reactor Projects - 1/11 Office of Nuclear Reactor Regulation
Attachment:
Changes to the Te::hnical Specifications Date of issuance: March 17, 1998 4
I
{
i
/
i i
ATTACHMENTTO LICENSE AMENDMENTS l
AMENDMENT NO226 FACILITY OPERATING LICENSE NO. DPR-53 l
AMENDMENT NG00 FACILITY OPERATING LICENSE NO. DPR-69 l
DOCKET NOS. 50-317 AND 50-318 l
Revise Appendix A as follows:
Remove Paoes Insert Paaes
~
3/4 3-12 3/4 3-12 3/4 3-17 3/4 3-17 3/4 3-21 3/4 3-21 3/4 8-4 3/4 8-4 l
l l
l
- Pages that did not change, but are overleaf.
I l
l R
"!=5 l
NO I
T 8
8 7
7 7
CA ELBS 3
3 3
AE CD 2
2 2
IO 6
6 LM PP 1
1 1
A N
SE O
M LL e
I U
v s
s s
EB T
M l
u u
u NA A
I NR a
3 B
D B
T N
v
/
/
/
AE N
I HP
/
3 3
3 E
M 1
M CO URTSN I
M S
P e
L E
I v
s s
s T
E
)
R l
u u
u d
MT S
a 2
B B
B e
Y v
/
/
/
u S
A O
/
2 2
2 n
H T 1
N C
i t
O n
I o
T C
A
(
UT 3
C A
.S 3
L E
OE e
3 NM v
s s
s R
l u
u u
U EL T
LA a
4 B
B B
B A
AH v
/
/
/
E TC
/
4 4
4 A
F O
1 T
TF Y
O TEFAS lo e
D r
t E
t a
R n
t t
E o
n S
E C
n sf se s
N S
o uo ui uy I
E e
i B
Bs Bd G
V v
t s
n a
N L
l ar ys ya) ye)
E A
a io co cre cte V
V dt nL nTg nSg ai e(
e(a e( a E
e Rn g
g t
g t
G g
o re rel rel R
r tM eg ego ego U
u n
ma maV maV P
P) ea R
Et Et Et (s
me E
l) ld ld T
T e
nr W
voe voe voe I
N lh iA O
kvg kvd kvd N
EN ac a
P ra ra ra U
MO ut th 6et 6er 6er
=
NI ni ng F
1.d l
- 1. d g
- 1. d g L
IT aw oi O
no ne ne A
TL S
O NO S
I OS O
T CI a
b L
a b
c CNU F
6 7
g b q" c%
- R*
kEl+c E.
o
n R=' w Eg>dE y
y k
aa a
a a
n l
l e
a he he hm S
t td d
i t
t E
e e
i t
i i
we e
U l
e l
r m
w m w
L b
v b
d h
si si s
A a
o a
n V
c bm c
/
tt t
o t
t r
l cy i
ao i
m od od l
l S
E l
t l
E L
p st p
vn n
o ea sl U
B p
eo p
0 o
v v
o e
t L
A A
hb A
2 5c 0c 0 5. d A
M c
2 0e e
8 8
1s s
3 V
O t
n t
L o
i o
5 P
L N
N 12 1
11 4
I A
4 R
2 00 0
0 0
1 0
1 5
7 0
T 2
41 1 9 1
2 3
3 N
2 8
O IT4 y
y y
a T
aa a
al N
k a
n l
l e
E he he h
a d
W t
td d
t t
R T
e e
i e
i i
we e
r m
w m w m l
e l
T N
b v
b
)
i S
I h
si i
t d
l a
o a
s s
e l
O c
bm c
/
tt t
r t
t I
P d
u l
i ao i
n T
l l
m od od o n l
t l
M E
t E
S p
st p
vn n
o i
T p
eo p
0 o
v o v c 2
5c c
e no S
P A
hb A
c 2
0e 0
0 e
8s 8
Y I
1 s s
C t
n t
S RT o
i o
5 5
(
4 N
N N
12 1
1.
4 O
4 0
0 3 I
2 00 0
1 0
5 91 3
T 7
A 1
41 1
2 3
3 3
1 U
2 8
0 E
T 1
L C
B A
A E
e e
e T
R a
g g
g U
)
e a
a a
T S
r t
t t)
A A
N A
l l
l e E
R O
o o
og F
(
I h
v v) va T
l g
r re rt Y
N w
A o
i e
eg el T
O
)
o L
r H
d da do E
I s
L O
t n
nt nV F
T n
S n
U Ul U
A A
o I
o o
d S
L t
C n
s sV se U
t k
S o
u u
ud D
C u
n E
e i
B Bd Ba E
R B
a V
v t
e r
R I
T L
l a
y) yd yg E
C p
A a
i ce ca ce E
E i
r V
V d
ng nr nD N
R r
e a
ea eg e
I T
t E
E R
gt ge ge G
P
(
a G
G rl rD rt N
M W
R R
t eo e
ea E
U S
U U
n mV mt mt S
A g
P P) e R
E En ES R
n (s
m E
f e
T T
i T
e nr W vo vi vy I
N l
l N
lh io O k
ks kd N
E a
e E
ac at P s
n a
U M
u u
M ut ti 6s 6a 6e f
n f
ni nn F o
r t
L l
a e
l aw oo O
- 1. L
- 1. T
- 1. S l
A A
M R
A MS CM 4(
4(
4(
N T
T S
O N
N S
I O
O O
T C
a b
C a
b L
a b
c CNU F
5 6
7 gr b,m e5~ "
R= " G (a(=,.,P M.
R*' w "k5>
ND WAE 3
3 3
3 3
3 LR 3
NLI A
IIU 2
2 2
EQ 2
N 2
2 2
S SVE T
ERR 1
1 1
1 1
1 N
DU 1
OS E
M E
R I
L U
L A ML Q
N A
E E
R N OT I
N IS L V TE Q Q Q Q
E Q Q W R
E E
A CT U T Q
C N N F
N N
C U E
I A
F R
L L
IE N
V O
MLMLML ML MLML R
LI A
A A
A A
A U
ET I
I I
L V L V L V I
R E
E E R L V IL V I S
R R
R A
R L V MA E
N E E RA E
E E
E E
N AB U
T U T U EN T U T U T U
O HI F
F T
F F
E E N N
F E
N F N
N I
I I
I E
E N I
CL E
T A
R R
R R
R R I I
A C
T
)
d N
e E
u W
n i
R t
T n
S o
N L
EK C
I
(
'N MC A
A A
A A
A E
E AN N
N N
N N
S S
2 N
T HC 3
S C
4 YS EL N
B O
I AT T
e e
e A
g g
g U
a a
a T
t t
t) h C
l l
l e g
A o
o og i
v v)va H
E r
rert w
R e
egel o
U d
dado n
L h
c T
n ntnV we g
i A
U UlU or i
g E
o d
du H
o F
s sVse ts
)
l L
u u
ud es s
e Y
B BdBa Le n
v n
T e
r
/r o
e P
o E
y) yd y g mP t
L A
i F
cecace o
t t
A ngnrnD om R
u r
r a
S eaege Ro E
B o
o u
gt g e g e o
T t
t t
D rl rDrt nR A
p a
a c
E eoe ea o
W i
r r
A R
mVmtmt N ir D
r e
e E
R E
EnES O te E
T n
n c
E E
f e
I ag E
(
e e
i N
T W
Vovivy T rn F
G G
t I
I O
k kthd A ta l
a M
M P
s n
a L eh Y
a m
m m
6s6a6e O nc R
u a
a o
E F
L O
- 1. Lo 1. Tr 1. S t S ex A
n e
e t
I PE I
a t
t u
A 4(4(4(
L M
S S
A N
S S
tt I
O S
C sa X
I O
V ee U
T L
a b
c C
WH A
a b
c d
CNU F
7 8
9 g G gw b y'" ' e g "
mA k
[? im 3
o 3/4.8 ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS 4.8.1.1.1 Each required independent circuit between the offsite transmission network and the onsite Class 1E Distribution System shall be:
a.
Demonstrated OPERABLE, as follows:
1.
For each 500 kV offsite circuit, at least once per 7 days by verifying correct breaker alignments and indicated power availability.
2.
For the 69 kV SMECO offsite power circuit, within one hour of substitution for a 500 kV offsite power circuit, and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter during use by verifying correct breaker alignments and indicated power availability and b.
Demonstrated OPERABLE at least once per REFUELING INTERVAL during shutdown by manually transferring unit power supply from the normal circuit to the alternate circuit.
4.8.1.1.2 Each diesel generator shall be demonstrated OPERABLE:
a.
At least once per 31 days on a STAGGERED TEST BASIS by:
1.
Verifying the fuel level in the day fuel tank.
2.
Verifying the fuel level in the fuel storage tank.
3.
Verifying the fuel transfer pump can be started and transfers fuel from the storage system to the day tank.
4.
Verifying the diesel starts and achieves a generator voltage and frequency,of 4160 +240, -100 volts and 60 1 1.2 Hz, l
respectively.
5.
Verifying the generator is synchronized, loaded to E 4000 kW for No. 1A Emergency Diesel Generator or 1 2700 kW for No. 1B Emergency Diesel Generator, and operates for E 60 minutes.
6.
Verifying the diesel generator is aligned to provide standby power to the associated emergency busses.
7.
Verifying that the automatic load sequencer timer is OPERABLE with the interval between each load block within i 10% of its design interval.
All engine starts for the purpose of this Surveillance Requirement may be preceded by an engine prelube period and/or other warmup procedures recommended by the manufacturer so that mechanical wear and stress on the diesel engine is minimized.
CALVERT CLIFFS - UNIT 1 3/4 8-4 Amendment No. 226
s Ra'w E $"'E E $ E l
N O
I T
8 8
7 7
7 CA EL BS 3
3 3
AE CD 2
2 2
IO 6
6 LM P
P 1
1 1
A s
N SE O
MLL e
I v
s s
s T
NEB l
u u
u DMR A
A a
3 B
B B
T N
v
/
/
/
AE N
I
/
3 3
3 E
M NP 1
M CO URTSN I
S M
L P e
E I
v s
s s
T E
)
R l
u u
u d
MT S
a 2
B B
B e
Y v
/
/
/
u S
A O
/
2 2
2
~
n H T 1
N C
it O
n I
o T
C A
(
UT 3
C S
A
.L 3
OE e
E NM v
s s
s 3
R l
u u
u U
LA a
4 B
B B
EL T
AH v
/
/
/
B A
/
4 4
4 E
O 1
A F
TF T
O Y
TEFA h
S l
g o
i D
r H
E t
R n
t E
o n
E C
n sf se N
S o
uo ui I
E e
i B
Bs G
V v
t s
n N
L l
a ys ya) y
)
E A
a i
co cre ce e
V V
d nL nTg ng g
a e(
e(a ea a
E e
R g
g t
gtet G
g r
re rel rltl R
r to eg ego eoao U
u nt ma maV mvtV P
P) ei R
Et Et ErS (s
mn E
l) ld e
d T
T e
no W
voe voe vd ye I
N lh iM O
kvg kvd kndd N
EN ac a
P ra ra Uaa MI U
O ut ta 6et 6er 6
er ni ne F
1.d l
- 1. d g 1 stg L
IT aw or O
no ne uSe A
AA MS CA 4UV 4UD 4B(D N
TL S
O NO S
I OS O
T CI a
b L
a b
c CNU F
6 7
grh nC]
g""
R. " M y3 E l e O.
o
il liII Il l)l il)l!i\\jljjiI1 l
1 R*.w ig>dE y
y k
aa a a a
n l
l e
a he he hm S
t td d
i t
t E
e e
i t
i i
we e
U l
e l
r m
w m wd L
b v
b h
si A
a o
a n
si s
/
tt t
to V
c bm c
t r
l cy i
ao i
l l
m od od o ea S
E l
t l
E L
p st p
vn n
sl v
v 0
o o
e U
B p
eo p
2 5c 0c 0 5. d L
A A
hb A
A W
c 2
0e 8e 8
1 s s
3 V
O t
n t
L o
i o
5 P
L N
N 12 1
11 4
I A
4 R
2 00 0
0 0
0 1
1 5
7 90 T
i 41 31 3 1
2 N
2 8
O IT y
A y
y a
TF k
aa a
al a
E n
l l
e I
a he he hd W
t td d
t t
i e
R T
e e
i we e
im l
e l
r m
w m T
N w
b v
b
)
i S
I h
si si s
d t
a o
a N
O
/
tt t
e c
bm c
t t
I P
r l
d u
i ao i
n T
m od od o
l l
n l
t l
M E
p st p
vn n
o i
0 o
v v
E S
o c
t T
p eo p
2 5c 0c 0 e n
S P
A hb A
c 2
0e e
8s o
Y I
1 s s
8 C
t n
t S
RT o
i o
5 5
(
N N
N 12 1
1.
4 4
2 00 0
0 3 O
4 0
0 1
I 5
7 91 3
TA 1
41 1
3 3
2 3
1 U
2 8
0 T
E 1
C LB A
A E
T e
e e
R g
g g
U
)
a a
a T
S t
t t)
A A
N l
l l e E
R O
o o
og F
(
I h
v v) va T
l g
r re rt Y
N w
A o
i e
eg el T
O
)
o L
r H
d da do E
I s
L O
t n
nt nV F
T n
S n
U Ul U
A A
o I
o o
d S
L t
C n
s sV se U
t k
S o
u u
ud D
C u
n E
e i
B Bd Ba E
R B
a V
v t
e r
R I
T L
l a
y) yd yg E
C p
A a
i ce ca ce E
E i
r V
V d
ng nr nD N
R r
e a
ea eg e
I T
t E
e R
gt ge ge G
P
(
a G
g r
rl rD rt N
M W
R r
to eo e
ea E
U S
U u
nt mV mt mt S
A g
P P) ei R E
En ES R
n (s
mn E f
e T
T i
T e
no W vo vi yy I
N l
l N
lh iM O k
ks kd N
E a
e E
ac a
P s
n a
U M
u u
M ut ta 6s 6a 6e N
n f
N ni ne F o
r t
L I
a e
I aw or O
- 1. L
- 1. T
- 1. S A
A M
R A
MS CA 4(
4(
4(
N T
T S
O N
N S
I O
O O
T C
a b
C a
b L
a b
c CNU F
5 6
7 gGg b5 e5* "
R * '*t O kokg,
m8 lll
I
'){l
!I I!.I{jji{
l 1
HND WAE 3
3 3
3 3
3 LR 3
NLI A
IIU 2
2 2
EQ 2
M 2
2 2
S SVE T
ERR 1
1 1
1 1
1 N
DU 1
E OS M
M ER I
L UQ L A ML N
E E
A R
N OT I
IS L V N TE Q Q Q Q
E Q Q W R
E A
E C
H CT U
Q T
N F
N C
N U
E I
A F
V O
MLMLML ML MLML R
LI A
U ET I
I A A
A L V L V I
A A
I MRA L V E
E R R
L V I
I S
L V L V RE E
E E R A
R RA E
E E
N AB U T U E
N E
F T U T
U U EN T
U O
HI F
T N
F F T F
E N N
F I
CL E N N
R R I E
E N E
E T
A R
R I I
I I
R R I A
C
)
T d
N eu E
n W
i R
tn TS o
C N
L I
EK
(
ME C
A A
A A
A M
N N
N N
M N
S S
A 2
MC N
E T
3 S
C Y
4 S
E M
LB I
AT T
e e
e A
g g
g U
a a
a T
t t
t) h C
l l
l e g
A o
o og i
v v
va E
r r)ert H
w R
e egel o
U d
dado n
L h
c T
n ntnV we g
A U
UlU or i
ig E
o d
du H
o F
s sVse t s
)
l L
u u
ud es s
e Y
B BdBa Le n
v n
T e
r
/r o
e P
o E
y) yd y g mP t
L A
F cecace o
t t
i A
ngnrnD om R
u r
r a
S eaege Ro E
B o
o u
gt g e g e o
T t
t t
D rl rDrt nR A
p a
a c
E eoe ea o
W i
r r
A R
mVmtmt N
ir D
r e
e E
R E
EnES O
t e E
T n
n c
E E
f e
I ag E
(
e e
i N
T W
vovivy T
rn F
G G
t I
I O
k kskd A
ta l
a M
N P
s n
a L
eh Y
a m
m m
U 6s6a6e O
nc R
u a
a o
E F
L O
- 1. L r 1. S o1 t
S ex A
n e
e t
.T I
PE I
a t
t u
A 4(4(4(
L M
S S
A N
S S
tt I
O S
C sa X
I O
V ee U
T L
a b
c C
WH A
a b
c d
CNU F
7 8
9 nC q" c5* "
w2 w l
kggg E. m8 3
(
4
'r 3/4.8 ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 2.
For the 69 kV SMECO offsite power circuit, within one hour of substitution for a 500 kV offsite power circuit, and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter during use by verifying correct breaker alignments and indicated power availability; and b.
Demonstrated OPERABLE at least once per REFUELING INTERVAL during shutdown by manually transferring unit power supply from the nonnal circuit to the alternate circuit.
4.8.1.1.2 Each diesel generator shall be demonstrated OPERABLE:
a.
At least once per 31 days on a STAGGERED TEST BASIS Ly:
1.
Verifying the fuel level in the day fuel tank.
2.
Verifying the fuel level in the fuel storage tank.
3.
Verifying the fuel transfer pump can be started and transfers fuel from the storage system to the day tank.
4.
Verifying the diesel starts and achieves a generator voltage and frequency,of 4160 +240, -100 volts and 60 1 1.2 Hz, l
respectively.
j 5.
Verifying the generator is synchronized, loaded to E 2700 kW, and operates for t 60 minutes.
6.
Verifying the diesel generator is aligned to provide standby power to'the associated emergency busses.
7.
Verifying that the automatic load sequencer timer is OPERABLE with the interval between each load block within + 10% of its
~
design interval.
b.
At least once per 92 days by verifying that a sample of diesel i
fuel from the fuel storage tank is within the acceptable limits specified in Table 1 of ASTM D975-81 when checked for viscosity, water and sediment.
All engine starts for the purpose of this Survet11ance Requirement may be preceded by an engine prelube period and/or other warmup procedures reconrnended by the manufacturer so that mechanical wear and stress on the diesel engine is minimized.
CALVERT CLIFFS - UNIT 2 3/4 8-4 Amendment No. 200