ML20216D506

From kanterella
Jump to navigation Jump to search
Amend 190 to License NPF-6,reducing Minimum Required Reactor Coolant Sys Flow Rate in TS 3.2.5 Until Plant SGs Are Replaced
ML20216D506
Person / Time
Site: Arkansas Nuclear 
(NPF-006)
Issue date: 03/12/1998
From: William Reckley
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20216D511 List:
References
NPF-06-A-190 NUDOCS 9803170089
Download: ML20216D506 (5)


Text

p*Uh

  • s[p
  • t UNITED STATES l

j NUCLEAR REGULATORY COMMISSION l

2 WASHINGTON, D.C. 30seH001

\\.. /

I ENTERGY OPERATIONS. INC.

DOCKET NO. 52.MR ARKANSAS NUCLEAR ONE. UNIT NO. 2 i

AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.190 License No. NPF-6 l

1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The app!ication for amendment by Entergy Operations, Inc. (the licensee) dated September 23,1997, as supplemented by the letters dated February 27 and March 4,1998, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, ihe provisions of the Act, and the rules and regulations of the Commission;

)

C.

There is reasonable assurance: (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the i

Comrnission's regulations; D.

The issuance of this license amendment will not be inimical to the common defense and security or to the health and safety of the public; and i

E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the CommWWs regulations and all applicable requirements have been satisfied.

l l

Y 9003170089 900312 PDR ADOCK 05000368 i

P PDR a

~

i 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Facility Operating License No. NPF-6 is hereby amended to read as follows:

2.

Technical Soecificatign_g The Technical Opecifications contained in Appendix A, as revised through Amendment No. 190, are hereby incorporated in the license. The licensee shall operate the facility in accordarice with the Technical Specifications.

3.

The license amendment is effective as ofits date ofissuance.

FOR THE NUCLEAR REGULATORY COMMISSION w

Wi!!iam Reckley, Project M nager

. Project Directorate IV-1 Division of Reactor Projects lil/IV Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of issuance: March 12, 1998 1

ATTACHMENT TO UCfNSE AMINOMENT NO.190 L

fAgJl.1IY OPERATING.UCENSE NO NPF-6 DOCKET NO.60-368 Revise the following page of the Appendix "A" Technical Specifications with the attached page.

The myised page is identified by Amendment number and contain vertical lines indicating the area of change. The corresponding overleaf page is also provided to maintain document completeness.

REMOVE PAGE INSERT PAGE 3/4 2-7 3/4 2-7 i

l l

l

I t

POWER DISTRXBUTION LIMITS RCS FLOW RATE LIMITING CONDITION FOR OPERATION 3.2.5 The actual Reactor Coolant System total flow rate shall be greater than or equal to 108.4 x 10' lbm/hr (Note 1).

l APPLICABILITY t,,

MODE 1.

I i

ACTION:

With the actual Reactor Coolant System total flow rate determined to be less than the above limit, reduce THERMAL POWER to less than 5% of RATED THERMAL POWER within the Mxt 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.2.5 The actual Reactor Coolant System total flow rate shall be determined to be within its limit at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

i I

Note 1: The alue of 120.4 x 10' lbm/hr has been reduced to 108.4 x 10' lbm/hr until s.ne steam generators are replaced. After the steam generators are replaced, this value returns to 120.4 x 10' lbm/hr.

ARKANSAS - UNIT 2 3/4 2-7 Amendment No. G4,m,190

POWER DISTRIBUTION LIg))

EACTOR COOLANT COLD LEG TEMPMATURE fm7MfTING CONDfTION FOR OPTRATION 3.2.6 The Reactor Coolant Cold Leg Temperature (7,) shall be maintained between 542'T and 354.7'F.

APPLICAEILITY: NODE 1 above 30% of RATED TERMAL POWER.

AGII0ti:

With the Reactor Coolant Cold Les Temperature exceeding its limit, restore the tosperature to within its limit within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or reduce TERMAL POWER to less than 30% of RATED TERMAL POWER within the next 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

i SURVEILLANCE REQUIREENTS 4.2.6 The Reactor Coolant Cold Leg Temperature shall be determined to be within its limit at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

')

ARKANSAS - UNIT 2 3/4 2-8 Amendment No. M, 157 l

-.