Special Rept 86-004:on 861017,filtration,recirculation & Ventilation Sys Vent Radiation Monitor Inoperable for More than 72 H.Caused by Crimped Signal Cable.Cable Replaced. Procedures Will Be Revised
ML20215N319
Person / Time
Site: Hope Creek PSEG icon.png
Issue date: 10/31/1986
From: Birley R, Salvesen R
Public Service Enterprise Group
To:
NRC OFFICE OF ADMINISTRATION (ADM)
References
86-004, 86-4, NUDOCS 8611050233
Download: ML20215N319 (4)


Text

4~

O PSEG Public Service Electric and Gas Company P.O. Box L Hancocks Bridge, New Jersey 08038 Hope Creek Operations October 31, 1986 U. S. Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555

Dear Sir:

HOPE'CREEK GENERATING STATION DOCKET NO. 50-354 UNIT NO. 1 SPECIAL REPORT 86-004 This Special . Report is being submitted pursuant to the requirements of Technical Specification 3.3.7.5.

Sincerely yours, fYbMw& M R. S Salvesen

. General Manager -

Hope Creek Operations

-RGB:tlb Attachment C Distribution P

mtolosu $8ha# f ii S

The Energy People 95 2173411W 12 85

weC Po,e Jeg u 8 muCLila(soutsfony Coastsienicas Mi Apenovg3 osse aso sigo4tos UCENSEE EVENT REPORT (LER) "*"'"

pACILITY esAass 113 , DOCEST .suesgGR (21 PAGE W Hope Creek Generating Station o1510101o1315l4 1 loFl013

ETS Vent Radiation Monitor Inoperable For More Than 72 Hours -

Special Report 86-004 eveer? OATS tel LOA Isumega Ice appon? OATE (71 OTwen F ACILITies larvoLves ist 8

esDasTw OAv ' VIAA VIAA ~

a,vM '"6

. $ amoseTM OAv vtAR P AC8L8 7' *ause occat? Numesm<st 0 Is po g oloi l l l ~ '-

1l 0 1l 718 6 8l 6 Nl Al l 1l0 3l 1 8l 6 o isto io ioi i !

,,, TM60 RSPORT es puenssTTic PupeuANT To Twa maouantantesT3 or to CFR $ (Chere e.e .e sae,. of rae 8ed8e=.e# litt MOOG WI 1 30 403ft) at 4054el 90 Thit2Hl.1 73 711b6 a 30805(sH1H6 80 StieHil to.7hH2H.6 71.71tel t100 01510 se .HiHei m 3.ieHai es w aH :

x g,w,Egsg,;.,A yf 30 easteH1Hm) 90 73 del (2 Hit OS134eH2HeimHA) J08AJ 8'"'*"'""' ">"2" ""*"*""

s _

3e HiH.,

_ _ Special Report essa H He ee rhH H.,

LIC8ssesE CossTACT Poe Twas Len (133 maass f ettawome Mupeen AntA coot R. G. Birlev 61019 31 3! 91 - I5 12 13 l R ConsPLETE C8e5 Leses PO81 EACM COesroestNT P A8Lume DESCRIOSO IN Tw68 REPORT (13)

C#USS systtu COuPONENT "Q,jC. CA R{o ,7 js CAUSE SvtTEM CouroNemT "'[$($O } 'y' f"f.f I I I I I l l l t I i I I I i I I I l l I I I l l l 1 I SUPPLSAsGNTAL RSPORT EXPGCTeo liet WomTw Day vtAm

$6 BMiSSION vi8199 ven, eenneo.o IK9tCTED SusutSSICM OA rti NO l l l A ? = ACT a-, ,.oo ., , A. ,.. ,, an ,,-. ,, ,, e , n i During performance of an energy response determination test on the Filtration, Recirculation, and Ventilation System (FRVS) Vent Radiation Monitor, the mid-range noble gas detector exhibited intermittent indication. I&C Department investigation of this event revealed that a cable between the detector and the monitor electronics was crimped which created a sporadic open circuit. The means by which the cable was crimped is unknown but is believed to have occurred during previous testing and maintenance activities. ~

The crimped signal cable was replaced and the monitor returned to service on October 28, 1986 following surveillance testing. This Special Report is being submitted pursuant to Technical Specification 3.3.7.5.

f62A Yi

=,- 1

gmC p.r= 304A u 8 huCLEAR E EIuk.tf07sv COMM'SSIC%

LICENSEE EVENT REPORT (LER) TEXT CONTINUATION ...aovto owe so vio-oica tapimES S1T 95 F ACatety maase ses pocagt muussa s3*

LEm huutt A ill Paos i3s

'"a "tP.W "'J?.O Hope Creek Generating Station o95101010I3l514 81 6 -

nl Al -

l 01 2 0F 013 7tXT M anse esmas e M use assumenf 4AC #esen Ms1IIM ELbET BED B1ETEB 1DEDT1ElChilDB General Electric - Boiling Water Reactor (BWR/4)

FRVS Vent Radiation Monitoring System (EIIS Designator: IP) 1DEBTIElCbTlDB DE DCCDEBEEE l

[ FRVS Vent Radiation Monitor Inoperable For More Than 72 Hours.

Event Date: 10/17/86 Event Time: 2045 CDEDlTlDEB RElDB TD DCCDBEEBCE Plant in OPERATIONAL CONDITION 1 with a Reactor power of 50% and a unit load of 500 MWe. Filtration, Recirculation, and Ventilation System (FRVS) Vent Radiation Monitor inoperable due to intermittent indication on the mid-range detector of the High Range Noble Gas Monitor.

DEBCBlETlDE DE DCCDEBEECE On October 14, 1986 during performance of an energy response determination test on the FRVS Vent Radiation Monitor, the mid-

-range noble gas detector exhibited. intermittent indication. At 2045 hours0.0237 days <br />0.568 hours <br />0.00338 weeks <br />7.781225e-4 months <br /> the monitor was declared inoperable and the I&C Department initiated troubleshooting and repair. Since the radiation monitor remained inoperable for more than 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, the Radiation Protection Department .was notified to implement the preplanned alternate method of monitoring, if required. This monitor. is normally in the standby condition and is automatically placed in service during high radiation' conditions. During the period of inoperability these conditions did not exist, therefore, alternate monitoring was not required, hNhL1BlB DE DCCDEBEBCE Investigation of this event revealed that the mid-range noble gas detector intermittent indication was caused by a crimped cable which connects the detector output to the monitor electronics.

This crimp- resulted in a sporadic open circuit in the detector signal. The means by which the cable was crimped is unknown but is believed to have occurred during previous testing and maintenance activities. This Special Report is being submitted pursuant to Technical Specification 3.3.7.5.

g...M 3 a

a.

gaC #was 386A U S %UCLi&M E EGUL&roav COMM'1860%

LICENSEE EVENT REPORT (LERI TEXT CONTINUATION are=ovic ewe so uso-oic.

E mpiagg g 311pg p acsks e y asaast e t DOCA tt muna0ER I21 Lan %Uweta 161 80831 Eaa " t'..; l

"'J '.O Hope Creek Generating Station a js jo jo go l 31 Sl 4 81 6 -

NIAl -

l Ol 3 0' 0 l3 rur o .- -w aac w anaw nn COBBBCTlHE bCZlDE The crimped signal cable was replaced with a new, in kind cable.

Surveillance testing was completed and the monitor was declared operable on October 28, 1986. I&C and Radiation Protection Department procedures will be revised to include precautions relative to the proper installation of these cables following testing and maintenance activities. In addition, all technicians in both departments will be trained in the proper method of installation of the detector cables.