- _ _ _.._ -.

TABLE TS.3.15-1 y EVENT MONITORING INSTRUMENTATION - PROCESS & CONTAINMENT Required Total No.

Minimum Channels Instrument of Channels Operable

1. Pressurizer Water Level 2

1

2. Auxiliary Feedwater Flow to Steam Generators 2/ steam gen 1/ steam gen (One Channel Flow and One Channel Wide Range Level for Each Steam Generator)
3. Reactor Coolant System Subcooling Margin 2

1

4. Pressurizer Power Operated Relief Valve Position 2/ valve 1/ valve (One Common Channel Temperature, One Channel Limit Switch per Valve, and One Channel Acoustic Sensor per Valve *)
5. Pressurizer Power Operated Relief Block Valve Position 2/ valve 1/ valve (One Common Channel Temperature, One Channel Limit Switch per Valve, and One Channel Acoustic Sensor per Valve *)

l

6. Pressurizer Safety Valve Position 2/ valve 1/ valve (One Channel Temperature per Valve and Common l

Acoustic Sensor **)

7. a. Containment Water Level (wide range) 2 1
b. Containment Water Level (narrow range) 2 1

r+ r+ 8. Containment Hydrogen Monitor (2 sensors per Channel) 2 1

%~~

g g 9. Containment Pressure (wide range) 2 1

gy

er osml0. Core Exit Thermocouples 4/ core quadrant 2/ core quadrant E

861019008S 861008 g

ADOCKOSOOg2 g

PDR mm w

.m.co p

i 3*

- A common acoustic sensor provides backup position indication for each pressurizer power operated y

3 relief valve and its associated block valve.

T

- The acoustic sensor channel is common to both valves. When operable, the acoustic sensor may be considered as an operable channel for each valve.

.. =

e f

t