I

. s m MAME HARHEE MGMICPOWERCOMPARUe

,uaug,,Tl,,?n",%'s h

(207) 623-3521 December 2, 1986 HN-86-152 Region I United States Nuclear Regulatory Commission Office of Inspection and Enforcement 631 Park Avenue King of Prussia, Pennsylvania 19406 Attention: Dr. Thomas E. Hurley, Regional Administrator

References:

(a)

License No. DPR-36 (Docket No. 50-309)

(b) USNRC Letter to HYAPCo dated October 8, 1986 - IE Compliance Bulletin 86-03

Subject:

Response to IE Compliance Bulletin 86-03:

Potential Failure of Multiple ECCS Pumps Due to Single Failure of Air-Operated Valve in Minimum Flow Recirculation Line Gentlemen:

Haine Yankee has reviewed system drawings of the recirculation paths for the High Pressure Safety Injection (HPSI), Low Pressure Safety Injection (LPSI), and Containment Spray (CS) pumps for a potential failure of all Emergency Core Cooling System (ECCS) pumps in a system due to a single failure of an air-operated valve in accordance with IE Compliance Pulletin 86-03, Reference (b). The following summarizes our evaluation.

The LPSI and CS pumps both recirculate to the refueling water storage tank through separate locked open manual isolation valves and a common recirculation header. The common header contains two motor operated isolation valves in series and a locked open manual valve.

The two MOVs are normally open and will fail "as is" on loss of power. Maine Yankee has determined that this line is not susceptible to a failure of the type descriped in the subject bulletin.

Flow from each HPSI pump recirculates through separate locked open manual isolation valves and a common header.

The common header contains a motor operated isolation valve and three normally open manual isolation valves. The H0V is normally open and will fail "as is" on loss of power. Maine Yankee has determined that this recirculation line is not susceptible to a failure of the type described in the subject bulletin.

g2170263861202 G

ADOCK 05000309 PDR qil I D 8221L-LHO

M AINE YANKEE ATOMIC POWER COMPANY United States Nuclear Regulatory Commission Page Two Attention: Dr. Thomas E. Murley, Regional Administrator MN-86-152 Maine Yankee has concluded that the ECCS pump recirculation lines are not vulnerable to a single active failure which would result in the failure of all Emergency Core Cooling System (ECCS) pumps.

If you have any further questions, please do not hesitate to contact us.

Very truly yours, MAINE YANKEE AT IC POWER COMPANY Charles D. Frizzle, Vice President / Manager of Operations CDF/bjp cc: Mr. Ashok C. Thadani Mr. Cornelius F. Holden Mr. Pat Sears Document Control Desk STATE OF MAINE Then personally appeared before me, Charles D. Frizzle, who being duly sworn did state that he is Vice President of Maine Yankee Atomic Power Company, that he is duly authorized to execute and file the foregoing response in the name and on behalf of Maine Yankee Atomic Power Company, and that the statements therein are true to the best of his knowledge and belief.

/V [

' Notary Public 0 RY US AN MY C0t.TJSS10N EXPIRES DCTOBER 3.1992 8221L-LM0