Cp&L Carolina Power & Light Company DEC 111986 SERIAL: NLS-86-450 Director of Nuclear Reactor Regulation l

Attention:

Mr. Dan Muller l

BWR Project Directorate #2 f

Division of BWR Licensing United States Nuclear Regulatory Commission Washington, DC 20555 BRUNSWICK STE AM ELECTRIC PLANT, UNIT NOS.1 AND 2 DOCKET NOS. 50-325 & 50-324/ LICENSE NOS. DPR-71 & DPR-62 APPENDIX 3 EXEMPTION REQUEST

Dear Sir:

On December 1,1986, a conference call regarding our October 25,1985 Appendix 3 exemption request was held. Exemption 2 and Exemption 3 were discussed. This letter documents the conclusions reached in the call.

The staff stated that Appendix 3 does not apply to the valves listed in Exemption 2, Lines Terminating Below Minimum Torus Level. As such, no exemption to Appendix 3 is required. Carolina Power & Light Company (CP&L) will perform testing of these valves in accordance with the provisions of Section XI of the ASME Boiler and Pressure Vessel Code.

With regard to Exemption 3, H /0 Monitor Isolation Valves, the staff agreed to approve 2

2 the exemption provided the Company performs soap bubble testing of the H /02 2

Monitoring System. CP&L will perform soap bubble testing of the H /0 Mon.toring 2 7 i

System at the frequency and pressure specified for type C testing in 10 CFR 50 Appendix J. Soap bubble testing of the affected portions will also be performed af ter maintenance.

Please refer any questions regarding this matter to Mr. Sherwood R. Zimmerman at (919) 836-6242.

Yours very

,1y, fb4m

. B. Cutter - Vice resident Nuclear Engineering & Licensing MAT /kts (5084 MAT) cc:

Mr. W. H. Rutand (NRC-BNP)

Dr. 3. Nelson Grace (NRC-RII)

Mr. E. Sylvester (NRC) gbd 8612170138 861211 DR ADDCK 0500 4