Docket No. 502289 December 5,,1986 MEMORANDUM FOR:

John F. Stolz, Director PWR Project Directorate #6 Division of PWR Licensing-B FROM:

John 0. Thoma, Project Manager PWR Project Directorate #6 Division of PWR Licensing-B

SUBJECT:

MEETING

SUMMARY

- TMI-1 FIRE PROTECTION On November 13, 1986, a meeting was held at the TMI-1 site to discuss the status of the review effort for the Appendix R submittal for TMI-1. The

~

intent was to obtain enough information to write a safety evaluation before mid December when a fire protection inspection is planned.

Enclosure (1) is a list of attendees.

Enclosure (2) contains the meeting agenda. The reviewer, Dennis Kubicki, discussed issues in his safety evaluation but at no time was a draft SE provided to the licensee. The conclusion of the meeting is that there are many open issues still left to be resolved. The status of all issues will be discussed in the SE scheduled for issuance before the inspection. However, it is anticipated, based on the number of unresolved issues, that a followup inspection and close out SE will need to be issued before startup (scheduled forMarch1987).

Enclosure (3) is'a handout provided by the licensee concerning an emergency lighting exemption request. Dennis Kubicki performed a plant tour to better understand the specifics of the request.

John 0. Thoma, Project Manager PWR Project Directorate #6 Division of PWR Licensing-B

Enclosures:

As stated cc w/ enclosures:

See next page To7 TA fav PWR#6 PW 6 PWR#6 TRoss,

JThoma;eh RWeller

(>/0/86 p/of/86

/2/f /P6 8612160181 8

$89 PDR ADOCK O PDR _

F

Mr. Henry D. Hukill Three Mile Island Nuclear Station, GPU Nuclear Corporation Unit No. 1 cc:

Mr. R. J. Toole Mr. Richard Conte 0&M Director, TMI-1 Senior Resident Inspector (TMI-1)

GPU Nuclear Corporation U.S.N.R.C.

Middletown, Pennsylvania 17057 P.O. Box 311 Middletown, Pennsylvania 17057 Richard J. McGoey Manager, PWR Licensing Regional Administrator, Region I GPU Nuclear Corporation U.S. Nuclear Regulatory Comission 100 Interpace Parkway 631 Park Avenue Parsippany, New Jersey 70754 King of Prussia, Pennsylvania 19406 Mr. C. W. Smyth Mr. Robert B. Borsum g'

TMI-1 Licensing Manager Babcock & Wilcox GPU Nuclear Corporation Nuclear Power Generation Division P. O. Box 480 Suite 220, 7910 Woodmont Avenue Middletown, Pennsylvania 17057 Bethesda, Maryland 20814 Ernest L. Blake, Jr., Esq.

Governor's Office of State Planning L

Shaw, Pittman, Potts & Trowbridge and Development L g- ~ ' '

P300 N Street, N.W.

ATTN:

Coordinator, Pennsylvenia Washington, D.C.

20037 State Clearinghousd l

P. O. Box 1373 Sheldon J. Wolfe, Esq., Chairman Harrisburg, Pennsylvania 17120 Atomic Safety and Licensing Board U.S. Nuclear Regulatory Comission Mr. Larry Hochendoner Washington, D.C.

20555 Dauphin County Commissioner Dauphin County Courthouse Mr. Frederick J. Shon Front and Market Streets Atomic Safety and Licensing Board Harrisburg, Pennsylvania 17101 U.S. Nuclear Pegulatory Comission Washington, D.C.

20555 Mr. David D. Maxwell, Chairman Board of Supervisors Dr. Oscar H. Paris Londonderry Township Atomic Safety and Licensing Board RFD#1 - Geyers Church Road U.S. Nuclear Regulatory Commission Middletown, Pennsylvania 17057 Washington, D.C.

20555 Mr. Thomas M. Gerusky, Director Atomic Safety & Licensing Board Panel Bureau of Radiation Protection U.S. Nuclear Regulatory Comission Pennsylvania Department of Washington, DC 20555 Environmental Resources P. O. Box 2063 Atomic Safety & Licensing Appeal Harrisburg, Pennsylvania 17120 Bo rd Panel (8) j U.S. Nuclear Regulatory Commission Thomas Y. Au, Esq.

j Washington, D.C.

20555 Office of Chief Ccunsel Department of Environmental Pesources Docketing and Service Section 505 Executive House Office of the Secretary P. O. Box 2357 U.S. Nuclear Regulatory Comission Harrisburg, Pennsylvania 17120 Washington, D.C.

20555 Ms. Louise Bradford TPIA 1011 Green Street Harrisburg, Pennsylvania 17102 y

h

Mr. Henry D. Hukill Three Mile Island Nuclear Station GPU Nuclear Corporation Unit 1 TMIA 315 Peffer Street Harrisburg, Pennsylvania 17102

)

Bruce W. Churchill, Esq.

Shaw,- Pittman,. Potts & Trowbridge 2300 N Street,1N.W.

Washington, D.C.

20037 l

-. ~.... -

c..

List of Attendees for Hovember 13, 1986 Meetino Name Office John Thoma NRC-NRR Joe Mangeno G/C,Inc.

J. W. Strausser G/C,Inc.

H. B. Shipman TMI-1 Ops D. H. Stevens G/C,Inc.,M.E.

A. Thaik G/C, Inc., E.E.

J. H. Brendien, Jr.

G/C, Inc., Pro.iect Jack Siegel GPUN Philip Moor GPUN - Projects Boris Gan GPUN - Project Engineer Susan Otto GPUN - Licensing

' John Mateychick GPUN - Pro.iect Engineer Chester Shorts Manager - Tech Functions Site John P. Rogers HRC-TMI-1 Dennis Kubicki NRC-NRR David J. Distel GPUN - Licensing Chet Incorvati GPUN - THI-1 Audit Supv T. A. O'Connor GPUN - Lead FP Eng.

F. Young NRC-RI-TMI-1 Grea Gurican GPUN - Technicaf Contact-CYGNA

__._.~.

l.

Enclosure (2)

'~

AGENDA

~GPUN/NRC Meeting, 11/13/86, TMI-l Compliance with 10 CFR 50 Appendix R

-I.

INTRODUCTION A.

Status of Appendix R Modifications B.

Discuss Significant Changes in Appendix R Compliance Effort II.

REVIEW NRC DRAFT SER l

III.

DISCUSS STATUS OF EXISTING OPEN ITEMS I

-A.

Emergency Lighting B.

Statistical San >1e Analysis for Associated Circuits By Coninon Enclosure l-IV.

NRC APPENDIX R AUDIT:

12/8/36 - 12/12/86 Discuss NRC requirements in terms of documentation required, GPUN support personnel needed, etc.

V.

FSAR/ Tech. Spec. update A.

Status of Technical Specifications 1.

Remote Shutdown System 2.

Existing Tech. Spec. update for Appendix R modifications B.

Deletion of Fire Protection Tech. Spec's.

f 1411g I-

w w_

GPUN APPENDIX R EMERGENCY LIGHTING PRESENTATION Allg

CURRENT DESIGN BASIS o

FIXED EMERGENCY LIGHTING UNITS INSTALLED IN AREAS WHERE MANUAL OPERATION OF SAFE SHUTDO$iN EQUIPMENT IS REQUIRED AND ACCESS AND EGRESS ROUTES THERETO, EXCEPT FOR THE REACTOR BUILDING.

o IN THE REACTOR BUILDING, PORTABLE EMERGENCY LIGHTING UNITS SHALL BE l

USED FOR BOTH ACCESS / EGRESS AND PERFORMANCE OF THE MANUAL OPERATIONS.

o ACCESS TO REACTOR BUILDING WITHIN 8 HOURS REQUIRED ONLY FOR A FIRE WHICH CAUSES SPURIOUS OPERATION OF ONE OF THREE NORMALLY OPEN VALVES, LOCATED IN ZONE RB-FZ-lc, ASSOCIATED WITH REACTOR COOLANT LETDOWN COOLER IN OPERATION.

MANUAL REALIGNMENT REQUIRED WITHIN 4 HOURS TO REESTABLISH REACTOR COOLANT LETDOWN.

Lid 11

~

s i#

PRESENT DESIGN e

o 8 HOUR BATTERY POWERED PORTABLE LIGHTS d'JMINISTRATIVELY. CONTROLLED-AND MAINTAINED AT THE ENTRANCE OF THE REACTOR BUILDING.

1 i

i I

l l

l 4

l 4

l i

s

THE GPUN EXEMPTION' REQUEST. APPROACH UTILIZING PORTABLE LIGHTING FOR' ACCESS / EGRESS:

AND PERFORMANCE OF MANUAL OPERATION OF SAFE SHUTDOWN EQUIPMENT-IN THE REACTOR BUILDING IS EQUIVALENT TO OR BETTER THAN FIXED EMERGENCY LIGHTING BECAUSE:

1.

FLEXIBILITY - WITH PORTABLE LIGHTS THE OPERATOR HAS CONTROL OF THE BEAM DIRECTION.

1 THIS PROVIDES ENHANCED ABILITY TO SELECT ALTERNATE ROUTES TO ACCOMPLISH MANUAL ACTION (ADVANTAGE).

2.

RELIABILITY AND MAINTENANCE - PORTABLE LIGHTS WILL BE RATED FOR 8-HOUR OPERABILITY THE SAME AS FIXED LIGHTS.

SURVEILLANCE WILL MAINTAIN A FULLY CHARGED. CONDITION.

ADMINISTRATIVE CONTROL INSURES AVAILABILITY.

(EQUIVALENCY) i INACCESSIBILITY OF FIXED UNITS INSIDE REACTOR BUILDING DTIRING NORMAL OPERATION REDUCES RELIABILITY OF FIXED UNITS SINCE THEY ARE NOT AVAILABLE FOR MAINTENANCE AND/OR PERIODIC CHECKING. (ADVANTAGE).

2 USE OF PORTABLE LIGHTING WOULD ELIMINATE PERSONNEL EXPOSURES RECEIVED DURING MAINTENANCE AND SURVEILLANCE OF INSTALLED FIXED EMERGENCY LIGHTS, WHICH IS CONSISTENT WITH ALARA PROGRAM OBJECTIVES (ADVANTAGE).

3.

DESIGN - RADIATION DEGRADATION OF THE BATTERY ENCLOSURE INSTALLED INSIDE CONTAINMENT COULD LEAD TO LEAKAGE OR RUPTURE OVER A PERIOD OF TIME.

BATTERY PACKS FOR FIXED EMERGENCY LIGHTING UNITS NOT QUALIFIED FOR POSTULATED ACCIDENT TEMPERATURE / PRESSURE k

INSIDE' REACTOR BUILDIN'd ANDITHEREFORE COULD INTRODUCE HAZARDOUS. MATERIAL SUCH AS BATTERY ACID WHICH WOULD INCREASE HYDROGEN GENERATION AND ALSO POSE THREAT TO CABLES AND OTHER COMPONENTS (ADVANTAGE).

4.

REDUNDANCY - PORTABLE LIGHTS-ARE READILY AVAILABLE TO ACCOMMODATE MALFUNCTIONS, DAMAGE, LOSS, DROPPING (ADVANTAGE).

i BURDEN TO OPERATOR - DURING INGRESS / EGRESS, CARRYING A PORTABLE LIGHT IS NOT AN 5.

i i

IMPACT SINCE HE IS NOT PERFORMING A FUNCTION OTHER THAN MOVEMENT.

ONE HAND CAN BE-

~

USED TO CARRY THE LIGHT AND PROCEDURE WITH THE SECOND HAND FOR OPENING DOORS, FEELING PATH AS NECESSARY, ADJUSTING AIR PACK AS APPROPRIATE, COMMUNICATE, ETC.

{

ENTRY INTO REACTOR BUILDING IS A PLANNED ACTIVITY BY AT LEAST TWO OPERATORS, AT THE MANUAL WORKSTATION ONE OPERATOR WILL HOLD LIGHTS TO ILLUMINATE THE VALVE LOCATION WHITiE THE OTHER OPERATOR IS ABLE TO PERFORM THE MANUAL ACTIONS WITH BOTH HANDS.

(EQUIVALENT) l 6.

LOCAL VISIBILITY - WHEN ARRIVING AT THE MANUAL OPERATING STATION ONE OPERATOR WILL i

HOLD LIGHTS TO ILLUMINATE THE VALVE LOCATION WHILE THE OTHER OPERATOR IS-ABLE TO PERFORM THE MANUAL ACTIONS WITH BOTH HANDS.

PORTABLE LIGHT IS NOW AVAILABLE FOR CLOSE VISIBILITY TO VERIFY DETAILS SUCH AS VALVE TAG NUMBER.

THIS ENHANCES t

I l

VISIBILIT" IN CASES OF EXTREME SMOKE DENSITY, OBSTRUCTION, ETC. (ADVANTAGE) i

i INSIDE REACTOR BUILDING AND'THEREFORE COULD INTRODUCE HAZARDOUS MATERI'AL BATTERY ACID WHICH WOULD INCREASE HYDROGEN GENERATION AND ALSO POSE THREAT AND OTHER COMPONENTS (ADVANTAGE).

./

4.

REDUNDANCY - PORTABLE LIGHTS ARE READILY.AVAILABLE TO ACCOMMODATE MALFUNCTIONS, 1

I DAMAGE, LOSS, DROPPING (ADVANTAGE).

/

r S.

BURDEN TO OPERATOR - DURING INGRESS / EGRESS, CARRYING A PORTABLE LIGHT IS NOT AN IMPACT SINCE HE IS NOT PERFORMING A FUNCTION OTHER THAN MOVEMENT.

ONE HAND CAN BE USED TO CARRY THE LIGHT AND PROCEDURE WITH THE SECOND HAND FOR OPENING DOORS, u.

FEELING PATH AS NECESSARY, ADJUSTING AIR PACK AS APPROPRIATE, COMMUNICATE, ETC.

ENTRY INTO REACTOR BUILDING IS A PLANNED ACTIVITY BY AT LEAST TWO OPERATORS, AT THE j

]

\\ -

MANUAL WORKSTATION ONE OPERATOR WILL HOLD LIGHTS TO ILLUMINATE THE VALVE LOCATI WHILE THE OTHER OPERATOR IS ABLE TO PERFORM THE MANUAL ACTIONS WITH BOTH HANDS.

4 (EQUIVALENT) i f

6.

LOCAL VISIBILITY - WHEN ARRIVING AT THE MANUAL OPERATING STATION ONE OPERATOR WILL

'"' N, HOLD LIGHTS TO ILLUMINATE THE VALVE LOCATION WHILE THE OTHER OPERATOR IS ABLE TO PERFORM THE MANUAL ACTIONS WITH BOTH HANDS.

PORTABLE LIGHT IS NOW AVAILABLE FOR a

]

CLOSE VISIBILITY TO VERIFY DETAILS SUCH AS VALVE TAG NUMBER.

THIS ENHANCES VISIBILITY IN CASES OF EXTREME SMOKE DENSITY, OBSTRUCTION, ETC. (ADVANTAGE) l i